USNS TRENTON (T-EPF 5)

Outfit, Furnishings, Habitability VRR #17-013 18 May 2017 Service Order #17-021 Category “A” RDR/SBM/WCL

Inspect and Calibrate Tank Level Indicators (TLIs)

SO 17-021-1

1.0 ABSTRACT

1.1 This item describes the requirements for surveying, assessing, and calibration of the existing Vega Tank level indicator system.

2.0 REFERENCES/ENCLOSURES:

2.1 MSC General Technical Requirements.

2.2 NAVSEA Drawing 8612612_A: Booklet of Tank Capacity Tables

2.3 Technical Manual SN572-A6-MMC-010

3.0 ITEM LOCATION/DESCRIPTION

3.1 Location/Quantity: 18 tank tops throughout ship; see below.

3.2 Item Description/Manufacturer's Data:

3.2.1 VEGA Grieshaber KG, models VEGAPULS 60 or VEGAPULS 66.

4.0 GOVERNMENT FURNISHED EQUIPMENT/MATERIAL/SERVICES: None.

5.0 NOTES:

5.1 The contractor must consult the General Technical Requirements (GTR) to determine applicability to this work item, and must comply with the requirements of all applicable GTR’s including but not limited to GTR’s 1 through 7, 22, 23, 26, 28, and 29.

5.2 Performance Period: 15-29 June 2017

5.3 Location of Work: US Army Transportation Unit, Piraeus, Greece

5.4 Port Engineer: Wayne Lefebvre; cell #757-274-8389; wayne.lefebvre@navy.mil.

6.0 QUALITY ASSURANCE REQUIREMENTS: None additional

7.0 STATEMENT OF WORK REQUIRED:

7.1 Provide the services of Vega authorized technical representative to perform a comprehensive inspection and calibration of all TLIs.

7.1.1 Repair or replace TLI for STBD fwd FO Storage Tank (Model # PS66-

MXZCB2HKNASFSII, Mfr Drawing V-2474S0).

7.1.2 Perform and record manual soundings of each tank with the assistance of ship’s force.

7.1.3 Perform operational test on each TLI head and system display screens.

7.1.4 Verify recorded manual soundings with those displayed by TLI system, calibrate/adjust display values as required to achieve an accurate reading.

7.2 Upon completion of work, provide a Service Report detailing as-found condition;

work performed for each listed item per para 7.1, and final operating condition.

8.0 GENERAL REQUIREMENTS. None.

mailto:wayne.lefebvre@navy.mil

USNS TRENTON (T-EPF 5)

Outfit, Furnishings, Habitability VRR #17-013 18 May 2017 Service Order #17-021 Category “A” RDR/SBM/WCL

Inspect and Calibrate Tank Level Indicators (TLIs)

SO 17-021-2

Tank Locations

Description Tank Location

1 Oily Waste Holding Frame 47 Stbd 2 JP 5 Service No 1 Frame 37 Stbd 3 JP 5 Service No 2 Frame 37 Port 4 JP 5 Storage No 1 5-39-1 5 JP 5 Storage No 2 5-39-2 6 Lube Oil No 1 5-49-01 7 Lube Oil No 2 5-49-2 8 Potable Water No 1 Space 3-16-2, Frame 17 9 Potable Water No 2 Space 3-16-2, Frame 20 10 Fwd DFM Storage No 1 5-24-1 11 Fwd DFM Storage No 2 5-24-2 12 Aft DFM Storage No 1 5-41-1 13 Aft DFM Storage No 2 5-41-2 14 Aft DFM Service No 1 Space 4-41-1, Frame 46 15 Aft DFM Service No 2 Space 4-41-2, Frame 46 16 Sewage CHT 5-22-1 17 Waste Oil No 1 Space 4-41-1, Frame 42 18 Waste Oil No 2 Space 4-41-2, Frame 42

1.0 ABSTRACT
2.0 REFERENCES/ENCLOSURES:
2.1 MSC General Technical Requirements.
2.2 NAVSEA Drawing 8612612_A: Booklet of Tank Capacity Tables
2.3 Technical Manual SN572-A6-MMC-010
3.0 ITEM LOCATION/DESCRIPTION
3.2 Item Description/Manufacturer's Data:
5.0 NOTES:
5.4 Port Engineer: Wayne Lefebvre; cell #757-274-8389; wayne.lefebvre@navy.mil.
6.0 QUALITY ASSURANCE REQUIREMENTS: None additional
8.0 GENERAL REQUIREMENTS. None.
Tank Locations