23d Communications Squadron UPS Battery Replacement Statement of Work
Performed During Installation:
1. New 93 PM UPS Batteries
a. Removal and EPA approved disposal of old batteries from 3 separate locations.
Building 454 UPS Serial Number: EN493UJJ05
Building 803 UPS Serial Number: EN482UJJ02
Building 458 UPS Serial Number: EP456UJJ01
b. Installation of new batteries in 3 separate locations utilizing proper torque values (where applicable) as well as verification of batteries.
Building 454 UPS Serial Number: EN493UJJ05
Building 803 UPS Serial Number: EN482UJJ02
Building 458 UPS Serial Number: EP456UJJ01
2. Visually inspect conditions and appearance of the following:
a. Connection terminals inter cell/battery connectors, cables, and associated hardware.
b. Cell/battery covers, containers, and post seals.
c. Battery racks or cabinets and associated components and hardware.
d. Cell/battery jar or cover, noting any excessive distortion.
3. Perform cleaning of all accessible surfaces as required.
4. Reporting of Battery Update Visit:
a. The technician(s) will issue the customer a verbal report summarizing the work that was performed, condition of the battery and identifying any critical issues before leaving the customer’s site.
b. A Field Activity Report containing applicable notes and observations will be sent to the customer within 5 business days.
File details come from the government source that posted it. Updated .