Minot AFB BLDG 774 Chiller
INCLUDING:
YLAA0058HE46XFBBCTX
• Refrigerant Type: R410A
• Power: 460-3-60.0 Application
• Power Connection: SP CB w/ L Handle and 65 kA SCWR
• TEAO Fan Motors
• Low Sound Fans with VSD Control
• 3/4 Inch Thick Insulation of Evaporator
• All Aluminum Microchannel Coils
• Both Low/High Ambient Kit Required
• Louvered (Full Unit) Enclosure Panels
• Hot Gas Bypass (1 circuit)
• Acoustic Sound Blanket
• Flow Switch + Extension Kit
SCROLL COMPRESSOR-MOTOR ASSEMBLY
• High Efficiency Rotary Scroll Compressor
• Hermetic High Efficiency Induction Motor
• HFC-410a factory refrigerant and oil charge
• Neoprene isolators
BRAZED PLATE HEAT EXCHANGER EVAPORATOR
• 316L stainless steel corrugated plates
• Factory wired and mounted flow switch
• Reduces refrigerant charge by 40% - eligible for LEED Credit EAc4
• Electronic Expansion Valve – factory piped
• Liquid level sight glass, replaceable core filter-drier, and Schraeder charging valves
• 20 mesh wye-strainer -supplied by York and piped by Contractor
• Thermostatically controlled heater to -20 °F (standard)
• ¾“ factory applied insulation
MICRO-CHANNEL AIR-COOLED REFRIGERANT CONDENSER
• Variable speed low sound composite condenser fans
• Refrigerant Isolation Valves - to store refrigerant in the condenser
• Low ambient option to 0°F
• Full unit louvered panels for protection from hail and debris
MICRO-CONTROL AND POWER CENTER
• UL and FCC approved, ISN Micro-Computer control center
• 40 character Liquid Crystal Display (LCD) touch-screen display
• BACnet BAS control interface
• Factory mounted temperature and pressure sensors
• Factory mounted thermal dispersion water flow sensors
• Unit Mounted and wired 115/1 control power transformer
• Single Point Power circuit breaker connection
ELECTRICAL
• NEMA 3R enclosure
• UL listed ground fault protection
• Overvoltage and under-voltage protection
• 3 phase sensing motor overcurrent protection
FACTORY CERTIFIED START-UP SERVICE
• Start-up of chiller
EQUIPMENT WARRANTY
• Entire unit Parts & Labor Warranty 2 year from start-up
• 2 Year Refrigerant Warranty
• Five Year Compressor Parts and Labor Warranty
EXCLUSIONS
• Rigging and setting of chiller
• Rigging Warranty
• Electrical wiring
NOTES FOR INSTALLING CONTRACTOR
• York chillers are factory charged with HFC-410a
• Flow sensors and temperature chilled water sensors are factory mounted and wired
• Refrigerant isolation valves allow the charge to be laid up in the condenser while servicing
• Vibration isolators are provided by York, and field mounted by Contractor
• 20 mesh wye-strainer is provided by York, and field piped by Contractor
• Electrical wiring of 115/1 GFCI receptacles and evaporator heater by Contractor - if required