PROJECT:

DRAWING No:

Department of Veterans Affairs

IT Operations and Services

Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd

DRAWN BY: Kevin Grzelka

CHECKED BY:

DOC VERSION No:

PROJECT No:

SHEET TITLE

COVER

PRINT DATE: Oct 5, 2017

ISSUE DATE: Oct 5, 2017

SHEET: 1 OF 15

Michael Julian, RCDD

1.0

CBOC ITS

SPECIFICATIONS

N/A

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

Solution Delivery

COVER PAGE

DEVELOPED BY:

DATA CENTER ENGINEERING

DATA CENTER & CLOUD ENGINEERING

COMMUNITY BASED OUTPATIENT CLINIC (CBOC)

INSIDE PLANT

INFORMATION TRANSPORT SYSTEMS SPECIFICATIONS

Department of Veterans Affairs

IT Operations and Services

Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd

DRAWN BY: Kevin Grzelka

CHECKED BY:

DOC VERSION No:

PROJECT No:

SHEET TITLE

FRONT MATTER

PRINT DATE: Oct 5, 2017

ISSUE DATE: Oct 5, 2017

SHEET: 2 OF 15

Michael Julian, RCDD

1.0

CBOC ITS

SPECIFICATIONS

N/A

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

Solution Delivery

FRONT MATTER

DESIGN OBJECTIVES

1. MODULARITY: THIS DESIGN IS HIGHLY MODULAR.

3.CABLE PLANT: UTP CATEGORY 6A CABLE PLANT WILL SUPPORT 10 GIGABIT ETHERNET.

FIBER PLANT WILL UTILIZE LASER ENHANCED OM4 40 GbE RATED 50/125

MULTIMODE.

Standard or Document Description

ANSI/TIA-606-C, Administration Standard for Telecommunications Infrastructure

ANSI/TIA-606-B-1, Administration Standard for Telecommunications Infrastructure Addendum 1- Automated Infrastructure Management Systems - Addendum to ANSI/TIA-606-B

ANSI/TIA-607-C, Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises

ANSI/TIA-607-C-1, Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises - Addendum to TIA-607-C

ANSI/TIA-942-A, Telecommunications Infrastructure Standard for Data Centers

ANSI/TIA-942-A-1, Telecommunications Infrastructure Standard for Data Centers Addendum 1- Cabling Guidelines for Data Center Fabrics - Addendum to TIA-942-A

ANSI/TIA-1179, Healthcare Facility Telecommunications Infrastructure

BICSI 002, Data Center Design and Implementation Best Practices

BICSI ITSIMM, Information Technology Systems Installation Methods Manual (ITSIMM) - 7th Edition

BICSI/NECA 568, Standard for Installing Commercial Building Telecommunications Cabling

BICSI/NECA 607 Standard for Telecommunications Bonding and Grounding Planning and Installation Methods for Commercial Buildings 2011

CSI MASTERFORMAT ™ 2004 EDITION NUMBERS & TITLES

Construction Specifications Institute (CSI)

NFPA 70, National Electrical Code

NFPA 75, Standard for the Fire Protection of Information Technology Equipment

2. FLEXIBLE: THIS DESIGN IS FLEXIBLE TO ACCOMMODATE CHANGES TO FLOOR PLANS.

THIS DRAWING IS SCALED TO 11X17 FORMAT.

THIS DRAWING SET REPRESENTS THE COMPUTING AND PASSIVE INFRASTRUCTURE

DESIGN AND RACK ELEVATIONS FOR A GENERIC HEALHCARE FACILITY EQUIPMENT

ROOM (ER) AND A GENERIC TELECOMMUNICATION ROOM (TR). UNLESS NOTED

OTHERWISE, ACTIVE EQUIPMENT WILL BE FURNISHED AND INSTALLED BY VA OR

VA CONTRACTORS. THE STRUCTURED CABLING PLANT INSTALLERS WILL FURNISH

AND INSTALL PASSIVE CABLE PLANT INFRASTRUCTURE INCLUDING HORIZONTAL

CABLE MANAGERS, UTP AND FO HORIZONTAL CABLE, PATCH PANELS, PATHWAY

RACKS, FIBER DISTRIBUTION CABINETS AND FIBER CASSETTES.

T0 – Campus or Site Plans - Exterior Pathways and Inter-Building Backbones

T1 – Layout of complete building per floor - Serving Zone Boundaries, Backbone Systems, and Horizontal Pathways

T2 – Serving Zones Drawings - Drop Locations and Cable ID’s

T3 – Communication Equipment Rooms - Plan Views - Tech and AMEP /Elevations - Racks and Walls Elevations

T4 – Typical Detail Drawings - Faceplate Labeling, Firestopping, ADA, Safety, DOT, etc...

T5 – Schedules (Cabling and Equipment Spreadsheets) for cutovers

DRAWING TYPE DEFINITIONS

PURPOSE:

FRONT MATTER

Department of Veterans Affairs

IT Operations and Services

Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd

DRAWN BY: Kevin Grzelka

CHECKED BY:

DOC VERSION No:

PROJECT No:

SHEET TITLE

SYMBOLS

PRINT DATE: Oct 5, 2017

ISSUE DATE: Oct 5, 2017

SHEET: 3 OF 15

Michael Julian, RCDD

1.0

CBOC ITS

SPECIFICATIONS

N/A

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

Solution Delivery

T2 SYMBOLS

DATA

WALL PHONEW

FLOOR MOUNT

FIRE ALARM PANELF

EMERGENCY PHONEE

SECURITY OR FIRE ALARM DIALERSD

CR SECURITY SYSTEM CARD READER

CC CLOSED CIRCUIT SURVEILLANCE CAMERA

OUTLET

MD MOTION DETECTOR

T3 SYMBOLS

TGB

T

TWIST LOCK RECEPTACLE

THERMOSTAT

110 RECEPTACLE

TELECOMMUNICATIONS

GROUNDING

BUSBAR

STRIP LIGHT

HORIZONTAL SLEEVE (SIZE AS

INDICATED)

CONDUIT (SIZE AS INDICATED)

VERTICAL SLEEVE (SIZE AS

INDICATED)

CABLE RACEWAY

T4 SYMBOLS

CHATSWORTH SERVER

RACK. 24"WIDE X 47.5"

DEEP

QUADRUPLEX OUTLET

TELECOMMUNICATIONS

OUTLET

PERFORATED FLOOR

TILE

OR-60401015

1 1

2 2

3 3

4 4

5 5

OR-M2LCQ24-50E

1 12

24 13

OR-MM6HM61RU

FC01U-P

A

B

OZ

GROUP B

OX OY

OX

GROUP A

OY OZ

OY

GROUP B

OZ OX

OZ

GROUP A

OX OY

LEG 1 LEG 2 LEG 2LEG 1

PHASE Z PHASE Y PHASE X

GRP A

GRP B LEG 1

LEG 2 GRP A

GRP B LEG 1

LEG 2 GRP A

GRP B LEG 1

LEG 2

MAIN

POWER

POWER

ON

GROUP B

0FF

0N

MAIN

POWER

POWER

ON

GROUP A

0FF

0N

GROUP A

0FF

0N

A

0FF

0N

B

0FF

0N

C

0FF

0N

0FF

0N

0FF

0N

GROUP B

0FF

0N

A

0FF

0N

B

0FF

0N

C

0FF

0N

0FF

0N

0FF

0N

A B CA B C

zPDU (R/F)

L21-30

20A 120/ 208V

Y

L21-20

IEC 320-C19

IEC 320-C20

IEC 320-C13

IEC 320-C14

DATA / TELEPHONE

TELEPHONE SERVICE PANEL

1 1

2 2

3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35

36 36

37 37

38 38

39 39

40 40

41 41

42 42

43 43

44 44

45 45

OR-MM20730-W.

30" DEEP CHANNEL

7'H. 45RU.

ORTRONICS MM20

CHANNEL RACK

SYMBOLS

Department of Veterans Affairs

IT Operations and Services

Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd

DRAWN BY: Kevin Grzelka

CHECKED BY:

DOC VERSION No:

PROJECT No:

SHEET TITLE

T3- GENERIC HEALTH CARE

FACILITY EQUIPMENT ROOM

PRINT DATE: Oct 5, 2017

ISSUE DATE: Oct 5, 2017

SHEET: 4 OF 15

Michael Julian, RCDD

1.0

CBOC ITS

SPECIFICATIONS

N/A

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

Solution Delivery

EQUIPMENT ROOM

GENERIC FLOOR PLAN FOR HEALTH CARE FACILITY EQUIPMENT ROOM

AC

SERVICE PANEL FOR

DEDICATED ROOM AIR

CONDITIONING. NON-IT

LOAD ONLY. SHALL BE

EQUIPPED WITH SCHNEIDER

EM3500 SERIES DIN RAIL

METER OR EQUIVALENT

SERVICE PANEL FOR RACK

POWER IN

TELECOMMUNICATION ROOM. IT

LOAD ONLY. SHALL BE

EQUIPPED WITH SCHNEIDER

EM3500 SERIES DIN RAIL METER

OR EQUIVALENT

TWO (2) CONDUITS

INTERCONNECTING NETWORK

SUPPORT CENTER WITH ENTRANCE

FACILITY. TRADE SIZE 2

HORIZONTAL SLOT OR SLEEVE FOR

CABLING FROM WORK AREA OUTLETS

AND TELECOMMUNICATIONS ROOMS

L21-30R

CABLOFIL 2"X16" CF 54/400

CABLE TRAY

AC GRADE ¾’ PLYWOOD

BACKBOARD PAINTED HIGH-

GLOSS WHITE. MOUNTED 6"

AFF, 3 WALLS

MINIMUM 170 FT21 WITH STATIC

DISSIPATING FLOOR, NO DROP

CEILING, WALLS FULL HEIGHT TO

FLOOR ABOVE

VERTICAL CABLE MANAGER WITH

DOOR. ORTRONICS OR-

MM10VMD706-W 6" VERTICAL CABLE

MANAGEMENT CAGE

TYPICAL UNSWITCHED

QUADRAPLEX CONVENIENCE

OUTLETS

TELECOMMUNICATIONS

GROUNDING BUS BAR TO

ELECTRICAL GROUND AT

MAIN PANEL.

SPLIT PACKAGE AIR CONDITIONER

(32,600 BTU/H)

AC

L21-30R

ADDITIONAL SPLIT PACKAGE AIR

CONDITIONER (32,600 BTU) WHEN

NECESSARY

T

AIR CONDITIONER THERMOSTAT

OR-MM20730-W. 30" DEEP CHANNEL

7'H. 45RU. ORTRONICS MM20

CHANNEL RACK

SERVER CABINET, 45U, 24"X48"

(NOMINAL), SQUARE PUNCHED RAIL,

SINGLE PERFORATED FRONT DOOR,

SOLID REAR DOOR, TWO-POINT

KEYED LOCKS, WHITE,SOLID SIDE

PANELS

3'-0"

RK-1 RK-2 RK-3 RK-4

NOTE:

THERE SHALL BE A MINIMUM OF ONE

TELECOMMUNICATIONS ROOM (TR) PER FLOOR.

THE EQUIPMENT ROOM CAN SERVE AS A TR. ADDITIONAL

ROOMS SHOULD BE PROVIDED WHEN:

A) THE FLOOR AREA TO BE SERVED EXCEEDS 1000 M2 (10

000 FT2);

OR

B) THE HORIZONTAL DISTRIBUTION DISTANCE TO THE

WORK AREA EXCEEDS 90 M (295 FT).

NO RAISED FLOOR.

C

PIV/

KEYPAD

Department of Veterans Affairs

IT Operations and Services

Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd

DRAWN BY: Kevin Grzelka

CHECKED BY:

DOC VERSION No:

PROJECT No:

SHEET TITLE

T3-GENERIC HEALTH CARE

FACILITY TR

PRINT DATE: Oct 5, 2017

ISSUE DATE: Oct 5, 2017

SHEET: 5 OF 15

Michael Julian, RCDD

1.0

CBOC ITS

SPECIFICATIONS

N/A

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

Solution Delivery

TELECOMMUNICATIONS

ROOM

GENERIC FLOOR PLAN FOR HEALTH CARE FACILITY TELECOMMUNICATIONS ROOMS

AC

SERVICE PANEL FOR

DEDICATED ROOM AIR

CONDITIONING. NON-IT

LOAD ONLY. SHALL BE

EQUIPPED WITH SCHNEIDER

EM3500 SERIES DIN RAIL

METER OR EQUIVALENT

SERVICE PANEL FOR RACK

POWER IN

TELECOMMUNICATION ROOM. IT

LOAD ONLY. SHALL BE

EQUIPPED WITH SCHNEIDER

EM3500 SERIES DIN RAIL METER

OR EQUIVALENT

TWO (2) CONDUITS

INTERCONNECTING NETWORK

SUPPORT CENTER WITH ENTRANCE

FACILITY. TRADE SIZE 2

HORIZONTAL SLOT OR SLEEVE FOR

CABLING FROM WORK AREA OUTLETS

AND TELECOMMUNICATIONS ROOMS

L21-30R

CABLOFIL 2"X16" CF 54/400

CABLE TRAY

AC GRADE ¾’ PLYWOOD

BACKBOARD PAINTED HIGH-

GLOSS WHITE. MOUNTED 6"

AFF, 3 WALLS

MINIMUM 170 FT21 WITH STATIC

DISSIPATING FLOOR, NO DROP

CEILING, WALLS FULL HEIGHT TO

FLOOR ABOVE

VERTICAL CABLE MANAGER WITH

DOOR. ORTRONICS OR-

MM10VMD706-W 6" VERTICAL CABLE

MANAGEMENT CAGE

TYPICAL UNSWITCHED

QUADRAPLEX CONVENIENCE

OUTLETS

TELECOMMUNICATIONS

GROUNDING BUS BAR

SPLIT PACKAGE AIR CONDITIONER

(32,600 BTU/H)

AC

L21-30R

ADDITIONAL SPLIT PACKAGE AIR

CONDITIONER (32,600 BTU) WHEN

NECESSARY

T

AIR CONDITIONER THERMOSTAT

OR-MM20730-W. 30" DEEP CHANNEL

7'H. 45RU. ORTRONICS MM20

CHANNEL RACK

3'-0"

NOTE:

THERE SHALL BE A MINIMUM OF ONE

TELECOMMUNICATIONS ROOM (TR) PER FLOOR.

THE EQUIPMENT ROOM CAN SERVE AS A TR. ADDITIONAL

ROOMS SHOULD BE PROVIDED WHEN:

A) THE FLOOR AREA TO BE SERVED EXCEEDS 1000 M2 (10

000 FT2);

OR

B) THE HORIZONTAL DISTRIBUTION DISTANCE TO THE

WORK AREA EXCEEDS 90 M (295 FT).

NO RAISED FLOOR.

RK-1 RK-2 RK-3 RK-4

C

PIV/

KEYPAD

Department of Veterans Affairs

IT Operations and Services

Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd

DRAWN BY: Kevin Grzelka

CHECKED BY:

DOC VERSION No:

PROJECT No:

SHEET TITLE

T3 - TYPICAL BACKBOARD

ELEVATION

PRINT DATE: Oct 5, 2017

ISSUE DATE: Oct 5, 2017

SHEET: 6 OF 15

Michael Julian, RCDD

1.0

CBOC ITS

SPECIFICATIONS

N/A

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

Solution Delivery

AC AC T

3'-0"

RESERVED

VIDEO DISTRIBUTION

WAN/DEMARK

SECURITY POWER METERING

FIRE ALARM/

ANNOUNCIATOR

TYPICAL BACKBOARD

ELEVATION

Department of Veterans Affairs

IT Operations and Services

Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd

DRAWN BY: Kevin Grzelka

CHECKED BY:

DOC VERSION No:

PROJECT No:

SHEET TITLE

T3 - TYPICAL RACK

ELEVATION

PRINT DATE: Oct 5, 2017

ISSUE DATE: Oct 5, 2017

SHEET: 7 OF 15

Michael Julian, RCDD

1.0

CBOC ITS

SPECIFICATIONS

N/A

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

Solution Delivery

1 1

2 2

3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35

36 36

37 37

38 38

39 39

40 40

41 41

42 42

43 43

44 44

45 45

1 1

2 2

3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35

36 36

37 37

38 38

39 39

40 40

41 41

42 42

43 43

44 44

45 45

1 1

2 2

3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35

36 36

37 37

38 38

39 39

40 40

41 41

42 42

43 43

44 44

45 45

1 1

2 2

3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35

36 36

37 37

38 38

39 39

40 40

41 41

42 42

43 43

44 44

45 45

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

MAIN

POWER

POWER

ON

GROUP B

0FF

0N

MAIN

POWER

POWER

ON

GROUP A

0FF

0N

GROUP A

0FF

0N

A

0FF

0N

B

0FF

0N

C

0FF

0N

0FF

0N

0FF

0N

GROUP B

0FF

0N

A

0FF

0N

B

0FF

0N

C

0FF

0N

0FF

0N

0FF

0N

A B CA B C

BladeUPS

Powerware

BladeUPS

Powerware

BladeUPS

Powerware

BladeUPS

Powerware

MAIN

POWER

POWER

ON

GROUP B

0FF

0N

MAIN

POWER

POWER

ON

GROUP A

0FF

0N

GROUP A

0FF

0N

A

0FF

0N

B

0FF

0N

C

0FF

0N

0FF

0N

0FF

0N

GROUP B

0FF

0N

A

0FF

0N

B

0FF

0N

C

0FF

0N

0FF

0N

0FF

0N

A B CA B C

MODE

CONSOL E

37X

Catalyst 3850 48 PoE+

25X 36X13X 24X01X 12X 48X

Po EDUPLX

ACTV

STAT

SYST

SPEED

XPS

STACK

S-PWR

C3850-NM-4-10G

G1 G2 G3 G4

NETWORK MODULE

TE3 TE4TE1 TE2

MODE

CONSOL E

37X

Catalyst 3850 48 PoE+

25X 36X13X 24X01X 12X 48X

Po EDUPLX

ACTV

STAT

SYST

SPEED

XPS

STACK

S-PWR

C3850-NM-4-10G

G1 G2 G3 G4

NETWORK MODULE

TE3 TE4TE1 TE2

MODE

CONSOL E

37X

Catalyst 3850 48 PoE+

25X 36X13X 24X01X 12X 48X

Po EDUPLX

ACTV

STAT

SYST

SPEED

XPS

STACK

S-PWR

C3850-NM-4-10G

G1 G2 G3 G4

NETWORK MODULE

TE3 TE4TE1 TE2

MODE

CONSOL E

37X

Catalyst 3850 48 PoE+

25X 36X13X 24X01X 12X 48X

Po EDUPLX

ACTV

STAT

SYST

SPEED

XPS

STACK

S-PWR

C3850-NM-4-10G

G1 G2 G3 G4

NETWORK MODULE

TE3 TE4TE1 TE2

MODE

CONSOL E

37X

Catalyst 3850 48 PoE+

25X 36X13X 24X01X 12X 48X

Po EDUPLX

ACTV

STAT

SYST

SPEED

XPS

STACK

S-PWR

C3850-NM-4-10G

G1 G2 G3 G4

NETWORK MODULE

TE3 TE4TE1 TE2

RK-1

MAXIMUM OF 12 ANGLED CATEGORY 6A, 24 PORT PATCH

PANELS PER RACK. IF MORE THAN TWELVE (12) PATCH

PANELS ARE REQUIRED, INSTALL NEXT SET IN RK-3.

1 RU BLANKING PANELS BETWEEN LOWEST

PATCH PANEL AND RU32

1 RU CABLE MANAGER. SIX POSITION SPACING

WITH DOOR AT RU31

3850 POE LAN SWITCH WITH 1100 WATT

POWER SUPPLIES. MAX OF SIX (6) PER RACK.

2 RU CABLE MANAGER. SIX POSITION SPACING

WITH DOOR.

1 RU CABLE MANAGER. SIX POSITION

SPACING WITH DOOR.

ZONE PDU

UPS

RK-2 RK-3

RK-4

TYPICAL RACK ELEVATION FOR HEALTH CARE FACILITY TELECOMMUNICATIONS ROOMS

TYPICAL RACK ELEVATION

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

MODE

CONSOL E

37X

Catalyst 3850 48 PoE+

25X 36X13X 24X01X 12X 48X

Po EDUPLX

ACTV

STAT

SYST

SPEED

XPS

STACK

S-PWR

C3850-NM-4-10G

G1 G2 G3 G4

NETWORK MODULE

TE3 TE4TE1 TE2

MODE

CONSOL E

37X

Catalyst 3850 48 PoE+

25X 36X13X 24X01X 12X 48X

Po EDUPLX

ACTV

STAT

SYST

SPEED

XPS

STACK

S-PWR

C3850-NM-4-10G

G1 G2 G3 G4

NETWORK MODULE

TE3 TE4TE1 TE2

MODE

CONSOL E

37X

Catalyst 3850 48 PoE+

25X 36X13X 24X01X 12X 48X

Po EDUPLX

ACTV

STAT

SYST

SPEED

XPS

STACK

S-PWR

C3850-NM-4-10G

G1 G2 G3 G4

NETWORK MODULE

TE3 TE4TE1 TE2

MODE

CONSOL E

37X

Catalyst 3850 48 PoE+

25X 36X13X 24X01X 12X 48X

Po EDUPLX

ACTV

STAT

SYST

SPEED

XPS

STACK

S-PWR

C3850-NM-4-10G

G1 G2 G3 G4

NETWORK MODULE

TE3 TE4TE1 TE2

MODE

CONSOL E

37X

Catalyst 3850 48 PoE+

25X 36X13X 24X01X 12X 48X

Po EDUPLX

ACTV

STAT

SYST

SPEED

XPS

STACK

S-PWR

C3850-NM-4-10G

G1 G2 G3 G4

NETWORK MODULE

TE3 TE4TE1 TE2

SPACE

RESERVED

FOR WAN

ROUTERS, IP

PBX,

SECURITY

EQUIPMENT,

ETC.

SPACE

RESERVED

FOR

SERVERS.

SERVICE PROVIDER MAIN CROSS CONNECT

FIRST LEVEL BACKBONE (FIBER)

Department of Veterans Affairs

IT Operations and Services

Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd

DRAWN BY: Kevin Grzelka

CHECKED BY:

DOC VERSION No:

PROJECT No:

SHEET TITLE

T4 - TYPICAL RACK DETAIL

PRINT DATE: Oct 5, 2017

ISSUE DATE: Oct 5, 2017

SHEET: 8 OF 15

Michael Julian, RCDD

1.0

CBOC ITS

SPECIFICATIONS

N/A

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

Solution Delivery

6" WIDE VERTICAL CABLE MANAGEMENT

P/N: OR-MM20VMD706 (OR EQUIVALENT)

MM20 VERTICAL CABLE MANAGEMENT "CAGE", WITH DOOR, 6"

X 8.61" X 7' , BLACK

CAPACITY: 350 CATEGORY 6 PATCH CORDS OR 245 CATEGORY

6A PATCH CORDS

6 in

TYPICAL RACK PARTS LISTTYPICAL RACK DIMENSIONS AND SPECIFICATIONS

NTS

P/N: OR-MM2073038-W (OR EQUIVALENT)

MIGHTY MO 20 CABLE MANAGEMENT RACK

30" CHANNEL DEPTH, 7' HIGH, WHITE FINISH OR EQUIVALENT

DIMENSIONS:

USABLE HEIGHT: 45RU

DEPTH (US): 30

HEIGHT (US): 7'

WIDTH (US): 23.75"

STATIC LOAD CAPACITY: 2000 LBS

SQUARE HOLE

FRONT AND REAR HEAVY DUTY PERFORATED SECURITY DOOR (OR-MM20724PDHD-W)

SECURITY DOOR FRONT MOUNTING

HARDWARE (OR-MM2024DMFHD-W)

SECURITY DOOR REAR MOUNTING

HARDWARE (OR-MM2024DMRHD-W)

PDU MOUNTING BRACKET KIT (TWO

KITS PER RACK)

P/N: OR-MM20PDUMB1D2W-W

Department of Veterans Affairs

IT Operations and Services

Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd

DRAWN BY: Kevin Grzelka

CHECKED BY:

DOC VERSION No:

PROJECT No:

SHEET TITLE

T4 - TYPICAL CABINET DETAIL

PRINT DATE: Oct 5, 2017

ISSUE DATE: Oct 5, 2017

SHEET: 9 OF 15

Michael Julian, RCDD

1.0

CBOC ITS

SPECIFICATIONS

N/A

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

Solution Delivery

TYPICAL ENCLOSURE PARTS LIST

TYPICAL ENCLOSURE SPECIFICATION

NTS

TYPICAL ENCLOSURE FRONT

NTS

TYPICAL ENCLOSURE SIDE VIEW

NTS

CP3210245 F-Series TeraFrame Gen 3 Cabinet System with accessories installed

Configuration includes the following components:

Item Number Description (Qty)

FF1N-113C-E42-B F-Series TeraFrame Gen 3 Cabinet System, 45 RMU, 84.6 in. (2149mm) H x 23.6" (600mm) W x 43.30"

(1100mm) D Square-Punched Rails, 2-Pair, Single, Perforated Metal Front Door, Two Point, Keyed Swing

Handle Lock, Double Perforated Metal Rear Door, Two Point, Keyed Swing Handle Latch, Server Top Panel, 2 Solid Side Panel, Glacier White, 6-Slide Frame

024-739003-E63 Frame, 6 Slide, 23.6'' (600 mm) W x 43.3'' (1100 mm) D x 45 RMU, Glacier White (1)

024-739060-E03 Door, TeraFrame, Front, Asssembly, 23.6'' (600 mm) W x 45 RMU, Glacier White (1)

024-739064-703 Lock Kit, 2-Point, Keyed, Front Door, 45 RMU (1)

024-739050-E03 Double Door Assembly, 23.6'' (600 mm) W x 45 RMU, Glacier White (1)

024-739054-703 Lock Kit, 2-Point Latching, Keyed, Perforated Door, 45 RMU (1)

024-739140-E12 Top Panel, 2-Piece, Brush, 23.6'' (600 mm) W x 43.3'' (1100 mm) D, Glacier White

024-739046-E63 Side Panel, 6 SLIDE, 43.3'' (1100 mm) D x 45 RMU, Glacier White (2)

024-739200-002 Kit,Common Parts Parts,Teraframe,UL,White (1)

024-739110-701 PDU Bracket, Assembly, Standard, 0.7'' (17 mm) W x 3.9'' (100 mm) D x 2.4" (60 mm), Black (1)

39110-C01 PDU Bracket, Assembly, Standard, 0.7'' (17 mm) W x 3.9'' (100 mm) D x 2.4" (60 mm), Black (1)

024-739240-003 Kit, Packaging, 600 W x 1075-1200D x 42U - 48U (1)

024-739029-001 Caster Kit, Two Swivel, Two Fixed, 1.6'' (41 mm) W x 2'' (51 mm) D x 2" (41 mm) H

39085-E03 Air Dam, 6 SLIDE, 23.6'' (600 mm) W x 45 RMU, Glacier White (1)

39137-703 Baying Seal Kit, 45U (2)

39132-E00 Bottom Panel, With Brush, 23.6'' (600 mm) W x 39.4" - 47.2" (1000 - 1200 mm) D, Glacier White (1)

31920-E03 Finger Cable Manager no Cover (2)

UL2416 This Cabinet and any included accessories are UL Listed under the NWIN category per the UL2416 Standard.

UL file number E227626. Note, the UL Listing only applies to cabinets manufactured in the United States.

(VENDOR TO PROVIDE 45 RU OF PLENAFILL BLANKING PANEL PER ENCLOSURE)

TYPICAL ENCLOSURE TOP VIEW WITH FOUR (4) BRUSHED

GROMMET CABLE OPENINGS

NTS

1 1

2 2

3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35

36 36

37 37

38 38

39 39

40 40

41 41

42 42

43 43

44 44

45 45

.6

23.6"43.3"

Department of Veterans Affairs

IT Operations and Services

Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd

DRAWN BY: Kevin Grzelka

CHECKED BY:

DOC VERSION No:

PROJECT No:

SHEET TITLE

T4 - TYPICAL WORK AREA

OUTLETS

PRINT DATE: Oct 5, 2017

ISSUE DATE: Oct 5, 2017

SHEET: 10 OF 15

Michael Julian, RCDD

1.0

CBOC ITS

SPECIFICATIONS

N/A

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

Solution Delivery

TYPICAL WORK FLOOR MOUNT OUTLET

NTS

TYPICAL WALL MOUNT PHONE OUTLET

NTS

ONE (1) CATEGORY

6A 8P8C OUTLET

ACTIVE FOR

TELEPHONY

TYPICAL WORK AREA OUTLET FACEPLATE WILL BE INSTALLED WITH CATEGORY 6A COMPONENT-

COMPLIANT 8P8C MEDIA INTERFACE CONNECTORS (RJ45). EACH CONNECTOR WILL BE

TERMINATED TO HIGH QUALITY CATEGORY 6A HORIZONTAL CABLING WHICH WILL TERMINATE IN

THE TELECOMMUNICATIONS ROOM AS SPECIFIED ELSEWHERE IN THIS DESIGN PACKAGE.

ALL HORIZONTAL UTP SHALL BE CATEGORY 6A AND TERMINATED TO T568B.

TYPICAL FACEPLATE WILL BE INSTALLED WITH TWO (2) RJ45s. HIGH DENSITY FACEPLATES WILL

BE ISNTALLED WITH FOUR (4) RJ45s.

NOTES:

ALL LABELING SHALL BE ANSI/TIA/EIA/606C COMPLIANT. BLACK LETTERING ON WHITE FIELD.

MACHINE PRINTED. FURTHER GUIDANCE ON ADMINISTRATION MAY BE SPECIFIED IN OTHER

SECTIONS OF THIS DESIGN PACKAGE.

TYPICAL HIGH DENSITY WALL MOUNTED WORK AREA OUTLET

CONFIGURATION4

MINIMUM OF TWO

CATEGORY 6A 8P8C

OUTLETS FOR DATA OR

TELEPHONY

STANDARD DENSITY WALL MOUNTED WORK AREA OUTLET

CONFIGURATION2

EIGHT (8) POSITION

FACEPLATE MOUNTED ON

DUAL GANG WORKBOX.

FACEPLATE COLOR

SPECIFIED BY OTHERS.

FOUR (4) CATEGORY 6A

8P8C OUTLETS ACTIVE

FOR TELEPHONY/DATA

DUAL GANG WORKBOX

WITH TWO CONNECTOR

CHASSIS.

EIGHT (8) POSITION

FACEPLATE MOUNTED ON

DUAL GANG WORKBOX.

FACEPLATE COLOR

SPECIFIED BY OTHERS.

TWO (2) CATEGORY 6A

8P8C OUTLETS ACTIVE

FOR TELEPHONY/DATA

DUAL GANG WORKBOX

WITH ONE CONNECTOR

CHASSIS.

Department of Veterans Affairs

IT Operations and Services

Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd

DRAWN BY: Kevin Grzelka

CHECKED BY:

DOC VERSION No:

PROJECT No:

SHEET TITLE

T4 - TYPICAL RACK POWER

DISTRIBUTION

PRINT DATE: Oct 5, 2017

ISSUE DATE: Oct 5, 2017

SHEET: 11 OF 15

Michael Julian, RCDD

1.0

CBOC ITS

SPECIFICATIONS

N/A

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

Solution Delivery

NOTIONAL POWER SCHEMATIC FOR INFORMATION ONLY – NOT FOR CONSTRUCTION

TYPICAL MAIN PDU UNIT WITH REAR DETAIL AND ADAPTORS REQUIRED FOR VERTICAL PDU5

APC AP7900 Rack PDU, Switched, 1U, 15A, 100/120V, (8)5-15 APC Switched

Rack PDU , Input: 120V (OR EQUIVALENT)

30 Amp 3-Phase PDU BASE UNIT – FRONT

(ZONIT ZON-C-ZPDU1)

REQUIRES TWO 30 AMP 3-PHASE (WYE) CIRCUITS WITH L21-

30R RECEPTACLES

(OR EQUIVALENT)

30 Amp 3-Phase PDU BASE UNIT – REAR

FOUR (4) L21-20R

SIX (6) NEMA 5-15/20 T-SLOT

(OR EQUIVALENT)

110 Volt PDU FOR PLACEMENT AS NEEDED4

PDU INPUTS REQUIRE TWO

L21-30Rs

POWER SCHEMATIC FOR POWER RACK- LEVEL REDUNDANCY

The correct specification for the PDU is to feed it with a two power sources. Power inputs should originate from two independent power sources. Each input will use identical specs: WYE (5-wire) configured, 208V, 30A, three-phase, terminating in a NEMA L21-30R locking receptacle. The neutral conductor should be upsized one gauge to match the upsized neutral conductors in the PDU units. The neutral "upsizing" should ideally be continued in the power distribution system back to the UPS or transformer winding pole. This increases the efficiency of the power distribution system and suppresses harmonics in the system.

NOTE:

RACK/ENCLOSURE

ZONE PDU

PDUB

PDUA

LEG1 LEG2

BUS A BUS B

RACK/ENCLOSURE

RACKED EQUIPMENT

PDUB

PDUA

PS1 PS2

ONE ZONE PDU FOR TWO

SERVER CABINETS

NOTE:

THIS DESIGN PROVIDES DIVERSE POWER INPUTS FOR ACTIVE EQUIPMENT BY SPLITTING THE SOURCE POWER

ACROSS TWO INPUTS ON THE ZONE PDU. EACH INPUT WILL SUPPORT TWO EQUIPMENT-FACING PDUs. EACH

SERVER CABINET WILL CONTAIN A MINIMUM OF TWO EQUIPMENT-FACING PDUs – EACH WILL BE ENERGIZED BY

SEPARATE ZONE PDU INPUTS.

208 VOLT PDU FOR EQUIPMENT POWER – TO BE ENERGIZED BY ZONE PDU3

TYPICAL POWER

DISTRIBUTION

REQUIRES ONE (1) L21-20R

APC AP8961 Rack PDU 2G,Switched, Zero U,5.7kW, 200/

208V,(21)C13 & (3)C19, 6' cord

Temp/Humidity Out USB

Network In Serial

Reset

- Overload

- Warning

- OK

Select

Scroll

Main Menu by Schne ider Elec tr ic

Rack PDU

L3-L1

17 18 19 20 21 22 23 24

L1-L2

1 2 3 4 5 6 7 8

L2-L3

9 10 11 12 13 14 15 16

20A 120/ 208V

Y

DUAL 3-PHASE 480 VOLT INPUTS

(WITH 480 – 208 TRANSFORMER)

BUS OR FEEDER

3-PHASE 208-VOLT 30-AMP PDU

PDU PDU

COMPUTER

ZONE PDU

“ZERO U” VERTICAL PDU

DUAL POWER SUPPLY

DUAL INPUT UPS 250-500 kVA

UPS RACK MOUNT UPS

RACK-MOUNTED UPS

RACKED EQUIPMENT

PS1 PS2

RACK-MOUNTED UPS

MAIN

POWER

POWER

ON

GROUP B

0FF

0N

MAIN

POWER

POWER

ON

GROUP A

0FF

0N

GROUP A

0FF

0N

A

0FF

0N

B

0FF

0N

C

0FF

0N

0FF

0N

0FF

0N

GROUP B

0FF

0N

A

0FF

0N

B

0FF

0N

C

0FF

0N

0FF

0N

0FF

0N

A B CA B C

A

B

OZ

GROUP B

OX OY

OX

GROUP A

OY OZ

OY

GROUP B

OZ OX

OZ

GROUP A

OX OY

LEG 1 LEG 2 LEG 2LEG 1

PHASE Z PHASE Y PHASE X

GRP A

GRP B LEG 1

LEG 2 GRP A

GRP B LEG 1

LEG 2 GRP A

GRP B LEG 1

LEG 2

Department of Veterans Affairs

IT Operations and Services

Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd

DRAWN BY: Kevin Grzelka

CHECKED BY:

DOC VERSION No:

PROJECT No:

SHEET TITLE

T4 - POWER DISTRIBUTION

PRINT DATE: Oct 5, 2017

ISSUE DATE: Oct 5, 2017

SHEET: 12 OF 15

Michael Julian, RCDD

1.0

CBOC ITS

SPECIFICATIONS

N/A

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

Solution Delivery

T e m p

/H u m id it y

O u t U

S B

N e tw o rk In

S e ri a l

R e s e t

O v e rl o a d

W a rn in g

O

K

S e le c t

S c ro ll

M a in M e n u b y

S c h n e id e r

E le c tr ic

R a c k

P D

U

L

-L

L

-L

L

-L

T e m p

/H u m id it y

O u t U

S B

N e tw o rk In

S e ri a l

R e s e t

O v e rl o a d

W a rn in g

O

K

S e le c t

S c ro ll

M a in M e n u b y

S c h n e id e r

E le c tr ic

R a c k

P D

U

L

-L

L

-L

L

-L

1 1

2 2

3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35

36 36

37 37

38 38

39 39

40 40

41 41

42 42

43 43

44 44

45 45

PDU BRACKET P/N:

OR-MM20PDUMB1D2W-B

(FOR OTRONICS RACK ONLY)

POWER SCHEMATIC RACKS – REAR VIEW

POWER DISTRIBUTION

1 1

2 2

3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35

36 36

37 37

38 38

39 39

40 40

41 41

42 42

43 43

44 44

45 45

A

B

OZ

GROUP B

OX OY

OX

GROUP A

OY OZ

OY

GROUP B

OZ OX

OZ

GROUP A

OX OY

LEG 1 LEG 2 LEG 2LEG 1

PHASE Z PHASE Y PHASE X

GRP A

GRP B LEG 1

LEG 2 GRP A

GRP B LEG 1

LEG 2 GRP A

GRP B LEG 1

LEG 2

L21-30P “A” SIDE

REQUIRES A 208V, 30A, THREE-PHASE WHIP,

TERMINATING IN A NEMA L21-30R LOCKING

RECEPTACLE. THE NEUTRAL CONDUCTOR SHOULD BE

UPSIZED ONE GAUGE TO MATCH THE UPSIZED

NEUTRAL CONDUCTORS IN THE ZONE PDU UNITS.

L21-30P “B” SIDE

REQUIRES A 208V, 30A, THREE-PHASE WHIP,

TERMINATING IN A NEMA L21-30R LOCKING

RECEPTACLE. THE NEUTRAL CONDUCTOR SHOULD BE

UPSIZED ONE GAUGE TO MATCH THE UPSIZED

NEUTRAL CONDUCTORS IN THE ZONE PDU UNITS

ZONEIT

30 Amp 3-Phase PDU BASE UNIT – FRONT

(ZONIT ZON-C-ZPDU1)

REQUIRES TWO 30 AMP 3-PHASE (WYE) CIRCUITS

WITH L21-30R RECEPTACLES

(OR EQUIVALENT)

APC AP8961 RACK PDU

2G,SWITCHED, ZERO U,5.7KW,

200/208V,(21)C13 & (3)C19, 6'

CORD

RACK-MOUNTED 5KW 208V UNINTERRUPTIBLE

POWER SUPPLY (UPS) WITH NEMA 20A L21-

20P INPUT AND L21-20R OUTPUT. MODEL

EXAMPLE: ZC0517700110000 5 KW 208V W/

20A 5W IN/5W OUT, ONE INTERNAL BATTERY

STRING

T e m p

/H u m id it y

O u t U

S B

N e tw o rk In

S e ri a l

R e s e t

O v e rl o a d

W a rn in g

O

K

S e le c t

S c ro ll

M a in M e n u b y

S c h n e id e r

E le c tr ic

R a c k

P D

U

L

-L

L

-L

L

-L

T e m p

/H u m id it y

O u t U

S B

N e tw o rk In

S e ri a l

R e s e t

O v e rl o a d

W a rn in g

O

K

S e le c t

S c ro ll

M a in M e n u b y

S c h n e id e r

E le c tr ic

R a c k

P D

U

L

-L

L

-L

L

-L

Department of Veterans Affairs

IT Operations and Services

Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd

DRAWN BY: Kevin Grzelka

CHECKED BY:

DOC VERSION No:

PROJECT No:

SHEET TITLE

T5 - COLOR CODING

PRINT DATE: Oct 5, 2017

ISSUE DATE: Oct 5, 2017

SHEET: 13 OF 15

Michael Julian, RCDD

1.0

CBOC ITS

SPECIFICATIONS

N/A

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

Solution Delivery

PATCH PANEL LABEL FIELD COLOR CODING

Department of Veterans Affairs

IT Operations and Services

Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd

DRAWN BY: Kevin Grzelka

CHECKED BY:

DOC VERSION No:

PROJECT No:

SHEET TITLE

T5 - CBOC ITS NAMING

STANDARDS

PRINT DATE: Oct 5, 2017

ISSUE DATE: Oct 5, 2017

SHEET: 14 OF 15

Michael Julian, RCDD

1.0

CBOC ITS

SPECIFICATIONS

N/A

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

Solution Delivery

· RACK = RK1 THROUGH RK4. LABELED LEFT TO RIGHT WHEN

LOOKING AT THE FRONT OF THE RACK. APPLIES TO RACKS AND

CABINETS.

· UTP PATCH PANEL = CPL-RACK NAME-01 THROUGH 45. EXAMPLE:

CPL-RK1-01 FOR THE PANEL LOCATED IN RACK UNIT #1 IN RACK

#1.

· UTP PATCH PANEL POSITION = PANEL ID.01 THROUGH 24.

EXAMPLE CPL-RK1-01.01

· FIBER DISTRIBUTION PANEL = FPL-RACK NAME-01 THROUGH 45.

EXAMPLE: FPL-RK1-01 FOR THE PANEL IN RACK UNIT #1 RACK #1.

· FIBER DISTRIBUTION CASSETTE = FCS-RACK NAME-01

THROUGH 45.1 THROUGH 3. EXAMPLE: FCS-RK1-01.1 FOR THE

CASSETTE IN POSITION #1 IN PANEL LOCATED IN RACK UNIT

#1 IN RACK #1.

· UTP PATCH CORDS = CCA[SOURCE.PORT]/[DESTINATION.PORT].

EXAMPLE CCA[CPL-RK1-01.01]/[CPL-RK2-02.02] AS A PATCH CORD

CONNECTING PORT #1 IN THE COPPER PATCH PANEL LOCATED IN

RACK #1, RACK UNIT #1 WITH PORT 2 LOCATED IN RACK 2, RACK

UNIT #2.

· FIBER PATCH CORDS = FCA[SOURCE.PORT]/

[DESTINATION.PORT]. EXAMPLE FCA[FDP-RK1-01.01.01]/[FDP-RK2-

02.02.02] AS A PATCH CORD CONNECTING PORT #1 IN THE FIBER

PATCH PANEL LOCATED IN RACK #1, RACK UNIT #1 WITH PORT 2

LOCATED IN RACK 2, RACK UNIT #2.

· FACEPLATE = TR ROOM NUMBER-PATCH PANEL ID.PORT.

EXAMPLE. 1A-CPL-RK1-01.1 FOR TELECOMMUNICATIONS ROOM 1,

UTP PANEL IN RACK #1, RACK UNIT #1, PORT POSITION #1.

EXAMPLE INSIDE PLANT ADMINISTRATION

Department of Veterans Affairs

IT Operations and Services

Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd

DRAWN BY: Kevin Grzelka

CHECKED BY:

DOC VERSION No:

PROJECT No:

SHEET TITLE

T5 - SPECIFICATIONS

PRINT DATE: Oct 5, 2017

ISSUE DATE: Oct 5, 2017

SHEET: 15 OF 15

Michael Julian, RCDD

1.0

CBOC ITS

SPECIFICATIONS

N/A

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

Solution Delivery

TELECOMMUNICATIONS MEDIA AND INTERFACES SPECIFICATION

SPECIFICATIONPRIMARY ATTRIBUTEID SECONDARY ATTRIBUTE

1 COPPER PATCH PANELS

PERFORMANCE CATEGORY CATEGORY 6A (10 GBE)

POSITION COUNT 24 (4 SIX-PORT MODULES)

FORM FACTOR ANGLED

SIZE ONE RACK UNIT

COLOR CODING BLACK

CASSETTE CAPACITY 24 STRAND (TWO 12-STRAND MULTI-FIBER PUSH ON (MPO))

CASSETTE USER INTERFACES LC QUAD CONNECTORS

FIBER DISTRIBUTION CASSETTES CASSETTE BACKBONE INTERFACES MPO

PERFORMANCE CHARACTERISTICS OM4 LASER ENHANCED 40 GBE 50/125 MULTIMODE

FORM FACTOR ONE (1) RU

3 UTP (HORIZONTAL AND FIRST LEVEL BACKBONE)

PERFORMANCE CATEGORY CATEGORY 6A (10 GBE)

PERFORMANCE SPECIFICATIONS MEETS OR EXCEEDS TIA-EIA-568-C.2-10, TSB-155.

JACKET COLOR BLUE (HORIZONTAL), WHITE (1ST LEVEL BACKBONE)

SIZE ONE RACK UNIT

COLOR CODING BLACK

PERFORMANCE CATEGORY OM4 LASER ENHANCED TO 40 GIGABIT ETHERNET (GBE

PERFORMANCE SPECIFICATIONS

LASER OPTIMIZED 50/125 ΜM FIBERS WITH EFFECTIVE MODAL

BANDWIDTH OF AT LEAST 4,700 MHZ∙KM AT 850 NM

FIBER (HORIZONTAL AND FIRST LEVEL BACKBONE)

MODE MULTIMODE

JACKET COLOR AQUA

MEDIA CONNECTOR PRE-TERMINATED WITH MPO, TYPE A

STRAND COUNT 12

BUNDLING LOOSE TUBE

5 UTP PATCH CORDS

PERFORMANCE CATEGORY CATEGORY 6A, 26-GAUGE, STRANDED

PERFORMANCE SPECIFICATIONS CENTER TUNED TO HORIZONTAL MEDIA

JACKET COLOR BLUE

TERMINATION METHOD FACTORY PRE-TERMINATED

PERFORMANCE CATEGORY OM4 LASER ENHANCED TO 40 GIGABIT ETHERNET (GBE

PERFORMANCE SPECIFICATIONS OM4

FIBER PATCH CORDS MODE MULTIMODE

JACKET COLOR AQUA

MEDIA CONNECTOR PRE-TERMINATED WITH DUPLEX LC

CBOC INSIDE PLANT ITS SPEC V1.vsd
COVER
FRONT MATTER
SYMBOLS
T3- GENERIC HEALTH CARE FACILITY EQUIPMENT ROOM
T3-GENERIC HEALTH CARE FACILITY TR
T3 - TYPICAL BACKBOARD ELEVATION
T3 - TYPICAL RACK ELEVATION
T4 - TYPICAL RACK DETAIL
T4 - TYPICAL CABINET DETAIL
T4 - TYPICAL WORK AREA OUTLETS
T4 - TYPICAL RACK POWER DISTRIBUTION
T4 - POWER DISTRIBUTION
T5 - COLOR CODING
T5 - CBOC ITS NAMING STANDARDS
T5 - SPECIFICATIONS