I. IT Specifications.pdf
PDF 1 MB Posted
- Attached to
- Richmond, TX. Proposal Amendment #1 Federal contract opportunity
- Solicitation number
- 36C25622R0154
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment 1 - Richmond TX OPC.pdf | ||
| C. GSA FORM 3516.pdf | ||
| J. Foreign+Ownership+and+Financing+Representation+Form+for+High+Security+Leased+Space+-+GSAR+Representation+552-270-33+%28Jun.+2021%29.pdf | ||
| A. Global_Lease_Template_L100_10_ 2021100.pdf | ||
| E. Attachment A B.pdf | ||
| D. GSA_Form_3517B_Rev_07_2021c90.pdf | ||
| F. Global Proposal to Lease Space Form 1364.pdf | ||
| Global_RLP_Template_R100_10_202199.pdf | ||
| K. FAR+52.204-24+Representation.pdf | ||
| Security Requirements - Facility Security Level I.pdf | ||
| G. GSA Form 1217 Lessor's Annual Cost Statement.pdf | ||
| H. GSA Form 12000 for Prelease FPLS (Parts AB).docx | DOCX document |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT:
DRAWING No:
Department of Veterans Affairs
IT Operations and Services
Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd
DRAWN BY: Kevin Grzelka
CHECKED BY:
DOC VERSION No:
PROJECT No:
SHEET TITLE
COVER
PRINT DATE: Oct 5, 2017
ISSUE DATE: Oct 5, 2017
SHEET: 1 OF 15
Michael Julian, RCDD
1.0
CBOC ITS
SPECIFICATIONS
N/A
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
Solution Delivery
COVER PAGE
DEVELOPED BY:
DATA CENTER ENGINEERING
DATA CENTER & CLOUD ENGINEERING
COMMUNITY BASED OUTPATIENT CLINIC (CBOC)
INSIDE PLANT
INFORMATION TRANSPORT SYSTEMS SPECIFICATIONS
Department of Veterans Affairs
IT Operations and Services
Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd
DRAWN BY: Kevin Grzelka
CHECKED BY:
DOC VERSION No:
PROJECT No:
SHEET TITLE
FRONT MATTER
PRINT DATE: Oct 5, 2017
ISSUE DATE: Oct 5, 2017
SHEET: 2 OF 15
Michael Julian, RCDD
1.0
CBOC ITS
SPECIFICATIONS
N/A
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
Solution Delivery
FRONT MATTER
DESIGN OBJECTIVES
1. MODULARITY: THIS DESIGN IS HIGHLY MODULAR.
3.CABLE PLANT: UTP CATEGORY 6A CABLE PLANT WILL SUPPORT 10 GIGABIT ETHERNET.
FIBER PLANT WILL UTILIZE LASER ENHANCED OM4 40 GbE RATED 50/125
MULTIMODE.
Standard or Document Description
ANSI/TIA-606-C, Administration Standard for Telecommunications Infrastructure
ANSI/TIA-606-B-1, Administration Standard for Telecommunications Infrastructure Addendum 1- Automated Infrastructure Management Systems - Addendum to ANSI/TIA-606-B
ANSI/TIA-607-C, Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises
ANSI/TIA-607-C-1, Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises - Addendum to TIA-607-C
ANSI/TIA-942-A, Telecommunications Infrastructure Standard for Data Centers
ANSI/TIA-942-A-1, Telecommunications Infrastructure Standard for Data Centers Addendum 1- Cabling Guidelines for Data Center Fabrics - Addendum to TIA-942-A
ANSI/TIA-1179, Healthcare Facility Telecommunications Infrastructure
BICSI 002, Data Center Design and Implementation Best Practices
BICSI ITSIMM, Information Technology Systems Installation Methods Manual (ITSIMM) - 7th Edition
BICSI/NECA 568, Standard for Installing Commercial Building Telecommunications Cabling
BICSI/NECA 607 Standard for Telecommunications Bonding and Grounding Planning and Installation Methods for Commercial Buildings 2011
CSI MASTERFORMAT ™ 2004 EDITION NUMBERS & TITLES
Construction Specifications Institute (CSI)
NFPA 70, National Electrical Code
NFPA 75, Standard for the Fire Protection of Information Technology Equipment
2. FLEXIBLE: THIS DESIGN IS FLEXIBLE TO ACCOMMODATE CHANGES TO FLOOR PLANS.
THIS DRAWING IS SCALED TO 11X17 FORMAT.
THIS DRAWING SET REPRESENTS THE COMPUTING AND PASSIVE INFRASTRUCTURE
DESIGN AND RACK ELEVATIONS FOR A GENERIC HEALHCARE FACILITY EQUIPMENT
ROOM (ER) AND A GENERIC TELECOMMUNICATION ROOM (TR). UNLESS NOTED
OTHERWISE, ACTIVE EQUIPMENT WILL BE FURNISHED AND INSTALLED BY VA OR
VA CONTRACTORS. THE STRUCTURED CABLING PLANT INSTALLERS WILL FURNISH
AND INSTALL PASSIVE CABLE PLANT INFRASTRUCTURE INCLUDING HORIZONTAL
CABLE MANAGERS, UTP AND FO HORIZONTAL CABLE, PATCH PANELS, PATHWAY
RACKS, FIBER DISTRIBUTION CABINETS AND FIBER CASSETTES.
T0 – Campus or Site Plans - Exterior Pathways and Inter-Building Backbones
T1 – Layout of complete building per floor - Serving Zone Boundaries, Backbone Systems, and Horizontal Pathways
T2 – Serving Zones Drawings - Drop Locations and Cable ID’s
T3 – Communication Equipment Rooms - Plan Views - Tech and AMEP /Elevations - Racks and Walls Elevations
T4 – Typical Detail Drawings - Faceplate Labeling, Firestopping, ADA, Safety, DOT, etc...
T5 – Schedules (Cabling and Equipment Spreadsheets) for cutovers
DRAWING TYPE DEFINITIONS
PURPOSE:
FRONT MATTER
Department of Veterans Affairs
IT Operations and Services
Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd
DRAWN BY: Kevin Grzelka
CHECKED BY:
DOC VERSION No:
PROJECT No:
SHEET TITLE
SYMBOLS
PRINT DATE: Oct 5, 2017
ISSUE DATE: Oct 5, 2017
SHEET: 3 OF 15
Michael Julian, RCDD
1.0
CBOC ITS
SPECIFICATIONS
N/A
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
Solution Delivery
T2 SYMBOLS
DATA
WALL PHONEW
FLOOR MOUNT
FIRE ALARM PANELF
EMERGENCY PHONEE
SECURITY OR FIRE ALARM DIALERSD
CR SECURITY SYSTEM CARD READER
CC CLOSED CIRCUIT SURVEILLANCE CAMERA
OUTLET
MD MOTION DETECTOR
T3 SYMBOLS
TGB
T
TWIST LOCK RECEPTACLE
THERMOSTAT
110 RECEPTACLE
TELECOMMUNICATIONS
GROUNDING
BUSBAR
STRIP LIGHT
HORIZONTAL SLEEVE (SIZE AS
INDICATED)
CONDUIT (SIZE AS INDICATED)
VERTICAL SLEEVE (SIZE AS
INDICATED)
CABLE RACEWAY
T4 SYMBOLS
CHATSWORTH SERVER
RACK. 24"WIDE X 47.5"
DEEP
QUADRUPLEX OUTLET
TELECOMMUNICATIONS
OUTLET
PERFORATED FLOOR
TILE
OR-60401015
1 1
2 2
3 3
4 4
5 5
OR-M2LCQ24-50E
1 12
24 13
OR-MM6HM61RU
FC01U-P
A
B
OZ
GROUP B
OX OY
OX
GROUP A
OY OZ
OY
GROUP B
OZ OX
OZ
GROUP A
OX OY
LEG 1 LEG 2 LEG 2LEG 1
PHASE Z PHASE Y PHASE X
GRP A
GRP B LEG 1
LEG 2 GRP A
GRP B LEG 1
LEG 2 GRP A
GRP B LEG 1
LEG 2
MAIN
POWER
POWER
ON
GROUP B
0FF
0N
MAIN
POWER
POWER
ON
GROUP A
0FF
0N
GROUP A
0FF
0N
A
0FF
0N
B
0FF
0N
C
0FF
0N
0FF
0N
0FF
0N
GROUP B
0FF
0N
A
0FF
0N
B
0FF
0N
C
0FF
0N
0FF
0N
0FF
0N
A B CA B C
zPDU (R/F)
L21-30
20A 120/ 208V
Y
L21-20
IEC 320-C19
IEC 320-C20
IEC 320-C13
IEC 320-C14
DATA / TELEPHONE
TELEPHONE SERVICE PANEL
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
30 30
31 31
32 32
33 33
34 34
35 35
36 36
37 37
38 38
39 39
40 40
41 41
42 42
43 43
44 44
45 45
OR-MM20730-W.
30" DEEP CHANNEL
7'H. 45RU.
ORTRONICS MM20
CHANNEL RACK
SYMBOLS
Department of Veterans Affairs
IT Operations and Services
Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd
DRAWN BY: Kevin Grzelka
CHECKED BY:
DOC VERSION No:
PROJECT No:
SHEET TITLE
T3- GENERIC HEALTH CARE
FACILITY EQUIPMENT ROOM
PRINT DATE: Oct 5, 2017
ISSUE DATE: Oct 5, 2017
SHEET: 4 OF 15
Michael Julian, RCDD
1.0
CBOC ITS
SPECIFICATIONS
N/A
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
Solution Delivery
EQUIPMENT ROOM
GENERIC FLOOR PLAN FOR HEALTH CARE FACILITY EQUIPMENT ROOM
AC
SERVICE PANEL FOR
DEDICATED ROOM AIR
CONDITIONING. NON-IT
LOAD ONLY. SHALL BE
EQUIPPED WITH SCHNEIDER
EM3500 SERIES DIN RAIL
METER OR EQUIVALENT
SERVICE PANEL FOR RACK
POWER IN
TELECOMMUNICATION ROOM. IT
LOAD ONLY. SHALL BE
EQUIPPED WITH SCHNEIDER
EM3500 SERIES DIN RAIL METER
OR EQUIVALENT
TWO (2) CONDUITS
INTERCONNECTING NETWORK
SUPPORT CENTER WITH ENTRANCE
FACILITY. TRADE SIZE 2
HORIZONTAL SLOT OR SLEEVE FOR
CABLING FROM WORK AREA OUTLETS
AND TELECOMMUNICATIONS ROOMS
L21-30R
CABLOFIL 2"X16" CF 54/400
CABLE TRAY
AC GRADE ¾’ PLYWOOD
BACKBOARD PAINTED HIGH-
GLOSS WHITE. MOUNTED 6"
AFF, 3 WALLS
MINIMUM 170 FT21 WITH STATIC
DISSIPATING FLOOR, NO DROP
CEILING, WALLS FULL HEIGHT TO
FLOOR ABOVE
VERTICAL CABLE MANAGER WITH
DOOR. ORTRONICS OR-
MM10VMD706-W 6" VERTICAL CABLE
MANAGEMENT CAGE
TYPICAL UNSWITCHED
QUADRAPLEX CONVENIENCE
OUTLETS
TELECOMMUNICATIONS
GROUNDING BUS BAR TO
ELECTRICAL GROUND AT
MAIN PANEL.
SPLIT PACKAGE AIR CONDITIONER
(32,600 BTU/H)
AC
L21-30R
ADDITIONAL SPLIT PACKAGE AIR
CONDITIONER (32,600 BTU) WHEN
NECESSARY
T
AIR CONDITIONER THERMOSTAT
OR-MM20730-W. 30" DEEP CHANNEL
7'H. 45RU. ORTRONICS MM20
CHANNEL RACK
SERVER CABINET, 45U, 24"X48"
(NOMINAL), SQUARE PUNCHED RAIL,
SINGLE PERFORATED FRONT DOOR,
SOLID REAR DOOR, TWO-POINT
KEYED LOCKS, WHITE,SOLID SIDE
PANELS
3'-0"
RK-1 RK-2 RK-3 RK-4
NOTE:
THERE SHALL BE A MINIMUM OF ONE
TELECOMMUNICATIONS ROOM (TR) PER FLOOR.
THE EQUIPMENT ROOM CAN SERVE AS A TR. ADDITIONAL
ROOMS SHOULD BE PROVIDED WHEN:
A) THE FLOOR AREA TO BE SERVED EXCEEDS 1000 M2 (10
000 FT2);
OR
B) THE HORIZONTAL DISTRIBUTION DISTANCE TO THE
WORK AREA EXCEEDS 90 M (295 FT).
NO RAISED FLOOR.
C
PIV/
KEYPAD
Department of Veterans Affairs
IT Operations and Services
Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd
DRAWN BY: Kevin Grzelka
CHECKED BY:
DOC VERSION No:
PROJECT No:
SHEET TITLE
T3-GENERIC HEALTH CARE
FACILITY TR
PRINT DATE: Oct 5, 2017
ISSUE DATE: Oct 5, 2017
SHEET: 5 OF 15
Michael Julian, RCDD
1.0
CBOC ITS
SPECIFICATIONS
N/A
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
Solution Delivery
TELECOMMUNICATIONS
ROOM
GENERIC FLOOR PLAN FOR HEALTH CARE FACILITY TELECOMMUNICATIONS ROOMS
AC
SERVICE PANEL FOR
DEDICATED ROOM AIR
CONDITIONING. NON-IT
LOAD ONLY. SHALL BE
EQUIPPED WITH SCHNEIDER
EM3500 SERIES DIN RAIL
METER OR EQUIVALENT
SERVICE PANEL FOR RACK
POWER IN
TELECOMMUNICATION ROOM. IT
LOAD ONLY. SHALL BE
EQUIPPED WITH SCHNEIDER
EM3500 SERIES DIN RAIL METER
OR EQUIVALENT
TWO (2) CONDUITS
INTERCONNECTING NETWORK
SUPPORT CENTER WITH ENTRANCE
FACILITY. TRADE SIZE 2
HORIZONTAL SLOT OR SLEEVE FOR
CABLING FROM WORK AREA OUTLETS
AND TELECOMMUNICATIONS ROOMS
L21-30R
CABLOFIL 2"X16" CF 54/400
CABLE TRAY
AC GRADE ¾’ PLYWOOD
BACKBOARD PAINTED HIGH-
GLOSS WHITE. MOUNTED 6"
AFF, 3 WALLS
MINIMUM 170 FT21 WITH STATIC
DISSIPATING FLOOR, NO DROP
CEILING, WALLS FULL HEIGHT TO
FLOOR ABOVE
VERTICAL CABLE MANAGER WITH
DOOR. ORTRONICS OR-
MM10VMD706-W 6" VERTICAL CABLE
MANAGEMENT CAGE
TYPICAL UNSWITCHED
QUADRAPLEX CONVENIENCE
OUTLETS
TELECOMMUNICATIONS
GROUNDING BUS BAR
SPLIT PACKAGE AIR CONDITIONER
(32,600 BTU/H)
AC
L21-30R
ADDITIONAL SPLIT PACKAGE AIR
CONDITIONER (32,600 BTU) WHEN
NECESSARY
T
AIR CONDITIONER THERMOSTAT
OR-MM20730-W. 30" DEEP CHANNEL
7'H. 45RU. ORTRONICS MM20
CHANNEL RACK
3'-0"
NOTE:
THERE SHALL BE A MINIMUM OF ONE
TELECOMMUNICATIONS ROOM (TR) PER FLOOR.
THE EQUIPMENT ROOM CAN SERVE AS A TR. ADDITIONAL
ROOMS SHOULD BE PROVIDED WHEN:
A) THE FLOOR AREA TO BE SERVED EXCEEDS 1000 M2 (10
000 FT2);
OR
B) THE HORIZONTAL DISTRIBUTION DISTANCE TO THE
WORK AREA EXCEEDS 90 M (295 FT).
NO RAISED FLOOR.
RK-1 RK-2 RK-3 RK-4
C
PIV/
KEYPAD
Department of Veterans Affairs
IT Operations and Services
Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd
DRAWN BY: Kevin Grzelka
CHECKED BY:
DOC VERSION No:
PROJECT No:
SHEET TITLE
T3 - TYPICAL BACKBOARD
ELEVATION
PRINT DATE: Oct 5, 2017
ISSUE DATE: Oct 5, 2017
SHEET: 6 OF 15
Michael Julian, RCDD
1.0
CBOC ITS
SPECIFICATIONS
N/A
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
Solution Delivery
AC AC T
3'-0"
RESERVED
VIDEO DISTRIBUTION
WAN/DEMARK
SECURITY POWER METERING
FIRE ALARM/
ANNOUNCIATOR
TYPICAL BACKBOARD
ELEVATION
Department of Veterans Affairs
IT Operations and Services
Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd
DRAWN BY: Kevin Grzelka
CHECKED BY:
DOC VERSION No:
PROJECT No:
SHEET TITLE
T3 - TYPICAL RACK
ELEVATION
PRINT DATE: Oct 5, 2017
ISSUE DATE: Oct 5, 2017
SHEET: 7 OF 15
Michael Julian, RCDD
1.0
CBOC ITS
SPECIFICATIONS
N/A
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
Solution Delivery
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
30 30
31 31
32 32
33 33
34 34
35 35
36 36
37 37
38 38
39 39
40 40
41 41
42 42
43 43
44 44
45 45
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
30 30
31 31
32 32
33 33
34 34
35 35
36 36
37 37
38 38
39 39
40 40
41 41
42 42
43 43
44 44
45 45
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
30 30
31 31
32 32
33 33
34 34
35 35
36 36
37 37
38 38
39 39
40 40
41 41
42 42
43 43
44 44
45 45
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
30 30
31 31
32 32
33 33
34 34
35 35
36 36
37 37
38 38
39 39
40 40
41 41
42 42
43 43
44 44
45 45
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
MAIN
POWER
POWER
ON
GROUP B
0FF
0N
MAIN
POWER
POWER
ON
GROUP A
0FF
0N
GROUP A
0FF
0N
A
0FF
0N
B
0FF
0N
C
0FF
0N
0FF
0N
0FF
0N
GROUP B
0FF
0N
A
0FF
0N
B
0FF
0N
C
0FF
0N
0FF
0N
0FF
0N
A B CA B C
BladeUPS
Powerware
BladeUPS
Powerware
BladeUPS
Powerware
BladeUPS
Powerware
MAIN
POWER
POWER
ON
GROUP B
0FF
0N
MAIN
POWER
POWER
ON
GROUP A
0FF
0N
GROUP A
0FF
0N
A
0FF
0N
B
0FF
0N
C
0FF
0N
0FF
0N
0FF
0N
GROUP B
0FF
0N
A
0FF
0N
B
0FF
0N
C
0FF
0N
0FF
0N
0FF
0N
A B CA B C
MODE
CONSOL E
37X
Catalyst 3850 48 PoE+
25X 36X13X 24X01X 12X 48X
Po EDUPLX
ACTV
STAT
SYST
SPEED
XPS
STACK
S-PWR
C3850-NM-4-10G
G1 G2 G3 G4
NETWORK MODULE
TE3 TE4TE1 TE2
MODE
CONSOL E
37X
Catalyst 3850 48 PoE+
25X 36X13X 24X01X 12X 48X
Po EDUPLX
ACTV
STAT
SYST
SPEED
XPS
STACK
S-PWR
C3850-NM-4-10G
G1 G2 G3 G4
NETWORK MODULE
TE3 TE4TE1 TE2
MODE
CONSOL E
37X
Catalyst 3850 48 PoE+
25X 36X13X 24X01X 12X 48X
Po EDUPLX
ACTV
STAT
SYST
SPEED
XPS
STACK
S-PWR
C3850-NM-4-10G
G1 G2 G3 G4
NETWORK MODULE
TE3 TE4TE1 TE2
MODE
CONSOL E
37X
Catalyst 3850 48 PoE+
25X 36X13X 24X01X 12X 48X
Po EDUPLX
ACTV
STAT
SYST
SPEED
XPS
STACK
S-PWR
C3850-NM-4-10G
G1 G2 G3 G4
NETWORK MODULE
TE3 TE4TE1 TE2
MODE
CONSOL E
37X
Catalyst 3850 48 PoE+
25X 36X13X 24X01X 12X 48X
Po EDUPLX
ACTV
STAT
SYST
SPEED
XPS
STACK
S-PWR
C3850-NM-4-10G
G1 G2 G3 G4
NETWORK MODULE
TE3 TE4TE1 TE2
RK-1
MAXIMUM OF 12 ANGLED CATEGORY 6A, 24 PORT PATCH
PANELS PER RACK. IF MORE THAN TWELVE (12) PATCH
PANELS ARE REQUIRED, INSTALL NEXT SET IN RK-3.
1 RU BLANKING PANELS BETWEEN LOWEST
PATCH PANEL AND RU32
1 RU CABLE MANAGER. SIX POSITION SPACING
WITH DOOR AT RU31
3850 POE LAN SWITCH WITH 1100 WATT
POWER SUPPLIES. MAX OF SIX (6) PER RACK.
2 RU CABLE MANAGER. SIX POSITION SPACING
WITH DOOR.
1 RU CABLE MANAGER. SIX POSITION
SPACING WITH DOOR.
ZONE PDU
UPS
RK-2 RK-3
RK-4
TYPICAL RACK ELEVATION FOR HEALTH CARE FACILITY TELECOMMUNICATIONS ROOMS
TYPICAL RACK ELEVATION
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
MODE
CONSOL E
37X
Catalyst 3850 48 PoE+
25X 36X13X 24X01X 12X 48X
Po EDUPLX
ACTV
STAT
SYST
SPEED
XPS
STACK
S-PWR
C3850-NM-4-10G
G1 G2 G3 G4
NETWORK MODULE
TE3 TE4TE1 TE2
MODE
CONSOL E
37X
Catalyst 3850 48 PoE+
25X 36X13X 24X01X 12X 48X
Po EDUPLX
ACTV
STAT
SYST
SPEED
XPS
STACK
S-PWR
C3850-NM-4-10G
G1 G2 G3 G4
NETWORK MODULE
TE3 TE4TE1 TE2
MODE
CONSOL E
37X
Catalyst 3850 48 PoE+
25X 36X13X 24X01X 12X 48X
Po EDUPLX
ACTV
STAT
SYST
SPEED
XPS
STACK
S-PWR
C3850-NM-4-10G
G1 G2 G3 G4
NETWORK MODULE
TE3 TE4TE1 TE2
MODE
CONSOL E
37X
Catalyst 3850 48 PoE+
25X 36X13X 24X01X 12X 48X
Po EDUPLX
ACTV
STAT
SYST
SPEED
XPS
STACK
S-PWR
C3850-NM-4-10G
G1 G2 G3 G4
NETWORK MODULE
TE3 TE4TE1 TE2
MODE
CONSOL E
37X
Catalyst 3850 48 PoE+
25X 36X13X 24X01X 12X 48X
Po EDUPLX
ACTV
STAT
SYST
SPEED
XPS
STACK
S-PWR
C3850-NM-4-10G
G1 G2 G3 G4
NETWORK MODULE
TE3 TE4TE1 TE2
SPACE
RESERVED
FOR WAN
ROUTERS, IP
PBX,
SECURITY
EQUIPMENT,
ETC.
SPACE
RESERVED
FOR
SERVERS.
SERVICE PROVIDER MAIN CROSS CONNECT
FIRST LEVEL BACKBONE (FIBER)
Department of Veterans Affairs
IT Operations and Services
Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd
DRAWN BY: Kevin Grzelka
CHECKED BY:
DOC VERSION No:
PROJECT No:
SHEET TITLE
T4 - TYPICAL RACK DETAIL
PRINT DATE: Oct 5, 2017
ISSUE DATE: Oct 5, 2017
SHEET: 8 OF 15
Michael Julian, RCDD
1.0
CBOC ITS
SPECIFICATIONS
N/A
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
Solution Delivery
6" WIDE VERTICAL CABLE MANAGEMENT
P/N: OR-MM20VMD706 (OR EQUIVALENT)
MM20 VERTICAL CABLE MANAGEMENT "CAGE", WITH DOOR, 6"
X 8.61" X 7' , BLACK
CAPACITY: 350 CATEGORY 6 PATCH CORDS OR 245 CATEGORY
6A PATCH CORDS
6 in
TYPICAL RACK PARTS LISTTYPICAL RACK DIMENSIONS AND SPECIFICATIONS
NTS
P/N: OR-MM2073038-W (OR EQUIVALENT)
MIGHTY MO 20 CABLE MANAGEMENT RACK
30" CHANNEL DEPTH, 7' HIGH, WHITE FINISH OR EQUIVALENT
DIMENSIONS:
USABLE HEIGHT: 45RU
DEPTH (US): 30
HEIGHT (US): 7'
WIDTH (US): 23.75"
STATIC LOAD CAPACITY: 2000 LBS
SQUARE HOLE
FRONT AND REAR HEAVY DUTY PERFORATED SECURITY DOOR (OR-MM20724PDHD-W)
SECURITY DOOR FRONT MOUNTING
HARDWARE (OR-MM2024DMFHD-W)
SECURITY DOOR REAR MOUNTING
HARDWARE (OR-MM2024DMRHD-W)
PDU MOUNTING BRACKET KIT (TWO
KITS PER RACK)
P/N: OR-MM20PDUMB1D2W-W
Department of Veterans Affairs
IT Operations and Services
Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd
DRAWN BY: Kevin Grzelka
CHECKED BY:
DOC VERSION No:
PROJECT No:
SHEET TITLE
T4 - TYPICAL CABINET DETAIL
PRINT DATE: Oct 5, 2017
ISSUE DATE: Oct 5, 2017
SHEET: 9 OF 15
Michael Julian, RCDD
1.0
CBOC ITS
SPECIFICATIONS
N/A
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
Solution Delivery
TYPICAL ENCLOSURE PARTS LIST
TYPICAL ENCLOSURE SPECIFICATION
NTS
TYPICAL ENCLOSURE FRONT
NTS
TYPICAL ENCLOSURE SIDE VIEW
NTS
CP3210245 F-Series TeraFrame Gen 3 Cabinet System with accessories installed
Configuration includes the following components:
Item Number Description (Qty)
FF1N-113C-E42-B F-Series TeraFrame Gen 3 Cabinet System, 45 RMU, 84.6 in. (2149mm) H x 23.6" (600mm) W x 43.30"
(1100mm) D Square-Punched Rails, 2-Pair, Single, Perforated Metal Front Door, Two Point, Keyed Swing
Handle Lock, Double Perforated Metal Rear Door, Two Point, Keyed Swing Handle Latch, Server Top Panel, 2 Solid Side Panel, Glacier White, 6-Slide Frame
024-739003-E63 Frame, 6 Slide, 23.6'' (600 mm) W x 43.3'' (1100 mm) D x 45 RMU, Glacier White (1)
024-739060-E03 Door, TeraFrame, Front, Asssembly, 23.6'' (600 mm) W x 45 RMU, Glacier White (1)
024-739064-703 Lock Kit, 2-Point, Keyed, Front Door, 45 RMU (1)
024-739050-E03 Double Door Assembly, 23.6'' (600 mm) W x 45 RMU, Glacier White (1)
024-739054-703 Lock Kit, 2-Point Latching, Keyed, Perforated Door, 45 RMU (1)
024-739140-E12 Top Panel, 2-Piece, Brush, 23.6'' (600 mm) W x 43.3'' (1100 mm) D, Glacier White
024-739046-E63 Side Panel, 6 SLIDE, 43.3'' (1100 mm) D x 45 RMU, Glacier White (2)
024-739200-002 Kit,Common Parts Parts,Teraframe,UL,White (1)
024-739110-701 PDU Bracket, Assembly, Standard, 0.7'' (17 mm) W x 3.9'' (100 mm) D x 2.4" (60 mm), Black (1)
39110-C01 PDU Bracket, Assembly, Standard, 0.7'' (17 mm) W x 3.9'' (100 mm) D x 2.4" (60 mm), Black (1)
024-739240-003 Kit, Packaging, 600 W x 1075-1200D x 42U - 48U (1)
024-739029-001 Caster Kit, Two Swivel, Two Fixed, 1.6'' (41 mm) W x 2'' (51 mm) D x 2" (41 mm) H
39085-E03 Air Dam, 6 SLIDE, 23.6'' (600 mm) W x 45 RMU, Glacier White (1)
39137-703 Baying Seal Kit, 45U (2)
39132-E00 Bottom Panel, With Brush, 23.6'' (600 mm) W x 39.4" - 47.2" (1000 - 1200 mm) D, Glacier White (1)
31920-E03 Finger Cable Manager no Cover (2)
UL2416 This Cabinet and any included accessories are UL Listed under the NWIN category per the UL2416 Standard.
UL file number E227626. Note, the UL Listing only applies to cabinets manufactured in the United States.
(VENDOR TO PROVIDE 45 RU OF PLENAFILL BLANKING PANEL PER ENCLOSURE)
TYPICAL ENCLOSURE TOP VIEW WITH FOUR (4) BRUSHED
GROMMET CABLE OPENINGS
NTS
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
30 30
31 31
32 32
33 33
34 34
35 35
36 36
37 37
38 38
39 39
40 40
41 41
42 42
43 43
44 44
45 45
.6
23.6"43.3"
Department of Veterans Affairs
IT Operations and Services
Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd
DRAWN BY: Kevin Grzelka
CHECKED BY:
DOC VERSION No:
PROJECT No:
SHEET TITLE
T4 - TYPICAL WORK AREA
OUTLETS
PRINT DATE: Oct 5, 2017
ISSUE DATE: Oct 5, 2017
SHEET: 10 OF 15
Michael Julian, RCDD
1.0
CBOC ITS
SPECIFICATIONS
N/A
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
Solution Delivery
TYPICAL WORK FLOOR MOUNT OUTLET
NTS
TYPICAL WALL MOUNT PHONE OUTLET
NTS
ONE (1) CATEGORY
6A 8P8C OUTLET
ACTIVE FOR
TELEPHONY
TYPICAL WORK AREA OUTLET FACEPLATE WILL BE INSTALLED WITH CATEGORY 6A COMPONENT-
COMPLIANT 8P8C MEDIA INTERFACE CONNECTORS (RJ45). EACH CONNECTOR WILL BE
TERMINATED TO HIGH QUALITY CATEGORY 6A HORIZONTAL CABLING WHICH WILL TERMINATE IN
THE TELECOMMUNICATIONS ROOM AS SPECIFIED ELSEWHERE IN THIS DESIGN PACKAGE.
ALL HORIZONTAL UTP SHALL BE CATEGORY 6A AND TERMINATED TO T568B.
TYPICAL FACEPLATE WILL BE INSTALLED WITH TWO (2) RJ45s. HIGH DENSITY FACEPLATES WILL
BE ISNTALLED WITH FOUR (4) RJ45s.
NOTES:
ALL LABELING SHALL BE ANSI/TIA/EIA/606C COMPLIANT. BLACK LETTERING ON WHITE FIELD.
MACHINE PRINTED. FURTHER GUIDANCE ON ADMINISTRATION MAY BE SPECIFIED IN OTHER
SECTIONS OF THIS DESIGN PACKAGE.
TYPICAL HIGH DENSITY WALL MOUNTED WORK AREA OUTLET
CONFIGURATION4
MINIMUM OF TWO
CATEGORY 6A 8P8C
OUTLETS FOR DATA OR
TELEPHONY
STANDARD DENSITY WALL MOUNTED WORK AREA OUTLET
CONFIGURATION2
EIGHT (8) POSITION
FACEPLATE MOUNTED ON
DUAL GANG WORKBOX.
FACEPLATE COLOR
SPECIFIED BY OTHERS.
FOUR (4) CATEGORY 6A
8P8C OUTLETS ACTIVE
FOR TELEPHONY/DATA
DUAL GANG WORKBOX
WITH TWO CONNECTOR
CHASSIS.
EIGHT (8) POSITION
FACEPLATE MOUNTED ON
DUAL GANG WORKBOX.
FACEPLATE COLOR
SPECIFIED BY OTHERS.
TWO (2) CATEGORY 6A
8P8C OUTLETS ACTIVE
FOR TELEPHONY/DATA
DUAL GANG WORKBOX
WITH ONE CONNECTOR
CHASSIS.
Department of Veterans Affairs
IT Operations and Services
Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd
DRAWN BY: Kevin Grzelka
CHECKED BY:
DOC VERSION No:
PROJECT No:
SHEET TITLE
T4 - TYPICAL RACK POWER
DISTRIBUTION
PRINT DATE: Oct 5, 2017
ISSUE DATE: Oct 5, 2017
SHEET: 11 OF 15
Michael Julian, RCDD
1.0
CBOC ITS
SPECIFICATIONS
N/A
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
Solution Delivery
NOTIONAL POWER SCHEMATIC FOR INFORMATION ONLY – NOT FOR CONSTRUCTION
TYPICAL MAIN PDU UNIT WITH REAR DETAIL AND ADAPTORS REQUIRED FOR VERTICAL PDU5
APC AP7900 Rack PDU, Switched, 1U, 15A, 100/120V, (8)5-15 APC Switched
Rack PDU , Input: 120V (OR EQUIVALENT)
30 Amp 3-Phase PDU BASE UNIT – FRONT
(ZONIT ZON-C-ZPDU1)
REQUIRES TWO 30 AMP 3-PHASE (WYE) CIRCUITS WITH L21-
30R RECEPTACLES
(OR EQUIVALENT)
30 Amp 3-Phase PDU BASE UNIT – REAR
FOUR (4) L21-20R
SIX (6) NEMA 5-15/20 T-SLOT
(OR EQUIVALENT)
110 Volt PDU FOR PLACEMENT AS NEEDED4
PDU INPUTS REQUIRE TWO
L21-30Rs
POWER SCHEMATIC FOR POWER RACK- LEVEL REDUNDANCY
The correct specification for the PDU is to feed it with a two power sources. Power inputs should originate from two independent power sources. Each input will use identical specs: WYE (5-wire) configured, 208V, 30A, three-phase, terminating in a NEMA L21-30R locking receptacle. The neutral conductor should be upsized one gauge to match the upsized neutral conductors in the PDU units. The neutral "upsizing" should ideally be continued in the power distribution system back to the UPS or transformer winding pole. This increases the efficiency of the power distribution system and suppresses harmonics in the system.
NOTE:
RACK/ENCLOSURE
ZONE PDU
PDUB
PDUA
LEG1 LEG2
BUS A BUS B
RACK/ENCLOSURE
RACKED EQUIPMENT
PDUB
PDUA
PS1 PS2
ONE ZONE PDU FOR TWO
SERVER CABINETS
NOTE:
THIS DESIGN PROVIDES DIVERSE POWER INPUTS FOR ACTIVE EQUIPMENT BY SPLITTING THE SOURCE POWER
ACROSS TWO INPUTS ON THE ZONE PDU. EACH INPUT WILL SUPPORT TWO EQUIPMENT-FACING PDUs. EACH
SERVER CABINET WILL CONTAIN A MINIMUM OF TWO EQUIPMENT-FACING PDUs – EACH WILL BE ENERGIZED BY
SEPARATE ZONE PDU INPUTS.
208 VOLT PDU FOR EQUIPMENT POWER – TO BE ENERGIZED BY ZONE PDU3
TYPICAL POWER
DISTRIBUTION
REQUIRES ONE (1) L21-20R
APC AP8961 Rack PDU 2G,Switched, Zero U,5.7kW, 200/
208V,(21)C13 & (3)C19, 6' cord
Temp/Humidity Out USB
Network In Serial
Reset
- Overload
- Warning
- OK
Select
Scroll
Main Menu by Schne ider Elec tr ic
Rack PDU
L3-L1
17 18 19 20 21 22 23 24
L1-L2
1 2 3 4 5 6 7 8
L2-L3
9 10 11 12 13 14 15 16
20A 120/ 208V
Y
DUAL 3-PHASE 480 VOLT INPUTS
(WITH 480 – 208 TRANSFORMER)
BUS OR FEEDER
3-PHASE 208-VOLT 30-AMP PDU
PDU PDU
COMPUTER
ZONE PDU
“ZERO U” VERTICAL PDU
DUAL POWER SUPPLY
DUAL INPUT UPS 250-500 kVA
UPS RACK MOUNT UPS
RACK-MOUNTED UPS
RACKED EQUIPMENT
PS1 PS2
RACK-MOUNTED UPS
MAIN
POWER
POWER
ON
GROUP B
0FF
0N
MAIN
POWER
POWER
ON
GROUP A
0FF
0N
GROUP A
0FF
0N
A
0FF
0N
B
0FF
0N
C
0FF
0N
0FF
0N
0FF
0N
GROUP B
0FF
0N
A
0FF
0N
B
0FF
0N
C
0FF
0N
0FF
0N
0FF
0N
A B CA B C
A
B
OZ
GROUP B
OX OY
OX
GROUP A
OY OZ
OY
GROUP B
OZ OX
OZ
GROUP A
OX OY
LEG 1 LEG 2 LEG 2LEG 1
PHASE Z PHASE Y PHASE X
GRP A
GRP B LEG 1
LEG 2 GRP A
GRP B LEG 1
LEG 2 GRP A
GRP B LEG 1
LEG 2
Department of Veterans Affairs
IT Operations and Services
Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd
DRAWN BY: Kevin Grzelka
CHECKED BY:
DOC VERSION No:
PROJECT No:
SHEET TITLE
T4 - POWER DISTRIBUTION
PRINT DATE: Oct 5, 2017
ISSUE DATE: Oct 5, 2017
SHEET: 12 OF 15
Michael Julian, RCDD
1.0
CBOC ITS
SPECIFICATIONS
N/A
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
Solution Delivery
T e m p
/H u m id it y
O u t U
S B
N e tw o rk In
S e ri a l
R e s e t
O v e rl o a d
W a rn in g
O
K
S e le c t
S c ro ll
M a in M e n u b y
S c h n e id e r
E le c tr ic
R a c k
P D
U
L
-L
L
-L
L
-L
T e m p
/H u m id it y
O u t U
S B
N e tw o rk In
S e ri a l
R e s e t
O v e rl o a d
W a rn in g
O
K
S e le c t
S c ro ll
M a in M e n u b y
S c h n e id e r
E le c tr ic
R a c k
P D
U
L
-L
L
-L
L
-L
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
30 30
31 31
32 32
33 33
34 34
35 35
36 36
37 37
38 38
39 39
40 40
41 41
42 42
43 43
44 44
45 45
PDU BRACKET P/N:
OR-MM20PDUMB1D2W-B
(FOR OTRONICS RACK ONLY)
POWER SCHEMATIC RACKS – REAR VIEW
POWER DISTRIBUTION
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
30 30
31 31
32 32
33 33
34 34
35 35
36 36
37 37
38 38
39 39
40 40
41 41
42 42
43 43
44 44
45 45
A
B
OZ
GROUP B
OX OY
OX
GROUP A
OY OZ
OY
GROUP B
OZ OX
OZ
GROUP A
OX OY
LEG 1 LEG 2 LEG 2LEG 1
PHASE Z PHASE Y PHASE X
GRP A
GRP B LEG 1
LEG 2 GRP A
GRP B LEG 1
LEG 2 GRP A
GRP B LEG 1
LEG 2
L21-30P “A” SIDE
REQUIRES A 208V, 30A, THREE-PHASE WHIP,
TERMINATING IN A NEMA L21-30R LOCKING
RECEPTACLE. THE NEUTRAL CONDUCTOR SHOULD BE
UPSIZED ONE GAUGE TO MATCH THE UPSIZED
NEUTRAL CONDUCTORS IN THE ZONE PDU UNITS.
L21-30P “B” SIDE
REQUIRES A 208V, 30A, THREE-PHASE WHIP,
TERMINATING IN A NEMA L21-30R LOCKING
RECEPTACLE. THE NEUTRAL CONDUCTOR SHOULD BE
UPSIZED ONE GAUGE TO MATCH THE UPSIZED
NEUTRAL CONDUCTORS IN THE ZONE PDU UNITS
ZONEIT
30 Amp 3-Phase PDU BASE UNIT – FRONT
(ZONIT ZON-C-ZPDU1)
REQUIRES TWO 30 AMP 3-PHASE (WYE) CIRCUITS
WITH L21-30R RECEPTACLES
(OR EQUIVALENT)
APC AP8961 RACK PDU
2G,SWITCHED, ZERO U,5.7KW,
200/208V,(21)C13 & (3)C19, 6'
CORD
RACK-MOUNTED 5KW 208V UNINTERRUPTIBLE
POWER SUPPLY (UPS) WITH NEMA 20A L21-
20P INPUT AND L21-20R OUTPUT. MODEL
EXAMPLE: ZC0517700110000 5 KW 208V W/
20A 5W IN/5W OUT, ONE INTERNAL BATTERY
STRING
T e m p
/H u m id it y
O u t U
S B
N e tw o rk In
S e ri a l
R e s e t
O v e rl o a d
W a rn in g
O
K
S e le c t
S c ro ll
M a in M e n u b y
S c h n e id e r
E le c tr ic
R a c k
P D
U
L
-L
L
-L
L
-L
T e m p
/H u m id it y
O u t U
S B
N e tw o rk In
S e ri a l
R e s e t
O v e rl o a d
W a rn in g
O
K
S e le c t
S c ro ll
M a in M e n u b y
S c h n e id e r
E le c tr ic
R a c k
P D
U
L
-L
L
-L
L
-L
Department of Veterans Affairs
IT Operations and Services
Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd
DRAWN BY: Kevin Grzelka
CHECKED BY:
DOC VERSION No:
PROJECT No:
SHEET TITLE
T5 - COLOR CODING
PRINT DATE: Oct 5, 2017
ISSUE DATE: Oct 5, 2017
SHEET: 13 OF 15
Michael Julian, RCDD
1.0
CBOC ITS
SPECIFICATIONS
N/A
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
Solution Delivery
PATCH PANEL LABEL FIELD COLOR CODING
Department of Veterans Affairs
IT Operations and Services
Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd
DRAWN BY: Kevin Grzelka
CHECKED BY:
DOC VERSION No:
PROJECT No:
SHEET TITLE
T5 - CBOC ITS NAMING
STANDARDS
PRINT DATE: Oct 5, 2017
ISSUE DATE: Oct 5, 2017
SHEET: 14 OF 15
Michael Julian, RCDD
1.0
CBOC ITS
SPECIFICATIONS
N/A
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
Solution Delivery
· RACK = RK1 THROUGH RK4. LABELED LEFT TO RIGHT WHEN
LOOKING AT THE FRONT OF THE RACK. APPLIES TO RACKS AND
CABINETS.
· UTP PATCH PANEL = CPL-RACK NAME-01 THROUGH 45. EXAMPLE:
CPL-RK1-01 FOR THE PANEL LOCATED IN RACK UNIT #1 IN RACK
#1.
· UTP PATCH PANEL POSITION = PANEL ID.01 THROUGH 24.
EXAMPLE CPL-RK1-01.01
· FIBER DISTRIBUTION PANEL = FPL-RACK NAME-01 THROUGH 45.
EXAMPLE: FPL-RK1-01 FOR THE PANEL IN RACK UNIT #1 RACK #1.
· FIBER DISTRIBUTION CASSETTE = FCS-RACK NAME-01
THROUGH 45.1 THROUGH 3. EXAMPLE: FCS-RK1-01.1 FOR THE
CASSETTE IN POSITION #1 IN PANEL LOCATED IN RACK UNIT
#1 IN RACK #1.
· UTP PATCH CORDS = CCA[SOURCE.PORT]/[DESTINATION.PORT].
EXAMPLE CCA[CPL-RK1-01.01]/[CPL-RK2-02.02] AS A PATCH CORD
CONNECTING PORT #1 IN THE COPPER PATCH PANEL LOCATED IN
RACK #1, RACK UNIT #1 WITH PORT 2 LOCATED IN RACK 2, RACK
UNIT #2.
· FIBER PATCH CORDS = FCA[SOURCE.PORT]/
[DESTINATION.PORT]. EXAMPLE FCA[FDP-RK1-01.01.01]/[FDP-RK2-
02.02.02] AS A PATCH CORD CONNECTING PORT #1 IN THE FIBER
PATCH PANEL LOCATED IN RACK #1, RACK UNIT #1 WITH PORT 2
LOCATED IN RACK 2, RACK UNIT #2.
· FACEPLATE = TR ROOM NUMBER-PATCH PANEL ID.PORT.
EXAMPLE. 1A-CPL-RK1-01.1 FOR TELECOMMUNICATIONS ROOM 1,
UTP PANEL IN RACK #1, RACK UNIT #1, PORT POSITION #1.
EXAMPLE INSIDE PLANT ADMINISTRATION
Department of Veterans Affairs
IT Operations and Services
Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC INSIDE PLANT ITS SPEC V1.vsd
DRAWN BY: Kevin Grzelka
CHECKED BY:
DOC VERSION No:
PROJECT No:
SHEET TITLE
T5 - SPECIFICATIONS
PRINT DATE: Oct 5, 2017
ISSUE DATE: Oct 5, 2017
SHEET: 15 OF 15
Michael Julian, RCDD
1.0
CBOC ITS
SPECIFICATIONS
N/A
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
Solution Delivery
TELECOMMUNICATIONS MEDIA AND INTERFACES SPECIFICATION
SPECIFICATIONPRIMARY ATTRIBUTEID SECONDARY ATTRIBUTE
1 COPPER PATCH PANELS
PERFORMANCE CATEGORY CATEGORY 6A (10 GBE)
POSITION COUNT 24 (4 SIX-PORT MODULES)
FORM FACTOR ANGLED
SIZE ONE RACK UNIT
COLOR CODING BLACK
CASSETTE CAPACITY 24 STRAND (TWO 12-STRAND MULTI-FIBER PUSH ON (MPO))
CASSETTE USER INTERFACES LC QUAD CONNECTORS
FIBER DISTRIBUTION CASSETTES CASSETTE BACKBONE INTERFACES MPO
PERFORMANCE CHARACTERISTICS OM4 LASER ENHANCED 40 GBE 50/125 MULTIMODE
FORM FACTOR ONE (1) RU
3 UTP (HORIZONTAL AND FIRST LEVEL BACKBONE)
PERFORMANCE CATEGORY CATEGORY 6A (10 GBE)
PERFORMANCE SPECIFICATIONS MEETS OR EXCEEDS TIA-EIA-568-C.2-10, TSB-155.
JACKET COLOR BLUE (HORIZONTAL), WHITE (1ST LEVEL BACKBONE)
SIZE ONE RACK UNIT
COLOR CODING BLACK
PERFORMANCE CATEGORY OM4 LASER ENHANCED TO 40 GIGABIT ETHERNET (GBE
PERFORMANCE SPECIFICATIONS
LASER OPTIMIZED 50/125 ΜM FIBERS WITH EFFECTIVE MODAL
BANDWIDTH OF AT LEAST 4,700 MHZ∙KM AT 850 NM
FIBER (HORIZONTAL AND FIRST LEVEL BACKBONE)
MODE MULTIMODE
JACKET COLOR AQUA
MEDIA CONNECTOR PRE-TERMINATED WITH MPO, TYPE A
STRAND COUNT 12
BUNDLING LOOSE TUBE
5 UTP PATCH CORDS
PERFORMANCE CATEGORY CATEGORY 6A, 26-GAUGE, STRANDED
PERFORMANCE SPECIFICATIONS CENTER TUNED TO HORIZONTAL MEDIA
JACKET COLOR BLUE
TERMINATION METHOD FACTORY PRE-TERMINATED
PERFORMANCE CATEGORY OM4 LASER ENHANCED TO 40 GIGABIT ETHERNET (GBE
PERFORMANCE SPECIFICATIONS OM4
FIBER PATCH CORDS MODE MULTIMODE
JACKET COLOR AQUA
MEDIA CONNECTOR PRE-TERMINATED WITH DUPLEX LC
| CBOC INSIDE PLANT ITS SPEC V1.vsd |
| COVER |
| FRONT MATTER |
| SYMBOLS |
| T3- GENERIC HEALTH CARE FACILITY EQUIPMENT ROOM |
| T3-GENERIC HEALTH CARE FACILITY TR |
| T3 - TYPICAL BACKBOARD ELEVATION |
| T3 - TYPICAL RACK ELEVATION |
| T4 - TYPICAL RACK DETAIL |
| T4 - TYPICAL CABINET DETAIL |
| T4 - TYPICAL WORK AREA OUTLETS |
| T4 - TYPICAL RACK POWER DISTRIBUTION |
| T4 - POWER DISTRIBUTION |
| T5 - COLOR CODING |
| T5 - CBOC ITS NAMING STANDARDS |
| T5 - SPECIFICATIONS |