STATEMENT OF WORK

FEMA HVAC REQUIREMENTS

1.0 Introduction

This Statement of Work describes the requirements necessary for the purchase, installation and delivery of a HVAC Mobile System. The requirements include building and designing for use in an austere environment to provide heat and air conditioning through a mobile platform. These systems will be a part of a rapid deployment system that quickly responds to disasters, emergency, or special events to provide initial support to disaster victims or disaster management. It will be used for the immediate standup of a communications work center.

Capability:

50 Ton.

475,000 BTU Cooling 277,000 BTU Heating

Will cool and or heat a 16,000 Square Foot space

2.0 Generator

Heavy duty, 4-cycle, direct injection, turbocharged, air to air intercooled diesel engine provides maximum reliability.

Brushless alternator reduces service and maintenance requirements and meets temperature rise standards for Class F insulation systems.

Open delta alternator design provides virtually unlimited excitation for maximum motor starting capability.

Automatic voltage regulator (AVR) provides precise regulation.

Electronic governor system maintains frequency to ±0.25%.

Full load acceptance of standby nameplate rating in one step (NFPA110, para 5- 13.2.6).

Sound attenuated, weather resistant, steel housing provides operation at 75 dB(A) at 23 feet. Fully lockable enclosure allows safe unattended operation.

Internal fuel tank with direct reading fuel gauges is standard.

Seven stage powder coat paint provides durability and weather protection.

Jacket Water Heater (750 watts) for easy starting in cold weather climates (above 0° C).

Digital engine gauges including oil pressure, water temperature, battery volts, engine speed, and fuel level.

Analog generator instrumentation including AC ammeter, AC voltmeter, frequency meter, ammeter phase selector switch, voltmeter phase selector switch, and voltage regulator adjustment potentiometer.

ECU830 microprocessor-based digital generator controller.

• Remote 2-wire start/stop control.

• Operational temperature range of -40° to 85° C.

• High visibility LCD display with heated screen and alphanumeric readout.

• 50/60 Hz engine speed selection; engine is EPA dual-speed rated.

• Modbus interface for gauge panel and expansion options.

• DPF cleaning cycle indication.

Automatic safety shutdown system monitors the water temperature, engine oil pressure, low coolant, over speed, and over crank. Warning lights indicate abnormal conditions.

Complete power panel. Fully covered; three-phase terminals and single phase receptacles allow fast and convenient hookup for most applications including temporary power boxes, tools and lighting equipment. All are NEMA standard.

Fuel/water separator. Removes condensation from fuel for extended engine life.

Simultaneous single and three phase power.

Emergency Stop Switch. When manually activated, shuts down generator in the event of an emergency.

EPA emissions certified - Tier 4i emissions compliant.

Engine fitted with DOC and DPF Generator Specifications

- Design Revolving field, self-ventilated

- Drip-proof, single bearing

- Armature Connection Star with Neutral

- Phase 3

- Standby Output 158 KW (198 KVA)

- Prime Output 144 KW (180 KVA)

- 3Ø Voltage (L-L/L-N)

- Voltage Selector Switch at 3Ø 240/139 208Y/120, 220Y/127, 240Y/139

- 3Ø Voltage (L-L/L-N)

- Voltage Selector Switch at 3Ø 480/277 416Y/240, 440Y/254, 480Y/277

- 1Ø Voltage (L-L/L-N)

- (Voltage Selector Switch at 1Ø 240/120) N/A

- Power Factor 0.8

- Voltage Regulation (No load to full load) ±0.5%

- Generator RPM 1800

- Frequency 60 Hz

- No. of Poles 4

- Excitation Brushless with AVR

- Frequency Regulation:

- No Load to Full Load

- Isochronous under varying loads from

- no load to 100% rated load

- Frequency Regulation: Steady State ±0.25% of mean value for constant loads

- from no load to full load.

- Insulation Class F

- Sound Level dB(A) Full load at 23 feet 74

- Engine Specifications

- Make / Model Cummins / QSB7-G6

- Emissions EPA Interim Tier 4 Certified

- Starting System Electric

- Design

- 4-cycle, water cooled,

- direct injection, turbocharged. Charged

- Air Cooled and EGR.

- Displacement 409 in3 (6.7 liters)

- No. cylinders 6

- Bore x Stroke 4.21 x 4.88 in. (107 x 124 mm)

- Gross Engine Power Output 314 hp (234 kW)

- BMEP 304 psi (2097 kPa)

- Piston Speed 1464 ft/min (7.4 m/s)

- Compression Ratio 17.3:1

- Engine Speed 1800 rpm

- Overspeed Limit 2070 rpm

- Oil Capacity 4.6 gallons (17.5 liters)

- Battery 12V 100Ah x 2 (24 V Systems)

- Fuel System

- Recommended Fuel ASTM-D975-No.1 & No.2-D*

- Maximum Fuel Flow (per hour) 35.4 gallons (134 liters)

- Maximum Inlet Restriction (Hg) 4.0 in (100 mm)

- Fuel Tank Capacity 100 gallons (380 liters)

- Fuel Consumption gph lph

- At full load 10.3 39.1

- At 3/4 load 8.0 30.4

- At 1/2 load 5.9 22.5

- At 1/4 load 4.0 15.3

- - Use ultra-low sulfur diesel fuel.

- Warranty*

- Cummins Engine

- 12 months from date of purchase with unlimited hours.

- Generator

- 24 months from date of purchase or 2000 hours (whichever occurs first).

- Cooling System

- Fan Load 13 hp (9.7 kW)

- Coolant Capacity (with radiator) 11.4 gallons (43 liters)

- Coolant Flow Rate (per minute) 40 gallons (151 liters)

- Heat Rejection to Coolant (per minute) 7197 Btu (7.59 MJ)

- Maximum Coolant Friction Head 5 psi (34.5 kPa)

- Maximum Coolant Static Head 60 feet (18.3 meters)

- Ambient Temperature Rating 104°F (40°C)

- Air

- Combustion Air 430 cfm (12.18 m3/min)

- Maximum Air Cleaner Restriction 25 in. H2O (6.25 kPa)

- Alternator Cooling Air 1459 cfm (41.3 m3/min)

- Radiator Cooling Air 12325 cfm (349 m3/min)

- Exhaust System

- Gas Flow (full load) 996 cfm (28.2 m3/min)

- Gas Temperature 948°F (509°C )

- Maximum Back Pressure 88.3 in. H2O (22 kPa)

- Amperage

- Rated Voltage Maximum Amps

- 1Ø 120 Volt 400 Amps (4 wire)

- 1Ø 240 Volt 200 Amps (4 wire)

- 3Ø 240 Volt 433 Amps

- 3Ø 480 Volt 216 Amps

- Main Line Circuit Breaker Rating 500 Amps

- Over Current Relay Trip Set Point

- 480V Mode Only 216 Amps

Extra Requirement:

Generator must be mounted on independent tandem axle trailer with same standards below:

Technical Data

Gross Vehicle Weight Rating (GVWR) -13,500 lbs (6,124 kg) Tire Size — ST235/80R16

LR-E

Gross Axle Weight Rating (GAWR) - 7,000 lbs (3,175 kg) (ea.) Wheel Bolt Pattern - 8 Lug on 6.5 in

Actuator Rating — 20,000 lbs (9,072 kg) Tire Load Rating — 3,500 lbs/1,588 kg (ea.)

- Fits MQ Power Generator Models DCA150SSCU

- Tandem-axle Design with Leaf Spring Suspension

- H.D. Welded Steel Frame Construction

- Structural Channel for Generator Mounting and Support

- Integral Fuel Cell; Single-wall Steel Design, 210-Gallon Capacity

- Replaceable, Bolt-on Hydraulic Brake Actuator

- Surge Hydraulic-actuated Drum Brakes (all axles)

- Hydraulic Uni-servo Drum Brakes with Free-backing Plates- 12-inch Cluster

- D.O.T. Steel Brake Lines, Brass Tees and Rubber Hydraulic Brake Hoses

- 4-hole Channel Allows 3-position, Adjustable Coupler Height; 4-inches O/A

- Heavy Duty Tongue Mounted, Drop-leg Jack (rated 10,000lbs/4,536 kg lift)

- Replaceable Bolt-on Steel Fenders

- High-gloss Enamel Coated Frame, Channel, Actuator and Fenders

- D.O.T. Approved Tail Lamps, Stop Lamps, Turn Signal Lamps, Side Marker Lamps

- Weatherproof, Rubber Armored, 3-piece Trailer Light Wiring Harness

- Adjustable 2 5/16-inch Ball Coupler

- Rear Stabilizer Stands

- Tongue-Mounted Utility Storage Box

- Anti-Theft Wheel Lock

- Spare Tire with Locking Mount

- Electric Breakaway Safety Device (Electric-actuated brakes)

NOTICE

Generator is not intended for use in enclosed areas or where free flow of air is restricted.

Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any buildings electrical system except through an approved device.

3.0 PAINT

The final finishing of the vehicle shall be to commercial truck/trailer/unit standards.

All paint applications shall conform to the paint manufacturer's requirements and recommendations.

Single color, high gloss white.

4.0 HVAC UNIT

50 ton trailer mounted Cooling Unit (460 VAC, 3-phase) 108 kW Electric Heat Attached to a Tandem Axle Trailer w/electric brakes (same requirements as above for trailer) 10 each 20”x25’ Canvas supply/return ducts 8 each 4-0 x 50’ Camlock power cables Remote thermostat 1 year warranty 5 year compressor warranty (parts only) Similar if not exact to a Trane Packaged Rooftop Air Conditioner Voyager Commercial with ReliaTel Controls as the main operating unit Housing within a metal frame box with proper exhaust pipes as well as any other standard safety features for a trailer

5.0 WIRING REQUIREMENTS

6-gauge minimum copper stranded battery cable to be used for 12V DC main supply lines. All cable runs to be full length, no splices. All cable is to be enclosed in convoluted polyethylene tubing and the ends of the cable sealed with color coded shrink wrap identifying the function of the cable.

Circuit breaker functions are to be identified by engraved or printed labels.

All added wiring for load runs shall be AWG 8, 10, 12, 14 and 18 and must conform to MIL-W-1678D type D.

All wiring shall be numbered or lettered on 6" centers minimum.

All wiring is to be protected from chafing and abrasion. Where wire passes through sheet metal, bulkheads and structural supports, plastic grommets shall be used to protect both wiring and wire looms.

Install a battery cutoff switch (safety)

6.0 MISCELLANEOUS FEATURES

Six (6) Whelen white quartz halogen model 810 scene lights, with 8-32 optics located on exterior of body. Two (2) mounted on each side and two (2) mounted on the rear of the vehicle.

Class IV hitch, 2" receiver, and 10,000 lb. tow capacity without distribution bars.

Provide tire valve extenders on rear inside dual wheels.

Provide delivery to 4420 Buckeystown Pike, Frederick MD 21740

Trailers must be delivered to FEMA on ground delivery (if brought on a flatbed trailer, delivery company is responsible for labor and costs to put trailers on the ground.

7.0 TRAINING/OPERATIONAL GUIDE

An operational step by step guide will be provided for operation of the HVAC system Training also will be provided by HVAC technicians if contract awarded