Drawings
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FTFA15-1214_Specifications_Final.pdf | ||
| Climatic_Lab_HX_SOW.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BROWN.RUSSEL
L.A.1230011881
Digitally signed by
BROWN.RUSSELL.A.1230011881
DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USAF, cn=BROWN.RUSSELL.A.1230011881 Date: 2016.11.07 09:43:56 -06'00'
BENNETT.CRAIG.
R.1061792798
Digitally signed by
BENNETT.CRAIG.R.1061792798
DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USAF, cn=BENNETT.CRAIG.R.1061792798 Date: 2016.11.07 09:50:10 -06'00'
HORNE.JAMES.E.
1034686412
Digitally signed by HORNE.JAMES.E.1034686412 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USAF, cn=HORNE.JAMES.E.1034686412 Date: 2016.11.08 07:49:49 -06'00'
CARRICO.STEPHEN.P.11046
09844
Digitally signed by CARRICO.STEPHEN.P.1104609844 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USAF, cn=CARRICO.STEPHEN.P.1104609844 Date: 2016.11.08 13:17:12 -06'00'
FERNANDEZ.MICHAE
L.J.1230018720
Digitally signed by FERNANDEZ.MICHAEL.J.1230018720 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USAF, cn=FERNANDEZ.MICHAEL.J.1230018720 Date: 2016.11.16 13:13:01 -06'00'
KAAK.GEOFFREY.JOSE
F.1260252310
Digitally signed by KAAK.GEOFFREY.JOSEF.1260252310 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USAF, cn=KAAK.GEOFFREY.JOSEF.1260252310 Date: 2016.12.02 09:05:23 -06'00'
BELL.JACKIE.D.12306882
Digitally signed by BELL.JACKIE.D.1230688288 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USAF, cn=BELL.JACKIE.D.1230688288 Date: 2016.12.13 07:57:40 -06'00'
CRUZ.PABLO.J.118253
Digitally signed by CRUZ.PABLO.J.1182531045 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USAF, cn=CRUZ.PABLO.J.1182531045 Date: 2016.12.13 12:52:10 -06'00'
SCHLUETER.MARK.A.11366
56933
Digitally signed by SCHLUETER.MARK.A.1136656933 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USAF, cn=SCHLUETER.MARK.A.1136656933 Date: 2016.12.19 16:22:18 -06'00'
ROBEEN.DANIEL.B.1230040679
Digitally signed by ROBEEN.DANIEL.B.1230040679 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USAF, cn=ROBEEN.DANIEL.B.1230040679 Date: 2016.12.23 07:47:06 -06'00'
BLALOCK.STEPHE
N.D.1103123000
Digitally signed by
BLALOCK.STEPHEN.D.1103123000
DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USAF, cn=BLALOCK.STEPHEN.D.1103123000 Date: 2017.01.13 09:49:39 -06'00'
HVAC GENERAL NOTES
1. INSTALL A COMPLETE AND OPERABLE MECHANICAL SYSTEM AS INDICATED ON THE DRAWINGS, AS SPECIFIED AND AS REQUIRED BY CODE.
2. CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE
AND GENERAL ARRANGEMENT ONLY.
3. INSTALL ALL MECHANICAL EQUIPMENT IN ACCORDANCE WITH MANUFACTURERS' RECOMMENDATIONS, CONTRACT DOCUMENTS, AND
APPLICABLE CODES AND REGULATIONS.
4. THE APPROXIMATE LOCATIONS OF EXISTING UTILITIES ARE SHOWN. THE CONTRACTOR SHALL DETERMINE THE EXACT
LOCATION OF ALL EXISTING UTILITIES BEFORE COMMENCING WORK.
5. COORDINATE EQUIPMENT CLEARANCES (AS RECOMMENDED BY MANUFACTURER) WITH ALL DISCIPLINES BEFORE INSTALLATION.
6. COORDINATE AND PROVIDE ALL PIPING TRANSITION REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED
EQUIPMENT, VERIFY AND COORDINATE ALL PIPING DIMENSIONS BEFORE FABRICATION.
7. ALL EQUIPMENT, PIPING, PIPE ACCESSORIES, SHALL BE SUPPORTED AS DETAILED, SPECIFIED, AND REQUIRED TO PROVIDE A VIBRATION-
FREE INSTALLATION.
8. REFER TO TYPICAL DETAILS FOR PIPING, AND EQUIPMENT INSTALLATION.
HX HEAT EXCHANGER
AMU AIR MAKE-UP UNIT
P PUMP
EX. EXISTING
SS STAINLESS STEEL
HVAC ABBREVIATIONS
HVAC LEGEND
HX
EXISTING
NEW WORK
PIPE DOWN
PIPE UP
DEMO
SYMBOLS
NEW WORK SHEET NOTE
DEMO SHEET NOTE
CONNECT TO EXISTING
INDICATES SECTION
SHEET WHERE
SECTION IS DRAWN
SECTION
DEMO TO THIS POINT
8"ø R-22
8"ø R-30
8"ø CACL2
GATE VALVE
2-WAY CONTROL VALVE
BALL VALVE
BUTTERFLY VALVE
GLOBE VALVE
CHECK VALVE
PRESSURE REDUCING VALVE
THERMOMETER WITH WELL
FLEX PIPE CONNECTION
FLANGE CONNECTION
UNION
PRESSURE GAGE WITH GAGE COCK
PRESSURE & TEMPERATURE RELIEF VALVE
STRAINER WITH VALVE & BLOWDOWN
3-WAY CONTROL VALVE
TRIPLE DUTY VALVE
SIGHT GLASS
MAX FLOW ORIFIC
SINGLE LINE DIAGRAM DEMO
SINGLE LINE DIAGRAM EXISTING
PIPE REDUCER
SINGLE LINE DIAGRAM NEW
PHASING NOTES
PHASE 1 - PROCUREMENT:
1. THE CONTRACTOR SHALL SUBMIT ALL EQUIPMENT FOR APPROVAL PRIOR TO PURCHASE.
2. AFTER APPROVAL, THE CONTRACTOR SHALL OBTAIN ALL EQUIPMENT ON SITE PRIOR TO DEMO/NEW WORK.
PHASE 2 - CONSTRUCTION:
1. CLIMATIC LAB HANGAR 440 WILL BE IN OPERATION/OCCUPIED DURING CONSTRUCTION.
2. AFTER ALL EQUIPMENT IS APPROVED AND ON SITE THE CONTRACTOR SHALL RECEIVE A NOTIFICATION FROM THE CONTRACTING OFFICER BEFORE COMMENCING WITH DEMO/NEW WORK. THE CONTRACTOR WILL THEN HAVE 60 DAYS TO COMPLETE THE DEMO/NEW WORK.
3. CONTRACTOR SHALL COORDINATE AND RECIEVE APPROVAL PRIOR TO ALL SYSTEM SHUT-DOWNS WITH THE CONTRACTING OFFICER'S
REPRESENTATIVE.
PHASE 3 - START UP:
1. CONTRACTOR SHALL COORDINATE WITH FACILITY MANAGEMENT TO VALIDATE SYSTEM IS OPERATING AS INTENDED.
FLOW MEASURING STATION
FM
75 SOUTH "F" STREET
PENSACOLA, FLORIDA 32502
(850) 434-0513
(PROF. ENG. #: 3600)
PEI JOB #2015185
PETERSON ENGINEERING INC.
BASE CIVIL ENGINEER
EGLIN AIR FORCE BASE, FLORIDA
AS-BUILT
REPLACE HEAT EXCHANGER
CLIMATIC LAB HANGAR 440
96 CEG, OFFICE FORM 002, FY2014
TITLE
DATEREVISION APPR'DBY
CENM
SIGNATURE
APPROVED
DATE
PROJ. ENGR.
DRAWN BY
INDEX NO.
SPEC. NO. PROJ. NO.
FTFA
DRAWING NO. FILE NO.
96 CEG/CEN
BASE CIVIL ENGINEER
APPROVED
APPROVED DATE
SCALE
CONTENTS
SHEET
DESCRIPTION
09/15/2016
AS SHOWN
16AS15-121416AS OF2
BEJ
GDP
M-001
HVAC LEGENDS, NOTES & ABBREVIATION
UP
U P
D N
UP
DN
UP
UP
UP
UP
UP
UPUP
UP
UP
UP
DN
UP
UP
EX. HX
EX. HX
EX. HX
EX. HX
EX. HX
EX. HX
EX. HX
EX. HX
EX. HX
M-101
M-101
M-101
M-101
8" ø
C A
C L2
4"ø 4"ø
BLDG 435
B
LD
G
8" ø
R -2
8" ø
R -2
CACL2
CACL2
8" ø
R -2
8"ø R-22
M-101
EX. HX
EX. HX
502 EX. HX
EX. HX
EX. HX
8"ø R-22 8"ø R-22
M-101
EX. HX
EX. HX
EX. HX
EX. HX
EX. HX
8"ø CACL2
8"ø CACL2
8" ø
R -2
EX. HX
EX. HX
EX. HX
EX. HX
M-101
M-101
EX. HX
EX. HX
BLDG 440
75 SOUTH "F" STREET
PENSACOLA, FLORIDA 32502
(850) 434-0513
(PROF. ENG. #: 3600)
PEI JOB #2015185
PETERSON ENGINEERING INC.
BASE CIVIL ENGINEER
EGLIN AIR FORCE BASE, FLORIDA
AS-BUILT
REPLACE HEAT EXCHANGER
CLIMATIC LAB HANGAR 440
96 CEG, OFFICE FORM 002, FY2014
TITLE
DATEREVISION APPR'DBY
CENM
SIGNATURE
APPROVED
DATE
PROJ. ENGR.
DRAWN BY
INDEX NO.
SPEC. NO. PROJ. NO.
FTFA
DRAWING NO. FILE NO.
96 CEG/CEN
BASE CIVIL ENGINEER
APPROVED
APPROVED DATE
SCALE
CONTENTS
SHEET
DESCRIPTION
09/15/2016
AS SHOWN
16AS15-121416AS OF3
BEJ
GDP
M-101
PARTIAL FLOOR PLAN - HVAC DEMO
1/8" = 1'-0"1
PARTIAL FLOOR PLAN - HVAC DEMO
KEY PLAN
NOT TO SCALEN
N
1/8" = 1'-0"2
AMU-2 DEMO SECTION-2
1/8" = 1'-0"3
AMU-2 DEMO SECTION-3
1/8" = 1'-0"4
AMU-1 DEMO SECTION-4
1/8" = 1'-0"5
AMU-1 DEMO SECTION-5
AREA SHOWN
DEMO SHEET NOTES
1 DEMO EXISTING HX-501/502 & ASSOCIATED PIPING AS INDICATED. EXISTING HOIST
SHALL BE REMOVED PRIOR TO INSTALLATION OF HEAT EXCHANGER.
DEMO EXISTING HX-508/509 & ASSOCIATED PIPING AS INDICATED. EXISTING HOIST
SHALL BE REMOVED PRIOR TO INSTALLATION OF HEAT EXCHANGER.
NOTE REFER TO SINGLE LINE DIAGRAM FOR PIPE VALVES AND ACCESSORIES.
U P
D N
UP
DN
UP
UP
UP
UP
UP
UPUP
UP
UP
UP
DN
UP
UP
EX. HX
EX. HX
EX. HX
EX. HX
EX. HX
M-301
M-301
M-301
M-301
HX
HX
HX
HX
4 TYP.
8" ø
C A
C L2
REFER TO M-103 FOR CONTINUATION.
BLDG 435
B
LD
G
8" ø
R -2
8" ø
R -2
8" ø
R -2
8"ø R-22
8"ø CACL2 8"ø CACL2
BLDG 440
75 SOUTH "F" STREET
PENSACOLA, FLORIDA 32502
(850) 434-0513
(PROF. ENG. #: 3600)
PEI JOB #2015185
PETERSON ENGINEERING INC.
BASE CIVIL ENGINEER
EGLIN AIR FORCE BASE, FLORIDA
AS-BUILT
REPLACE HEAT EXCHANGER
CLIMATIC LAB HANGAR 440
96 CEG, OFFICE FORM 002, FY2014
TITLE
DATEREVISION APPR'DBY
CENM
SIGNATURE
APPROVED
DATE
PROJ. ENGR.
DRAWN BY
INDEX NO.
SPEC. NO. PROJ. NO.
FTFA
DRAWING NO. FILE NO.
96 CEG/CEN
BASE CIVIL ENGINEER
APPROVED
APPROVED DATE
SCALE
CONTENTS
SHEET
DESCRIPTION
09/15/2016
AS SHOWN
16AS15-121416AS OF4
BEJ
GDP
M-102
PARTIAL FLOOR PLAN - HVAC NEW WORK
1/8" = 1'-0"
PARTIAL FLOOR PLAN - HVAC NEW WORK
NEW WORK SHEET NOTES
1 CONTRACTOR SHALL VERIFY THAT THE SIZE OF THE HEAT EXCHANGE WILL FIT
BETWEEN EXISTING STRUCTURE AND EQUIPMENT WITH THE REQUIRED
CLEARANCE TO ALLOW FOR PIPE INSTALLATION PRIOR TO CONSTRUCTION.
ROUTE 8"ø R-22 SS PIPING TO SHELL SIDE OF HEAT EXCHANGER. PROVIDE
INSULATION TO MATCH EXISTING.
ROUTE 8"ø CACL2 SS PIPING TO TUBE SIDE OF HEAT EXCHANGER. PROVIDE
INSULATION TO MATCH EXISTING.
EXTEND HEAT EXCHANGER SUPPORTS AS RECOMMENDED BY
MANUFACTURER. PROVIDE DOWELS TO SECURE CONCRETE SUPPORT TO
EXISTING, REFER TO DETAILS.
KEY PLAN
NOT TO SCALEN
AREA SHOWN
N
NOTE REFER TO SINGLE LINE DIAGRAM FOR PIPE VALVES AND ACCESSORIES.
U P
D N
UP
DN
UP
UP
UP
UP
UP
UPUP
UP
UP
UP
DN
UP
UP
UP
DN
UP
DN
12"ø CACL2
12"ø CACL2
REFER TO M-102 FOR CONTINUATION.
P
8"ø CACL2
8"ø CACL2
8" ø
BLDG 440
8" ø
C A
C L2
8"ø CACL2
"ø
C A
C L2
"ø
C A
C L2
8"ø CACL2
12"ø CACL2
P
EX. P
REFER TO M-101 FOR CONTINUATION.
4"ø
12"ø CACL2
12"ø CACL2
6" ø
4"ø
CACL2
CACL2
EX. P
12"ø CACL2
8" ø
C A
C L2
8"ø CACL2
8"ø CACL2
"ø
C A
C L2
"ø
C A
C L2
75 SOUTH "F" STREET
PENSACOLA, FLORIDA 32502
(850) 434-0513
(PROF. ENG. #: 3600)
PEI JOB #2015185
PETERSON ENGINEERING INC.
BASE CIVIL ENGINEER
EGLIN AIR FORCE BASE, FLORIDA
AS-BUILT
REPLACE HEAT EXCHANGER
CLIMATIC LAB HANGAR 440
96 CEG, OFFICE FORM 002, FY2014
TITLE
DATEREVISION APPR'DBY
CENM
SIGNATURE
APPROVED
DATE
PROJ. ENGR.
DRAWN BY
INDEX NO.
SPEC. NO. PROJ. NO.
FTFA
DRAWING NO. FILE NO.
96 CEG/CEN
BASE CIVIL ENGINEER
APPROVED
APPROVED DATE
SCALE
CONTENTS
SHEET
DESCRIPTION
09/15/2016
AS SHOWN
16AS15-121416AS OF5
BEJ
GDP
M-103
PARTIAL FLOOR PLAN - PUMP HOUSE HVAC
1/8" = 1'-0"
PARTIAL FLOOR PLAN - PUMP HOUSE AMU-1 NEW WORK
KEY PLAN
NOT TO SCALEN
AREA SHOWN
AREA SHOWN
1/8" = 1'-0"
PARTIAL FLOOR PLAN - PUMP HOUSE AMU-2 NEW WORK
N N
DEMO SHEET NOTES
1 DEMO EXISTING REGENERATING CACL2 PUMPS AND PIPING AS
INDICATED. EXISTING PUMPS SHALL BE TURNED OVER TO THE
GOVERNMENT.
DEMO MAX FLOW ORIFIC APPROXIMATE LOCATION SHOWN.
NOTE REFER TO SINGLE LINE DIAGRAM FOR PIPE VALVES AND ACCESSORIES. NOTE REFER TO SINGLE LINE DIAGRAM FOR PIPE VALVES AND ACCESSORIES.
1/8" = 1'-0"
PARTIAL FLOOR PLAN - PUMP HOUSE AMU-1 DEMO
1/8" = 1'-0"
PARTIAL FLOOR PLAN - PUMP HOUSE AMU-2 DEMO
N N
NEW WORK SHEET NOTES
1 EXTEND 53.5"x24" PUMP PAD AS REQUIRED TO ALLOW FOR A MIN OF 6" AROUND
PUMP. REFER TO DETAIL 1/M-601 FOR PUMP INSTALLATION DETAIL. REFER TO
ELECTRICAL FOR VFD MOUNTING AND LOCATION.
EXISTING 84"x42" PUMP PAD SHALL BE OF SUFFICIENT SIZE TO ALLOW FOR A MIN OF
6" AROUND PUMP. REFER TO DETAIL 1/M-601 FOR PUMP INSTALLATION DETAIL.
REFER TO ELECTRICAL FOR VFD MOUNTING AND LOCATION.
NOTE REFER TO SINGLE LINE DIAGRAM FOR PIPE VALVES AND ACCESSORIES. NOTE REFER TO SINGLE LINE DIAGRAM FOR PIPE VALVES AND ACCESSORIES.
M-301
HX
HX
13' - 2"
8"ø R-22
8"ø R-22
EX. HX
EX. HX
EX. HX
2' - 9"
11' - 2"
5' - 2"
APPROX.
APPROX.
APPROX.
APPROX.
M-301
HX
HX
28"ø R-22
8" ø
C A
C L2
8" ø
C A
C L2
EX. HX
EX. HX
EX. HX
8" ø
R -2
M-301
HX
HX
TYP.
3' - 6"
14' - 11"
7' - 3"
EX. HX
EX. HX
506 8" ø C
A C
L2
8"ø CACL2
8"ø R-22
8"ø R-22
8" ø
C A
C L2
8' - 8"
APPROX.
APPROX.
APPROX.
APPROX.
M-301
HX
HX
4 TYP.
8"ø CACL2
8"ø R-22
8"ø R-22
75 SOUTH "F" STREET
PENSACOLA, FLORIDA 32502
(850) 434-0513
(PROF. ENG. #: 3600)
PEI JOB #2015185
PETERSON ENGINEERING INC.
BASE CIVIL ENGINEER
EGLIN AIR FORCE BASE, FLORIDA
AS-BUILT
REPLACE HEAT EXCHANGER
CLIMATIC LAB HANGAR 440
96 CEG, OFFICE FORM 002, FY2014
TITLE
DATEREVISION APPR'DBY
CENM
SIGNATURE
APPROVED
DATE
PROJ. ENGR.
DRAWN BY
INDEX NO.
SPEC. NO. PROJ. NO.
FTFA
DRAWING NO. FILE NO.
96 CEG/CEN
BASE CIVIL ENGINEER
APPROVED
APPROVED DATE
SCALE
CONTENTS
SHEET
DESCRIPTION
09/15/2016
AS SHOWN
16AS15-121416AS OF6
BEJ
GDP
M-301
HVAC SECTIONS
1/4" = 1'-0"1
AMU-2 SECTION-1
1/4" = 1'-0"2
AMU-2 SECTION-2
1/4" = 1'-0"3
AMU-1 SECTION-3
1/4" = 1'-0"4
AMU-1 SECTION-4
NEW WORK SHEET NOTES
1 CONTRACTOR SHALL VERIFY THAT THE SIZE OF THE HEAT EXCHANGE WILL FIT
BETWEEN EXISTING STRUCTURE AND EQUIPMENT WITH THE REQUIRED CLEARANCE
TO ALLOW FOR PIPE INSTALLATION PRIOR TO CONSTRUCTION.
ROUTE 8"ø R-22 SS PIPING TO SHELL SIDE OF HEAT EXCHANGER. PROVIDE
INSULATION TO MATCH EXISTING.
ROUTE 8"ø CACL2 SS PIPING TO TUBE SIDE OF HEAT EXCHANGER. PROVIDE
INSULATION TO MATCH EXISTING.
EXTEND HEAT EXCHANGER SUPPORTS AS RECOMMENDED BY MANUFACTURER.
PROVIDE DOWELS TO SECURE CONCRETE SUPPORT TO EXISTING, REFER TO
DETAILS.
PUMP SCHEDULE
MARK LOCATION SERVICE TYPE SUCT/DISCH
IMP. DIA.
IN.
PERFORMANCE DATA ELECTRICAL DATA BASIS OF DESIGN
REMARKSMAX.
CAPACITY
GPM
MIN.
CAPACITY
GPM
MAX. DISCHARGE
PSI
MAX. RPM NPSHr
MIN.
EFFICIENCY
MAX. MOTOR
HP
V/ф/Hz MAKE MODEL
P-4 PUMP HOUSE AMU-1 HX-508 & 509 HRZ. FRAME END SUCTION 6" x 4" 10.25 800 340 150 3600 19.6 72.5% 125 460/3/60 GOULDS PUMPS 3196 REFER TO ALL NOTES
P-503 PUMP HOUSE AMU-2 HX-501 & 502 HRZ. FRAME END SUCTION 6" x 4" 10.25 800 340 150 3600 19.6 72.5% 125 460/3/60 GOULDS PUMPS 3196 REFER TO ALL NOTES
PUMP SCHEDULES NOTES:
1. PUMP SHALL BE NON OVER LOADING THROUGHOUT THE ENTIRE PUMP CURVE.
2. PROVIDE VFD WITH NEMA 4 ENCLOSURE.
3. PROVIDE FLOW MEASURING STATION.
4. PUMPS SHALL BE STAINLESS STEEL CONSTRUCTION.
HEAT EXCHANGER SCHEDULE
MARK SHELLS/UNITS ARRANGEMENT TYPE
MAX. CAPACITY
BTU/HR
BRINE DATA REFRIGERANT DATA TUBES SHELL BASIS OF DESIGN
REMARKS
TYPE
GPM
(MIN/MAX)
ENT °F
LVG °F
(MIN/MAX)
∆T °F
(MIN/MAX)
PRESSURE DROP PSI
(MIN/MAX)
TYPE GPM ENT °F LVG °F
PRESSURE
DROP PSI
OD LENGTH IN MATERIAL INLET OUTLET ID MATERIAL INLET OUTLET MANUFACTURER
HX-501 & 502 2 2 SERIES AFM 6,000,300 27% CACL2 364 / 787 40 0 / 21.7 40 / 20 10.77 / 36.84 R-22 1,000 -18 14.5 10.62 0.75 240 316 SS 8" 8" 36 316 SS 8" 8" ALABAMA HEAT EXCHANGER REFER TO ALL NOTES
HX-508 & 509 2 2 SERIES AFM 6,000,300 27% CACL2 364 / 787 40 0 / 21.7 40 / 20 10.77 / 36.84 R-22 1,000 -18 14.5 10.62 0.75 240 316 SS 8" 8" 36 316 SS 8" 8" ALABAMA HEAT EXCHANGER REFER TO ALL NOTES
HEAT EXCHANGER SCHEDULE NOTES:
1. PROVIDE INSULATION TO MATCH EXISTING.
2. CONTRACTOR SHALL SUBMIT SHOP DRAWINSG OF PROPOSED NEW HEAT EXCHANGERS TO INCLUDE ALL REQUIRED CLEARANCES. SHOP DRAWINGS SHALL BE SUBMITTED AND APPROVED PRIOR TO ORDERING EQUIPMENT.
3. CHANNEL, BAFFLE-CROSS, BAFFLE-LONG, T-SHTS.-STAT & CHANNEL COVER SHALL BE 316 SS.
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE1
PUMP INSTALLATION DETAIL
DOWEL DETAIL
TRAPEZE HANGER DETAIL
AFM TYPE 2-SERIES HEAT EXCHANGER DETAIL
PRESSURE GAGE
GAGE COCK TYP.
P
X
GUARD
EXISTING CONCRETE NEW CONCRETE
DOWEL
COMPRESSIBLE FILLER
JOINT SEALANT
ANGLED PIPE SUPPORT
SHALL BE MIN 2"x2"x1/4".
HANGAR ROD SHALL BE
MIN 3/8".
HOLE PACKED WITH
LOCKSET OR SIMILAR
BEFORE INSERTING DOWEL.
FLEX CONNECTION.
CONCENTRIC REDUCERS.
DRAIN PAN.
1/2" DRAIN SLOPE TO FLOOR DRAIN.
ADJUSTABLE FOOT SUPPORT.
BLOWDOWN GATE VALVE
WITH 3/4" HOSE END.
SUCTION DIFFUSER WITH
INTEGRAL STRAINER.
EXTEND EXISTING CONCRETE PAD W/CHAMFER
EDGES WITH WWF 6x6-W4xW4 3000 PSI CONC. USE
A MIN. OF 6 EA DOWELS TO ANCHOR PAD TO
EXISTING FLOOR. DRILL DOWN A MIN. 3" TO
ALLOW INSTALLATION OF DOWELS. DOWELS
SHALL BE #4 REBAR.
BALANCING/SHUT-OFF
VALVE WITH PRESSURE
TAPS
CONNECT TO EXISTING
PIPING FOR AMU-2 ONLY.
CONNECT TO EXISTING
PIPING FOR AMU-2 ONLY.
R-22 IN OR OUT
R-22 IN OR OUT
CALCIUM IN OR OUT
CALCIUM IN OR OUT
DIVISION SHEET
(REMOVABLE)
SEAL STRIP
R-22 SHELL SIDE
REMOVABLE END CAP
SOLID ROUND PLATE
WITH GASKET.
TUBE SHEET WITH GASKET TYP.
R-22 SHELL SIDE
75 SOUTH "F" STREET
PENSACOLA, FLORIDA 32502
(850) 434-0513
(PROF. ENG. #: 3600)
PEI JOB #2015185
PETERSON ENGINEERING INC.
BASE CIVIL ENGINEER
EGLIN AIR FORCE BASE, FLORIDA
AS-BUILT
REPLACE HEAT EXCHANGER
CLIMATIC LAB HANGAR 440
96 CEG, OFFICE FORM 002, FY2014
TITLE
DATEREVISION APPR'DBY
CENM
SIGNATURE
APPROVED
DATE
PROJ. ENGR.
DRAWN BY
INDEX NO.
SPEC. NO. PROJ. NO.
FTFA
DRAWING NO. FILE NO.
96 CEG/CEN
BASE CIVIL ENGINEER
APPROVED
APPROVED DATE
SCALE
CONTENTS
SHEET
DESCRIPTION
09/15/2016
AS SHOWN
16AS15-121416AS OF7
BEJ
GDP
M-601
HVAC SCHEDULES, DETAILS & CONTROLS
CACL2 PUMP SEQUENCE OF OPERATION
1. PUMPS SHALL BE STARTED MANUALLY BY OPERATOR INPUT TO CONTROL PANEL LOCATED IN CONTROL ROOM. COORDINATE EXACT
LOCATION OF PANEL(S) WITH CONTRACTING OFFICER'S REPRESENTATIVE AND OPERATOR.
2. CONTROL PANEL SHALL DISPLAY PUMP GPM AND VFD FREQUENCY.
3. OPERATOR SHALL BE ABLE TO SET PUMP FLOW (GPM) AND VFD SHALL MAINTAIN SETPOINT.
4. THE CONTROLS SHALL HAVE A SWITCH WHICH ALLOWS MANUAL SETTING OF PUMP SPEED AND/OR AN AUTOMATIC POSITION WHICH
ALLOWS THE PUMP TO VARY SPEED TO MAINTAIN A SPECIFIC FLOW.
5. PUMP SHALL RUN CONTINUOUSLY UNTIL MANUALLY SHUT DOWN.
EX. P
EX. HX
EX. CACL2 STORAGE TANK
FROM EX. AMU-1 COILS
TO EX. PRIMARY PUMP
FROM EX. CACL2 STORAGE TANK
TO EX. CACL2 STORAGE TANK
TO EX. CACL2 STORAGE TANK
FROM EX. CACL2 STORAGE TANK
EX. 12" CACL2
EX. 12" CACL2
EX. 4" CACL2
EX. 4" CACL2
EX. 4" CACL2
EX. 6" CACL2
EX. 12" CACL2
EX. 12" CACL2
EX. 8" R-22
EX. HX
P
HX
HX
CACL2 STORAGE TANK
FROM EX. AMU-1 COILS
TO EX. PRIMARY PUMP
FROM EX. CACL2 STORAGE TANK
TO EX. CACL2 STORAGE TANK
TO EX. CACL2 STORAGE TANK
FROM EX. CACL2 STORAGE TANK
EX. 12" CACL2
EX. 12" CACL2
8" CACL2
8" CACL2
8" CACL2
8" CACL2
EX. 12" CACL2
EX. 12" CACL2
8" R-22
FM
6" CACL2
4" CACL2
8" CACL2
75 SOUTH "F" STREET
PENSACOLA, FLORIDA 32502
(850) 434-0513
(PROF. ENG. #: 3600)
PEI JOB #2015185
PETERSON ENGINEERING INC.
BASE CIVIL ENGINEER
EGLIN AIR FORCE BASE, FLORIDA
AS-BUILT
REPLACE HEAT EXCHANGER
CLIMATIC LAB HANGAR 440
96 CEG, OFFICE FORM 002, FY2014
TITLE
DATEREVISION APPR'DBY
CENM
SIGNATURE
APPROVED
DATE
PROJ. ENGR.
DRAWN BY
INDEX NO.
SPEC. NO. PROJ. NO.
FTFA
DRAWING NO. FILE NO.
96 CEG/CEN
BASE CIVIL ENGINEER
APPROVED
APPROVED DATE
SCALE
CONTENTS
SHEET
DESCRIPTION
09/15/2016
AS SHOWN
16AS15-121416AS OF8
BEJ
GDP
M-701
SINGLE LINE DIAGRAM AMU-1
NOT TO SCALE1
DEMO SINGLE LINE DIAGRAM - AMU-1
NOT TO SCALE
NEW WORK SINGLE LINE DIAGRAM - AMU-1
DEMO SHEET NOTES
1 DEMO EXISTING REGENERATING CACL2 PUMPS AND TURN OVER TO THE
GOVERNMENT.
DEMO EXISTING HEAT EXCHANGERS.
DEMO PIPING AND ASSOCIATED EQUIPMENT AS INDICATED. REFER TO NEW WORK
PLAN THIS SHEET FOR NEW LOCATION OF VALVES.
NEW WORK SHEET NOTES
NEW REGENERATING PUMP, REFER TO DETAIL 1/M-601 FOR PUMP INSTALLATION
DETAIL.
ROUTE 8"ø R-22 SS PIPING TO SHELL SIDE OF HEAT EXCHANGER. PROVIDE
INSULATION TO MATCH EXISTING.
ROUTE 8"ø CACL2 SS PIPING TO TUBE SIDE OF HEAT EXCHANGER. PROVIDE
INSULATION TO MATCH EXISTING. ALL VALVES AND STRAINERS SHALL BE REPLACED
WITH SS TYPE.
INSTALL SS FLOW MEASURING STATION. PROVIDE STRAIGHT PIPE PER
MANUFACTURERS RECOMMENDATION.
EX. P
EX.HX
EX. CACL2 STORAGE TANK
FROM EX. CACL2 STORAGE TANK
TO EX. CACL2 STORAGE TANK
EX. 20" CACL2
EX. 18"
CACL2
EX. 8" CACL2
EX. 8" CACL2
EX. 8" CACL2
EX. 8" CACL2
EX. 12" CACL2
EX. 12" CACL2
FROM EX. AMU-2 COILS
TO EX. PRIMARY PUMP P-501
EX. RESIDUAL TANK T-507
EX. 6" CACL2
EX. 4" CACL2
EX. 8" R-22
EX.HX
P
HX
HX
EX. CACL2 STORAGE TANK
FROM EX. CACL2 STORAGE TANK
TO EX. CACL2 STORAGE TANK
EX. 20" CACL2
EX. 18"
CACL2EX. 8" CACL2
EX. 8" CACL2
EX. 8"
CACL2
EX. 8" CACL2
EX. 12" CACL2
EX. 12" CACL2
FROM EX. AMU-2 COILS
TO PRIMARY PUMP P-501
EX. RESIDUAL TANK T-507
6" CACL2
4" CACL2
8" R-22
FM
8" CACL2
75 SOUTH "F" STREET
PENSACOLA, FLORIDA 32502
(850) 434-0513
(PROF. ENG. #: 3600)
PEI JOB #2015185
PETERSON ENGINEERING INC.
BASE CIVIL ENGINEER
EGLIN AIR FORCE BASE, FLORIDA
AS-BUILT
REPLACE HEAT EXCHANGER
CLIMATIC LAB HANGAR 440
96 CEG, OFFICE FORM 002, FY2014
TITLE
DATEREVISION APPR'DBY
CENM
SIGNATURE
APPROVED
DATE
PROJ. ENGR.
DRAWN BY
INDEX NO.
SPEC. NO. PROJ. NO.
FTFA
DRAWING NO. FILE NO.
96 CEG/CEN
BASE CIVIL ENGINEER
APPROVED
APPROVED DATE
SCALE
CONTENTS
SHEET
DESCRIPTION
09/15/2016
AS SHOWN
16AS15-121416AS OF9
BEJ
GDP
M-702
SINGLE LINE DIAGRAM AMU-2
NOT TO SCALE
DEMO SINGLE LINE DIAGRAM - AMU-2
NOT TO SCALE
NEW WORK SINGLE LINE DIAGRAM - AMU-2
DEMO SHEET NOTES
NEW WORK SHEET NOTES
1 DEMO EXISTING REGENERATING CACL2 PUMPS AND TURN OVER TO THE
GOVERNMENT.
DEMO EXISTING HEAT EXCHANGERS.
DEMO PIPING AND ASSOCIATED EQUIPMENT AS INDICATED. REFER TO NEW WORK
PLAN THIS SHEET FOR NEW LOCATION OF VALVES.
DEMO MAX FLOW ORIFIC.
NEW REGENERATING PUMP, REFER TO DETAIL 1/M-601 FOR PUMP INSTALLATION
DETAIL.
ROUTE 8"ø R-22 SS PIPING TO SHELL SIDE OF HEAT EXCHANGER. PROVIDE
INSULATION TO MATCH EXISTING.
ROUTE 8"ø CACL2 SS PIPING TO TUBE SIDE OF HEAT EXCHANGER. PROVIDE
INSULATION TO MATCH EXISTING.
INSTALL SS FLOW MEASURING STATION. PROVIDE STRAIGHT PIPE PER
MANUFACTURERS RECOMMENDATION.
M
ELECTRICAL PLAN - PUMP HOUSE AMU-1 - DEMOLITION
SCALE: 1/8" = 1'-0"
ELECTRICAL PLAN - PUMP HOUSE AMU-1 - NEW WORK
SCALE: 1/8" = 1'-0"
EXISTING MOTOR CONTROL CENTER "MCC-2"
(SIEMENS MOTOR CONTROL CENTER - 800 AMP,
480 V., 3Ø, 3 W.)
REMOVE EXISTING PUSHBUTTON STATION.
REMOVE EXISTING CONTROL WIRING & CONDUIT FROM
PUSHBUTTON STATION BACK TO MOTOR STARTER IN "MCC-2."
REMOVE EXISTING POWER WIRING FROM MOTOR BACK TO "MCC-2."
REMOVE EXISTING POWER WIRING ROUTED IN CABLE TRAY
BACK TO "MCC-2."
REMOVE EXISTING CONDUIT FROM MOTOR BACK TO EXISTING CABLE TRAY.
REMOVE EXISTING FLEXIBLE CONDUIT & WIRING CONNECTION TO
EXISTING PUMP. REMOVE EXISTING RIGID STEEL CONDUIT DROP FROM
OVERHEAD STRUCTURE TO FLOOR, INCLUDING FLOOR FLANGE.
EXISTING PUMP "P-4" IS 25 HP, 480 V., 3Ø
NEW PUMP P-4
125 HP, 480 V., 3Ø
NEW LIQUID-TIGHT FLEXIBLE CONDUIT AND
WIRING CONNECTION FROM VFD TO PUMP P-4.
NEW VARIABLE FREQUENCY DRIVE - FURNISHED BY
MECHANICAL CONTRACTOR & INSTALLED BY ELECTRICAL
CONTRACTOR. SEE "DETAIL - VFD STRUCTURE," THIS SHEET.
ELEVATION - MOTOR CONTROL
CENTER "MCC-2"
N.T.S.
400 A., 3 P., NEMA 3R DISCONNECT SWITCH.
SEE "DETAIL - VFD STRUCTURE," THIS SHEET.
145 KVA, 3Ø DRIVE ISOLATION TRANSFORMER -
460 V. DELTA TO 460Y/266 VOLT. SEE "DETAIL -
VFD STRUCTURE," THIS SHEET.
EXTEND WIRING FROM DISCONNECT SWITCH TO ENCLOSED CIRCUIT
BREAKER IN ELECTRICAL ROOM AS SHOWN ON "WIRING DIAGRAM -
PUMP P-4," THIS SHEET.
EXTEND NEW CONTROL WIRING IN 1" RIGID GALV. STEEL CONDUIT FROM NEW VFD TO
EXISTING CABLE TRAY AND THRU CABLE TRAY TO EXISTING CONTROL ROOM IN HANGAR 440.
DETAIL - VFD STRUCTURE
NO SCALE
FRONT VIEW
CONC. EXPANSION ANCHORS (TYP.)
TRANSFORMER
DRIVE ISOLATION
VFD
CONC. FLOOR
ANGLE
1/4" THICK
SIDE VIEW
12"
3'-0"± OR AS
REQUIRED BY
EQUIPMENT BEING
INSTALLED
HEIGHT AS
REQUIRED BY VFD
BEING INSTALLED
5'-0"± OR AS
REQUIRED BY
TRANSFORMER
BEING INSTALLED
CORE DRILL EXISTING EXTERIOR CONCRETE BLOCK WALL FOR NEW CONDUIT
PENETRATIONS. GROUT AROUND CONDUIT PENETRATIONS W/ NON-SHRINK GROUT.
CORE DRILL EXISTING EXTERIOR CONCRETE BLOCK WALL FOR NEW CONDUIT
PENETRATIONS. GROUT AROUND CONDUIT PENETRATIONS W/ NON-SHRINK GROUT.
REMOVE EXISTING CIRCUIT BREAKER AND MOTOR STARTER
CURRENTLY SERVING PUMP P-4. REMOVE ALL COMPONENTS
FROM CUBICLE. REMOVE CONDUCTORS FROM BREAKER TO
EXISTING MCC BUSSING. INSTALL A NEW BLANK DOOR ON
CUBICLE (12" HIGH). EXISTING MCC IS MANUFACTURED BY
SIEMENS, SERIES 2100.
AREA OF WORK - PUMP P-4
KEY PLAN
N.T.S.
400 A., 3 P., NEMA 3R
DISCONNECT SWITCH.
NEW VARIABLE FREQUENCY DRIVE -
FURNISHED BY MECHANICAL
CONTRACTOR & INSTALLED BY
ELECTRICAL CONTRACTOR. PROVIDE VFD
W/ NEMA 4 OUTDOOR ENCLOSURE.
145 KVA, 3Ø DRIVE ISOLATION
TRANSFORMER - 460 V. DELTA
TO 460Y/266 VOLT - W/ NEMA 3R
WEATHERSHIELD.
12 GAUGE, 1 5/8" X 1 5/8"
HOT-DIPPED
GALVANIZED STEEL
CHANNEL (TYP.)
12 GAUGE, 1 5/8" X 1 5/8"
HOT-DIPPED
GALVANIZED STEEL
CHANNEL (TYP.)
12 GAUGE, 1 5/8" X 1 5/8"
HOT-DIPPED
GALVANIZED STEEL
CHANNEL (TYP.)
M
400 A., 3 P., NEMA 3R
DISCONNECT SWITCH.
NEW VARIABLE FREQUENCY DRIVE - FURNISHED BY MECHANICAL
CONTRACTOR & INSTALLED BY ELECTRICAL CONTRACTOR.
PROVIDE VFD W/ NEMA 4 OUTDOOR ENCLOSURE.
145 KVA, 3Ø DRIVE ISOLATION TRANSFORMER - 460 V.
DELTA TO 460Y/266 VOLT - W/ NEMA 3R WEATHERSHIELD.
EXTEND 3/C # 4/0 TC POWER CABLE W/ # 4
GND. IN 3" RIGID GALV. STEEL CONDUIT FROM
CIRCUIT BREAKER THRU EXTERIOR WALL TO
EXISTING CABLE TRAY. CORE DRILL
CONCRETE BLOCK WALL FOR CONDUIT
PENETRATION & GROUT AROUND CONDUIT.
3 # 4/0 & 1 # 4 GND. IN 2" LIQUID
TIGHT FLEXIBLE METAL CONDUIT.
4 # 4/0 & 1 # 4 GND. IN 2 1/2" LIQUID
TIGHT FLEXIBLE METAL CONDUIT.
# 4 BARE COPPER GROUND CONDUCTOR TO 3/4" X 20'-0"
COPPERCLAD GROUND ROD. BOND GROUND CONDUCTOR TO
ROD W/ EXOTHERMIC WELD. CORE DRILL THRU CONC SLAB &
INSTALL ROD BELOW TRANSFORMER. DRILL 1" HOLE. LEAVE
2" OF ROD EXPOSED W/ GROUND CONNECTION ABOVE SLAB.
3 # 4/0 & 1 # 4 GND. IN 2" LIQUID
TIGHT FLEXIBLE METAL CONDUIT.
NEW PUMP P-4
125 HP, 480 V., 3Ø
WIRING DIAGRAM - PUMP P-4
N.T.S.
225 A., 3 P., 480 V., 65 KAIC CIRCUIT
BREAKER IN NEMA 1 ENCLOSURE.
EXTEND 3 - 300 MCM & 1 # 4 GND. IN 3" RIGID GALV. STEEL
CONDUIT TO EXISTING MOTOR CONTROL CENTER. TAP
EXISTING BUSSING IN MOTOR CONTROL CENTER ON
LOAD SIDE OF EXISTING MAIN BREAKER & EXTEND
CONDUIT & WIRING TO ENCLOSED CIRCUIT BREAKER.
ROUTE TC CABLE THRU CABLE
TRAY FROM PUMP ROOM TO
ELECTRICAL ROOM.
EXTEND 3/C # 4/0 TC POWER CABLE W/ # 4
GND. IN 3" RIGID GALV. STEEL CONDUIT FROM
DISCONNECT SWITCH TO EXISTING CABLE
TRAY.
225 A., 3 P., 480 V., 65 KAIC CIRCUIT
BREAKER IN NEMA 1 ENCLOSURE.
PENSACOLA, FLORIDA 32502
75 SOUTH "F" STREET
PETERSON ENGINEERING INC.
(850) 434-0513
ELECTRICAL PLAN - PUMP HOUSE AMU-2 - DEMOLITION
SCALE: 1/8" = 1'-0"
ELECTRICAL PLAN - PUMP HOUSE AMU-2 - NEW WORK
SCALE: 1/8" = 1'-0"
EXISTING MOTOR CONTROL CENTER "EMC-502"
(CUTLER HAMMER - WESTINGHOUSE SERIES
2100 MOTOR CONTROL CENTER - 1600 AMP,
480Y/277 V., 3Ø, 4 W.)
EXISTING MOTOR CONTROL CENTER "EMC-502"
AREA OF WORK - PUMP P-503
KEY PLAN
N.T.S.
REMOVE EXISTING PUSHBUTTON STATION.
REMOVE EXISTING CONTROL WIRING & CONDUIT FROM
PUSHBUTTON STATION BACK TO MOTOR STARTER IN "MCC-2."
REMOVE EXISTING POWER WIRING FROM MOTOR BACK TO "MCC-2."
REMOVE EXISTING FLEXIBLE CONDUIT & WIRING
CONNECTION TO EXISTING PUMP. REMOVE EXISTING
DISCONNECT SWITCH & SUPPORT STRUCTURE CHANNELS IN
THEIR ENTIRETY. EXISTING PUMP "P-503" IS 40 HP, 480 V., 3Ø
NEW PUMP P-503
125 HP, 480 V., 3Ø
NEW LIQUID-TIGHT FLEXIBLE CONDUIT AND WIRING
CONNECTION FROM VFD TO PUMP P-503.
NEW VARIABLE FREQUENCY DRIVE - FURNISHED BY
MECHANICAL CONTRACTOR & INSTALLED BY ELECTRICAL
CONTRACTOR. MOUNT ON CONCRETE BLOCK WALL
ADJACENT TO DRIVE ISOLATION TRANSFORMER.
400 A., 3 P., NEMA 3R DISCONNECT SWITCH.
MOUNT ON CONCRETE BLOCK WALL ADJACENT
TO DRIVE ISOLATION TRANSFORMER.
145 KVA, 3Ø DRIVE ISOLATION TRANSFORMER -
460 V. DELTA TO 460Y/266 VOLT. SEE "DETAIL -
VFD STRUCTURE," SHEET E-103.
EXTEND 3 # 4/0 & 1 # 4 GND. IN 2" RIGID GALV. STEEL
CONDUIT FROM VFD TO NEW MOTOR LOCATION. SEE
"WIRING DIAGRAM - PUMP P-503," SHEET E-103.
EXTEND WIRING FROM DISCONNECT SWITCH TO MOTOR CONTROL
CENTER EMC-502 AS SHOWN ON "WIRING DIAGRAM - PUMP P-503,"
SHEET E-103.
EXTEND NEW CONTROL WIRING IN 1" RIGID GALV. STEEL
CONDUIT FROM NEW VFD TO EXISTING CABLE TRAY AND THRU
CABLE TRAY TO EXISTING CONTROL ROOM IN HANGAR 440.
PENSACOLA, FLORIDA 32502
75 SOUTH "F" STREET
ELEVATION - MOTOR CONTROL
CENTER "EMC-502"
N.T.S.
REMOVE EXISTING CIRCUIT BREAKER AND MOTOR STARTER CURRENTLY SERVING PUMP
P-503. REMOVE ALL COMPONENTS FROM CUBICLE. REMOVE CONDUCTORS FROM BREAKER
TO EXISTING MCC BUSSING. INSTALL A NEW MCC BUCKET, 225 A., 3 P., 65 KAIC CIRCUIT
BREAKER, NEW 18" DOOR FOR CIRCUIT BREAKER, NEW 12" DOOR AND HORIZONTAL BARRIER
BELOW NEW CIRCUIT BREAKER, INCLUSIVE OF ALL HARDWARE AND ACCESSORIES REQUIRED
FOR THE NEW INSTALLATION IN EXISTING MCC CUBICLE FOR NEW PUMP P-503. PROVIDE NEW
# 4/0 CONDUCTORS FROM CIRCUIT BREAKER TO EXISTING MCC BUSSING. PROVIDE NEW LUGS
ON EXISTING MCC BUSSING IF REQUIRED FOR LARGER CONDUCTOR SIZE. EXISTING MCC IS
MANUFACTURED BY CUTLER HAMMER/WESTINGHOUSE, SERIES 2100.
DETAIL - VFD STRUCTURE
NO SCALE
FRONT VIEW SIDE VIEW
145 KVA, 3Ø DRIVE ISOLATION
TRANSFORMER - 460 V. DELTA TO 460Y/266
VOLT - W/ NEMA 3R WEATHERSHIELD.
M
400 A., 3 P., NEMA 3R
DISCONNECT SWITCH.
NEW VARIABLE FREQUENCY DRIVE - FURNISHED BY MECHANICAL
CONTRACTOR & INSTALLED BY ELECTRICAL CONTRACTOR.
PROVIDE VFD W/ NEMA 4 OUTDOOR ENCLOSURE.
145 KVA, 3Ø DRIVE ISOLATION TRANSFORMER - 460 V.
DELTA TO 460Y/266 VOLT - W/ NEMA 3R WEATHERSHIELD.
3 # 4/0 & 1 # 4 GND. IN 2" LIQUID
TIGHT FLEXIBLE METAL CONDUIT.
4 # 4/0 & 1 # 4 GND. IN 2 1/2" LIQUID
TIGHT FLEXIBLE METAL CONDUIT.
3 # 4/0 & 1 # 4 GND. IN 2" RIGID
GALV. STEEL CONDUIT.
3 # 4/0 & 1 # 4 GND. IN 2" LIQUID
TIGHT FLEXIBLE METAL CONDUIT.
NEW PUMP P-503
125 HP, 480 V., 3Ø
2" WEATHERPROOF "TEE" FITTING
2" FLOOR FLANGE. ATTACH TO CONCRETE
SLAB W/ MASONRY EXPANSION ANCHORS.
WIRING DIAGRAM - PUMP P-503
N.T.S.
EXTEND 3/C # 4/0 TC POWER CABLE W/ # 4
GND. IN 3" RIGID GALV. STEEL CONDUIT FROM
MCC CIRCUIT BREAKER TO EXISTING CABLE
TRAY.
ROUTE TC CABLE THRU CABLE
TRAY FROM MCC TO PUMP ROOM.
EXTEND 3/C # 4/0 TC POWER CABLE W/ # 4
GND. IN 3" RIGID GALV. STEEL CONDUIT FROM
DISCONNECT SWITCH TO EXISTING CABLE
TRAY.
# 4 BARE COPPER GROUND CONDUCTOR TO 3/4" X 20'-0"
COPPERCLAD GROUND ROD. BOND GROUND CONDUCTOR TO
ROD W/ EXOTHERMIC WELD. CORE DRILL THRU CONC SLAB &
INSTALL ROD BELOW TRANSFORMER. DRILL 1" HOLE. LEAVE
2" OF ROD EXPOSED W/ GROUND CONNECTION ABOVE SLAB.
NEW TRANSFORMER SUPPORT
STRUCTURE - SEE DETAIL, THIS SHEET.
TRANSFORMER
DRIVE ISOLATION
12 GAUGE, 1 5/8" X 3 1/4"
HOT-DIPPED GALVANIZED
STEEL CHANNEL (TYP.)
1/4" THICK ANGLE (TYP.)
CONC. EXPANSION ANCHORS (TYP.)
1/4" THICK ANGLE (TYP.)
EXISTING CONCRETE BLOCK WALL
4'-0" A.F.F.
CONCRETE FLOOR
CONC. EXPANSION
ANCHORS (TYP.)
WIDTH AS REQUIRED
BY TRANSFORMER
BEING INSTALLED
CONC. EXPANSION
ANCHORS (TYP.)
DEPTH AS REQUIRED
BY TRANSFORMER
BEING INSTALLED
TRANSFORMER
DRIVE ISOLATION
NEW 225 A., 3 P., 65 KAIC
CIRCUIT BREAKER
12 GAUGE, 1 5/8" X 3 1/4"
HOT-DIPPED GALVANIZED
STEEL CHANNEL (TYP.)
PENSACOLA, FLORIDA 32502
75 SOUTH "F" STREET
| FTFA15-1214_REPLACE HEAT EXCHANGER CLIMATIC LAB HANGAR 440_ T-001_SIGN-1 |
| FTFA15-1214 Drawings Final |
| 15185 M-001 |
| 15185 M-101 |
| 15185 M-102 |
| 15185 M-103 |
| 15185 M-301 |
| 15185 M-601 |
| 15185 M-701 |
| 15185 M-702 |
| 15185 E101-E101 |
| 15185 E102-E102 |
| 15185 E103-E103 |