FTFA15-1214_Drawings_Final.pdf

PDF 2 MB Posted

Attached to
Replace Heat Exchanger Coils, Climactic Lab, Hangar 440 Federal contract opportunity
Solicitation number
FTFA15-1214
Issued by
Department of the Air Force Materiel Command Test Center

About this file

Drawings

View the file

Other files for this federal contract opportunity

Other files attached to Replace Heat Exchanger Coils, Climactic Lab, Hangar 440, newest first.
File Type Posted
FTFA15-1214_Specifications_Final.pdf PDF
Climatic_Lab_HX_SOW.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BROWN.RUSSEL

L.A.1230011881

Digitally signed by

BROWN.RUSSELL.A.1230011881

DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USAF, cn=BROWN.RUSSELL.A.1230011881 Date: 2016.11.07 09:43:56 -06'00'

BENNETT.CRAIG.

R.1061792798

Digitally signed by

BENNETT.CRAIG.R.1061792798

DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USAF, cn=BENNETT.CRAIG.R.1061792798 Date: 2016.11.07 09:50:10 -06'00'

HORNE.JAMES.E.

1034686412

Digitally signed by HORNE.JAMES.E.1034686412 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USAF, cn=HORNE.JAMES.E.1034686412 Date: 2016.11.08 07:49:49 -06'00'

CARRICO.STEPHEN.P.11046

09844

Digitally signed by CARRICO.STEPHEN.P.1104609844 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USAF, cn=CARRICO.STEPHEN.P.1104609844 Date: 2016.11.08 13:17:12 -06'00'

FERNANDEZ.MICHAE

L.J.1230018720

Digitally signed by FERNANDEZ.MICHAEL.J.1230018720 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USAF, cn=FERNANDEZ.MICHAEL.J.1230018720 Date: 2016.11.16 13:13:01 -06'00'

KAAK.GEOFFREY.JOSE

F.1260252310

Digitally signed by KAAK.GEOFFREY.JOSEF.1260252310 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USAF, cn=KAAK.GEOFFREY.JOSEF.1260252310 Date: 2016.12.02 09:05:23 -06'00'

BELL.JACKIE.D.12306882

Digitally signed by BELL.JACKIE.D.1230688288 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USAF, cn=BELL.JACKIE.D.1230688288 Date: 2016.12.13 07:57:40 -06'00'

CRUZ.PABLO.J.118253

Digitally signed by CRUZ.PABLO.J.1182531045 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USAF, cn=CRUZ.PABLO.J.1182531045 Date: 2016.12.13 12:52:10 -06'00'

SCHLUETER.MARK.A.11366

56933

Digitally signed by SCHLUETER.MARK.A.1136656933 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USAF, cn=SCHLUETER.MARK.A.1136656933 Date: 2016.12.19 16:22:18 -06'00'

ROBEEN.DANIEL.B.1230040679

Digitally signed by ROBEEN.DANIEL.B.1230040679 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USAF, cn=ROBEEN.DANIEL.B.1230040679 Date: 2016.12.23 07:47:06 -06'00'

BLALOCK.STEPHE

N.D.1103123000

Digitally signed by

BLALOCK.STEPHEN.D.1103123000

DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USAF, cn=BLALOCK.STEPHEN.D.1103123000 Date: 2017.01.13 09:49:39 -06'00'

HVAC GENERAL NOTES

1. INSTALL A COMPLETE AND OPERABLE MECHANICAL SYSTEM AS INDICATED ON THE DRAWINGS, AS SPECIFIED AND AS REQUIRED BY CODE.

2. CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE

AND GENERAL ARRANGEMENT ONLY.

3. INSTALL ALL MECHANICAL EQUIPMENT IN ACCORDANCE WITH MANUFACTURERS' RECOMMENDATIONS, CONTRACT DOCUMENTS, AND

APPLICABLE CODES AND REGULATIONS.

4. THE APPROXIMATE LOCATIONS OF EXISTING UTILITIES ARE SHOWN. THE CONTRACTOR SHALL DETERMINE THE EXACT

LOCATION OF ALL EXISTING UTILITIES BEFORE COMMENCING WORK.

5. COORDINATE EQUIPMENT CLEARANCES (AS RECOMMENDED BY MANUFACTURER) WITH ALL DISCIPLINES BEFORE INSTALLATION.

6. COORDINATE AND PROVIDE ALL PIPING TRANSITION REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED

EQUIPMENT, VERIFY AND COORDINATE ALL PIPING DIMENSIONS BEFORE FABRICATION.

7. ALL EQUIPMENT, PIPING, PIPE ACCESSORIES, SHALL BE SUPPORTED AS DETAILED, SPECIFIED, AND REQUIRED TO PROVIDE A VIBRATION-

FREE INSTALLATION.

8. REFER TO TYPICAL DETAILS FOR PIPING, AND EQUIPMENT INSTALLATION.

HX HEAT EXCHANGER

AMU AIR MAKE-UP UNIT

P PUMP

EX. EXISTING

SS STAINLESS STEEL

HVAC ABBREVIATIONS

HVAC LEGEND

HX

EXISTING

NEW WORK

PIPE DOWN

PIPE UP

DEMO

SYMBOLS

NEW WORK SHEET NOTE

DEMO SHEET NOTE

CONNECT TO EXISTING

INDICATES SECTION

SHEET WHERE

SECTION IS DRAWN

SECTION

DEMO TO THIS POINT

8"ø R-22

8"ø R-30

8"ø CACL2

GATE VALVE

2-WAY CONTROL VALVE

BALL VALVE

BUTTERFLY VALVE

GLOBE VALVE

CHECK VALVE

PRESSURE REDUCING VALVE

THERMOMETER WITH WELL

FLEX PIPE CONNECTION

FLANGE CONNECTION

UNION

PRESSURE GAGE WITH GAGE COCK

PRESSURE & TEMPERATURE RELIEF VALVE

STRAINER WITH VALVE & BLOWDOWN

3-WAY CONTROL VALVE

TRIPLE DUTY VALVE

SIGHT GLASS

MAX FLOW ORIFIC

SINGLE LINE DIAGRAM DEMO

SINGLE LINE DIAGRAM EXISTING

PIPE REDUCER

SINGLE LINE DIAGRAM NEW

PHASING NOTES

PHASE 1 - PROCUREMENT:

1. THE CONTRACTOR SHALL SUBMIT ALL EQUIPMENT FOR APPROVAL PRIOR TO PURCHASE.

2. AFTER APPROVAL, THE CONTRACTOR SHALL OBTAIN ALL EQUIPMENT ON SITE PRIOR TO DEMO/NEW WORK.

PHASE 2 - CONSTRUCTION:

1. CLIMATIC LAB HANGAR 440 WILL BE IN OPERATION/OCCUPIED DURING CONSTRUCTION.

2. AFTER ALL EQUIPMENT IS APPROVED AND ON SITE THE CONTRACTOR SHALL RECEIVE A NOTIFICATION FROM THE CONTRACTING OFFICER BEFORE COMMENCING WITH DEMO/NEW WORK. THE CONTRACTOR WILL THEN HAVE 60 DAYS TO COMPLETE THE DEMO/NEW WORK.

3. CONTRACTOR SHALL COORDINATE AND RECIEVE APPROVAL PRIOR TO ALL SYSTEM SHUT-DOWNS WITH THE CONTRACTING OFFICER'S

REPRESENTATIVE.

PHASE 3 - START UP:

1. CONTRACTOR SHALL COORDINATE WITH FACILITY MANAGEMENT TO VALIDATE SYSTEM IS OPERATING AS INTENDED.

FLOW MEASURING STATION

FM

75 SOUTH "F" STREET

PENSACOLA, FLORIDA 32502

(850) 434-0513

(PROF. ENG. #: 3600)

PEI JOB #2015185

PETERSON ENGINEERING INC.

BASE CIVIL ENGINEER

EGLIN AIR FORCE BASE, FLORIDA

AS-BUILT

REPLACE HEAT EXCHANGER

CLIMATIC LAB HANGAR 440

96 CEG, OFFICE FORM 002, FY2014

TITLE

DATEREVISION APPR'DBY

CENM

SIGNATURE

APPROVED

DATE

PROJ. ENGR.

DRAWN BY

INDEX NO.

SPEC. NO. PROJ. NO.

FTFA

DRAWING NO. FILE NO.

96 CEG/CEN

BASE CIVIL ENGINEER

APPROVED

APPROVED DATE

SCALE

CONTENTS

SHEET

DESCRIPTION

09/15/2016

AS SHOWN

16AS15-121416AS OF2

BEJ

GDP

M-001

HVAC LEGENDS, NOTES & ABBREVIATION

UP

U P

D N

UP

DN

UP

UP

UP

UP

UP

UPUP

UP

UP

UP

DN

UP

UP

EX. HX

EX. HX

EX. HX

EX. HX

EX. HX

EX. HX

EX. HX

EX. HX

EX. HX

M-101

M-101

M-101

M-101

8" ø

C A

C L2

4"ø 4"ø

BLDG 435

B

LD

G

8" ø

R -2

8" ø

R -2

CACL2

CACL2

8" ø

R -2

8"ø R-22

M-101

EX. HX

EX. HX

502 EX. HX

EX. HX

EX. HX

8"ø R-22 8"ø R-22

M-101

EX. HX

EX. HX

EX. HX

EX. HX

EX. HX

8"ø CACL2

8"ø CACL2

8" ø

R -2

EX. HX

EX. HX

EX. HX

EX. HX

M-101

M-101

EX. HX

EX. HX

BLDG 440

75 SOUTH "F" STREET

PENSACOLA, FLORIDA 32502

(850) 434-0513

(PROF. ENG. #: 3600)

PEI JOB #2015185

PETERSON ENGINEERING INC.

BASE CIVIL ENGINEER

EGLIN AIR FORCE BASE, FLORIDA

AS-BUILT

REPLACE HEAT EXCHANGER

CLIMATIC LAB HANGAR 440

96 CEG, OFFICE FORM 002, FY2014

TITLE

DATEREVISION APPR'DBY

CENM

SIGNATURE

APPROVED

DATE

PROJ. ENGR.

DRAWN BY

INDEX NO.

SPEC. NO. PROJ. NO.

FTFA

DRAWING NO. FILE NO.

96 CEG/CEN

BASE CIVIL ENGINEER

APPROVED

APPROVED DATE

SCALE

CONTENTS

SHEET

DESCRIPTION

09/15/2016

AS SHOWN

16AS15-121416AS OF3

BEJ

GDP

M-101

PARTIAL FLOOR PLAN - HVAC DEMO

1/8" = 1'-0"1

PARTIAL FLOOR PLAN - HVAC DEMO

KEY PLAN

NOT TO SCALEN

N

1/8" = 1'-0"2

AMU-2 DEMO SECTION-2

1/8" = 1'-0"3

AMU-2 DEMO SECTION-3

1/8" = 1'-0"4

AMU-1 DEMO SECTION-4

1/8" = 1'-0"5

AMU-1 DEMO SECTION-5

AREA SHOWN

DEMO SHEET NOTES

1 DEMO EXISTING HX-501/502 & ASSOCIATED PIPING AS INDICATED. EXISTING HOIST

SHALL BE REMOVED PRIOR TO INSTALLATION OF HEAT EXCHANGER.

DEMO EXISTING HX-508/509 & ASSOCIATED PIPING AS INDICATED. EXISTING HOIST

SHALL BE REMOVED PRIOR TO INSTALLATION OF HEAT EXCHANGER.

NOTE REFER TO SINGLE LINE DIAGRAM FOR PIPE VALVES AND ACCESSORIES.

U P

D N

UP

DN

UP

UP

UP

UP

UP

UPUP

UP

UP

UP

DN

UP

UP

EX. HX

EX. HX

EX. HX

EX. HX

EX. HX

M-301

M-301

M-301

M-301

HX

HX

HX

HX

4 TYP.

8" ø

C A

C L2

REFER TO M-103 FOR CONTINUATION.

BLDG 435

B

LD

G

8" ø

R -2

8" ø

R -2

8" ø

R -2

8"ø R-22

8"ø CACL2 8"ø CACL2

BLDG 440

75 SOUTH "F" STREET

PENSACOLA, FLORIDA 32502

(850) 434-0513

(PROF. ENG. #: 3600)

PEI JOB #2015185

PETERSON ENGINEERING INC.

BASE CIVIL ENGINEER

EGLIN AIR FORCE BASE, FLORIDA

AS-BUILT

REPLACE HEAT EXCHANGER

CLIMATIC LAB HANGAR 440

96 CEG, OFFICE FORM 002, FY2014

TITLE

DATEREVISION APPR'DBY

CENM

SIGNATURE

APPROVED

DATE

PROJ. ENGR.

DRAWN BY

INDEX NO.

SPEC. NO. PROJ. NO.

FTFA

DRAWING NO. FILE NO.

96 CEG/CEN

BASE CIVIL ENGINEER

APPROVED

APPROVED DATE

SCALE

CONTENTS

SHEET

DESCRIPTION

09/15/2016

AS SHOWN

16AS15-121416AS OF4

BEJ

GDP

M-102

PARTIAL FLOOR PLAN - HVAC NEW WORK

1/8" = 1'-0"

PARTIAL FLOOR PLAN - HVAC NEW WORK

NEW WORK SHEET NOTES

1 CONTRACTOR SHALL VERIFY THAT THE SIZE OF THE HEAT EXCHANGE WILL FIT

BETWEEN EXISTING STRUCTURE AND EQUIPMENT WITH THE REQUIRED

CLEARANCE TO ALLOW FOR PIPE INSTALLATION PRIOR TO CONSTRUCTION.

ROUTE 8"ø R-22 SS PIPING TO SHELL SIDE OF HEAT EXCHANGER. PROVIDE

INSULATION TO MATCH EXISTING.

ROUTE 8"ø CACL2 SS PIPING TO TUBE SIDE OF HEAT EXCHANGER. PROVIDE

INSULATION TO MATCH EXISTING.

EXTEND HEAT EXCHANGER SUPPORTS AS RECOMMENDED BY

MANUFACTURER. PROVIDE DOWELS TO SECURE CONCRETE SUPPORT TO

EXISTING, REFER TO DETAILS.

KEY PLAN

NOT TO SCALEN

AREA SHOWN

N

NOTE REFER TO SINGLE LINE DIAGRAM FOR PIPE VALVES AND ACCESSORIES.

U P

D N

UP

DN

UP

UP

UP

UP

UP

UPUP

UP

UP

UP

DN

UP

UP

UP

DN

UP

DN

12"ø CACL2

12"ø CACL2

REFER TO M-102 FOR CONTINUATION.

P

8"ø CACL2

8"ø CACL2

8" ø

BLDG 440

8" ø

C A

C L2

8"ø CACL2

"ø

C A

C L2

"ø

C A

C L2

8"ø CACL2

12"ø CACL2

P

EX. P

REFER TO M-101 FOR CONTINUATION.

4"ø

12"ø CACL2

12"ø CACL2

6" ø

4"ø

CACL2

CACL2

EX. P

12"ø CACL2

8" ø

C A

C L2

8"ø CACL2

8"ø CACL2

"ø

C A

C L2

"ø

C A

C L2

75 SOUTH "F" STREET

PENSACOLA, FLORIDA 32502

(850) 434-0513

(PROF. ENG. #: 3600)

PEI JOB #2015185

PETERSON ENGINEERING INC.

BASE CIVIL ENGINEER

EGLIN AIR FORCE BASE, FLORIDA

AS-BUILT

REPLACE HEAT EXCHANGER

CLIMATIC LAB HANGAR 440

96 CEG, OFFICE FORM 002, FY2014

TITLE

DATEREVISION APPR'DBY

CENM

SIGNATURE

APPROVED

DATE

PROJ. ENGR.

DRAWN BY

INDEX NO.

SPEC. NO. PROJ. NO.

FTFA

DRAWING NO. FILE NO.

96 CEG/CEN

BASE CIVIL ENGINEER

APPROVED

APPROVED DATE

SCALE

CONTENTS

SHEET

DESCRIPTION

09/15/2016

AS SHOWN

16AS15-121416AS OF5

BEJ

GDP

M-103

PARTIAL FLOOR PLAN - PUMP HOUSE HVAC

1/8" = 1'-0"

PARTIAL FLOOR PLAN - PUMP HOUSE AMU-1 NEW WORK

KEY PLAN

NOT TO SCALEN

AREA SHOWN

AREA SHOWN

1/8" = 1'-0"

PARTIAL FLOOR PLAN - PUMP HOUSE AMU-2 NEW WORK

N N

DEMO SHEET NOTES

1 DEMO EXISTING REGENERATING CACL2 PUMPS AND PIPING AS

INDICATED. EXISTING PUMPS SHALL BE TURNED OVER TO THE

GOVERNMENT.

DEMO MAX FLOW ORIFIC APPROXIMATE LOCATION SHOWN.

NOTE REFER TO SINGLE LINE DIAGRAM FOR PIPE VALVES AND ACCESSORIES. NOTE REFER TO SINGLE LINE DIAGRAM FOR PIPE VALVES AND ACCESSORIES.

1/8" = 1'-0"

PARTIAL FLOOR PLAN - PUMP HOUSE AMU-1 DEMO

1/8" = 1'-0"

PARTIAL FLOOR PLAN - PUMP HOUSE AMU-2 DEMO

N N

NEW WORK SHEET NOTES

1 EXTEND 53.5"x24" PUMP PAD AS REQUIRED TO ALLOW FOR A MIN OF 6" AROUND

PUMP. REFER TO DETAIL 1/M-601 FOR PUMP INSTALLATION DETAIL. REFER TO

ELECTRICAL FOR VFD MOUNTING AND LOCATION.

EXISTING 84"x42" PUMP PAD SHALL BE OF SUFFICIENT SIZE TO ALLOW FOR A MIN OF

6" AROUND PUMP. REFER TO DETAIL 1/M-601 FOR PUMP INSTALLATION DETAIL.

REFER TO ELECTRICAL FOR VFD MOUNTING AND LOCATION.

NOTE REFER TO SINGLE LINE DIAGRAM FOR PIPE VALVES AND ACCESSORIES. NOTE REFER TO SINGLE LINE DIAGRAM FOR PIPE VALVES AND ACCESSORIES.

M-301

HX

HX

13' - 2"

8"ø R-22

8"ø R-22

EX. HX

EX. HX

EX. HX

2' - 9"

11' - 2"

5' - 2"

APPROX.

APPROX.

APPROX.

APPROX.

M-301

HX

HX

28"ø R-22

8" ø

C A

C L2

8" ø

C A

C L2

EX. HX

EX. HX

EX. HX

8" ø

R -2

M-301

HX

HX

TYP.

3' - 6"

14' - 11"

7' - 3"

EX. HX

EX. HX

506 8" ø C

A C

L2

8"ø CACL2

8"ø R-22

8"ø R-22

8" ø

C A

C L2

8' - 8"

APPROX.

APPROX.

APPROX.

APPROX.

M-301

HX

HX

4 TYP.

8"ø CACL2

8"ø R-22

8"ø R-22

75 SOUTH "F" STREET

PENSACOLA, FLORIDA 32502

(850) 434-0513

(PROF. ENG. #: 3600)

PEI JOB #2015185

PETERSON ENGINEERING INC.

BASE CIVIL ENGINEER

EGLIN AIR FORCE BASE, FLORIDA

AS-BUILT

REPLACE HEAT EXCHANGER

CLIMATIC LAB HANGAR 440

96 CEG, OFFICE FORM 002, FY2014

TITLE

DATEREVISION APPR'DBY

CENM

SIGNATURE

APPROVED

DATE

PROJ. ENGR.

DRAWN BY

INDEX NO.

SPEC. NO. PROJ. NO.

FTFA

DRAWING NO. FILE NO.

96 CEG/CEN

BASE CIVIL ENGINEER

APPROVED

APPROVED DATE

SCALE

CONTENTS

SHEET

DESCRIPTION

09/15/2016

AS SHOWN

16AS15-121416AS OF6

BEJ

GDP

M-301

HVAC SECTIONS

1/4" = 1'-0"1

AMU-2 SECTION-1

1/4" = 1'-0"2

AMU-2 SECTION-2

1/4" = 1'-0"3

AMU-1 SECTION-3

1/4" = 1'-0"4

AMU-1 SECTION-4

NEW WORK SHEET NOTES

1 CONTRACTOR SHALL VERIFY THAT THE SIZE OF THE HEAT EXCHANGE WILL FIT

BETWEEN EXISTING STRUCTURE AND EQUIPMENT WITH THE REQUIRED CLEARANCE

TO ALLOW FOR PIPE INSTALLATION PRIOR TO CONSTRUCTION.

ROUTE 8"ø R-22 SS PIPING TO SHELL SIDE OF HEAT EXCHANGER. PROVIDE

INSULATION TO MATCH EXISTING.

ROUTE 8"ø CACL2 SS PIPING TO TUBE SIDE OF HEAT EXCHANGER. PROVIDE

INSULATION TO MATCH EXISTING.

EXTEND HEAT EXCHANGER SUPPORTS AS RECOMMENDED BY MANUFACTURER.

PROVIDE DOWELS TO SECURE CONCRETE SUPPORT TO EXISTING, REFER TO

DETAILS.

PUMP SCHEDULE

MARK LOCATION SERVICE TYPE SUCT/DISCH

IMP. DIA.

IN.

PERFORMANCE DATA ELECTRICAL DATA BASIS OF DESIGN

REMARKSMAX.

CAPACITY

GPM

MIN.

CAPACITY

GPM

MAX. DISCHARGE

PSI

MAX. RPM NPSHr

MIN.

EFFICIENCY

MAX. MOTOR

HP

V/ф/Hz MAKE MODEL

P-4 PUMP HOUSE AMU-1 HX-508 & 509 HRZ. FRAME END SUCTION 6" x 4" 10.25 800 340 150 3600 19.6 72.5% 125 460/3/60 GOULDS PUMPS 3196 REFER TO ALL NOTES

P-503 PUMP HOUSE AMU-2 HX-501 & 502 HRZ. FRAME END SUCTION 6" x 4" 10.25 800 340 150 3600 19.6 72.5% 125 460/3/60 GOULDS PUMPS 3196 REFER TO ALL NOTES

PUMP SCHEDULES NOTES:

1. PUMP SHALL BE NON OVER LOADING THROUGHOUT THE ENTIRE PUMP CURVE.

2. PROVIDE VFD WITH NEMA 4 ENCLOSURE.

3. PROVIDE FLOW MEASURING STATION.

4. PUMPS SHALL BE STAINLESS STEEL CONSTRUCTION.

HEAT EXCHANGER SCHEDULE

MARK SHELLS/UNITS ARRANGEMENT TYPE

MAX. CAPACITY

BTU/HR

BRINE DATA REFRIGERANT DATA TUBES SHELL BASIS OF DESIGN

REMARKS

TYPE

GPM

(MIN/MAX)

ENT °F

LVG °F

(MIN/MAX)

∆T °F

(MIN/MAX)

PRESSURE DROP PSI

(MIN/MAX)

TYPE GPM ENT °F LVG °F

PRESSURE

DROP PSI

OD LENGTH IN MATERIAL INLET OUTLET ID MATERIAL INLET OUTLET MANUFACTURER

HX-501 & 502 2 2 SERIES AFM 6,000,300 27% CACL2 364 / 787 40 0 / 21.7 40 / 20 10.77 / 36.84 R-22 1,000 -18 14.5 10.62 0.75 240 316 SS 8" 8" 36 316 SS 8" 8" ALABAMA HEAT EXCHANGER REFER TO ALL NOTES

HX-508 & 509 2 2 SERIES AFM 6,000,300 27% CACL2 364 / 787 40 0 / 21.7 40 / 20 10.77 / 36.84 R-22 1,000 -18 14.5 10.62 0.75 240 316 SS 8" 8" 36 316 SS 8" 8" ALABAMA HEAT EXCHANGER REFER TO ALL NOTES

HEAT EXCHANGER SCHEDULE NOTES:

1. PROVIDE INSULATION TO MATCH EXISTING.

2. CONTRACTOR SHALL SUBMIT SHOP DRAWINSG OF PROPOSED NEW HEAT EXCHANGERS TO INCLUDE ALL REQUIRED CLEARANCES. SHOP DRAWINGS SHALL BE SUBMITTED AND APPROVED PRIOR TO ORDERING EQUIPMENT.

3. CHANNEL, BAFFLE-CROSS, BAFFLE-LONG, T-SHTS.-STAT & CHANNEL COVER SHALL BE 316 SS.

NOT TO SCALE

NOT TO SCALE

NOT TO SCALE

NOT TO SCALE1

PUMP INSTALLATION DETAIL

DOWEL DETAIL

TRAPEZE HANGER DETAIL

AFM TYPE 2-SERIES HEAT EXCHANGER DETAIL

PRESSURE GAGE

GAGE COCK TYP.

P

X

GUARD

EXISTING CONCRETE NEW CONCRETE

DOWEL

COMPRESSIBLE FILLER

JOINT SEALANT

ANGLED PIPE SUPPORT

SHALL BE MIN 2"x2"x1/4".

HANGAR ROD SHALL BE

MIN 3/8".

HOLE PACKED WITH

LOCKSET OR SIMILAR

BEFORE INSERTING DOWEL.

FLEX CONNECTION.

CONCENTRIC REDUCERS.

DRAIN PAN.

1/2" DRAIN SLOPE TO FLOOR DRAIN.

ADJUSTABLE FOOT SUPPORT.

BLOWDOWN GATE VALVE

WITH 3/4" HOSE END.

SUCTION DIFFUSER WITH

INTEGRAL STRAINER.

EXTEND EXISTING CONCRETE PAD W/CHAMFER

EDGES WITH WWF 6x6-W4xW4 3000 PSI CONC. USE

A MIN. OF 6 EA DOWELS TO ANCHOR PAD TO

EXISTING FLOOR. DRILL DOWN A MIN. 3" TO

ALLOW INSTALLATION OF DOWELS. DOWELS

SHALL BE #4 REBAR.

BALANCING/SHUT-OFF

VALVE WITH PRESSURE

TAPS

CONNECT TO EXISTING

PIPING FOR AMU-2 ONLY.

CONNECT TO EXISTING

PIPING FOR AMU-2 ONLY.

R-22 IN OR OUT

R-22 IN OR OUT

CALCIUM IN OR OUT

CALCIUM IN OR OUT

DIVISION SHEET

(REMOVABLE)

SEAL STRIP

R-22 SHELL SIDE

REMOVABLE END CAP

SOLID ROUND PLATE

WITH GASKET.

TUBE SHEET WITH GASKET TYP.

R-22 SHELL SIDE

75 SOUTH "F" STREET

PENSACOLA, FLORIDA 32502

(850) 434-0513

(PROF. ENG. #: 3600)

PEI JOB #2015185

PETERSON ENGINEERING INC.

BASE CIVIL ENGINEER

EGLIN AIR FORCE BASE, FLORIDA

AS-BUILT

REPLACE HEAT EXCHANGER

CLIMATIC LAB HANGAR 440

96 CEG, OFFICE FORM 002, FY2014

TITLE

DATEREVISION APPR'DBY

CENM

SIGNATURE

APPROVED

DATE

PROJ. ENGR.

DRAWN BY

INDEX NO.

SPEC. NO. PROJ. NO.

FTFA

DRAWING NO. FILE NO.

96 CEG/CEN

BASE CIVIL ENGINEER

APPROVED

APPROVED DATE

SCALE

CONTENTS

SHEET

DESCRIPTION

09/15/2016

AS SHOWN

16AS15-121416AS OF7

BEJ

GDP

M-601

HVAC SCHEDULES, DETAILS & CONTROLS

CACL2 PUMP SEQUENCE OF OPERATION

1. PUMPS SHALL BE STARTED MANUALLY BY OPERATOR INPUT TO CONTROL PANEL LOCATED IN CONTROL ROOM. COORDINATE EXACT

LOCATION OF PANEL(S) WITH CONTRACTING OFFICER'S REPRESENTATIVE AND OPERATOR.

2. CONTROL PANEL SHALL DISPLAY PUMP GPM AND VFD FREQUENCY.

3. OPERATOR SHALL BE ABLE TO SET PUMP FLOW (GPM) AND VFD SHALL MAINTAIN SETPOINT.

4. THE CONTROLS SHALL HAVE A SWITCH WHICH ALLOWS MANUAL SETTING OF PUMP SPEED AND/OR AN AUTOMATIC POSITION WHICH

ALLOWS THE PUMP TO VARY SPEED TO MAINTAIN A SPECIFIC FLOW.

5. PUMP SHALL RUN CONTINUOUSLY UNTIL MANUALLY SHUT DOWN.

EX. P

EX. HX

EX. CACL2 STORAGE TANK

FROM EX. AMU-1 COILS

TO EX. PRIMARY PUMP

FROM EX. CACL2 STORAGE TANK

TO EX. CACL2 STORAGE TANK

TO EX. CACL2 STORAGE TANK

FROM EX. CACL2 STORAGE TANK

EX. 12" CACL2

EX. 12" CACL2

EX. 4" CACL2

EX. 4" CACL2

EX. 4" CACL2

EX. 6" CACL2

EX. 12" CACL2

EX. 12" CACL2

EX. 8" R-22

EX. HX

P

HX

HX

CACL2 STORAGE TANK

FROM EX. AMU-1 COILS

TO EX. PRIMARY PUMP

FROM EX. CACL2 STORAGE TANK

TO EX. CACL2 STORAGE TANK

TO EX. CACL2 STORAGE TANK

FROM EX. CACL2 STORAGE TANK

EX. 12" CACL2

EX. 12" CACL2

8" CACL2

8" CACL2

8" CACL2

8" CACL2

EX. 12" CACL2

EX. 12" CACL2

8" R-22

FM

6" CACL2

4" CACL2

8" CACL2

75 SOUTH "F" STREET

PENSACOLA, FLORIDA 32502

(850) 434-0513

(PROF. ENG. #: 3600)

PEI JOB #2015185

PETERSON ENGINEERING INC.

BASE CIVIL ENGINEER

EGLIN AIR FORCE BASE, FLORIDA

AS-BUILT

REPLACE HEAT EXCHANGER

CLIMATIC LAB HANGAR 440

96 CEG, OFFICE FORM 002, FY2014

TITLE

DATEREVISION APPR'DBY

CENM

SIGNATURE

APPROVED

DATE

PROJ. ENGR.

DRAWN BY

INDEX NO.

SPEC. NO. PROJ. NO.

FTFA

DRAWING NO. FILE NO.

96 CEG/CEN

BASE CIVIL ENGINEER

APPROVED

APPROVED DATE

SCALE

CONTENTS

SHEET

DESCRIPTION

09/15/2016

AS SHOWN

16AS15-121416AS OF8

BEJ

GDP

M-701

SINGLE LINE DIAGRAM AMU-1

NOT TO SCALE1

DEMO SINGLE LINE DIAGRAM - AMU-1

NOT TO SCALE

NEW WORK SINGLE LINE DIAGRAM - AMU-1

DEMO SHEET NOTES

1 DEMO EXISTING REGENERATING CACL2 PUMPS AND TURN OVER TO THE

GOVERNMENT.

DEMO EXISTING HEAT EXCHANGERS.

DEMO PIPING AND ASSOCIATED EQUIPMENT AS INDICATED. REFER TO NEW WORK

PLAN THIS SHEET FOR NEW LOCATION OF VALVES.

NEW WORK SHEET NOTES

NEW REGENERATING PUMP, REFER TO DETAIL 1/M-601 FOR PUMP INSTALLATION

DETAIL.

ROUTE 8"ø R-22 SS PIPING TO SHELL SIDE OF HEAT EXCHANGER. PROVIDE

INSULATION TO MATCH EXISTING.

ROUTE 8"ø CACL2 SS PIPING TO TUBE SIDE OF HEAT EXCHANGER. PROVIDE

INSULATION TO MATCH EXISTING. ALL VALVES AND STRAINERS SHALL BE REPLACED

WITH SS TYPE.

INSTALL SS FLOW MEASURING STATION. PROVIDE STRAIGHT PIPE PER

MANUFACTURERS RECOMMENDATION.

EX. P

EX.HX

EX. CACL2 STORAGE TANK

FROM EX. CACL2 STORAGE TANK

TO EX. CACL2 STORAGE TANK

EX. 20" CACL2

EX. 18"

CACL2

EX. 8" CACL2

EX. 8" CACL2

EX. 8" CACL2

EX. 8" CACL2

EX. 12" CACL2

EX. 12" CACL2

FROM EX. AMU-2 COILS

TO EX. PRIMARY PUMP P-501

EX. RESIDUAL TANK T-507

EX. 6" CACL2

EX. 4" CACL2

EX. 8" R-22

EX.HX

P

HX

HX

EX. CACL2 STORAGE TANK

FROM EX. CACL2 STORAGE TANK

TO EX. CACL2 STORAGE TANK

EX. 20" CACL2

EX. 18"

CACL2EX. 8" CACL2

EX. 8" CACL2

EX. 8"

CACL2

EX. 8" CACL2

EX. 12" CACL2

EX. 12" CACL2

FROM EX. AMU-2 COILS

TO PRIMARY PUMP P-501

EX. RESIDUAL TANK T-507

6" CACL2

4" CACL2

8" R-22

FM

8" CACL2

75 SOUTH "F" STREET

PENSACOLA, FLORIDA 32502

(850) 434-0513

(PROF. ENG. #: 3600)

PEI JOB #2015185

PETERSON ENGINEERING INC.

BASE CIVIL ENGINEER

EGLIN AIR FORCE BASE, FLORIDA

AS-BUILT

REPLACE HEAT EXCHANGER

CLIMATIC LAB HANGAR 440

96 CEG, OFFICE FORM 002, FY2014

TITLE

DATEREVISION APPR'DBY

CENM

SIGNATURE

APPROVED

DATE

PROJ. ENGR.

DRAWN BY

INDEX NO.

SPEC. NO. PROJ. NO.

FTFA

DRAWING NO. FILE NO.

96 CEG/CEN

BASE CIVIL ENGINEER

APPROVED

APPROVED DATE

SCALE

CONTENTS

SHEET

DESCRIPTION

09/15/2016

AS SHOWN

16AS15-121416AS OF9

BEJ

GDP

M-702

SINGLE LINE DIAGRAM AMU-2

NOT TO SCALE

DEMO SINGLE LINE DIAGRAM - AMU-2

NOT TO SCALE

NEW WORK SINGLE LINE DIAGRAM - AMU-2

DEMO SHEET NOTES

NEW WORK SHEET NOTES

1 DEMO EXISTING REGENERATING CACL2 PUMPS AND TURN OVER TO THE

GOVERNMENT.

DEMO EXISTING HEAT EXCHANGERS.

DEMO PIPING AND ASSOCIATED EQUIPMENT AS INDICATED. REFER TO NEW WORK

PLAN THIS SHEET FOR NEW LOCATION OF VALVES.

DEMO MAX FLOW ORIFIC.

NEW REGENERATING PUMP, REFER TO DETAIL 1/M-601 FOR PUMP INSTALLATION

DETAIL.

ROUTE 8"ø R-22 SS PIPING TO SHELL SIDE OF HEAT EXCHANGER. PROVIDE

INSULATION TO MATCH EXISTING.

ROUTE 8"ø CACL2 SS PIPING TO TUBE SIDE OF HEAT EXCHANGER. PROVIDE

INSULATION TO MATCH EXISTING.

INSTALL SS FLOW MEASURING STATION. PROVIDE STRAIGHT PIPE PER

MANUFACTURERS RECOMMENDATION.

M

ELECTRICAL PLAN - PUMP HOUSE AMU-1 - DEMOLITION

SCALE: 1/8" = 1'-0"

ELECTRICAL PLAN - PUMP HOUSE AMU-1 - NEW WORK

SCALE: 1/8" = 1'-0"

EXISTING MOTOR CONTROL CENTER "MCC-2"

(SIEMENS MOTOR CONTROL CENTER - 800 AMP,

480 V., 3Ø, 3 W.)

REMOVE EXISTING PUSHBUTTON STATION.

REMOVE EXISTING CONTROL WIRING & CONDUIT FROM

PUSHBUTTON STATION BACK TO MOTOR STARTER IN "MCC-2."

REMOVE EXISTING POWER WIRING FROM MOTOR BACK TO "MCC-2."

REMOVE EXISTING POWER WIRING ROUTED IN CABLE TRAY

BACK TO "MCC-2."

REMOVE EXISTING CONDUIT FROM MOTOR BACK TO EXISTING CABLE TRAY.

REMOVE EXISTING FLEXIBLE CONDUIT & WIRING CONNECTION TO

EXISTING PUMP. REMOVE EXISTING RIGID STEEL CONDUIT DROP FROM

OVERHEAD STRUCTURE TO FLOOR, INCLUDING FLOOR FLANGE.

EXISTING PUMP "P-4" IS 25 HP, 480 V., 3Ø

NEW PUMP P-4

125 HP, 480 V., 3Ø

NEW LIQUID-TIGHT FLEXIBLE CONDUIT AND

WIRING CONNECTION FROM VFD TO PUMP P-4.

NEW VARIABLE FREQUENCY DRIVE - FURNISHED BY

MECHANICAL CONTRACTOR & INSTALLED BY ELECTRICAL

CONTRACTOR. SEE "DETAIL - VFD STRUCTURE," THIS SHEET.

ELEVATION - MOTOR CONTROL

CENTER "MCC-2"

N.T.S.

400 A., 3 P., NEMA 3R DISCONNECT SWITCH.

SEE "DETAIL - VFD STRUCTURE," THIS SHEET.

145 KVA, 3Ø DRIVE ISOLATION TRANSFORMER -

460 V. DELTA TO 460Y/266 VOLT. SEE "DETAIL -

VFD STRUCTURE," THIS SHEET.

EXTEND WIRING FROM DISCONNECT SWITCH TO ENCLOSED CIRCUIT

BREAKER IN ELECTRICAL ROOM AS SHOWN ON "WIRING DIAGRAM -

PUMP P-4," THIS SHEET.

EXTEND NEW CONTROL WIRING IN 1" RIGID GALV. STEEL CONDUIT FROM NEW VFD TO

EXISTING CABLE TRAY AND THRU CABLE TRAY TO EXISTING CONTROL ROOM IN HANGAR 440.

DETAIL - VFD STRUCTURE

NO SCALE

FRONT VIEW

CONC. EXPANSION ANCHORS (TYP.)

TRANSFORMER

DRIVE ISOLATION

VFD

CONC. FLOOR

ANGLE

1/4" THICK

SIDE VIEW

12"

3'-0"± OR AS

REQUIRED BY

EQUIPMENT BEING

INSTALLED

HEIGHT AS

REQUIRED BY VFD

BEING INSTALLED

5'-0"± OR AS

REQUIRED BY

TRANSFORMER

BEING INSTALLED

CORE DRILL EXISTING EXTERIOR CONCRETE BLOCK WALL FOR NEW CONDUIT

PENETRATIONS. GROUT AROUND CONDUIT PENETRATIONS W/ NON-SHRINK GROUT.

CORE DRILL EXISTING EXTERIOR CONCRETE BLOCK WALL FOR NEW CONDUIT

PENETRATIONS. GROUT AROUND CONDUIT PENETRATIONS W/ NON-SHRINK GROUT.

REMOVE EXISTING CIRCUIT BREAKER AND MOTOR STARTER

CURRENTLY SERVING PUMP P-4. REMOVE ALL COMPONENTS

FROM CUBICLE. REMOVE CONDUCTORS FROM BREAKER TO

EXISTING MCC BUSSING. INSTALL A NEW BLANK DOOR ON

CUBICLE (12" HIGH). EXISTING MCC IS MANUFACTURED BY

SIEMENS, SERIES 2100.

AREA OF WORK - PUMP P-4

KEY PLAN

N.T.S.

400 A., 3 P., NEMA 3R

DISCONNECT SWITCH.

NEW VARIABLE FREQUENCY DRIVE -

FURNISHED BY MECHANICAL

CONTRACTOR & INSTALLED BY

ELECTRICAL CONTRACTOR. PROVIDE VFD

W/ NEMA 4 OUTDOOR ENCLOSURE.

145 KVA, 3Ø DRIVE ISOLATION

TRANSFORMER - 460 V. DELTA

TO 460Y/266 VOLT - W/ NEMA 3R

WEATHERSHIELD.

12 GAUGE, 1 5/8" X 1 5/8"

HOT-DIPPED

GALVANIZED STEEL

CHANNEL (TYP.)

12 GAUGE, 1 5/8" X 1 5/8"

HOT-DIPPED

GALVANIZED STEEL

CHANNEL (TYP.)

12 GAUGE, 1 5/8" X 1 5/8"

HOT-DIPPED

GALVANIZED STEEL

CHANNEL (TYP.)

M

400 A., 3 P., NEMA 3R

DISCONNECT SWITCH.

NEW VARIABLE FREQUENCY DRIVE - FURNISHED BY MECHANICAL

CONTRACTOR & INSTALLED BY ELECTRICAL CONTRACTOR.

PROVIDE VFD W/ NEMA 4 OUTDOOR ENCLOSURE.

145 KVA, 3Ø DRIVE ISOLATION TRANSFORMER - 460 V.

DELTA TO 460Y/266 VOLT - W/ NEMA 3R WEATHERSHIELD.

EXTEND 3/C # 4/0 TC POWER CABLE W/ # 4

GND. IN 3" RIGID GALV. STEEL CONDUIT FROM

CIRCUIT BREAKER THRU EXTERIOR WALL TO

EXISTING CABLE TRAY. CORE DRILL

CONCRETE BLOCK WALL FOR CONDUIT

PENETRATION & GROUT AROUND CONDUIT.

3 # 4/0 & 1 # 4 GND. IN 2" LIQUID

TIGHT FLEXIBLE METAL CONDUIT.

4 # 4/0 & 1 # 4 GND. IN 2 1/2" LIQUID

TIGHT FLEXIBLE METAL CONDUIT.

# 4 BARE COPPER GROUND CONDUCTOR TO 3/4" X 20'-0"

COPPERCLAD GROUND ROD. BOND GROUND CONDUCTOR TO

ROD W/ EXOTHERMIC WELD. CORE DRILL THRU CONC SLAB &

INSTALL ROD BELOW TRANSFORMER. DRILL 1" HOLE. LEAVE

2" OF ROD EXPOSED W/ GROUND CONNECTION ABOVE SLAB.

3 # 4/0 & 1 # 4 GND. IN 2" LIQUID

TIGHT FLEXIBLE METAL CONDUIT.

NEW PUMP P-4

125 HP, 480 V., 3Ø

WIRING DIAGRAM - PUMP P-4

N.T.S.

225 A., 3 P., 480 V., 65 KAIC CIRCUIT

BREAKER IN NEMA 1 ENCLOSURE.

EXTEND 3 - 300 MCM & 1 # 4 GND. IN 3" RIGID GALV. STEEL

CONDUIT TO EXISTING MOTOR CONTROL CENTER. TAP

EXISTING BUSSING IN MOTOR CONTROL CENTER ON

LOAD SIDE OF EXISTING MAIN BREAKER & EXTEND

CONDUIT & WIRING TO ENCLOSED CIRCUIT BREAKER.

ROUTE TC CABLE THRU CABLE

TRAY FROM PUMP ROOM TO

ELECTRICAL ROOM.

EXTEND 3/C # 4/0 TC POWER CABLE W/ # 4

GND. IN 3" RIGID GALV. STEEL CONDUIT FROM

DISCONNECT SWITCH TO EXISTING CABLE

TRAY.

225 A., 3 P., 480 V., 65 KAIC CIRCUIT

BREAKER IN NEMA 1 ENCLOSURE.

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

PETERSON ENGINEERING INC.

(850) 434-0513

ELECTRICAL PLAN - PUMP HOUSE AMU-2 - DEMOLITION

SCALE: 1/8" = 1'-0"

ELECTRICAL PLAN - PUMP HOUSE AMU-2 - NEW WORK

SCALE: 1/8" = 1'-0"

EXISTING MOTOR CONTROL CENTER "EMC-502"

(CUTLER HAMMER - WESTINGHOUSE SERIES

2100 MOTOR CONTROL CENTER - 1600 AMP,

480Y/277 V., 3Ø, 4 W.)

EXISTING MOTOR CONTROL CENTER "EMC-502"

AREA OF WORK - PUMP P-503

KEY PLAN

N.T.S.

REMOVE EXISTING PUSHBUTTON STATION.

REMOVE EXISTING CONTROL WIRING & CONDUIT FROM

PUSHBUTTON STATION BACK TO MOTOR STARTER IN "MCC-2."

REMOVE EXISTING POWER WIRING FROM MOTOR BACK TO "MCC-2."

REMOVE EXISTING FLEXIBLE CONDUIT & WIRING

CONNECTION TO EXISTING PUMP. REMOVE EXISTING

DISCONNECT SWITCH & SUPPORT STRUCTURE CHANNELS IN

THEIR ENTIRETY. EXISTING PUMP "P-503" IS 40 HP, 480 V., 3Ø

NEW PUMP P-503

125 HP, 480 V., 3Ø

NEW LIQUID-TIGHT FLEXIBLE CONDUIT AND WIRING

CONNECTION FROM VFD TO PUMP P-503.

NEW VARIABLE FREQUENCY DRIVE - FURNISHED BY

MECHANICAL CONTRACTOR & INSTALLED BY ELECTRICAL

CONTRACTOR. MOUNT ON CONCRETE BLOCK WALL

ADJACENT TO DRIVE ISOLATION TRANSFORMER.

400 A., 3 P., NEMA 3R DISCONNECT SWITCH.

MOUNT ON CONCRETE BLOCK WALL ADJACENT

TO DRIVE ISOLATION TRANSFORMER.

145 KVA, 3Ø DRIVE ISOLATION TRANSFORMER -

460 V. DELTA TO 460Y/266 VOLT. SEE "DETAIL -

VFD STRUCTURE," SHEET E-103.

EXTEND 3 # 4/0 & 1 # 4 GND. IN 2" RIGID GALV. STEEL

CONDUIT FROM VFD TO NEW MOTOR LOCATION. SEE

"WIRING DIAGRAM - PUMP P-503," SHEET E-103.

EXTEND WIRING FROM DISCONNECT SWITCH TO MOTOR CONTROL

CENTER EMC-502 AS SHOWN ON "WIRING DIAGRAM - PUMP P-503,"

SHEET E-103.

EXTEND NEW CONTROL WIRING IN 1" RIGID GALV. STEEL

CONDUIT FROM NEW VFD TO EXISTING CABLE TRAY AND THRU

CABLE TRAY TO EXISTING CONTROL ROOM IN HANGAR 440.

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

ELEVATION - MOTOR CONTROL

CENTER "EMC-502"

N.T.S.

REMOVE EXISTING CIRCUIT BREAKER AND MOTOR STARTER CURRENTLY SERVING PUMP

P-503. REMOVE ALL COMPONENTS FROM CUBICLE. REMOVE CONDUCTORS FROM BREAKER

TO EXISTING MCC BUSSING. INSTALL A NEW MCC BUCKET, 225 A., 3 P., 65 KAIC CIRCUIT

BREAKER, NEW 18" DOOR FOR CIRCUIT BREAKER, NEW 12" DOOR AND HORIZONTAL BARRIER

BELOW NEW CIRCUIT BREAKER, INCLUSIVE OF ALL HARDWARE AND ACCESSORIES REQUIRED

FOR THE NEW INSTALLATION IN EXISTING MCC CUBICLE FOR NEW PUMP P-503. PROVIDE NEW

# 4/0 CONDUCTORS FROM CIRCUIT BREAKER TO EXISTING MCC BUSSING. PROVIDE NEW LUGS

ON EXISTING MCC BUSSING IF REQUIRED FOR LARGER CONDUCTOR SIZE. EXISTING MCC IS

MANUFACTURED BY CUTLER HAMMER/WESTINGHOUSE, SERIES 2100.

DETAIL - VFD STRUCTURE

NO SCALE

FRONT VIEW SIDE VIEW

145 KVA, 3Ø DRIVE ISOLATION

TRANSFORMER - 460 V. DELTA TO 460Y/266

VOLT - W/ NEMA 3R WEATHERSHIELD.

M

400 A., 3 P., NEMA 3R

DISCONNECT SWITCH.

NEW VARIABLE FREQUENCY DRIVE - FURNISHED BY MECHANICAL

CONTRACTOR & INSTALLED BY ELECTRICAL CONTRACTOR.

PROVIDE VFD W/ NEMA 4 OUTDOOR ENCLOSURE.

145 KVA, 3Ø DRIVE ISOLATION TRANSFORMER - 460 V.

DELTA TO 460Y/266 VOLT - W/ NEMA 3R WEATHERSHIELD.

3 # 4/0 & 1 # 4 GND. IN 2" LIQUID

TIGHT FLEXIBLE METAL CONDUIT.

4 # 4/0 & 1 # 4 GND. IN 2 1/2" LIQUID

TIGHT FLEXIBLE METAL CONDUIT.

3 # 4/0 & 1 # 4 GND. IN 2" RIGID

GALV. STEEL CONDUIT.

3 # 4/0 & 1 # 4 GND. IN 2" LIQUID

TIGHT FLEXIBLE METAL CONDUIT.

NEW PUMP P-503

125 HP, 480 V., 3Ø

2" WEATHERPROOF "TEE" FITTING

2" FLOOR FLANGE. ATTACH TO CONCRETE

SLAB W/ MASONRY EXPANSION ANCHORS.

WIRING DIAGRAM - PUMP P-503

N.T.S.

EXTEND 3/C # 4/0 TC POWER CABLE W/ # 4

GND. IN 3" RIGID GALV. STEEL CONDUIT FROM

MCC CIRCUIT BREAKER TO EXISTING CABLE

TRAY.

ROUTE TC CABLE THRU CABLE

TRAY FROM MCC TO PUMP ROOM.

EXTEND 3/C # 4/0 TC POWER CABLE W/ # 4

GND. IN 3" RIGID GALV. STEEL CONDUIT FROM

DISCONNECT SWITCH TO EXISTING CABLE

TRAY.

# 4 BARE COPPER GROUND CONDUCTOR TO 3/4" X 20'-0"

COPPERCLAD GROUND ROD. BOND GROUND CONDUCTOR TO

ROD W/ EXOTHERMIC WELD. CORE DRILL THRU CONC SLAB &

INSTALL ROD BELOW TRANSFORMER. DRILL 1" HOLE. LEAVE

2" OF ROD EXPOSED W/ GROUND CONNECTION ABOVE SLAB.

NEW TRANSFORMER SUPPORT

STRUCTURE - SEE DETAIL, THIS SHEET.

TRANSFORMER

DRIVE ISOLATION

12 GAUGE, 1 5/8" X 3 1/4"

HOT-DIPPED GALVANIZED

STEEL CHANNEL (TYP.)

1/4" THICK ANGLE (TYP.)

CONC. EXPANSION ANCHORS (TYP.)

1/4" THICK ANGLE (TYP.)

EXISTING CONCRETE BLOCK WALL

4'-0" A.F.F.

CONCRETE FLOOR

CONC. EXPANSION

ANCHORS (TYP.)

WIDTH AS REQUIRED

BY TRANSFORMER

BEING INSTALLED

CONC. EXPANSION

ANCHORS (TYP.)

DEPTH AS REQUIRED

BY TRANSFORMER

BEING INSTALLED

TRANSFORMER

DRIVE ISOLATION

NEW 225 A., 3 P., 65 KAIC

CIRCUIT BREAKER

12 GAUGE, 1 5/8" X 3 1/4"

HOT-DIPPED GALVANIZED

STEEL CHANNEL (TYP.)

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

FTFA15-1214_REPLACE HEAT EXCHANGER CLIMATIC LAB HANGAR 440_ T-001_SIGN-1
FTFA15-1214 Drawings Final
15185 M-001
15185 M-101
15185 M-102
15185 M-103
15185 M-301
15185 M-601
15185 M-701
15185 M-702
15185 E101-E101
15185 E102-E102
15185 E103-E103

File details come from the government source that posted it. Updated .