Final Dwgs 22JUL22.pdf
PDF 14 MB Posted
- Attached to
- Cold Room Expansion Federal contract opportunity
- Solicitation number
- 12305B22R0022
About this file
This document outlines a federal contract opportunity for a cold room expansion project. The United States Department of Agriculture Agricultural Research Service is seeking proposals for a cold room expansion at its facility in Geneva, New York, with a project magnitude between $250,000 and $500,000 and a performance period of 250 days from the receipt of notice to proceed. This is a total small business set-aside with a NAICS code of 236220 and small business size standard of $39.5 million. Proposals are due by email to Jason Robbins by the dates specified. An organized site visit will be held on August 23, 2022, with registration required by August 22. All questions must be submitted to the contracting officer in writing by August 26 and answers will be posted as an amendment. The successful contractor must comply with all terms, conditions, and specifications referenced in the solicitation documents.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Final Spec 22JUL22.pdf | ||
| Wage Decision NY20220032 5AUG22.pdf | ||
| 12305B22R0022 Cold Room Expansion PGRU Geneva NY.pdf | ||
| Self Performed Work worksheet.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PLANT GENETIC RESOURCES UNIT (PGRU)
21 Crabapple Drive, Geneva, New York 14456
USDA Contract No.: 12305B21D0015 TASK ORDER No.: 12305B21F0240 PAGE Project No.: 721040.01
ISSUED FOR CONSTRUCTION
COLD ROOM EXPANSION
JULY 22, 2022
RESEARCH, EDUCATION, AND ECONOMICS
AGRIGULTURAL RESEARCH SERVICE
Northeast Area Director's Office 10300 Baltimore Avenue Building 003, Room 223 Beltsville, Maryland 20705-2350 Phone No. (309) 681-6118 Fax No. (301) 504-5863
UNITED STATES DEPARTMENT OF AGRICULTURE
NORTHEAST AREA DIRECTOR'S OFFICE
10300 BALTIMORE AVENUE
BUILDING 003, ROOM 223
BELTSVILLE, MARYLAND 20705
PHONE NO. (309) 681-6118
FAX NO. (301) 504-5863
KEY PLAN
PROFESSIONAL CERTIFICATION. I HERE BY CERTIFY THAT
THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME,
AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER
UNDER THE LAWS OF THE STATE OF MARYLAND,
LICENSE No.
EXPIRATION DATE: .
REGISTRATION / STAMP
PROJECT TITLE:
SHEET NO.
DATE:
CAD FILE NO.:
A/E PROJECT NO.:
USDA CONTRACT NO.:
LRS Federal, LLC
Plumbing/FA/FP Engineers
565 Benfield Road, Suite 400
Severna Park, MD 21146
TEL: (410) 544-3570
www.lrsfederal.com
Page Southerland Page, Inc.
1615 M Street, NW, Suite 700
Washington, DC 20036
TEL: 202-909-4900
FAX: 202-785-7336
www.pagethink.com
SOUTHNORTH
12305B21D0015
721040.01
USDA ARS
Plant Genetic Resources Unit Cold Room Expansion
A/E DRAWN BY:
ISSUED FOR
CONSTRUCTION
USDA COR:
USDA EPM.:
T. VIGIL
USDA S&H.: B. DI SALVO
USDA REAL PROP.: P. BORDELON
A/E PROJ. MGR.:
A/E DESIGNER.: PAGE - WA
A/E CHECKED BY: PAGE - MA
PAGE - DR
SHEET TITLE:
21 Crabapple Drive, Geneva, New York 14456
A001
07/22/2022
TITLE SHEET
ARCHITECTURAL SHEET INDEX
Sheet Number Sheet Name
A001 TITLE SHEET
A002 ARCHITECTURAL & LABORATORY ABBREVIATIONS & SYMBOLS
A100 FIRST FLOOR PLAN
AD101 PARTIAL FIRST FLOOR DEMOLITION PLAN & CEILING PLAN
A101 FIRST FLOOR PARTIAL PLAN & REFLECTED CEILING PLAN
A201 FIRST FLOOR PARTIAL LAB PLAB
A301 ARCHITECTURAL DETAILS & SCHEDULES
A401 LAB CASEWORK DETAILS
ELECTRICAL SHEET INDEX
Sheet Number Sheet Name
E101 ELECTRICAL LIGHTING AND POWER FIRST FLOOR PLAN
E102 ELECTRICAL DETAILS
VICINITY MAP AERIAL VIEW
STREET VIEW
SHEET INDEX
MECHANICAL PLUMBING SHEET INDEX
Sheet Number Sheet Name
MP101 MECHANICAL FIRST FLOOR PLAN
MP102 PLUMBING FIRST FLOOR PLAN
MP103 MECHANICAL DETAILS & SCHEDULES
HAUL ROUTE
Revisions
No. Date Item
Digitally signed by Michael J. Mace
DN: C=US,
E=mmace@pagethink.com, O=Page, CN=Michael J. Mace Date: 2022.07.25 16:37:28-05'00'
DRAWING TITLEBAR:
DRAWING
IDENTIFICATION
DRAWING
TITLE
GRAPHIC SYMBOLS:
CALLED NORTH
TRUE NORTH
PROPERTY
LINE
DRAWING REFERENCE
SYMBOL:
REFER TO THIS
DRAWING
IDENTIFICATION
REFER TO THIS
SHEET NUMBER
CATEGORY
DISCIPLINE
REFER TO THIS
DRAWING
IDENTIFICATION
BUILDING / WALL SECTION
REFERENCE:
SCOPE OF
NEW WORK
EXISTING WORK
(CORE & SHELL)
COLUMN CENTER
LINE
COLUMN GRID
NUMBER
REFER TO THIS
DRAWING
IDENTIFICATION
EXTERIOR
ELEVATIONS
INTERIOR
ELEVATIONS
DETAIL REFERENCE:
REFER TO THIS
DRAWING IDENTIFICATION
MATCHLINE SEE:
A/A201
SPACE NAME / NUMBER SYMBOL:
ROOM
NAME
SPACE
IDENTIFICATION
SPACE NUMBER
DOOR, MISC. SYMBOLS:
SHEET KEYNOTE
REVISED AREA &
REVISION
NUMBER
NOTE: INDICATES
FINISHED SURFACES
SHALL ALIGN
NOTE: INDICATES
+/- FROM REF
ELEVATION
DIMENSION POINT
FL ELEVATION
GRAPHIC ARROWS:
ALIGN
TITLE
1/8" = 1'-0"
ORIGINAL SCALE
N
A201
A701
2A601
A301
A941
MATCHLINE SEE:
A/A202
+12"
DP
FF EL
0' - 0"
.0
0°
5'-0" DIM.
R
'-0
A
1 1.1
DIMENSION LINES:
101B
A701
DOOR TAG:
A501
X
PARTITION
TYPE TAG
PARTITION TYPE SYMBOL:
ADJ ADJACENT,
ADJUSTABLE
AFF ABOVE FINISHED
FLOOR
APPROX APPROXIMATE
AP ACCESS PANEL
ARCH ARCHITECT(URAL)
AS ADJUSTABLE SHELVING
BLDG BUILDING
BLKG BLOCKING
BH_ BASE CABINET
CFM CUBIC FEET
PER MINUTE
CK CAULK(ING)
C/L CENTERLINE
CLG CEILING
COL COLUMN
CONT CONTINUOUS
CONTR CONTRACTOR
DIM DIMENSION
DIV DIVISION
DTL, DET DETAIL
DWG DRAWING
E ELECTRIC OUTLET
EA EACH
ELEC
ELEV ELEVATION
EM EMERGENCY POWER
EP ELECTRICAL PANEL
EQ EQUAL
EQUIP EQUIPMENT
EXIST EXISTING
FBO FURNISHED BY OTHER
FIN FINISH
FIX FIXTURE
FPM FEET PER MINUTE
FT FOOT(FEET)
FURN FURNISH , FURNISHED
HW HOT WATER
ID INSIDE DIAMETER
IN INCHES
INT INTERIOR
JT JOINT
HT HEIGHT
INCL INCLUDE(D)
KS KNEE SPACE
L LENGTH
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MIN MINIMUM
MISC MISCELLANEOUS
MTD MOUNTED
NIC NOT IN CONTRACT
NTS NOT TO SCALE
MT MOVABLE TABLE
NO NUMBER
LC LOCKABLE
LT LIGHT
NOM NOMINAL
OFOI OWNER FURNISHED
OWNER INSTALLED
PLYWD PLYWOOD
PLBG PLUMBING
OFCI OWNER FURNISHED
CONTRACTOR INSTALLED
OC ON CENTER(S)
RE: REFERENCE
REV REVISION(S)
RM ROOM
SHT SHEET
SIM SIMILAR
SPECS SPECIFICATIONS
STD STANDARD
SNT SEALANT
ST.STL. STAINLESS STEEL
STL STEEL
REM REMOVE
SQ SQUARE
RECPT RECEPTACLE
REQ'D REQUIRED
STORAGE
STRUCT STRUCTURAL
SUSP SUSPENDED
TYP TYPICAL
UON UNLESS OTHERWISE
NOTED
SYM SYMMETRICAL
THK THICK
UNFIN UNFINISHED
W/ WITH
WD WOOD
W/O WITHOUT
ELECTRIC
STOR
CW COLD WATER
C+HW COLD AND HOT WATER
FD FLOOR DRAIN
ADA AMERICANS WITH DISABILITIES ACT
ABA ARCHITECTURAL BARRIERS ACT
VIF VERIFY IN FIELDOPP OPPOSITE
CFCI CONTRACTOR FURNISHED
CONTRACTOR INSTALLED
UC UNDERCOUNTER
EW EYEWASH
MINIMUM SPACING BETWEEN FITTINGS COORDINATE
EXACT SPACING REQUIRED WITH FIXTURE SUPPLIER.
0' - 4 1/2" 0' - 7" 0' - 9" 0' - 10 1/2" 1' - 0" 0' - 9"
NORTHEAST AREA DIRECTOR'S OFFICE
10300 BALTIMORE AVENUE
BUILDING 003, ROOM 223
BELTSVILLE, MARYLAND 20705
PHONE NO. (309) 681-6118
FAX NO. (301) 504-5863
KEY PLAN
PROFESSIONAL CERTIFICATION. I HERE BY CERTIFY THAT
THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME,
AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER
UNDER THE LAWS OF THE STATE OF MARYLAND,
LICENSE No.
EXPIRATION DATE: .
REGISTRATION / STAMP
PROJECT TITLE:
SHEET NO.
DATE:
CAD FILE NO.:
A/E PROJECT NO.:
USDA CONTRACT NO.:
LRS Federal, LLC
Plumbing/FA/FP Engineers
565 Benfield Road, Suite 400
Severna Park, MD 21146
TEL: (410) 544-3570
www.lrsfederal.com
Page Southerland Page, Inc.
1615 M Street, NW, Suite 700
Washington, DC 20036
TEL: 202-909-4900
FAX: 202-785-7336
www.pagethink.com
SOUTHNORTH
12305B21D0015
721040.01
USDA ARS
Plant Genetic Resources Unit Cold Room Expansion
A/E DRAWN BY:
ISSUED FOR
CONSTRUCTION
USDA COR:
USDA EPM.:
T. VIGIL
USDA S&H.: B. DI SALVO
USDA REAL PROP.: P. BORDELON
A/E PROJ. MGR.:
A/E DESIGNER.: PAGE - WA
A/E CHECKED BY: PAGE - MA
PAGE - DR
SHEET TITLE:
21 Crabapple Drive, Geneva, New York 14456
A002
07/22/2022
ARCHITECTURAL
& LABORATORY
ABBREVIATIONS
& SYMBOLS
DRAWING SYMBOLS
TYPE SIZE( L x W x D) MATERIAL MOUNT REMARKS
S01 18" L x 15" W x 5"/11" D EPOXY DROP-IN ADA TIERED SINK
E1 DUPLEX 110V ELECTRICAL OUTLETS
E2 CONTINUOUS WIRE MOLD W/ DUPLEX 110V OUTLETS @ 2'-0" O.C.
1. GENERAL NOTES ARE APPLICABLE TO ALL ARCHITECTURAL AND LABORATORY DRAWINGS.
2. LEGENDS OF SYMBOLS AND ABBREVATIONS ARE GENERIC AND SHALL BE USED AS REQUIRED TO DEFINE ITEMS INDICATED ON DRAWINGS. NOT ALL SYMBOLS OR ABBREVIATIONS DEFINED ARE NECESSARILY
USED ON THIS PROJECT.
3. ALL DIMENSIONS ARE NOMINAL. COORDINATE VARIATIONS BASED ON FIELD CONDITIONS.
4. DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO ESTABLISH BASIC DIMENSION OF UNITS, SIGHT LINES & UNITS PROFILES AND SHOW GENERAL SCOPE INTENT OF WORK, SEE DETAILS, SCHEDULES AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
5. FIELD VERIFY ALL DIMENSIONS PRIOR TO COMMENCING ANY WORK AND PRIOR TOFABRICATION OF
CASEWORK. NOTIFY ARCHITECT OF ANY DISCREPANCY.
6. ALL CASEWORK TO BE PAINTED METAL UNLESS NOTED OTHERWISE.
7. ALL COUNTERTOPS TO BE BLACK MODIFIED EPOXY RESIN, UNLESS NOTED OTHERWISE.
8. ALL REAGENT AND WALL MOUNTED SHELVES SHALL BE PAINTED METAL, UNLESS NOTED OTHERWISE.
9. ALL SINKS TO BE MODIFIED EPOXY RESIN, UNLESS NOTED OTHERWISE. COLOR TO MATCH ADJACENT
COUNTER TOP. SEE SINK SCHEDULE FOR SINK TYPES.
10. ALL SINKS SHALL BE CENTERED IN THEIR CABINETS, UNLESS OTHERWISE SHOWN ON DRAWINGS.
11. SERVICE SHOWN ON PLANS ARE FOR INFORMATION ONLY. REFER TO MECHANICAL, ELECTRICAL &
PLUMBING DRAWINGS FOR EXACT QUANTITY & LOCATION OF SERVICE FIXTURES.
12. ALL SERVICES REQUIRED BY EQUIPMENT ARE NOT NECESSARILY INDICATED ON LAB PLANS. REFER TO
MEP DRAWINGS & SPECIFICATIONS.
13. SERVICES SHOWN ON PLANS ARE NOT NECESSARILY INDICATED ON ELEVATIONS.
14. PROVIDE END PANELS AND FILLERS AS REQUIRED.
15. ALL WALL MOUNTED CABINETS AND SHELVES SHALL BE 12" DEEP , UNLESS NOTED OTHERWISE.
16. ALL BASE CABINETS SHALL BE NOMINAL 22" DEEP UNLESS NOTED OTHERWISE.
17. COORDINATE CASEWORK AND EQUIPMENT WITH WORK OF OTHER TRADES.
18. REFER TO SPEC SECTION 115300 FOR EQUIPMENT SCHEDULE, SCOPE OF WORK, AND N.I.C. AND
OWNER/CONTRACTOR FURNISHED/INSTALLED EQUIPMENT INFORMATION.
19. PROVIDE REMOVABLE BACK ACCESS PANELS AT ALL CABINETS AND KNEE SPACES TO PROVIDE ACCESS
TO UTILITY CHASES BEHIND CABINETS.
20. FINISHED FLOORING SHALL BE INSTALLED UNDER ALL CABINETS. FLOORING INSTALLATION SHALL BE
COMPLETED PRIOR TO CABINETS INSTALLATION. REFER TO ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS FOR BASE TO BE PROVIDED AT TOE SPACE OF ALL FIXED CASEWORK AND AT KNEE
SPACES.
21. PROVIDE FULL BACK AT BASE CABINETS WITH DRAWERS TO PREVENT OBJECTS FROM FALLING INTO PIPE
CHASE BEHIND CABINETS.
22. ALL BACKSPLASH TO BE 4" HIGH, EXCEPT ABOVE SINKS WHERE IT SHALL BE 8" HIGH MIN. UNLESS NOTED
OTHERWISE.
23. CONTINUOUS WIREMOLD ARE SHOWN ON ELEVATIONS FOR INFORMATION ONLY. SEE ELECTRICAL
DRAWINGS.
24. CONTRACTOR COORDINATE ELECTRICAL RACEWAY MOUNTING HEIGHT WITH TOP OF CASEWORK
BACKSPLASH, 40" A.F.F. TYPICAL. SEE ELECTRICAL.
25. ELECTRICAL RECEPTACLES AND COMMUNICATION OUTLETS ARE SHOWN ON LABORATORY CASEWORK / EQUIPMENT DRAWINGS FOR LOCATION AND COORDINATION WITH OTHERS. REFER TO DIVISION 26 & 27
DRAWINGS FOR ADDITIONAL INFORMATION.
26. FOR JUNCTION BOX, SEE QUANTITY FOR LOCATION REF. TO ELECTRICAL DRAWINGS.
GENERAL NOTES ABBREVIATIONS
SINK SCHEDULE
ELECTRICAL OUTLETS
FITTING REQUIREMENTS
Revisions
No. Date Item
Digitally signed by Michael J. Mace
DN: C=US,
E=mmace@pagethink.com, Date: 2022.07.25 16:38:00-05'00'
106B
FREEZER ROOM
106C
COLD ROOM
-20°C FREEZER
109B
PREP ROOM
109A
VESTIBULE
CORRIDOR
100CB
101A
100TA
100TBJANITOR
100J
MECHANICAL
100U
106A
MECHANICAL
ROOM
100U
100C
A101
CORRIDOR
100C
NORTHEAST AREA DIRECTOR'S OFFICE
10300 BALTIMORE AVENUE
BUILDING 003, ROOM 223
BELTSVILLE, MARYLAND 20705
PHONE NO. (309) 681-6118
FAX NO. (301) 504-5863
KEY PLAN
PROFESSIONAL CERTIFICATION. I HERE BY CERTIFY THAT
THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME,
AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER
UNDER THE LAWS OF THE STATE OF MARYLAND,
LICENSE No.
EXPIRATION DATE: .
REGISTRATION / STAMP
PROJECT TITLE:
SHEET NO.
DATE:
CAD FILE NO.:
A/E PROJECT NO.:
USDA CONTRACT NO.:
LRS Federal, LLC
Plumbing/FA/FP Engineers
565 Benfield Road, Suite 400
Severna Park, MD 21146
TEL: (410) 544-3570
www.lrsfederal.com
Page Southerland Page, Inc.
1615 M Street, NW, Suite 700
Washington, DC 20036
TEL: 202-909-4900
FAX: 202-785-7336
www.pagethink.com
SOUTHNORTH
12305B21D0015
721040.01
USDA ARS
Plant Genetic Resources Unit Cold Room Expansion
A/E DRAWN BY:
ISSUED FOR
CONSTRUCTION
USDA COR:
USDA EPM.:
T. VIGIL
USDA S&H.: B. DI SALVO
USDA REAL PROP.: P. BORDELON
A/E PROJ. MGR.:
A/E DESIGNER.: PAGE - WA
A/E CHECKED BY: PAGE - MA
PAGE - DR
SHEET TITLE:
21 Crabapple Drive, Geneva, New York 14456
A100
07/22/2022
FIRST FLOOR
PLAN
SCALE: 1/4" = 1'-0"
FIRST FLOOR PLAN
0 8'2' 4'-2'
TRUE
NORTH
Revisions
No. Date Item
Digitally signed by Michael J. Mace
DN: C=US,
E=mmace@pagethink.com, Date: 2022.07.25 16:38:22-05'00'
AD101
REMOVE EXISTING INSULATED PARTITION
AD101
EXISTING DOUBLE
WIDTH INSULATED
PARTITION TO REMAIN
EXISTING CMU
WALL TO REMAIN
EXISTING CMU
WALL TO REMAIN
COLD ROOM
CORRIDOR
100CB
100TB
JANITOR
100J
MECHANICAL
100U
100C
MECHANICAL
ROOM
100U
REMOVE EXISTING SHELVING
UNITS AND TURN THEM TO OWNER
REMOVE EXISTING SHELVING
UNITS AND TURN THEM TO OWNER
EXISTING FLOOR
DRAIN TO REMAIN
EXISTING DOOR
TO REMAIN
EXISTING WALL
TO REMAIN
EXISTING WALL
TO REMAIN
EXISTING DOOR
TO REMAIN
EXISTING
DRYWALL TO
REMAIN
AD101
1. REMOVE INSULATED PANEL CEILING.
2. REMOVE EXISTING FLUOSRESCENT LIGHTING & ALL
CEILING MOUNTED MEP COMPONENTS.
COORDINATE WITH MEP DRAWINGS & SPECS.
END OF CEILING
DEMOLITION
A101
AD101
COLD ROOM
MECHANICAL
100U
100TB
CORRIDOR
100CB
JANITOR
100J
MECHANICAL
ROOM
100U
100C
Level 1 0' - 0"
Roof 14' - 8"
10" CONC.
BLOCK
TO REMAIN
REMOVE EXISTING 4"
INSULATED PARTITION
& CEILING PANEL
4" RIGID
INSULATION
TO REMAIN
4" CON. SLAB
TO REMAIN
4" CON. TOPPING
TO REMAIN
REMOVE
EXISTING 4"
INSULATED
PARTITION
ROOM
(109)
ROOM
(109)
CORRIDOR
(100CB)
10" CONC. BLOCK
TO REMAIN
Level 1 0' - 0"
Roof 14' - 8"
AD101
ROOM
(109)
MECHANICAL
(100U)
COLD ROOM
(108)
EXISTING
DOUBLE WIDTH
INSULATED
PARTITION TO
REMAIN
EXISTING
INSULTED
CEILING PANEL
TO REMAIN
4" RIGID
INSULATION
TO REMAIN
4" CON. SLAB
TO REMAIN
4" CON. TOPPING
TO REMAIN
8" CONC.
BLOCK
TO REMAIN
NORTHEAST AREA DIRECTOR'S OFFICE
10300 BALTIMORE AVENUE
BUILDING 003, ROOM 223
BELTSVILLE, MARYLAND 20705
PHONE NO. (309) 681-6118
FAX NO. (301) 504-5863
KEY PLAN
PROFESSIONAL CERTIFICATION. I HERE BY CERTIFY THAT
THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME,
AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER
UNDER THE LAWS OF THE STATE OF MARYLAND,
LICENSE No.
EXPIRATION DATE: .
REGISTRATION / STAMP
PROJECT TITLE:
SHEET NO.
DATE:
CAD FILE NO.:
A/E PROJECT NO.:
USDA CONTRACT NO.:
LRS Federal, LLC
Plumbing/FA/FP Engineers
565 Benfield Road, Suite 400
Severna Park, MD 21146
TEL: (410) 544-3570
www.lrsfederal.com
Page Southerland Page, Inc.
1615 M Street, NW, Suite 700
Washington, DC 20036
TEL: 202-909-4900
FAX: 202-785-7336
www.pagethink.com
SOUTHNORTH
12305B21D0015
721040.01
USDA ARS
Plant Genetic Resources Unit Cold Room Expansion
A/E DRAWN BY:
ISSUED FOR
CONSTRUCTION
USDA COR:
USDA EPM.:
T. VIGIL
USDA S&H.: B. DI SALVO
USDA REAL PROP.: P. BORDELON
A/E PROJ. MGR.:
A/E DESIGNER.: PAGE - WA
A/E CHECKED BY: PAGE - MA
PAGE - DR
SHEET TITLE:
21 Crabapple Drive, Geneva, New York 14456
AD101
07/22/2022
PARTIAL FIRST
FLOOR
DEMOLITION
PLAN & CEILING
PLAN
SCALE: 1/4" = 1'-0"
PARTIAL FIRST FLOOR DEMOLITION PLAN
SCALE: 1/4" = 1'-0"
PARTIAL FIRST FLOOR CEILING DEMOLITION PLAN
SCALE: 1/4" = 1'-0"
SECTION THROUGH NORTH-SOUTH DIRECTION - DEMOLITION
SCALE: 1/4" = 1'-0"
SECTION THROUGH EAST-WEST DIRECTION - DEMOLITION
0 8'2' 4'-2'
TRUE
NORTH
Revisions
No. Date Item
Digitally signed by Michael J. Mace
DN: C=US,
E=mmace@pagethink.com, Date: 2022.07.25 16:38:44-05'00'
A101
A101
A101
COLD ROOM
VESTIBULE
PREP ROOM
109A
JANITOR
100J
100TB
CORRIDOR
100CB
MECHANICAL
100U
PROPOSED LOCATION FOR
REMOTELY LOCATED FREEZER
ROOM CONDENSER
(SEE MEP DRAWINGS FOR
ADDITIONAL INFORMATION)
FD
CONNECT CONDENSATE
DRAIN FROM FREEZER
ROOM TO EXISTING
FLOOR DRAIN
109A
1 5 1
9 9
8 8
2 2
-20°C FREEZER
109B
F
B
F
MECHANICAL
ROOM
100U
VFT 1
VFT 1
VFT 1
10' - 4"
M
IN
M
IN
2" MIN.
2" MIN.
12' - 5"
A101
A101
A101
CEILING MOUNTED
EVAPORATOR
-20°C FREEZER
109B
PREP ROOM
109A VESTIBULE
CORRIDOR
100CB
COLD ROOM
MECHANICAL
ROOM
100U
100C
JANITOR
100J
100TB
MECHANICAL
100U
VAPORPROOF LED
LIGHT FIXTURE
2x2 LIGHT FIXTURE
(SEE ELECT DWGS.)
2x2 LIGHT
FIXTURE
(SEE ELECT
DWGS.)
2x2 CEILING DIFFUSER
(SEE MEP DWGS.)
2x2 RETURN
REGISTER.
(SEE MEP
DWGS.)
A.F.F.9' - 0"
A.F.F.9' - 0"
ACT-1ACT-1
10' - 4"
M
IN
2" MIN.
M
IN
2" MIN.
Level 1 0' - 0"
Roof 14' - 8"
10" CONC.
BLOCK EXISTING
2x2 ACT
(-20º C)
FREEZER
ROOM
VESTIBULE
4" INSULATED
WALL & CEILING
PANLE
4" INSULATED
FLOOR
INSULATED FLOOR
WITH A REMOVABLE
GRAY POLYVINYL
CHLORIDE DIAMOND
TREAD MAT
FILL GAP LEFT BY
INSULATED PANEL
DEMOLITION
EXISTING 4"
CON. TOPPING
EXISTING 4"
RIGID
INSULATION
EXISTING 4"
CON. SLAB
CEILING MOUNTED
EVAPORATOR
A101
A101
2' - 0" 2' - 2"
AD101
CORRIDOR
(100CB)
EXISTING ROOFING
SYSTEM
EXISTING
FOOTING
10" CONC.
BLOCK EXISTING
A301
MECHANICAL
ROOM
A301
2" MIN.
SEE PLAN FOR ROOM DIMENSIONS
2" MIN.
PREP ROOM
EXISTING
FLOOR DRAIN
TO REMAIN
A301
Level 1 0' - 0"
Roof 14' - 8"
A101
PREP ROOM
(109A)
MECHANICAL
(100U)
COLD ROOM
(108)
EXISTING 4" RIGID
INSULATION
EXISTING 4" CON.
SLAB
EXISTING 4"
CON. TOPPING
EXISTING
8" CONC.
BLOCK
2x2 ACT
VINYL FLOOR TILE
(VFT)
EXISTING ROOFING
SYSTEM
EXISTING INSULATED
DOUBLE WIDTH
PARTITION
DRYWALL PARTITION.
3 5/8" STUD WITH 5/8"
DRYWALL ON ONE SIDE.
EXISTING 4"
CONC. SLAB
SEE PLAN FOR ROOM DIMENSIONS
Level 1 0' - 0"
Roof 14' - 8"
A101
(-20º C)
FREEZER ROOM
(109B)
MECHANICAL
(100U)
COLD ROOM
(108)
EXISTING 4" RIGID
INSULATION
EXISTING 4"
CON. SLAB
EXISTING 4"
CON. TOPPING
EXISTING 8"
CONC. BLOCK
INSULATED
CEILING
INSULATED FLOOR WITH
A REMOVABLE GRAY
POLYVINYL CHLORIDE
DIAMOND TREAD MAT
EXISTING ROOFING
SYSTEM
2" GAP MIN.
INSULATED
WALL PANEL
2" GAP MIN.
EXISTING INSULATED
DOUBLE WIDTH PARTITION
VAPORPROOF LED
LIGHT FIXTURE
EXISTING 4"
CONC. SLAB
A301
7 A301
TRIM
A301
SEE PLAN FOR ROOM DIMENSIONS
NEW WORK KEYNOTES
EXISTING INSULATED DOUBLE WIDTH PARTITION TO REMAIN.
EXISTING CMU WALL TO REMAIN.
EXISTING FLOOR DRAIN TO REMAIN.
EXISTING DRYWALL PARTITION TO REMAIN.
NEW DRYWALL PARTITION. 3 5/8" STUD WITH 5/8" DRYWALL ON ONE SIDE.
REFER TO DWG. A301 FOR WALL TYPES. (TYP).
NEW DRYWALL PARTITION. 3 5/8" STUD WITH 5/8" DRYWALL ON EACH SIDE.
REFER TO DWG. A301 FOR WALL TYPES. (TYP).
NEW DOOR AND FRAME. REFER TO DWG. A301 FOR DOOR TYPES. (TYP).
PATCH & PAINT ALL EXISTING CMU WALLS. COLOR TO BE SELECTED BY ARCHITECT AND
USDA REPRESENTATIVE.
PAINT ALL NEW GYPSUM BOARD WALLS & PARTITIONS. COLOR TO BE SELECTED BY
ARCHITECT AND USDA REPRESENTATIVE.
NEW THRESHOLD.
EXISTING DOOR & FRAME TO REMAIN.
VFT 1 - VINYL FLOOR TILE. STANDARD PLUS - 21003 497 LIGHT GRAY W, BY TARKETT OR APPROVED EQUAL.
VWB 1 - VINYL WALL BASE. COLOR TO BE SELECTED FROM MANUFACTURER’S STANDARD COLORS.
CRP 1 - COLD ROOM PANEL. 4” INSULATED COLD ROOM PANELS WITH BAKED WHITE POLYESTER SMOOTH FINISH ON GALVANIZED STEEL.
WALLS & CEILINGS. INSULATED FLOOR SHALL HAVE A REMOVABLE GRAY POLYVINYL CHLORIDE DIAMOND TREAD MAT.
PTD CMU 1 - EXISTING CMU TO REMAIN. PATCH & CLEAN AS REQUIRED. COLOR TO BE SELECTED FROM MANUFACTURER'S STANDARD COLORS.
PTD GYP 1 - COLOR TO BE SELECTED FROM MANUFACTURER'S STANDARD COLORS
ACT 1 - 2x2 ARMSTRONG - ULTIMA HIGH CEILING TILE OR APPROVED EQUAL.
ROOM FINISH SCHEDULE KEYNOTES
NORTHEAST AREA DIRECTOR'S OFFICE
10300 BALTIMORE AVENUE
BUILDING 003, ROOM 223
BELTSVILLE, MARYLAND 20705
PHONE NO. (309) 681-6118
FAX NO. (301) 504-5863
KEY PLAN
PROFESSIONAL CERTIFICATION. I HERE BY CERTIFY THAT
THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME,
AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER
UNDER THE LAWS OF THE STATE OF MARYLAND,
LICENSE No.
EXPIRATION DATE: .
REGISTRATION / STAMP
PROJECT TITLE:
SHEET NO.
DATE:
CAD FILE NO.:
A/E PROJECT NO.:
USDA CONTRACT NO.:
LRS Federal, LLC
Plumbing/FA/FP Engineers
565 Benfield Road, Suite 400
Severna Park, MD 21146
TEL: (410) 544-3570
www.lrsfederal.com
Page Southerland Page, Inc.
1615 M Street, NW, Suite 700
Washington, DC 20036
TEL: 202-909-4900
FAX: 202-785-7336
www.pagethink.com
SOUTHNORTH
12305B21D0015
721040.01
USDA ARS
Plant Genetic Resources Unit Cold Room Expansion
A/E DRAWN BY:
ISSUED FOR
CONSTRUCTION
USDA COR:
USDA EPM.:
T. VIGIL
USDA S&H.: B. DI SALVO
USDA REAL PROP.: P. BORDELON
A/E PROJ. MGR.:
A/E DESIGNER.: PAGE - WA
A/E CHECKED BY: PAGE - MA
PAGE - DR
SHEET TITLE:
21 Crabapple Drive, Geneva, New York 14456
A101
07/22/2022
FIRST FLOOR
PARTIAL PLAN &
REFLECTED
CEILING PLAN
SCALE: 1/4" = 1'-0"
FIRST FLOOR PARTIAL PLAN
SCALE: 1/4" = 1'-0"
FIRST FLOOR PARTIAL REFLECTED CEILING PLAN
SCALE: 1/4" = 1'-0"
SECTION THROUGH NORTH-SOUTH DIRECTION
SCALE: 1/4" = 1'-0"
SECTION THROUGH EAST-WEST DIRECTION - ROOM 109A
SCALE: 1/4" = 1'-0"
SECTION THROUGH EAST-WEST DIRECTION - ROOM 109B
0 8'2' 4'-2'
TRUE
NORTH
ROOM FINISH SCHEDULE
ROOM
NUMBER ROOM NAME FLOOR FINISH BASE FINISH
WALL FINISH -
NORTH
WALL FINISH -
EAST
WALL FINISH -
SOUTH
WALL FINISH -
WEST CEILING FINISH
100CB CORRIDOR VFT 1 VWB 1 PTD GYP 1 PTD GYP 1 PTD GYP 1 PTD GYP 1 OPEN TO STRUCTURE
109 VESTIBULE VFT 1 VWB 1 PTD GYP 1 PTD CMU 1 PTD CMU 1 PTD CMU 1 ACT 1
109A PREP ROOM VFT 1 VWB 1 CRP 1 PTD GYP 1 PTD GYP 1 PTD CMU 1 ACT 1
Revisions
No. Date Item
Digitally signed by Michael J. Mace
DN: C=US,
E=mmace@pagethink.com, Date: 2022.07.25 16:39:06-05'00'
A201
SHELVING
SHELVING REF.
(NIC)
REF.
(NIC)
STAINLESS
STEEL
SHELVING
2'x4' REMOVABLE
RAMP
CONTROL
PANEL
REMOTELY
LOCATED
FREEZER ROOM
CONDENSER
FD
FD
EXISTING LOCATION
OF CONDENSATE
FLOOR DRAIN
BENCH DUST
COLLECTOR SYSTEM
REMOTE SWITCH FOR
DUST COLLECTOR
(SEE ELECT DWGS.)
CORRIDOR
COLD ROOM
100TB
JANITOR
100JMECHANICAL
100U
-20°C FREEZER
109B
PREP ROOM
109A VESTIBULE
E
E
C
H W
E
E1
E
A2018
A201
E
W01 W01
K01A02 K01
W06
R06
S 1 E
E
E
E
E
E
E
E
"E1" BELOW KNEE SPACE
"E1" ABOVE WALL SHELVES
E
E
MECHANICAL
ROOM
100U
E
EW
STAINLESS
STEEL
SHELVING
EYEWASH (EW)
Level 1 0' - 0"
W01 W01 W06
A02 K01 R06 K01
E2E2
3' - 0" 3' - 0" 3' - 0" 3' - 0"
3' - 0" 3' - 0" 3' - 0"
E1
E1
E1
WALL MOUNTED
WATER HEATER.
SEE MEP
DRAWINGS.
E1
SHELVING
Level 1 0' - 0"
REF.
(N.I.C.)
REF.
(N.I.C.)
3' - 0"
STAINLESS
STEEL
SHELVING
REMOVABLE
RAMP
E1E1E1 E1 E1E1
2' - 0"
E1
SHELVING
Level 1 0' - 0"
2' - 6"
REMOVABLE
RAMP
COLD ROOM
CONTROL PANEL
TOP OF CONTROL
ROOM ROOF
E1
CEILING MOUNTED
EVAPORATOR
SHELVING SHELVING
E1
SHELVING
VAPORPROOF LED
LIGHT FIXTURE
CEILING MOUNTED
EVAPORATOR
E1
SHELVING
VAPORPROOF LED
LIGHT FIXTURE
CEILING MOUNTED
EVAPORATOR
Level 1 0' - 0"
2' - 6"
E1
BENCH DUST
COLLECTOR SYSTEM
STAINLESS
STEEL
SHELVING
E1
Level 1 0' - 0"
2' - 6"
DUST COLLECTOR
HOOD
REMOTE SWITCH FOR
DUST COLLECTOR
TRANSFER GRILL.
SEE MEP DRAWINGS
FOR EXACT LOCATION. 1
CASEWORK TYPES
TYPE:
W
WALL
MOUNTED
CABINETS/
SHELVING
W01
SWINGING GLASS DOORS
W06
METAL RAILS W/ ADJ.
METAL SHELVES
TYPE:
R
SPECIAL
PURPOSE
CASEWORK R06
ADA ACCESSIBLE SINK
LINE OF
ADJACENT
CABINET
OR WALL
TYPE:
K
APRONS
AT KNEE
SPACES
/2
K01
KNEE SPACE
TYPE:
A
ACCESSIBLE
HEIGHT BASE
CABINET - 36"
A.F.F.
A .F
.F
A02
NORTHEAST AREA DIRECTOR'S OFFICE
10300 BALTIMORE AVENUE
BUILDING 003, ROOM 223
BELTSVILLE, MARYLAND 20705
PHONE NO. (309) 681-6118
FAX NO. (301) 504-5863
KEY PLAN
PROFESSIONAL CERTIFICATION. I HERE BY CERTIFY THAT
THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME,
AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER
UNDER THE LAWS OF THE STATE OF MARYLAND,
LICENSE No.
EXPIRATION DATE: .
REGISTRATION / STAMP
PROJECT TITLE:
SHEET NO.
DATE:
CAD FILE NO.:
A/E PROJECT NO.:
USDA CONTRACT NO.:
LRS Federal, LLC
Plumbing/FA/FP Engineers
565 Benfield Road, Suite 400
Severna Park, MD 21146
TEL: (410) 544-3570
www.lrsfederal.com
Page Southerland Page, Inc.
1615 M Street, NW, Suite 700
Washington, DC 20036
TEL: 202-909-4900
FAX: 202-785-7336
www.pagethink.com
SOUTHNORTH
12305B21D0015
721040.01
USDA ARS
Plant Genetic Resources Unit Cold Room Expansion
A/E DRAWN BY:
ISSUED FOR
CONSTRUCTION
USDA COR:
USDA EPM.:
T. VIGIL
USDA S&H.: B. DI SALVO
USDA REAL PROP.: P. BORDELON
A/E PROJ. MGR.:
A/E DESIGNER.: PAGE - WA
A/E CHECKED BY: PAGE - MA
PAGE - DR
SHEET TITLE:
21 Crabapple Drive, Geneva, New York 14456
A201
07/22/2022
FIRST FLOOR
PARTIAL LAB
PLAB
SCALE: 1/4" = 1'-0"
FREEZER ROOM FLOOR PLAN
SCALE: 1/4" = 1'-0"
PREP ROOM - 109A
SCALE: 1/4" = 1'-0"
PREP ROOM - 109A
SCALE: 1/4" = 1'-0"
PREP ROOM - 109A
SCALE: 1/4" = 1'-0"
-20°C FREEZER - 109B
SCALE: 1/4" = 1'-0"
-20°C FREEZER - 109B
SCALE: 1/4" = 1'-0"
-20°C FREEZER - 109B
SCALE: 1/4" = 1'-0"
VESTIBULE - 109
SCALE: 1/4" = 1'-0"
PREP ROOM - 109A
Revisions
No. Date Item
Digitally signed by Michael J. Mace
DN: C=US,
E=mmace@pagethink.com, Date: 2022.07.25 16:39:30-05'00'
REFER TO
PLAN FOR
PARTITION
TYPE
SEALANT,
BOTH SIDES
'Z' CLIPS
FLOOR CLIPS
W/ 3/8"ø EXP.
BOLTS
ALT.
WALL
CONDITIO
N
DOOR
TYPE AS
SCHED
/8
0' - 0 1/2" 0' - 0 1/2"
REFER TO PLANS FOR
PARTITION TYPE
SEALANT, BOTH
SIDES
DOOR REFER TO
SCHEDULE
MTL. STUD BOX
HEADER
DOOR TYPE "G"
(SEE SCHEDULE)
A301
A301
FRAME TYPE
01HM
DOOR OPENING
GLASS
TYPE
GL-08
8" 8"
A301
DOOR TYPE G
B3
PART. WIDTH
SOUND ATTENUATION BLANKETS
5/8" GYP. BOARD BOTH SIDES
STEEL STUDS
STEEL RUNNERS
BASE AS SCHEDULED
CONTINUOUS SEALANT BOTH SIDES
FLOOR FINISH AS SCHEDULED
LINE OF DECK
DO NOT ATTACH GYP. TO TOP TRACK
CEILING AS SCHEDULED
STRUCT. FRAMING BEYOND
CONTINUOUS SEALANT
M
IN4"
METAL STUDS (HORIZ. BETWEEN
STUDS AT TOP OF GYP.)
3/ 8"
3/ 8"
VERTICAL BRACING / BRIDGING AT
48" O.C. MAX
3 5/8" -N / A12' - 4" 14' - 11" 3 1/2"4 7/8"
'B' SERIES
PLAN
TYPE STUD MIN STC25 GA. 20 GA. INSUL
EST STC
W/O INSUL
MAX. HEIGHT
DESIGN NO.
DESIGN STC
SECTION
PART.
WIDTH
LIMITING HEIGHTS BASED ON SSMA/SFIA; L/240; 5 PSF
*ADD WEB STIFFENERS
STEEL STUD
SOUND
ATTENUATION
BLANKETS
P A
R T
. W
ID
T H
5/8" GYP. BOARD
BOTH SIDES
A301
Sim
A301
Sim
LINE OF DECK
STRUCT. FRAMING
BEYOND
CEILING AS SCHEDULED
BASE AS SCHEDULED
CONTINUOUS SEALANT
BOTH SIDES
FLOOR FINISH
AS SCHEDULED
M
IN4"
STEEL STUD
5/8" GYP. BD -ONE LAYER
3/ 8"
PART. WIDTH
2'-0".
'F' SERIES
TYPE STUD MIN STC25 GA. 20 GA. INSUL
EST STC
W/O INSUL
MAX. HEIGHT
DESIGN NO.
DESIGN STC
SECTION
PART.
WIDTH
F3 3 5/8" -N/A12' - 4" 14' - 11" 3 1/2"
LIMITING HEIGHTS BASED ON SSMA / SFIA; L/240; 5 PSF
* ADD WEB STIFFENERS
4 1/4" -
SOUND ATTENUATION
BLANKETS
A301
Sim
A301
Sim
A301
Sim
3 5/8" METAL STUDS TO
UNDERSIDE OF DECK OR
STRUCTURE ABOVE
A S
S H
O W
N O
N P
LA
N
S
ACOUSTICAL LAY-IN
CEILING, REF FINISH
SCHED.
4"
5/8" GYP. BOARD -
ONE LAYER
EXISTING RIGID INSULATED
PANEL TO REMAIN
3 5/8" 5/8"
ACOUSTICAL SEALANT w/ SOUND
ATTENUATION BLANKET BACKING
GLUED TO STEEL DECK FOR
UNRATED PARTITIONS AND
FIRESTOPPING SEALANT w/
BACKING GLUED TO STEEL DECK
FOR RATED PARTITIONS
WHERE STEEL DECK FLUTES ARE
PERPENDICULAR TO PARTITION, FILL
VOIDS SOLID ABOVE RUNNERS WITH
ACOUSTICAL SEALANT w/ SOUND
ATTENUATION BLANKET BACKING
GLUED TO STEEL DECK FOR UNRATED
PARTITIONS. FILL VOIDS ABOVE
RUNNERS WITH FIRESTOPPING
SEALANT w/ BACKING GLUED TO STEEL
DECK FOR RATED PARTITIONS
MET. RUNNER TRACK w/
SELF-THREADING STEEL
SCREWS @ 12" O.C.
1/ 2"
ROOF
INSULATION
3 5/8"
1/4" BEAD ACOUSTICAL
SEALANT OR FIRESTOPPING
AS APPLICABLE @ BOTH
SIDES
BASE (VARIES)
STEEL 'J' RUNNER ANCHORED
w/ POWDER DRIVEN
FASTENERS AT 24" O.C.
NUMBER OF
LAYERS OF GYP. BD.
SOUND ATTENUATION
BLANKETS AS APPLICABLE
5/8" 3 5/8" 5/8"
Level 1 0' - 0"
4"2" MIN.
FILL GAP LEFT BY
INSULATED PANEL
DEMOLITION
10" CONC.
BLOCK EXISTING
4" INSULATED
WALL PANEL &
FLOOR
EXISTING 4" CON.
TOPPING
EXISTING 4" RIGID
INSULATION
EXISTING 4" CON.
SLAB
Level 1 0' - 0"
EXISTING 4"
CONC. SLAB
EXISTING 4" RIGID
INSULATION
EXISTING 4"
CON. SLAB
2" MIN. 4"
EXISTING
INSULATED
DOUBLE WIDTH
PARTITION
4" INSULATED
WALL PANEL & FLOOR
Level 1 0' - 0"
EXISTING 4"
CONC. SLAB
4" INSULATED
WALL PANEL &
FLOOR
4" 2" MIN.
EXISTING 8"
CONC. BLOCK
EXISTING 4"
CONC. TOPPING
EXISTING 4" RIGID
INSULATION
EXISTING 4"
CON. SLAB
A S
S H
O W
N O
N P
LA
N
S
ACOUSTICAL LAY-IN
CEILING, REF FINISH
SCHED.
4" 2" MIN.
TRIM
4" INSULATED
WALL PANEL & CEILING
DRYWALL PARTITION.
3 5/8" STUD WITH 5/8"
DRYWALL ON ONE SIDE.
9' - 0"
2" MIN. 4"
EXISTING INSULATED
DOUBLE WIDTH PARTITION
TRIM
4" INSULATED
WALL PANEL & CEILING
9' - 0" Level 1
0' - 0"
EXISTING 4" CONC.
SLAB ON GRADE.
EXISTING 4" RIGID
INSULATION.
EXISTING 4" CONC.
TOPPING TO
REMAIN.
EXISTING FLOOR
DRAIN TO REMAIN.
NEW 2MM VINYL
FLOOR AND
ADHESIVE
NORTHEAST AREA DIRECTOR'S OFFICE
10300 BALTIMORE AVENUE
BUILDING 003, ROOM 223
BELTSVILLE, MARYLAND 20705
PHONE NO. (309) 681-6118
FAX NO. (301) 504-5863
KEY PLAN
PROFESSIONAL CERTIFICATION. I HERE BY CERTIFY THAT
THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME,
AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER
UNDER THE LAWS OF THE STATE OF MARYLAND,
LICENSE No.
EXPIRATION DATE: .
REGISTRATION / STAMP
PROJECT TITLE:
SHEET NO.
DATE:
CAD FILE NO.:
A/E PROJECT NO.:
USDA CONTRACT NO.:
LRS Federal, LLC
Plumbing/FA/FP Engineers
565 Benfield Road, Suite 400
Severna Park, MD 21146
TEL: (410) 544-3570
www.lrsfederal.com
Page Southerland Page, Inc.
1615 M Street, NW, Suite 700
Washington, DC 20036
TEL: 202-909-4900
FAX: 202-785-7336
www.pagethink.com
SOUTHNORTH
12305B21D0015
721040.01
USDA ARS
Plant Genetic Resources Unit Cold Room Expansion
A/E DRAWN BY:
ISSUED FOR
CONSTRUCTION
USDA COR:
USDA EPM.:
T. VIGIL
USDA S&H.: B. DI SALVO
USDA REAL PROP.: P. BORDELON
A/E PROJ. MGR.:
A/E DESIGNER.: PAGE - WA
A/E CHECKED BY: PAGE - MA
PAGE - DR
SHEET TITLE:
21 Crabapple Drive, Geneva, New York 14456
A301
07/22/2022
ARCHITECTURAL
DETAILS &
SCHEDULES
SCALE: 1 1/2" = 1'-0"
HM FRAME DOOR @ JAMB
SCALE: 1 1/2" = 1'-0"
HM FRAME DOOR HEAD
SCALE: 3/8" = 1'-0"
DOOR FRAME DIAGRAMS
SCALE: 3/8" = 1'-0"
DOOR TYPE DIAGRAMS
SCALE: 1 1/2" = 1'-0"
TYPE B: PARTITION HEAD, NON RATED
DOOR SCHEDULE
DOOR
NUMBER
ROOM
NAME
DOOR
TYPE
DOOR CONST.
TYPE
DOOR GLASS
TYPE
DOOR PANEL
FINISH
DOOR FRAME
FIRE
RATING HARDWARE TYPE CommentsWIDTH HEIGHT TYPE
CONST.T
YPE Jamb Head
109A PREP
ROOM
G HM GL-08 VE 3' - 0" 7' - 0" 01HM HM/PTD 3/A301 1/A301 - SEE SPEC.
SECTION 08 71 00
SCALE: 1 1/2" = 1'-0"
TYPE F: PARTITION HEAD, NON RATED
SCALE: 3" = 1'-0"
CEILING DETAIL
SCALE: 3" = 1'-0"
TOP ANCHORAGE OF PARTITION TO METAL DECK
SCALE: 3" = 1'-0"
FLOOR ANCHORAGE OF PARTITION
SCALE: 1" = 1'-0"
COLD ROOM DETAIL
THROUGH
NORTH-SOUTH
SCALE: 1" = 1'-0"
COLD ROOM DETAIL
THROUGH BOTTOM
CORNER EAST-WEST
SCALE: 1" = 1'-0"
COLD ROOM DETAIL
THROUGH EAST-WEST
SCALE: 1" = 1'-0"
COLD ROOM DETAIL
THROUGH TOP
CORNER NORTH-SOUTH
SCALE: 1" = 1'-0"
COLD ROOM DETAIL
THROUGH TOP
CORNER EAST-WEST
SCALE: 1" = 1'-0"
SECTION THROUGH
EXISTING FLOOR DRAIN
Revisions
No. Date Item
Digitally signed by Michael J. Mace
DN: C=US,
E=mmace@pagethink.com, Date: 2022.07.25 16:39:55-05'00'
25" MAX.
2' - 6"
4"
1" 8"
M A
X
/2
11" MIN.
M
IN
8" HIGH
BACKSPLASH
FOR SINK SIZE,
REFER TO SINK
SCHEDULE ON
SHEET A001
REMOVABLE
METAL PANEL
LINE OF
ADJACENT
UNIT
BEYOND
REMOVABLE
PROTECTIVE
METAL PANEL
6" MAX.
WALL MOUNTED
WATER HEATER.
SEE MEP
DRAWINGS.
SEE DETAIL
9/A401
4" HIGH
BACKSPLASH
TYP. U.N.O.
FULL DEPTH
ADJUSTABLE SHELF
REMOVABLE BACK
SEE DETAIL 4/A401FULLY ENCLOSED
TOE SPACE
ONE PIECE DRAWER
BODY RADIUSED
ALL FOUR SIDES
2' - 6"
1' - 10"
PAN FORMED
DRAWER HEAD
FILLED FOR SOUND
DEADENING
TWO-PIECE PAN
FORMED DOOR
FILLED FOR SOUND
DEADENING
ONE-PIECE BOTTOM
AND FRONT RAIL
TURNED UP AT
BACK AND SIDES
4" HIGH
BACKSPLASH
TYP. U.N.O.
WALL MOUNTED
ELECTRICAL
OUTLET. SEE ELEC
DWGS.
2' - 6"
LINE OF
ADJACENT UNIT
BEYOND
APRON
PROVIDE ELEC. &
DATA OUTLETS
PRE-WIRED UP
TO SERVICE
CHASE. SEE
ELEC. DWGS.
DRAWER SLIDES
FULL DEPTH
ADJUST. SHELF
REINFORCING
GUSSETS WITH
LEVELING BOLTS
( ALL FOUR
CORNERS)
REMOVABLE
BACK
BEYOND
METAL FINISH TO
MATCH ADJACENT
CABINETS
END PANELS
FINISH FLOOR
FIXED TOP
PANELS
CUT-OUT FOR
ELECTRICAL OUTLET
BASE (SEE ARCH DWGS)A
D
A H
G T
SECURE ALL SIDES
WALL BEYOND
TOP SHELF
ADJUSTABLE TO
6'-0" A.F.F.
UNLESS NOTED
OTHERWISE
METAL WALL RAIL
1 ADJUSTABLE
SHELVES ON METAL
BRACKETS
END CAP ON TOP
AND BOTTOM
U.N.O.
1' - 4"
BLOCKING
ONE PIECE BOTTOM &
FRONT RAIL TURNED
UP AT BACK & SIDES
TWO-PIECE SOLID
PAN FORMED
DOOR FILLED FOR
SOUND
DEADENING OR
GLASS SWINGING
DOOR
2 ADJUST. METAL
SHELVES
RECESSED BACK FOR
EASE OF SECURING
TO WALL
ONE PIECE 18 GAUGE
BOTTOM SOFFIT
1' - 1"
BLOCKING
EQ EQ
1" EPOXY RESIN TOP
EASED EDGE
1/4" DRIP
CONTINUOUS . TYP.
FACE OF CABINET
BELOW
TYPICAL COUNTER EDGE DRIP DETAIL
1" EPOXY RESIN TOP
EASED EDGE
1/4" DRIP
CONTINUOUS . TYP.
FACE OF
CABINET BELOW
U.N.O.
0' - 1"
EPOXY CEMENT.
PROVIDE SMOOTH
TRANSITION BETWEEN
SINK RIM AND
COUNTERTOP.
LIPPED (DROP-IN) SINK EDGE DETAIL
0' - 0 1/2"
0' - 0 1/4"
0' - 0 1/4"
END PANELS
FINISH FLOOR
FIXED TOP
PANEL
WALL
MOUNTED
ELECTRICAL
OUTLET. SEE
ELEC DWGS.
A D
A H
G T
SECURE ALL SIDES
WALL BEYOND
U.N.O.
1' - 4"
2' - 6"
1' - 10" 0' - 1"
1' - 0"
NORTHEAST AREA DIRECTOR'S OFFICE
10300 BALTIMORE AVENUE
BUILDING 003, ROOM 223
BELTSVILLE, MARYLAND 20705
PHONE NO. (309) 681-6118
FAX NO. (301) 504-5863
KEY PLAN
PROFESSIONAL CERTIFICATION. I HERE BY CERTIFY THAT
THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME,
AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER
UNDER THE LAWS OF THE STATE OF MARYLAND,
LICENSE No.
EXPIRATION DATE: .
REGISTRATION / STAMP
PROJECT TITLE:
SHEET NO.
DATE:
CAD FILE NO.:
A/E PROJECT NO.:
USDA CONTRACT NO.:
LRS Federal, LLC
Plumbing/FA/FP Engineers
565 Benfield Road, Suite 400
Severna Park, MD 21146
TEL: (410) 544-3570
www.lrsfederal.com
Page Southerland Page, Inc.
1615 M Street, NW, Suite 700
Washington, DC 20036
TEL: 202-909-4900
FAX: 202-785-7336
www.pagethink.com
SOUTHNORTH
12305B21D0015
721040.01
USDA ARS
Plant Genetic Resources Unit Cold Room Expansion
A/E DRAWN BY:
ISSUED FOR
CONSTRUCTION
USDA COR:
USDA EPM.:
T. VIGIL
USDA S&H.: B. DI SALVO
USDA REAL PROP.: P. BORDELON
A/E PROJ. MGR.:
A/E DESIGNER.: PAGE - WA
A/E CHECKED BY: PAGE - MA
PAGE - DR
SHEET TITLE:
21 Crabapple Drive, Geneva, New York 14456
A401
07/22/2022
LAB CASEWORK
DETAILS
SCALE: 1" = 1'-0"
SECTION THROUGH ADA TIERED SINK CABINET TYPE R06
SCALE: 1" = 1'-0"
SECTION THROUGH ADA BASE CABINET TYPE A02
SCALE: 1" = 1'-0"
SECTION THROUGH ADA METAL
KNEE SPACE WITH APRON TYPE K01
SCALE: 1" = 1'-0"
TRANSVERSE SECTION THROUGH
BASE CABINET (TYPICAL)
SCALE: 1" = 1'-0"
TRANSVERSE SECTION THROUGH
KNEE SPACE WITH OUTLET AT APRON
SCALE: 1" = 1'-0"
SECTION THROUGH METAL ADJUSTABLE
SHELF ON WALL RAILS TYPE W06
SCALE: 1" = 1'-0"
SECTION THROUGH WALL CABINET
WITH SWINGING DOORS TYPE W01
SCALE: 3" = 1'-0"
COUNTER TOP EDGE DETAIL
SCALE: 1" = 1'-0"
TRANSVERSE SECTION THROUGH
KNEE SPACE WITH OUTLET AT BACK PANEL
SCALE: 1" = 1'-0"
TYPIAL MOUNTING
HEIGHTS FOR
ACCESSIBLE HEIGHT
BASE CABINETS
SCALE: 1" = 1'-0"
TYPICAL MOUNTING
HEIGHTS FOR 30" HIGH
WALL CABINETS
NOTES:
1. CONTRACTOR COORDINATE
WALL BLOCKING
REQUIREMENTS FOR
ANCHORING CASEWORK WITH
CASEWORK SHOPDRAWINGS.
2. REFER TO DRAWING #A301
FOR WALL TYPES.
Revisions
No. Date Item
Digitally signed by Michael J. Mace DN: C=US, E=mmace@pagethink.com, Date: 2022.07.25 16:40:18-05'00' whorton Stamp whorton mspasyk
| MEP COMBINED.pdf |
| USDA.E101.20220728 |
| USDA.E102.20220728 |
| USDA.MP101 thru MP103.20220729 |
File details come from the government source that posted it. Updated .