Final Dwgs 22JUL22.pdf

PDF 14 MB Posted

Attached to
Cold Room Expansion Federal contract opportunity
Solicitation number
12305B22R0022
Issued by
Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Northeast Area

About this file

This document outlines a federal contract opportunity for a cold room expansion project. The United States Department of Agriculture Agricultural Research Service is seeking proposals for a cold room expansion at its facility in Geneva, New York, with a project magnitude between $250,000 and $500,000 and a performance period of 250 days from the receipt of notice to proceed. This is a total small business set-aside with a NAICS code of 236220 and small business size standard of $39.5 million. Proposals are due by email to Jason Robbins by the dates specified. An organized site visit will be held on August 23, 2022, with registration required by August 22. All questions must be submitted to the contracting officer in writing by August 26 and answers will be posted as an amendment. The successful contractor must comply with all terms, conditions, and specifications referenced in the solicitation documents.

View the file

Other files for this federal contract opportunity

Other files attached to Cold Room Expansion, newest first.
File Type Posted
Final Spec 22JUL22.pdf PDF
Wage Decision NY20220032 5AUG22.pdf PDF
12305B22R0022 Cold Room Expansion PGRU Geneva NY.pdf PDF
Self Performed Work worksheet.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PLANT GENETIC RESOURCES UNIT (PGRU)

21 Crabapple Drive, Geneva, New York 14456

USDA Contract No.: 12305B21D0015 TASK ORDER No.: 12305B21F0240 PAGE Project No.: 721040.01

ISSUED FOR CONSTRUCTION

COLD ROOM EXPANSION

JULY 22, 2022

RESEARCH, EDUCATION, AND ECONOMICS

AGRIGULTURAL RESEARCH SERVICE

Northeast Area Director's Office 10300 Baltimore Avenue Building 003, Room 223 Beltsville, Maryland 20705-2350 Phone No. (309) 681-6118 Fax No. (301) 504-5863

UNITED STATES DEPARTMENT OF AGRICULTURE

NORTHEAST AREA DIRECTOR'S OFFICE

10300 BALTIMORE AVENUE

BUILDING 003, ROOM 223

BELTSVILLE, MARYLAND 20705

PHONE NO. (309) 681-6118

FAX NO. (301) 504-5863

KEY PLAN

PROFESSIONAL CERTIFICATION. I HERE BY CERTIFY THAT

THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME,

AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER

UNDER THE LAWS OF THE STATE OF MARYLAND,

LICENSE No.

EXPIRATION DATE: .

REGISTRATION / STAMP

PROJECT TITLE:

SHEET NO.

DATE:

CAD FILE NO.:

A/E PROJECT NO.:

USDA CONTRACT NO.:

LRS Federal, LLC

Plumbing/FA/FP Engineers

565 Benfield Road, Suite 400

Severna Park, MD 21146

TEL: (410) 544-3570

www.lrsfederal.com

Page Southerland Page, Inc.

1615 M Street, NW, Suite 700

Washington, DC 20036

TEL: 202-909-4900

FAX: 202-785-7336

www.pagethink.com

SOUTHNORTH

12305B21D0015

721040.01

USDA ARS

Plant Genetic Resources Unit Cold Room Expansion

A/E DRAWN BY:

ISSUED FOR

CONSTRUCTION

USDA COR:

USDA EPM.:

T. VIGIL

USDA S&H.: B. DI SALVO

USDA REAL PROP.: P. BORDELON

A/E PROJ. MGR.:

A/E DESIGNER.: PAGE - WA

A/E CHECKED BY: PAGE - MA

PAGE - DR

SHEET TITLE:

21 Crabapple Drive, Geneva, New York 14456

A001

07/22/2022

TITLE SHEET

ARCHITECTURAL SHEET INDEX

Sheet Number Sheet Name

A001 TITLE SHEET

A002 ARCHITECTURAL & LABORATORY ABBREVIATIONS & SYMBOLS

A100 FIRST FLOOR PLAN

AD101 PARTIAL FIRST FLOOR DEMOLITION PLAN & CEILING PLAN

A101 FIRST FLOOR PARTIAL PLAN & REFLECTED CEILING PLAN

A201 FIRST FLOOR PARTIAL LAB PLAB

A301 ARCHITECTURAL DETAILS & SCHEDULES

A401 LAB CASEWORK DETAILS

ELECTRICAL SHEET INDEX

Sheet Number Sheet Name

E101 ELECTRICAL LIGHTING AND POWER FIRST FLOOR PLAN

E102 ELECTRICAL DETAILS

VICINITY MAP AERIAL VIEW

STREET VIEW

SHEET INDEX

MECHANICAL PLUMBING SHEET INDEX

Sheet Number Sheet Name

MP101 MECHANICAL FIRST FLOOR PLAN

MP102 PLUMBING FIRST FLOOR PLAN

MP103 MECHANICAL DETAILS & SCHEDULES

HAUL ROUTE

Revisions

No. Date Item

Digitally signed by Michael J. Mace

DN: C=US,

E=mmace@pagethink.com, O=Page, CN=Michael J. Mace Date: 2022.07.25 16:37:28-05'00'

DRAWING TITLEBAR:

DRAWING

IDENTIFICATION

DRAWING

TITLE

GRAPHIC SYMBOLS:

CALLED NORTH

TRUE NORTH

PROPERTY

LINE

DRAWING REFERENCE

SYMBOL:

REFER TO THIS

DRAWING

IDENTIFICATION

REFER TO THIS

SHEET NUMBER

CATEGORY

DISCIPLINE

REFER TO THIS

DRAWING

IDENTIFICATION

BUILDING / WALL SECTION

REFERENCE:

SCOPE OF

NEW WORK

EXISTING WORK

(CORE & SHELL)

COLUMN CENTER

LINE

COLUMN GRID

NUMBER

REFER TO THIS

DRAWING

IDENTIFICATION

EXTERIOR

ELEVATIONS

INTERIOR

ELEVATIONS

DETAIL REFERENCE:

REFER TO THIS

DRAWING IDENTIFICATION

MATCHLINE SEE:

A/A201

SPACE NAME / NUMBER SYMBOL:

ROOM

NAME

SPACE

IDENTIFICATION

SPACE NUMBER

DOOR, MISC. SYMBOLS:

SHEET KEYNOTE

REVISED AREA &

REVISION

NUMBER

NOTE: INDICATES

FINISHED SURFACES

SHALL ALIGN

NOTE: INDICATES

+/- FROM REF

ELEVATION

DIMENSION POINT

FL ELEVATION

GRAPHIC ARROWS:

ALIGN

TITLE

1/8" = 1'-0"

ORIGINAL SCALE

N

A201

A701

2A601

A301

A941

MATCHLINE SEE:

A/A202

+12"

DP

FF EL

0' - 0"

.0

0°

5'-0" DIM.

R

'-0

A

1 1.1

DIMENSION LINES:

101B

A701

DOOR TAG:

A501

X

PARTITION

TYPE TAG

PARTITION TYPE SYMBOL:

ADJ ADJACENT,

ADJUSTABLE

AFF ABOVE FINISHED

FLOOR

APPROX APPROXIMATE

AP ACCESS PANEL

ARCH ARCHITECT(URAL)

AS ADJUSTABLE SHELVING

BLDG BUILDING

BLKG BLOCKING

BH_ BASE CABINET

CFM CUBIC FEET

PER MINUTE

CK CAULK(ING)

C/L CENTERLINE

CLG CEILING

COL COLUMN

CONT CONTINUOUS

CONTR CONTRACTOR

DIM DIMENSION

DIV DIVISION

DTL, DET DETAIL

DWG DRAWING

E ELECTRIC OUTLET

EA EACH

ELEC

ELEV ELEVATION

EM EMERGENCY POWER

EP ELECTRICAL PANEL

EQ EQUAL

EQUIP EQUIPMENT

EXIST EXISTING

FBO FURNISHED BY OTHER

FIN FINISH

FIX FIXTURE

FPM FEET PER MINUTE

FT FOOT(FEET)

FURN FURNISH , FURNISHED

HW HOT WATER

ID INSIDE DIAMETER

IN INCHES

INT INTERIOR

JT JOINT

HT HEIGHT

INCL INCLUDE(D)

KS KNEE SPACE

L LENGTH

MATL MATERIAL

MAX MAXIMUM

MECH MECHANICAL

MIN MINIMUM

MISC MISCELLANEOUS

MTD MOUNTED

NIC NOT IN CONTRACT

NTS NOT TO SCALE

MT MOVABLE TABLE

NO NUMBER

LC LOCKABLE

LT LIGHT

NOM NOMINAL

OFOI OWNER FURNISHED

OWNER INSTALLED

PLYWD PLYWOOD

PLBG PLUMBING

OFCI OWNER FURNISHED

CONTRACTOR INSTALLED

OC ON CENTER(S)

RE: REFERENCE

REV REVISION(S)

RM ROOM

SHT SHEET

SIM SIMILAR

SPECS SPECIFICATIONS

STD STANDARD

SNT SEALANT

ST.STL. STAINLESS STEEL

STL STEEL

REM REMOVE

SQ SQUARE

RECPT RECEPTACLE

REQ'D REQUIRED

STORAGE

STRUCT STRUCTURAL

SUSP SUSPENDED

TYP TYPICAL

UON UNLESS OTHERWISE

NOTED

SYM SYMMETRICAL

THK THICK

UNFIN UNFINISHED

W/ WITH

WD WOOD

W/O WITHOUT

ELECTRIC

STOR

CW COLD WATER

C+HW COLD AND HOT WATER

FD FLOOR DRAIN

ADA AMERICANS WITH DISABILITIES ACT

ABA ARCHITECTURAL BARRIERS ACT

VIF VERIFY IN FIELDOPP OPPOSITE

CFCI CONTRACTOR FURNISHED

CONTRACTOR INSTALLED

UC UNDERCOUNTER

EW EYEWASH

MINIMUM SPACING BETWEEN FITTINGS COORDINATE

EXACT SPACING REQUIRED WITH FIXTURE SUPPLIER.

0' - 4 1/2" 0' - 7" 0' - 9" 0' - 10 1/2" 1' - 0" 0' - 9"

NORTHEAST AREA DIRECTOR'S OFFICE

10300 BALTIMORE AVENUE

BUILDING 003, ROOM 223

BELTSVILLE, MARYLAND 20705

PHONE NO. (309) 681-6118

FAX NO. (301) 504-5863

KEY PLAN

PROFESSIONAL CERTIFICATION. I HERE BY CERTIFY THAT

THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME,

AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER

UNDER THE LAWS OF THE STATE OF MARYLAND,

LICENSE No.

EXPIRATION DATE: .

REGISTRATION / STAMP

PROJECT TITLE:

SHEET NO.

DATE:

CAD FILE NO.:

A/E PROJECT NO.:

USDA CONTRACT NO.:

LRS Federal, LLC

Plumbing/FA/FP Engineers

565 Benfield Road, Suite 400

Severna Park, MD 21146

TEL: (410) 544-3570

www.lrsfederal.com

Page Southerland Page, Inc.

1615 M Street, NW, Suite 700

Washington, DC 20036

TEL: 202-909-4900

FAX: 202-785-7336

www.pagethink.com

SOUTHNORTH

12305B21D0015

721040.01

USDA ARS

Plant Genetic Resources Unit Cold Room Expansion

A/E DRAWN BY:

ISSUED FOR

CONSTRUCTION

USDA COR:

USDA EPM.:

T. VIGIL

USDA S&H.: B. DI SALVO

USDA REAL PROP.: P. BORDELON

A/E PROJ. MGR.:

A/E DESIGNER.: PAGE - WA

A/E CHECKED BY: PAGE - MA

PAGE - DR

SHEET TITLE:

21 Crabapple Drive, Geneva, New York 14456

A002

07/22/2022

ARCHITECTURAL

& LABORATORY

ABBREVIATIONS

& SYMBOLS

DRAWING SYMBOLS

TYPE SIZE( L x W x D) MATERIAL MOUNT REMARKS

S01 18" L x 15" W x 5"/11" D EPOXY DROP-IN ADA TIERED SINK

E1 DUPLEX 110V ELECTRICAL OUTLETS

E2 CONTINUOUS WIRE MOLD W/ DUPLEX 110V OUTLETS @ 2'-0" O.C.

1. GENERAL NOTES ARE APPLICABLE TO ALL ARCHITECTURAL AND LABORATORY DRAWINGS.

2. LEGENDS OF SYMBOLS AND ABBREVATIONS ARE GENERIC AND SHALL BE USED AS REQUIRED TO DEFINE ITEMS INDICATED ON DRAWINGS. NOT ALL SYMBOLS OR ABBREVIATIONS DEFINED ARE NECESSARILY

USED ON THIS PROJECT.

3. ALL DIMENSIONS ARE NOMINAL. COORDINATE VARIATIONS BASED ON FIELD CONDITIONS.

4. DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO ESTABLISH BASIC DIMENSION OF UNITS, SIGHT LINES & UNITS PROFILES AND SHOW GENERAL SCOPE INTENT OF WORK, SEE DETAILS, SCHEDULES AND

SPECIFICATIONS FOR ADDITIONAL INFORMATION.

5. FIELD VERIFY ALL DIMENSIONS PRIOR TO COMMENCING ANY WORK AND PRIOR TOFABRICATION OF

CASEWORK. NOTIFY ARCHITECT OF ANY DISCREPANCY.

6. ALL CASEWORK TO BE PAINTED METAL UNLESS NOTED OTHERWISE.

7. ALL COUNTERTOPS TO BE BLACK MODIFIED EPOXY RESIN, UNLESS NOTED OTHERWISE.

8. ALL REAGENT AND WALL MOUNTED SHELVES SHALL BE PAINTED METAL, UNLESS NOTED OTHERWISE.

9. ALL SINKS TO BE MODIFIED EPOXY RESIN, UNLESS NOTED OTHERWISE. COLOR TO MATCH ADJACENT

COUNTER TOP. SEE SINK SCHEDULE FOR SINK TYPES.

10. ALL SINKS SHALL BE CENTERED IN THEIR CABINETS, UNLESS OTHERWISE SHOWN ON DRAWINGS.

11. SERVICE SHOWN ON PLANS ARE FOR INFORMATION ONLY. REFER TO MECHANICAL, ELECTRICAL &

PLUMBING DRAWINGS FOR EXACT QUANTITY & LOCATION OF SERVICE FIXTURES.

12. ALL SERVICES REQUIRED BY EQUIPMENT ARE NOT NECESSARILY INDICATED ON LAB PLANS. REFER TO

MEP DRAWINGS & SPECIFICATIONS.

13. SERVICES SHOWN ON PLANS ARE NOT NECESSARILY INDICATED ON ELEVATIONS.

14. PROVIDE END PANELS AND FILLERS AS REQUIRED.

15. ALL WALL MOUNTED CABINETS AND SHELVES SHALL BE 12" DEEP , UNLESS NOTED OTHERWISE.

16. ALL BASE CABINETS SHALL BE NOMINAL 22" DEEP UNLESS NOTED OTHERWISE.

17. COORDINATE CASEWORK AND EQUIPMENT WITH WORK OF OTHER TRADES.

18. REFER TO SPEC SECTION 115300 FOR EQUIPMENT SCHEDULE, SCOPE OF WORK, AND N.I.C. AND

OWNER/CONTRACTOR FURNISHED/INSTALLED EQUIPMENT INFORMATION.

19. PROVIDE REMOVABLE BACK ACCESS PANELS AT ALL CABINETS AND KNEE SPACES TO PROVIDE ACCESS

TO UTILITY CHASES BEHIND CABINETS.

20. FINISHED FLOORING SHALL BE INSTALLED UNDER ALL CABINETS. FLOORING INSTALLATION SHALL BE

COMPLETED PRIOR TO CABINETS INSTALLATION. REFER TO ARCHITECTURAL DRAWINGS AND

SPECIFICATIONS FOR BASE TO BE PROVIDED AT TOE SPACE OF ALL FIXED CASEWORK AND AT KNEE

SPACES.

21. PROVIDE FULL BACK AT BASE CABINETS WITH DRAWERS TO PREVENT OBJECTS FROM FALLING INTO PIPE

CHASE BEHIND CABINETS.

22. ALL BACKSPLASH TO BE 4" HIGH, EXCEPT ABOVE SINKS WHERE IT SHALL BE 8" HIGH MIN. UNLESS NOTED

OTHERWISE.

23. CONTINUOUS WIREMOLD ARE SHOWN ON ELEVATIONS FOR INFORMATION ONLY. SEE ELECTRICAL

DRAWINGS.

24. CONTRACTOR COORDINATE ELECTRICAL RACEWAY MOUNTING HEIGHT WITH TOP OF CASEWORK

BACKSPLASH, 40" A.F.F. TYPICAL. SEE ELECTRICAL.

25. ELECTRICAL RECEPTACLES AND COMMUNICATION OUTLETS ARE SHOWN ON LABORATORY CASEWORK / EQUIPMENT DRAWINGS FOR LOCATION AND COORDINATION WITH OTHERS. REFER TO DIVISION 26 & 27

DRAWINGS FOR ADDITIONAL INFORMATION.

26. FOR JUNCTION BOX, SEE QUANTITY FOR LOCATION REF. TO ELECTRICAL DRAWINGS.

GENERAL NOTES ABBREVIATIONS

SINK SCHEDULE

ELECTRICAL OUTLETS

FITTING REQUIREMENTS

Revisions

No. Date Item

Digitally signed by Michael J. Mace

DN: C=US,

E=mmace@pagethink.com, Date: 2022.07.25 16:38:00-05'00'

106B

FREEZER ROOM

106C

COLD ROOM

-20°C FREEZER

109B

PREP ROOM

109A

VESTIBULE

CORRIDOR

100CB

101A

100TA

100TBJANITOR

100J

MECHANICAL

100U

106A

MECHANICAL

ROOM

100U

100C

A101

CORRIDOR

100C

NORTHEAST AREA DIRECTOR'S OFFICE

10300 BALTIMORE AVENUE

BUILDING 003, ROOM 223

BELTSVILLE, MARYLAND 20705

PHONE NO. (309) 681-6118

FAX NO. (301) 504-5863

KEY PLAN

PROFESSIONAL CERTIFICATION. I HERE BY CERTIFY THAT

THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME,

AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER

UNDER THE LAWS OF THE STATE OF MARYLAND,

LICENSE No.

EXPIRATION DATE: .

REGISTRATION / STAMP

PROJECT TITLE:

SHEET NO.

DATE:

CAD FILE NO.:

A/E PROJECT NO.:

USDA CONTRACT NO.:

LRS Federal, LLC

Plumbing/FA/FP Engineers

565 Benfield Road, Suite 400

Severna Park, MD 21146

TEL: (410) 544-3570

www.lrsfederal.com

Page Southerland Page, Inc.

1615 M Street, NW, Suite 700

Washington, DC 20036

TEL: 202-909-4900

FAX: 202-785-7336

www.pagethink.com

SOUTHNORTH

12305B21D0015

721040.01

USDA ARS

Plant Genetic Resources Unit Cold Room Expansion

A/E DRAWN BY:

ISSUED FOR

CONSTRUCTION

USDA COR:

USDA EPM.:

T. VIGIL

USDA S&H.: B. DI SALVO

USDA REAL PROP.: P. BORDELON

A/E PROJ. MGR.:

A/E DESIGNER.: PAGE - WA

A/E CHECKED BY: PAGE - MA

PAGE - DR

SHEET TITLE:

21 Crabapple Drive, Geneva, New York 14456

A100

07/22/2022

FIRST FLOOR

PLAN

SCALE: 1/4" = 1'-0"

FIRST FLOOR PLAN

0 8'2' 4'-2'

TRUE

NORTH

Revisions

No. Date Item

Digitally signed by Michael J. Mace

DN: C=US,

E=mmace@pagethink.com, Date: 2022.07.25 16:38:22-05'00'

AD101

REMOVE EXISTING INSULATED PARTITION

AD101

EXISTING DOUBLE

WIDTH INSULATED

PARTITION TO REMAIN

EXISTING CMU

WALL TO REMAIN

EXISTING CMU

WALL TO REMAIN

COLD ROOM

CORRIDOR

100CB

100TB

JANITOR

100J

MECHANICAL

100U

100C

MECHANICAL

ROOM

100U

REMOVE EXISTING SHELVING

UNITS AND TURN THEM TO OWNER

REMOVE EXISTING SHELVING

UNITS AND TURN THEM TO OWNER

EXISTING FLOOR

DRAIN TO REMAIN

EXISTING DOOR

TO REMAIN

EXISTING WALL

TO REMAIN

EXISTING WALL

TO REMAIN

EXISTING DOOR

TO REMAIN

EXISTING

DRYWALL TO

REMAIN

AD101

1. REMOVE INSULATED PANEL CEILING.

2. REMOVE EXISTING FLUOSRESCENT LIGHTING & ALL

CEILING MOUNTED MEP COMPONENTS.

COORDINATE WITH MEP DRAWINGS & SPECS.

END OF CEILING

DEMOLITION

A101

AD101

COLD ROOM

MECHANICAL

100U

100TB

CORRIDOR

100CB

JANITOR

100J

MECHANICAL

ROOM

100U

100C

Level 1 0' - 0"

Roof 14' - 8"

10" CONC.

BLOCK

TO REMAIN

REMOVE EXISTING 4"

INSULATED PARTITION

& CEILING PANEL

4" RIGID

INSULATION

TO REMAIN

4" CON. SLAB

TO REMAIN

4" CON. TOPPING

TO REMAIN

REMOVE

EXISTING 4"

INSULATED

PARTITION

ROOM

(109)

ROOM

(109)

CORRIDOR

(100CB)

10" CONC. BLOCK

TO REMAIN

Level 1 0' - 0"

Roof 14' - 8"

AD101

ROOM

(109)

MECHANICAL

(100U)

COLD ROOM

(108)

EXISTING

DOUBLE WIDTH

INSULATED

PARTITION TO

REMAIN

EXISTING

INSULTED

CEILING PANEL

TO REMAIN

4" RIGID

INSULATION

TO REMAIN

4" CON. SLAB

TO REMAIN

4" CON. TOPPING

TO REMAIN

8" CONC.

BLOCK

TO REMAIN

NORTHEAST AREA DIRECTOR'S OFFICE

10300 BALTIMORE AVENUE

BUILDING 003, ROOM 223

BELTSVILLE, MARYLAND 20705

PHONE NO. (309) 681-6118

FAX NO. (301) 504-5863

KEY PLAN

PROFESSIONAL CERTIFICATION. I HERE BY CERTIFY THAT

THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME,

AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER

UNDER THE LAWS OF THE STATE OF MARYLAND,

LICENSE No.

EXPIRATION DATE: .

REGISTRATION / STAMP

PROJECT TITLE:

SHEET NO.

DATE:

CAD FILE NO.:

A/E PROJECT NO.:

USDA CONTRACT NO.:

LRS Federal, LLC

Plumbing/FA/FP Engineers

565 Benfield Road, Suite 400

Severna Park, MD 21146

TEL: (410) 544-3570

www.lrsfederal.com

Page Southerland Page, Inc.

1615 M Street, NW, Suite 700

Washington, DC 20036

TEL: 202-909-4900

FAX: 202-785-7336

www.pagethink.com

SOUTHNORTH

12305B21D0015

721040.01

USDA ARS

Plant Genetic Resources Unit Cold Room Expansion

A/E DRAWN BY:

ISSUED FOR

CONSTRUCTION

USDA COR:

USDA EPM.:

T. VIGIL

USDA S&H.: B. DI SALVO

USDA REAL PROP.: P. BORDELON

A/E PROJ. MGR.:

A/E DESIGNER.: PAGE - WA

A/E CHECKED BY: PAGE - MA

PAGE - DR

SHEET TITLE:

21 Crabapple Drive, Geneva, New York 14456

AD101

07/22/2022

PARTIAL FIRST

FLOOR

DEMOLITION

PLAN & CEILING

PLAN

SCALE: 1/4" = 1'-0"

PARTIAL FIRST FLOOR DEMOLITION PLAN

SCALE: 1/4" = 1'-0"

PARTIAL FIRST FLOOR CEILING DEMOLITION PLAN

SCALE: 1/4" = 1'-0"

SECTION THROUGH NORTH-SOUTH DIRECTION - DEMOLITION

SCALE: 1/4" = 1'-0"

SECTION THROUGH EAST-WEST DIRECTION - DEMOLITION

0 8'2' 4'-2'

TRUE

NORTH

Revisions

No. Date Item

Digitally signed by Michael J. Mace

DN: C=US,

E=mmace@pagethink.com, Date: 2022.07.25 16:38:44-05'00'

A101

A101

A101

COLD ROOM

VESTIBULE

PREP ROOM

109A

JANITOR

100J

100TB

CORRIDOR

100CB

MECHANICAL

100U

PROPOSED LOCATION FOR

REMOTELY LOCATED FREEZER

ROOM CONDENSER

(SEE MEP DRAWINGS FOR

ADDITIONAL INFORMATION)

FD

CONNECT CONDENSATE

DRAIN FROM FREEZER

ROOM TO EXISTING

FLOOR DRAIN

109A

1 5 1

9 9

8 8

2 2

-20°C FREEZER

109B

F

B

F

MECHANICAL

ROOM

100U

VFT 1

VFT 1

VFT 1

10' - 4"

M

IN

M

IN

2" MIN.

2" MIN.

12' - 5"

A101

A101

A101

CEILING MOUNTED

EVAPORATOR

-20°C FREEZER

109B

PREP ROOM

109A VESTIBULE

CORRIDOR

100CB

COLD ROOM

MECHANICAL

ROOM

100U

100C

JANITOR

100J

100TB

MECHANICAL

100U

VAPORPROOF LED

LIGHT FIXTURE

2x2 LIGHT FIXTURE

(SEE ELECT DWGS.)

2x2 LIGHT

FIXTURE

(SEE ELECT

DWGS.)

2x2 CEILING DIFFUSER

(SEE MEP DWGS.)

2x2 RETURN

REGISTER.

(SEE MEP

DWGS.)

A.F.F.9' - 0"

A.F.F.9' - 0"

ACT-1ACT-1

10' - 4"

M

IN

2" MIN.

M

IN

2" MIN.

Level 1 0' - 0"

Roof 14' - 8"

10" CONC.

BLOCK EXISTING

2x2 ACT

(-20º C)

FREEZER

ROOM

VESTIBULE

4" INSULATED

WALL & CEILING

PANLE

4" INSULATED

FLOOR

INSULATED FLOOR

WITH A REMOVABLE

GRAY POLYVINYL

CHLORIDE DIAMOND

TREAD MAT

FILL GAP LEFT BY

INSULATED PANEL

DEMOLITION

EXISTING 4"

CON. TOPPING

EXISTING 4"

RIGID

INSULATION

EXISTING 4"

CON. SLAB

CEILING MOUNTED

EVAPORATOR

A101

A101

2' - 0" 2' - 2"

AD101

CORRIDOR

(100CB)

EXISTING ROOFING

SYSTEM

EXISTING

FOOTING

10" CONC.

BLOCK EXISTING

A301

MECHANICAL

ROOM

A301

2" MIN.

SEE PLAN FOR ROOM DIMENSIONS

2" MIN.

PREP ROOM

EXISTING

FLOOR DRAIN

TO REMAIN

A301

Level 1 0' - 0"

Roof 14' - 8"

A101

PREP ROOM

(109A)

MECHANICAL

(100U)

COLD ROOM

(108)

EXISTING 4" RIGID

INSULATION

EXISTING 4" CON.

SLAB

EXISTING 4"

CON. TOPPING

EXISTING

8" CONC.

BLOCK

2x2 ACT

VINYL FLOOR TILE

(VFT)

EXISTING ROOFING

SYSTEM

EXISTING INSULATED

DOUBLE WIDTH

PARTITION

DRYWALL PARTITION.

3 5/8" STUD WITH 5/8"

DRYWALL ON ONE SIDE.

EXISTING 4"

CONC. SLAB

SEE PLAN FOR ROOM DIMENSIONS

Level 1 0' - 0"

Roof 14' - 8"

A101

(-20º C)

FREEZER ROOM

(109B)

MECHANICAL

(100U)

COLD ROOM

(108)

EXISTING 4" RIGID

INSULATION

EXISTING 4"

CON. SLAB

EXISTING 4"

CON. TOPPING

EXISTING 8"

CONC. BLOCK

INSULATED

CEILING

INSULATED FLOOR WITH

A REMOVABLE GRAY

POLYVINYL CHLORIDE

DIAMOND TREAD MAT

EXISTING ROOFING

SYSTEM

2" GAP MIN.

INSULATED

WALL PANEL

2" GAP MIN.

EXISTING INSULATED

DOUBLE WIDTH PARTITION

VAPORPROOF LED

LIGHT FIXTURE

EXISTING 4"

CONC. SLAB

A301

7 A301

TRIM

A301

SEE PLAN FOR ROOM DIMENSIONS

NEW WORK KEYNOTES

EXISTING INSULATED DOUBLE WIDTH PARTITION TO REMAIN.

EXISTING CMU WALL TO REMAIN.

EXISTING FLOOR DRAIN TO REMAIN.

EXISTING DRYWALL PARTITION TO REMAIN.

NEW DRYWALL PARTITION. 3 5/8" STUD WITH 5/8" DRYWALL ON ONE SIDE.

REFER TO DWG. A301 FOR WALL TYPES. (TYP).

NEW DRYWALL PARTITION. 3 5/8" STUD WITH 5/8" DRYWALL ON EACH SIDE.

REFER TO DWG. A301 FOR WALL TYPES. (TYP).

NEW DOOR AND FRAME. REFER TO DWG. A301 FOR DOOR TYPES. (TYP).

PATCH & PAINT ALL EXISTING CMU WALLS. COLOR TO BE SELECTED BY ARCHITECT AND

USDA REPRESENTATIVE.

PAINT ALL NEW GYPSUM BOARD WALLS & PARTITIONS. COLOR TO BE SELECTED BY

ARCHITECT AND USDA REPRESENTATIVE.

NEW THRESHOLD.

EXISTING DOOR & FRAME TO REMAIN.

VFT 1 - VINYL FLOOR TILE. STANDARD PLUS - 21003 497 LIGHT GRAY W, BY TARKETT OR APPROVED EQUAL.

VWB 1 - VINYL WALL BASE. COLOR TO BE SELECTED FROM MANUFACTURER’S STANDARD COLORS.

CRP 1 - COLD ROOM PANEL. 4” INSULATED COLD ROOM PANELS WITH BAKED WHITE POLYESTER SMOOTH FINISH ON GALVANIZED STEEL.

WALLS & CEILINGS. INSULATED FLOOR SHALL HAVE A REMOVABLE GRAY POLYVINYL CHLORIDE DIAMOND TREAD MAT.

PTD CMU 1 - EXISTING CMU TO REMAIN. PATCH & CLEAN AS REQUIRED. COLOR TO BE SELECTED FROM MANUFACTURER'S STANDARD COLORS.

PTD GYP 1 - COLOR TO BE SELECTED FROM MANUFACTURER'S STANDARD COLORS

ACT 1 - 2x2 ARMSTRONG - ULTIMA HIGH CEILING TILE OR APPROVED EQUAL.

ROOM FINISH SCHEDULE KEYNOTES

NORTHEAST AREA DIRECTOR'S OFFICE

10300 BALTIMORE AVENUE

BUILDING 003, ROOM 223

BELTSVILLE, MARYLAND 20705

PHONE NO. (309) 681-6118

FAX NO. (301) 504-5863

KEY PLAN

PROFESSIONAL CERTIFICATION. I HERE BY CERTIFY THAT

THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME,

AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER

UNDER THE LAWS OF THE STATE OF MARYLAND,

LICENSE No.

EXPIRATION DATE: .

REGISTRATION / STAMP

PROJECT TITLE:

SHEET NO.

DATE:

CAD FILE NO.:

A/E PROJECT NO.:

USDA CONTRACT NO.:

LRS Federal, LLC

Plumbing/FA/FP Engineers

565 Benfield Road, Suite 400

Severna Park, MD 21146

TEL: (410) 544-3570

www.lrsfederal.com

Page Southerland Page, Inc.

1615 M Street, NW, Suite 700

Washington, DC 20036

TEL: 202-909-4900

FAX: 202-785-7336

www.pagethink.com

SOUTHNORTH

12305B21D0015

721040.01

USDA ARS

Plant Genetic Resources Unit Cold Room Expansion

A/E DRAWN BY:

ISSUED FOR

CONSTRUCTION

USDA COR:

USDA EPM.:

T. VIGIL

USDA S&H.: B. DI SALVO

USDA REAL PROP.: P. BORDELON

A/E PROJ. MGR.:

A/E DESIGNER.: PAGE - WA

A/E CHECKED BY: PAGE - MA

PAGE - DR

SHEET TITLE:

21 Crabapple Drive, Geneva, New York 14456

A101

07/22/2022

FIRST FLOOR

PARTIAL PLAN &

REFLECTED

CEILING PLAN

SCALE: 1/4" = 1'-0"

FIRST FLOOR PARTIAL PLAN

SCALE: 1/4" = 1'-0"

FIRST FLOOR PARTIAL REFLECTED CEILING PLAN

SCALE: 1/4" = 1'-0"

SECTION THROUGH NORTH-SOUTH DIRECTION

SCALE: 1/4" = 1'-0"

SECTION THROUGH EAST-WEST DIRECTION - ROOM 109A

SCALE: 1/4" = 1'-0"

SECTION THROUGH EAST-WEST DIRECTION - ROOM 109B

0 8'2' 4'-2'

TRUE

NORTH

ROOM FINISH SCHEDULE

ROOM

NUMBER ROOM NAME FLOOR FINISH BASE FINISH

WALL FINISH -

NORTH

WALL FINISH -

EAST

WALL FINISH -

SOUTH

WALL FINISH -

WEST CEILING FINISH

100CB CORRIDOR VFT 1 VWB 1 PTD GYP 1 PTD GYP 1 PTD GYP 1 PTD GYP 1 OPEN TO STRUCTURE

109 VESTIBULE VFT 1 VWB 1 PTD GYP 1 PTD CMU 1 PTD CMU 1 PTD CMU 1 ACT 1

109A PREP ROOM VFT 1 VWB 1 CRP 1 PTD GYP 1 PTD GYP 1 PTD CMU 1 ACT 1

Revisions

No. Date Item

Digitally signed by Michael J. Mace

DN: C=US,

E=mmace@pagethink.com, Date: 2022.07.25 16:39:06-05'00'

A201

SHELVING

SHELVING REF.

(NIC)

REF.

(NIC)

STAINLESS

STEEL

SHELVING

2'x4' REMOVABLE

RAMP

CONTROL

PANEL

REMOTELY

LOCATED

FREEZER ROOM

CONDENSER

FD

FD

EXISTING LOCATION

OF CONDENSATE

FLOOR DRAIN

BENCH DUST

COLLECTOR SYSTEM

REMOTE SWITCH FOR

DUST COLLECTOR

(SEE ELECT DWGS.)

CORRIDOR

COLD ROOM

100TB

JANITOR

100JMECHANICAL

100U

-20°C FREEZER

109B

PREP ROOM

109A VESTIBULE

E

E

C

H W

E

E1

E

A2018

A201

E

W01 W01

K01A02 K01

W06

R06

S 1 E

E

E

E

E

E

E

E

"E1" BELOW KNEE SPACE

"E1" ABOVE WALL SHELVES

E

E

MECHANICAL

ROOM

100U

E

EW

STAINLESS

STEEL

SHELVING

EYEWASH (EW)

Level 1 0' - 0"

W01 W01 W06

A02 K01 R06 K01

E2E2

3' - 0" 3' - 0" 3' - 0" 3' - 0"

3' - 0" 3' - 0" 3' - 0"

E1

E1

E1

WALL MOUNTED

WATER HEATER.

SEE MEP

DRAWINGS.

E1

SHELVING

Level 1 0' - 0"

REF.

(N.I.C.)

REF.

(N.I.C.)

3' - 0"

STAINLESS

STEEL

SHELVING

REMOVABLE

RAMP

E1E1E1 E1 E1E1

2' - 0"

E1

SHELVING

Level 1 0' - 0"

2' - 6"

REMOVABLE

RAMP

COLD ROOM

CONTROL PANEL

TOP OF CONTROL

ROOM ROOF

E1

CEILING MOUNTED

EVAPORATOR

SHELVING SHELVING

E1

SHELVING

VAPORPROOF LED

LIGHT FIXTURE

CEILING MOUNTED

EVAPORATOR

E1

SHELVING

VAPORPROOF LED

LIGHT FIXTURE

CEILING MOUNTED

EVAPORATOR

Level 1 0' - 0"

2' - 6"

E1

BENCH DUST

COLLECTOR SYSTEM

STAINLESS

STEEL

SHELVING

E1

Level 1 0' - 0"

2' - 6"

DUST COLLECTOR

HOOD

REMOTE SWITCH FOR

DUST COLLECTOR

TRANSFER GRILL.

SEE MEP DRAWINGS

FOR EXACT LOCATION. 1

CASEWORK TYPES

TYPE:

W

WALL

MOUNTED

CABINETS/

SHELVING

W01

SWINGING GLASS DOORS

W06

METAL RAILS W/ ADJ.

METAL SHELVES

TYPE:

R

SPECIAL

PURPOSE

CASEWORK R06

ADA ACCESSIBLE SINK

LINE OF

ADJACENT

CABINET

OR WALL

TYPE:

K

APRONS

AT KNEE

SPACES

/2

K01

KNEE SPACE

TYPE:

A

ACCESSIBLE

HEIGHT BASE

CABINET - 36"

A.F.F.

A .F

.F

A02

NORTHEAST AREA DIRECTOR'S OFFICE

10300 BALTIMORE AVENUE

BUILDING 003, ROOM 223

BELTSVILLE, MARYLAND 20705

PHONE NO. (309) 681-6118

FAX NO. (301) 504-5863

KEY PLAN

PROFESSIONAL CERTIFICATION. I HERE BY CERTIFY THAT

THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME,

AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER

UNDER THE LAWS OF THE STATE OF MARYLAND,

LICENSE No.

EXPIRATION DATE: .

REGISTRATION / STAMP

PROJECT TITLE:

SHEET NO.

DATE:

CAD FILE NO.:

A/E PROJECT NO.:

USDA CONTRACT NO.:

LRS Federal, LLC

Plumbing/FA/FP Engineers

565 Benfield Road, Suite 400

Severna Park, MD 21146

TEL: (410) 544-3570

www.lrsfederal.com

Page Southerland Page, Inc.

1615 M Street, NW, Suite 700

Washington, DC 20036

TEL: 202-909-4900

FAX: 202-785-7336

www.pagethink.com

SOUTHNORTH

12305B21D0015

721040.01

USDA ARS

Plant Genetic Resources Unit Cold Room Expansion

A/E DRAWN BY:

ISSUED FOR

CONSTRUCTION

USDA COR:

USDA EPM.:

T. VIGIL

USDA S&H.: B. DI SALVO

USDA REAL PROP.: P. BORDELON

A/E PROJ. MGR.:

A/E DESIGNER.: PAGE - WA

A/E CHECKED BY: PAGE - MA

PAGE - DR

SHEET TITLE:

21 Crabapple Drive, Geneva, New York 14456

A201

07/22/2022

FIRST FLOOR

PARTIAL LAB

PLAB

SCALE: 1/4" = 1'-0"

FREEZER ROOM FLOOR PLAN

SCALE: 1/4" = 1'-0"

PREP ROOM - 109A

SCALE: 1/4" = 1'-0"

PREP ROOM - 109A

SCALE: 1/4" = 1'-0"

PREP ROOM - 109A

SCALE: 1/4" = 1'-0"

-20°C FREEZER - 109B

SCALE: 1/4" = 1'-0"

-20°C FREEZER - 109B

SCALE: 1/4" = 1'-0"

-20°C FREEZER - 109B

SCALE: 1/4" = 1'-0"

VESTIBULE - 109

SCALE: 1/4" = 1'-0"

PREP ROOM - 109A

Revisions

No. Date Item

Digitally signed by Michael J. Mace

DN: C=US,

E=mmace@pagethink.com, Date: 2022.07.25 16:39:30-05'00'

REFER TO

PLAN FOR

PARTITION

TYPE

SEALANT,

BOTH SIDES

'Z' CLIPS

FLOOR CLIPS

W/ 3/8"ø EXP.

BOLTS

ALT.

WALL

CONDITIO

N

DOOR

TYPE AS

SCHED

/8

0' - 0 1/2" 0' - 0 1/2"

REFER TO PLANS FOR

PARTITION TYPE

SEALANT, BOTH

SIDES

DOOR REFER TO

SCHEDULE

MTL. STUD BOX

HEADER

DOOR TYPE "G"

(SEE SCHEDULE)

A301

A301

FRAME TYPE

01HM

DOOR OPENING

GLASS

TYPE

GL-08

8" 8"

A301

DOOR TYPE G

B3

PART. WIDTH

SOUND ATTENUATION BLANKETS

5/8" GYP. BOARD BOTH SIDES

STEEL STUDS

STEEL RUNNERS

BASE AS SCHEDULED

CONTINUOUS SEALANT BOTH SIDES

FLOOR FINISH AS SCHEDULED

LINE OF DECK

DO NOT ATTACH GYP. TO TOP TRACK

CEILING AS SCHEDULED

STRUCT. FRAMING BEYOND

CONTINUOUS SEALANT

M

IN4"

METAL STUDS (HORIZ. BETWEEN

STUDS AT TOP OF GYP.)

3/ 8"

3/ 8"

VERTICAL BRACING / BRIDGING AT

48" O.C. MAX

3 5/8" -N / A12' - 4" 14' - 11" 3 1/2"4 7/8"

'B' SERIES

PLAN

TYPE STUD MIN STC25 GA. 20 GA. INSUL

EST STC

W/O INSUL

MAX. HEIGHT

DESIGN NO.

DESIGN STC

SECTION

PART.

WIDTH

LIMITING HEIGHTS BASED ON SSMA/SFIA; L/240; 5 PSF

*ADD WEB STIFFENERS

STEEL STUD

SOUND

ATTENUATION

BLANKETS

P A

R T

. W

ID

T H

5/8" GYP. BOARD

BOTH SIDES

A301

Sim

A301

Sim

LINE OF DECK

STRUCT. FRAMING

BEYOND

CEILING AS SCHEDULED

BASE AS SCHEDULED

CONTINUOUS SEALANT

BOTH SIDES

FLOOR FINISH

AS SCHEDULED

M

IN4"

STEEL STUD

5/8" GYP. BD -ONE LAYER

3/ 8"

PART. WIDTH

2'-0".

'F' SERIES

TYPE STUD MIN STC25 GA. 20 GA. INSUL

EST STC

W/O INSUL

MAX. HEIGHT

DESIGN NO.

DESIGN STC

SECTION

PART.

WIDTH

F3 3 5/8" -N/A12' - 4" 14' - 11" 3 1/2"

LIMITING HEIGHTS BASED ON SSMA / SFIA; L/240; 5 PSF

* ADD WEB STIFFENERS

4 1/4" -

SOUND ATTENUATION

BLANKETS

A301

Sim

A301

Sim

A301

Sim

3 5/8" METAL STUDS TO

UNDERSIDE OF DECK OR

STRUCTURE ABOVE

A S

S H

O W

N O

N P

LA

N

S

ACOUSTICAL LAY-IN

CEILING, REF FINISH

SCHED.

4"

5/8" GYP. BOARD -

ONE LAYER

EXISTING RIGID INSULATED

PANEL TO REMAIN

3 5/8" 5/8"

ACOUSTICAL SEALANT w/ SOUND

ATTENUATION BLANKET BACKING

GLUED TO STEEL DECK FOR

UNRATED PARTITIONS AND

FIRESTOPPING SEALANT w/

BACKING GLUED TO STEEL DECK

FOR RATED PARTITIONS

WHERE STEEL DECK FLUTES ARE

PERPENDICULAR TO PARTITION, FILL

VOIDS SOLID ABOVE RUNNERS WITH

ACOUSTICAL SEALANT w/ SOUND

ATTENUATION BLANKET BACKING

GLUED TO STEEL DECK FOR UNRATED

PARTITIONS. FILL VOIDS ABOVE

RUNNERS WITH FIRESTOPPING

SEALANT w/ BACKING GLUED TO STEEL

DECK FOR RATED PARTITIONS

MET. RUNNER TRACK w/

SELF-THREADING STEEL

SCREWS @ 12" O.C.

1/ 2"

ROOF

INSULATION

3 5/8"

1/4" BEAD ACOUSTICAL

SEALANT OR FIRESTOPPING

AS APPLICABLE @ BOTH

SIDES

BASE (VARIES)

STEEL 'J' RUNNER ANCHORED

w/ POWDER DRIVEN

FASTENERS AT 24" O.C.

NUMBER OF

LAYERS OF GYP. BD.

SOUND ATTENUATION

BLANKETS AS APPLICABLE

5/8" 3 5/8" 5/8"

Level 1 0' - 0"

4"2" MIN.

FILL GAP LEFT BY

INSULATED PANEL

DEMOLITION

10" CONC.

BLOCK EXISTING

4" INSULATED

WALL PANEL &

FLOOR

EXISTING 4" CON.

TOPPING

EXISTING 4" RIGID

INSULATION

EXISTING 4" CON.

SLAB

Level 1 0' - 0"

EXISTING 4"

CONC. SLAB

EXISTING 4" RIGID

INSULATION

EXISTING 4"

CON. SLAB

2" MIN. 4"

EXISTING

INSULATED

DOUBLE WIDTH

PARTITION

4" INSULATED

WALL PANEL & FLOOR

Level 1 0' - 0"

EXISTING 4"

CONC. SLAB

4" INSULATED

WALL PANEL &

FLOOR

4" 2" MIN.

EXISTING 8"

CONC. BLOCK

EXISTING 4"

CONC. TOPPING

EXISTING 4" RIGID

INSULATION

EXISTING 4"

CON. SLAB

A S

S H

O W

N O

N P

LA

N

S

ACOUSTICAL LAY-IN

CEILING, REF FINISH

SCHED.

4" 2" MIN.

TRIM

4" INSULATED

WALL PANEL & CEILING

DRYWALL PARTITION.

3 5/8" STUD WITH 5/8"

DRYWALL ON ONE SIDE.

9' - 0"

2" MIN. 4"

EXISTING INSULATED

DOUBLE WIDTH PARTITION

TRIM

4" INSULATED

WALL PANEL & CEILING

9' - 0" Level 1

0' - 0"

EXISTING 4" CONC.

SLAB ON GRADE.

EXISTING 4" RIGID

INSULATION.

EXISTING 4" CONC.

TOPPING TO

REMAIN.

EXISTING FLOOR

DRAIN TO REMAIN.

NEW 2MM VINYL

FLOOR AND

ADHESIVE

NORTHEAST AREA DIRECTOR'S OFFICE

10300 BALTIMORE AVENUE

BUILDING 003, ROOM 223

BELTSVILLE, MARYLAND 20705

PHONE NO. (309) 681-6118

FAX NO. (301) 504-5863

KEY PLAN

PROFESSIONAL CERTIFICATION. I HERE BY CERTIFY THAT

THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME,

AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER

UNDER THE LAWS OF THE STATE OF MARYLAND,

LICENSE No.

EXPIRATION DATE: .

REGISTRATION / STAMP

PROJECT TITLE:

SHEET NO.

DATE:

CAD FILE NO.:

A/E PROJECT NO.:

USDA CONTRACT NO.:

LRS Federal, LLC

Plumbing/FA/FP Engineers

565 Benfield Road, Suite 400

Severna Park, MD 21146

TEL: (410) 544-3570

www.lrsfederal.com

Page Southerland Page, Inc.

1615 M Street, NW, Suite 700

Washington, DC 20036

TEL: 202-909-4900

FAX: 202-785-7336

www.pagethink.com

SOUTHNORTH

12305B21D0015

721040.01

USDA ARS

Plant Genetic Resources Unit Cold Room Expansion

A/E DRAWN BY:

ISSUED FOR

CONSTRUCTION

USDA COR:

USDA EPM.:

T. VIGIL

USDA S&H.: B. DI SALVO

USDA REAL PROP.: P. BORDELON

A/E PROJ. MGR.:

A/E DESIGNER.: PAGE - WA

A/E CHECKED BY: PAGE - MA

PAGE - DR

SHEET TITLE:

21 Crabapple Drive, Geneva, New York 14456

A301

07/22/2022

ARCHITECTURAL

DETAILS &

SCHEDULES

SCALE: 1 1/2" = 1'-0"

HM FRAME DOOR @ JAMB

SCALE: 1 1/2" = 1'-0"

HM FRAME DOOR HEAD

SCALE: 3/8" = 1'-0"

DOOR FRAME DIAGRAMS

SCALE: 3/8" = 1'-0"

DOOR TYPE DIAGRAMS

SCALE: 1 1/2" = 1'-0"

TYPE B: PARTITION HEAD, NON RATED

DOOR SCHEDULE

DOOR

NUMBER

ROOM

NAME

DOOR

TYPE

DOOR CONST.

TYPE

DOOR GLASS

TYPE

DOOR PANEL

FINISH

DOOR FRAME

FIRE

RATING HARDWARE TYPE CommentsWIDTH HEIGHT TYPE

CONST.T

YPE Jamb Head

109A PREP

ROOM

G HM GL-08 VE 3' - 0" 7' - 0" 01HM HM/PTD 3/A301 1/A301 - SEE SPEC.

SECTION 08 71 00

SCALE: 1 1/2" = 1'-0"

TYPE F: PARTITION HEAD, NON RATED

SCALE: 3" = 1'-0"

CEILING DETAIL

SCALE: 3" = 1'-0"

TOP ANCHORAGE OF PARTITION TO METAL DECK

SCALE: 3" = 1'-0"

FLOOR ANCHORAGE OF PARTITION

SCALE: 1" = 1'-0"

COLD ROOM DETAIL

THROUGH

NORTH-SOUTH

SCALE: 1" = 1'-0"

COLD ROOM DETAIL

THROUGH BOTTOM

CORNER EAST-WEST

SCALE: 1" = 1'-0"

COLD ROOM DETAIL

THROUGH EAST-WEST

SCALE: 1" = 1'-0"

COLD ROOM DETAIL

THROUGH TOP

CORNER NORTH-SOUTH

SCALE: 1" = 1'-0"

COLD ROOM DETAIL

THROUGH TOP

CORNER EAST-WEST

SCALE: 1" = 1'-0"

SECTION THROUGH

EXISTING FLOOR DRAIN

Revisions

No. Date Item

Digitally signed by Michael J. Mace

DN: C=US,

E=mmace@pagethink.com, Date: 2022.07.25 16:39:55-05'00'

25" MAX.

2' - 6"

4"

1" 8"

M A

X

/2

11" MIN.

M

IN

8" HIGH

BACKSPLASH

FOR SINK SIZE,

REFER TO SINK

SCHEDULE ON

SHEET A001

REMOVABLE

METAL PANEL

LINE OF

ADJACENT

UNIT

BEYOND

REMOVABLE

PROTECTIVE

METAL PANEL

6" MAX.

WALL MOUNTED

WATER HEATER.

SEE MEP

DRAWINGS.

SEE DETAIL

9/A401

4" HIGH

BACKSPLASH

TYP. U.N.O.

FULL DEPTH

ADJUSTABLE SHELF

REMOVABLE BACK

SEE DETAIL 4/A401FULLY ENCLOSED

TOE SPACE

ONE PIECE DRAWER

BODY RADIUSED

ALL FOUR SIDES

2' - 6"

1' - 10"

PAN FORMED

DRAWER HEAD

FILLED FOR SOUND

DEADENING

TWO-PIECE PAN

FORMED DOOR

FILLED FOR SOUND

DEADENING

ONE-PIECE BOTTOM

AND FRONT RAIL

TURNED UP AT

BACK AND SIDES

4" HIGH

BACKSPLASH

TYP. U.N.O.

WALL MOUNTED

ELECTRICAL

OUTLET. SEE ELEC

DWGS.

2' - 6"

LINE OF

ADJACENT UNIT

BEYOND

APRON

PROVIDE ELEC. &

DATA OUTLETS

PRE-WIRED UP

TO SERVICE

CHASE. SEE

ELEC. DWGS.

DRAWER SLIDES

FULL DEPTH

ADJUST. SHELF

REINFORCING

GUSSETS WITH

LEVELING BOLTS

( ALL FOUR

CORNERS)

REMOVABLE

BACK

BEYOND

METAL FINISH TO

MATCH ADJACENT

CABINETS

END PANELS

FINISH FLOOR

FIXED TOP

PANELS

CUT-OUT FOR

ELECTRICAL OUTLET

BASE (SEE ARCH DWGS)A

D

A H

G T

SECURE ALL SIDES

WALL BEYOND

TOP SHELF

ADJUSTABLE TO

6'-0" A.F.F.

UNLESS NOTED

OTHERWISE

METAL WALL RAIL

1 ADJUSTABLE

SHELVES ON METAL

BRACKETS

END CAP ON TOP

AND BOTTOM

U.N.O.

1' - 4"

BLOCKING

ONE PIECE BOTTOM &

FRONT RAIL TURNED

UP AT BACK & SIDES

TWO-PIECE SOLID

PAN FORMED

DOOR FILLED FOR

SOUND

DEADENING OR

GLASS SWINGING

DOOR

2 ADJUST. METAL

SHELVES

RECESSED BACK FOR

EASE OF SECURING

TO WALL

ONE PIECE 18 GAUGE

BOTTOM SOFFIT

1' - 1"

BLOCKING

EQ EQ

1" EPOXY RESIN TOP

EASED EDGE

1/4" DRIP

CONTINUOUS . TYP.

FACE OF CABINET

BELOW

TYPICAL COUNTER EDGE DRIP DETAIL

1" EPOXY RESIN TOP

EASED EDGE

1/4" DRIP

CONTINUOUS . TYP.

FACE OF

CABINET BELOW

U.N.O.

0' - 1"

EPOXY CEMENT.

PROVIDE SMOOTH

TRANSITION BETWEEN

SINK RIM AND

COUNTERTOP.

LIPPED (DROP-IN) SINK EDGE DETAIL

0' - 0 1/2"

0' - 0 1/4"

0' - 0 1/4"

END PANELS

FINISH FLOOR

FIXED TOP

PANEL

WALL

MOUNTED

ELECTRICAL

OUTLET. SEE

ELEC DWGS.

A D

A H

G T

SECURE ALL SIDES

WALL BEYOND

U.N.O.

1' - 4"

2' - 6"

1' - 10" 0' - 1"

1' - 0"

NORTHEAST AREA DIRECTOR'S OFFICE

10300 BALTIMORE AVENUE

BUILDING 003, ROOM 223

BELTSVILLE, MARYLAND 20705

PHONE NO. (309) 681-6118

FAX NO. (301) 504-5863

KEY PLAN

PROFESSIONAL CERTIFICATION. I HERE BY CERTIFY THAT

THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME,

AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER

UNDER THE LAWS OF THE STATE OF MARYLAND,

LICENSE No.

EXPIRATION DATE: .

REGISTRATION / STAMP

PROJECT TITLE:

SHEET NO.

DATE:

CAD FILE NO.:

A/E PROJECT NO.:

USDA CONTRACT NO.:

LRS Federal, LLC

Plumbing/FA/FP Engineers

565 Benfield Road, Suite 400

Severna Park, MD 21146

TEL: (410) 544-3570

www.lrsfederal.com

Page Southerland Page, Inc.

1615 M Street, NW, Suite 700

Washington, DC 20036

TEL: 202-909-4900

FAX: 202-785-7336

www.pagethink.com

SOUTHNORTH

12305B21D0015

721040.01

USDA ARS

Plant Genetic Resources Unit Cold Room Expansion

A/E DRAWN BY:

ISSUED FOR

CONSTRUCTION

USDA COR:

USDA EPM.:

T. VIGIL

USDA S&H.: B. DI SALVO

USDA REAL PROP.: P. BORDELON

A/E PROJ. MGR.:

A/E DESIGNER.: PAGE - WA

A/E CHECKED BY: PAGE - MA

PAGE - DR

SHEET TITLE:

21 Crabapple Drive, Geneva, New York 14456

A401

07/22/2022

LAB CASEWORK

DETAILS

SCALE: 1" = 1'-0"

SECTION THROUGH ADA TIERED SINK CABINET TYPE R06

SCALE: 1" = 1'-0"

SECTION THROUGH ADA BASE CABINET TYPE A02

SCALE: 1" = 1'-0"

SECTION THROUGH ADA METAL

KNEE SPACE WITH APRON TYPE K01

SCALE: 1" = 1'-0"

TRANSVERSE SECTION THROUGH

BASE CABINET (TYPICAL)

SCALE: 1" = 1'-0"

TRANSVERSE SECTION THROUGH

KNEE SPACE WITH OUTLET AT APRON

SCALE: 1" = 1'-0"

SECTION THROUGH METAL ADJUSTABLE

SHELF ON WALL RAILS TYPE W06

SCALE: 1" = 1'-0"

SECTION THROUGH WALL CABINET

WITH SWINGING DOORS TYPE W01

SCALE: 3" = 1'-0"

COUNTER TOP EDGE DETAIL

SCALE: 1" = 1'-0"

TRANSVERSE SECTION THROUGH

KNEE SPACE WITH OUTLET AT BACK PANEL

SCALE: 1" = 1'-0"

TYPIAL MOUNTING

HEIGHTS FOR

ACCESSIBLE HEIGHT

BASE CABINETS

SCALE: 1" = 1'-0"

TYPICAL MOUNTING

HEIGHTS FOR 30" HIGH

WALL CABINETS

NOTES:

1. CONTRACTOR COORDINATE

WALL BLOCKING

REQUIREMENTS FOR

ANCHORING CASEWORK WITH

CASEWORK SHOPDRAWINGS.

2. REFER TO DRAWING #A301

FOR WALL TYPES.

Revisions

No. Date Item

Digitally signed by Michael J. Mace DN: C=US, E=mmace@pagethink.com, Date: 2022.07.25 16:40:18-05'00' whorton Stamp whorton mspasyk

MEP COMBINED.pdf
USDA.E101.20220728
USDA.E102.20220728
USDA.MP101 thru MP103.20220729