DRAFT Appendix D 11 October 2016 Table 1.0 – Monitoring Parameters for Ovens

Equipment
Parameter
Gauge Installed
Range
Alarm Type
Failure Mode
Comment
Booth
Control Board
Y
No Power
Email
No Power
Monitoring--> Power
Booth
Heating Element
Y
<=100' F
Email
Low
Monitoring --> Heater
Booth
Blower Fan 1 RPM
Y
1800>Run<2200
Email
Low
Monitoring --> filter effectiveness
Booth
Blower fan 1 Vibe.
Y
>70 Hz
Email
High
Monitor for potential motor issues
Booth
Blower Fan 2 RPM
Y
1800>Run<2200
Email
Low
Proactively plan for filter changes
Booth
Blower Fan 2 Vibe.
Y
>70 Hz
Email
High
Monitor for potential motor issues
Booth
Exhaust Motor RPM
Y
1800>Run<2200
Email
Out OF Range
Monitor for potential Motor issues
Booth
Exhaust Motor Vibe.
Y
>70 Hz
Email
High
Monitor for potential Motor issues
Booth
Exhaust Motor Temp.
Y
>185' F
Email
Out OF Range
Monitor for potential Motor issues
Booth
Exhaust Fan SB-2 RPM
Y
1800>Run<2200
Email
Out OF Range
Monitor for potential fan issues
Booth
Exhaust Fan SB-2 Temp.
Y
>185' F
Email
High
Monitor for potential fan issues
Booth
Exhaust Fan SB-2 Vibe.
Y
>70 Hz
Email
High
Monitor for potential motor issues

Picture 1 – OC12184 Outside Panel

Picture 2 – OC12184 Outside Panel

Picture 3 – OC19627 Outside Panel

Picture 4 – OC19627 Inside Panel

Picture 5 – OC19627 Inside Panel

Picture 6 – OC21102 Outside Panel

Picture 7 – OC21102 Outside Panel

Picture 8 – OC21103 Inside Panel

Picture 9 – OC21153 Outside Panel

Draft Appendix D FA8125-17-R-0002 Page 1 image5.jpg image6.jpeg image7.jpeg image8.jpeg image9.jpg image1.jpg image2.jpg image3.jpeg image4.jpeg