Question: Do you require both generators to have a switch to switch between 50hz and 60hz ?
‐ Yes, Both gens will need 120/208 volts 60Hz and 400 volts 50 Hz switching capability.
Question: Do you want the bulk fuel tank mounted on the trailer with the generator? –
‐ We do not need a bulk fuel tank on unit, it needs to have a fitting on it to be capable of auxiliary fuel connection.
Question: Are these 2 generators going to be separate or running together.
‐ They will be separate from each other on their own trailers and will run to support different areas.
Question: What is the capacity of the day fuel tank?
‐ The fuel capacity will be 480 liters or 126.8 gallons. 30 hrs run time at 75% load.
Question: With the output requirement of 83 KW, do you know if that would be the standby rating or the prime output rating?
‐ They will be 83Kw prime power 24/7 capability