Text version

Product Data - Air-Cooled Scroll Item: A1 Qty: 1 Tag(s):

Air-Cooled Scroll Packaged Chiller Startup Included 52 nominal tons

46.96 tons at AHRI 208/60/3 High efficiency/performance

9.74 EER full load / 14.00 EER IPLV

4 compressors / Dual circuits – 2 compressors per circuit Full factory refrigerant charge (HFC-410A) With factory installed freeze protection Refrigerant isolation valves (discharge valve) UL listed to US and Canadian safety standard ASHRAE 90.1 2010 compliant AHRI certified Standard cooling application (leaving water temperature between 40°F to 65°F) Grooved pipe connection Factory insulation 0.75" - all cold parts Performance based on water Wide ambient operating capability (0°F to 125°F) Microchannel condenser coil Across the line starter/direct on line Single point connection main line unit power - ancillary items require other 115v power connection Circuit breaker Enclosure type UL 1995 rated for outdoor applications 5,000 amp short circuit rating BACnet interface Programmable quad relay alarm board Elastomeric isolators (Field Installed) With water strainer factory installed Factory installed IFM Efector flow switch Factory installed water strainer Standard low noise fans 89 dBA sound power 63 dBA sound pressure Architectural louvered panels – (hail guards covering upper and lower sections 1st year entire unit parts, labor, and refrigerant loss warranty 2nd thru 5th year compressor replacement parts warranty