Specifications for work task

- 3 phase, 60hz, 100kW standby rated generator wired to 277/480 VAC, Wye configuration

- Duty rating, standby power

- Diesel Engine

- UL listed (2200)

- NFPA 110 Type 10 Level 1 Capable

- Emissions Certification, EPA, Tier 3, NSPS CI Stationary Emergency

- Aluminum Enclosure, Sound Att, Level 2 with Exh System

- Alternator-60Hz, 12L, 480/277V, 120C, 40C ambient

- Generator Set Control compatible with PowerCommand 2.3 or industry equivelant

- Exciter/Regulator-Pmg, 3 phase sensor

- Engine Governor-Electronic, Isochonous Only

- Display with English language as primary setting

- Oil Pressure Gauge on display

- Analog AC Output meter on display

- AmpSentry TM or industry equivelant protective relay

- Emergency stop switch

- Single load connection

- Circuit Breaker, 70A-250A, 3 pole, 600VAC, 100% rated, UL Listed

- Enclosure wind load 180 MPH

- On board, double walled 24 hour minimum fuel tank mounted to belly of unit

- On board fuel/water separator

- Mechanical fuel gauge

- Installed fuel tank rupture basin switch

- Skid mounted

- 12VDC engine starter

- On-board battery charging alternator, normal output

- Engine Cooling-High ambient Air Temperature

- Exension-Engine Coolant Drain

- Engine Coolant-50% Antifreeze, 50% water mixture

- Coolant heater, Cold ambient

- Heavy duty engine air cleaner

- pre-filled with appropriate engine oil

- Standard warranty for base

- English language manuals

- Battery rack capable of holding appropriately sized batteries

- Oil Drain Extension

- Sound level 2 baffles

- Same branded 480VAC, 150 amp, 4 pole, 60 Hz, 3 phase, 4 wire, bypass transfer switch with delayed transition transfer mode in NEMA 3R cabinet with a digital display(protected from sun damage), level 2 transfer switch control, key front security panel

- Transfer switch must have 2 year warranty, including parts labor and travel, followed by a 3-5 year warranty parts only and a 10 year warranty on main contacts

Specification for Work Task

- 600kW, 60 Hz Diesel generator, wire for 277/480 VAC, 3 phase, 4 wire

- Standby power rated

- UL 2200 Listed

- EAP, Tier 2, NSPS CI Stationary Emergency, emission certification

- Tank mounted enclosure on 1000 gallon, UL142 compliant subbase tank

- 60 hz, 240/480 Volt alternator at 105C

- Powercommand 2.3 or industry standard generator controller

- English display language

- Analog AC output meter

- LCD control display

- Emergency stop switch

- equipped with 1200 amp, 3 phase, 600/690V, UL/IEC circuit breaker

- Fuel water separator

- Dual stub-up fuel tank connection

- High ambient air temperauture engine cooling

- Low coolant level warning alarm on board

- 208/240/480 V, 40 deg F manimum coolant heater

- Heavy duty entgine air cleaner

- Standard year long warranty on unit

- manuals written in English

- side inlet end outlet 10” critical muffler assembly

- flexible pipe kit.- complete with a 1200 amp, 4 pole, bypass transfer switch compatible with generator control programming

- Listed UL1008

- 60 Hz, 3 phase, 4 wire, 480VAC

- type 1 cabinet

- Key switch front panel security

- 2 year parts and labor warranty on transfer switch, 5 year parts only warranty on transfer switch and 10 year main contacts only warranty included

U.S. EPA, Stationary Emergency Application Genset-Diesel,60Hz,150kW Duty Rating-Standby Power Listing-UL 2200 Emissions Certification, EPA, Tier 3, NSPS CI Stationary Emergency Diesel Engine Enclosure-Steel,Sound Att,Level 2,w/Exhaust System Voltage-277/480,3 Phase,Wye,4 Wire Alternator-60Hz,12 Ld,Broad Rng,Full 1Ph Outp,105C Generator Set Control-PowerCommand 2.2 Exciter/Regulator-Pmg, 3 Phase Sensor Engine Governor-Electronic, Isochronous Only Display Language-English Control Mounting-Left Facing Meters-AC Output,Analog Stop Switch-Emergency Alarm-Audible, Engine Shutdown CB or EB or TB-Left Only CircuitBreaker-225A,Left,3P,600/525V,TM,80% UL/IEC Listing, ULC-S601-07 Wind Rating-150 MPH,Steel Housing Fuel Tank-Dual Wall Subset, 24 Hour Capacity Separator-Fuel/Water Warning-Fuel in Rupture Basin Engine Starter - 12 VDC Motor Battery Charging Alternator-Normal Output Engine Cooling-High Ambient Air Temperature Warning-Low Coolant Level Extension-Engine Coolant Drain Engine Coolant-50% Antifreeze, 50% Water Mixture Engine Air Cleaner-Heavy Duty Engine Oil Literature-English Rack-Battery Extension-Oil Drain Common Parts Listing Battery Charger. 10amp-120/208/240Vac (60/50Hz) Transfer Switch-Bypass,PwrCmd or industry equivelant,225Amp Transfer Mode-Delayed Transition Poles-4 Application-Utility To Genset Listing-UL 1008/CSA Certification Frequency-60 Hertz System-3 Phase,3 Wire Or 4 Wire Voltage-480 Vac

Cabinet-NEMA 1 rating Control-Transfer Switch,Level 2 Meters-Bar Graph Display Switch,Key,Front Panel Security Display-Digital with sun protection Monitoring-Load Transfer Switch Warranty - Yr 0-2: Parts, Labor and Travel; Yr 3-5:

Parts Only; Yr 6-10: Main Contacts Only Common Parts Listing

25kW, 60HZ, Standby, Diesel Duty Rating-Standby Power Listing-UL 2200 NFPA 110 Type 10 Level 1 Capable Emissions Certification, EPA, Tier 3, NSPS CI Stationary Emergency Diesel Engine Enclosure-Aluminum,Sound Att,Level 2, w/Exh System Voltage-120/208,3 Phase,Wye,4 Wire Alternator-60Hz,12L,208/120V,105C,40C amb,IMS Generator Set Control-PowerCommand 1.1 or industry equivalent Exciter/Regulator - EBS Engine Governor-Electronic, Isochronous Only Display Language-English Gauge-Oil Pressure Meters-AC OutputAnalog (kVA) Stop Switch-Emergency Load Connection-Single CB,Loc A,90A,3P,600VAC,80%,UL Enclosure - Wind Load 180MPH, ASCE7-10 Fuel Tank-Regional, 2 Wall, Sub Base, 24Hr Minimum Electronic Fuel Gauge Switch-Fuel Tank, Rupture Basin, Installed Skidbase-Housing Ready Engine Starter - 12 VDC Motor Battery Charging Alternator-Normal Output Battery Charger - 6 Amp, Regulated Engine Cooling-High Ambient Air Temperature Warning-Low Coolant Level Extension-Engine Coolant Drain Engine Coolant-50% Antifreeze, 50% Water Mixture Coolant Heater, Cold Ambient Engine Air Cleaner-Normal Duty Engine Oil Genset Warranty- Base Literature-English SL2 Baffle Rack, Larger Battery Extension-Oil Drain Common Parts Listing Sound Level 2 Enclosure Transfer Switch-Bypass,PwrCmd or industry standard equivelant,150Amp Transfer Mode-Delayed Transition Poles-4 Application-Utility To Genset

Listing-UL 1008/CSA Certification Frequency-60 Hertz System-3 Phase,3 Wire Or 4 Wire Voltage-208 Vac Cabinet-Type 3R Control-Transfer Switch,Level 2 Display-Digital with sun protection Switch,Key,Front Panel Security Transfer Switch Warranty - Yr 0-2: Parts, Labor and Travel; Yr 3-5:

15kW, 60HZ, Standby, Diesel Genset Duty Rating-Standby Power Listing-UL 2200 NFPA 110 Type 10 Level 1 Capable Emissions Certification, EPA, Tier 4i, NSPS CI Stationary Emergency Voltage-120/240,1 Phase,3 Wire Alternator-60HZ,4L,240/120V,1PH,105C,40C amb,IMS Generator Set Control-PowerCommand 1.1 or industry equivalent Exciter/Regulator - EBS Engine Governor-Electronic, Isochronous Only Display Language-English Gauge-Oil Pressure Meters-AC OutputAnalog (kVA) Stop Switch-Emergency Load Connection-Single CB,Loc A,70A,2P,600VAC,80%,UL Fuel Tank-Regional, 2 Wall, Sub Base, 24Hr Minimum Mechanical Fuel Gauge Switch-Fuel Tank, Rupture Basin, Installed Skidbase-Housing Ready Engine Starter - 12 VDC Motor Battery Charging Alternator-Normal Output Engine Cooling-High Ambient Air Temperature Warning-Low Coolant Level Extension-Engine Coolant Drain Engine Coolant-50% Antifreeze, 50% Water Mixture Coolant Heater, Cold Ambient Engine Air Cleaner-Heavy Duty Exhaust Connector-NPT Engine Oil Genset Warranty- Base Literature-English Rack-Battery Extension-Oil Drain Common Parts Listing Critical Muffler-Side Inlet End Outlet-2"NPT Exhaust Pipe Package-Side Inlet-2"NPT to 2"NPT Transfer Switch-Bypass, PwrCmd or industry equivalent ,150Amp Transfer Mode-Delayed Transition Poles-3 Application-Utility To Genset

System-Single Phase, 2 Wire Or 3 Wire Voltage-240 Vac Cabinet-Type 1 Control-Transfer Switch,Level 2 Switch,Key,Front Panel Security Display-Digital with sun shield Transfer Switch Warranty - Yr 0-2: Parts, Labor and Travel; Yr 3-5: Parts Only; Yr 6-10: Main Contacts Only

20kW, 60HZ, Standby, Diesel Genset Duty Rating-Standby Power Listing-UL 2200 NFPA 110 Type 10 Level 1 Capable Emissions Certification, EPA, Tier 4i, NSPS CI Stationary Emergency Enclosure-Alum, Sound,Att,Level 1,w/Exhaust System Voltage-120/208,3 Phase,Wye,4 Wire Alternator-60Hz,12L,208/120V,105C,40C amb,IMS Generator Set Control-PowerCommand 1.1 or industry equivalent Exciter/Regulator - EBS Engine Governor-Electronic, Isochronous Only Display Language-English Gauge-Oil Pressure Meters-AC OutputAnalog (kVA) Stop Switch-Emergency Load Connection-Single CB,Loc A,80A,3P,600VAC,80%,UL Aluminum Enclosure Enclosure - Wind Load 180MPH, ASCE7-10 Fuel Tank-Regional, 2 Wall, Sub Base, 24Hr Minimum Mechanical Fuel Gauge Switch-Fuel Tank, Rupture Basin, Installed Skidbase-Housing Ready Engine Starter - 12 VDC Motor Battery Charging Alternator-Normal Output Engine Cooling-High Ambient Air Temperature Warning-Low Coolant Level Extension-Engine Coolant Drain Engine Coolant-50% Antifreeze, 50% Water Mixture Coolant Heater, Cold Ambient Engine Air Cleaner-Heavy Duty Engine Oil Genset Warranty- Base Literature-English Rack-Battery Extension-Oil Drain Common Parts Listing Bypass Transfer Switch-Power Command: 150A/225A/260A Transfer Switch-Bypass,PwrCmd,150Amp Transfer Mode-Delayed Transition Poles-4

System-3 Phase, 4 Wire Voltage-208 Vac Cabinet-NEMA 1 Control-Transfer Switch,Level 2 Display-Digital Switch,Key,Front Panel Security Transfer Switch Warranty - Yr 0-2: Parts, Labor and Travel; Yr 3-5: Parts Only; Yr 6-10: Main Contacts Only

25kW, 60HZ, Standby, Diesel Duty Rating-Standby Power Listing-UL 2200 NFPA 110 Type 10 Level 1 Capable Emissions Certification, EPA, Tier 3, NSPS CI Stationary Emergency Voltage-120/208,3 Phase,Wye,4 Wire Alternator-60Hz,12L,208/120V,105C,40C amb,IMS Generator Set Control-PowerCommand 1.1 or industry equivalent Exciter/Regulator - EBS Engine Governor-Electronic, Isochronous Only Display Language-English Gauge-Oil Pressure Meters-AC OutputAnalog (kVA) Stop Switch-Emergency Load Connection-Single CB,Loc A,90A,3P,600VAC,80%,UL Fuel Tank-Regional, 2 Wall, Sub Base, 24Hr Minimum Electronic Fuel Gauge Switch-Fuel Tank, Rupture Basin, Installed Skidbase-Housing Ready Engine Starter - 12 VDC Motor Battery Charging Alternator-Normal Output Battery Charger - 6 Amp, Regulated Engine Cooling-High Ambient Air Temperature Warning-Low Coolant Level Extension-Engine Coolant Drain Engine Coolant-50% Antifreeze, 50% Water Mixture Duct Adaptor-Radiator Outlet Coolant Heater, Cold Ambient Engine Air Cleaner-Normal Duty Exhaust Connector-NPT Engine Oil Genset Warranty- Base Literature-English Rack, Larger Battery Extension-Oil Drain Common Parts Listing Critical Muffler-Side Inlet End Outlet-3"NPT Exhaust Pipe Package-Side Inlet-3"NPT to 3"NPT Transfer Switch-Bypass,PwrCmd or industry equivalent,150Amp Transfer Mode-Delayed Transition Poles-4

System-3 Phase,3 Wire Or 4 Wire Voltage-208 Vac Cabinet-Type 3R Control-Transfer Switch,Level 2 Display-Digital with sun shield Switch,Key,Front Panel Security Transfer Switch Warranty - Yr 0-2: Parts, Labor and Travel; Yr 3-5: