Attachment_2_-_Drawings.pdf

PDF 4 MB Posted

Attached to
Draft Solicitation Federal contract opportunity
Solicitation number
FA4608-17-R-0013
Issued by
Department of the Air Force Global Strike Command

About this file

Draft Drawings

View the file

Other files for this federal contract opportunity

Other files attached to Draft Solicitation, newest first.
File Type Posted
Attachment_4_-_AF66.pdf PDF
Attachment_5-_Insurance_Form.pdf PDF
Attachment_6_-_Special_Contract_Requirements.pdf PDF
Attachment_3_-_Environmental_Req'ts_(Jun_16).pdf PDF
Attachment_8_-_Past_Performance_Questionnaire.doc DOC document
Draft_Solicitation.docx.pdf PDF
Attachment_7_-_PPQ_Letter.pdf PDF
Attachment_9-_Wage_Determination.pdf PDF
Attachment_1_-_Statement_of_Work.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DEMOLITION FLOOR PLAN

SCALE: 1/8" = 1'-0"

04 05

02 03 02 03

13 15

22 22 22

KEYNOTES:

01. REMOVE EXISTING DOOR, FRAME, AND HARDWARE.

02. REMOVE PORTION OF EXISTING DRYWALL PARTITION TO CREATE OPENING

FOR NEW FRAME.

03. REMOVE EXISTING BORROWED LITE (FRAME AND GLAZING) AND PREPARE

OPENING FOR IN-FILL OR NEW FRAME.

04. REMOVE EXISTING CARPET AND RUBBER BASE; SCRAPE/CLEAN SLAB TO RECEIVE

05. PREPARE OPENING FOR IN-FILL.

06. REMOVE EXISTING DRYWALL FURRING (3/8" DRYWALL OVER 5/8" DRYWALL OVER

3/4" WOOD LATH) TO REVEAL EXISTING CMU WALL.

07. REMOVE EXISTING DRYWALL FURRING (1/2" DRYWALL OVER 3/4" WOOD LATH)

TO REVEAL EXISTING CMU WALL.

08. EXISTING RAMP SHALL REMAIN.

09. REMOVE AND SALVAGE FOR REINSTALLATION EXISTING RAISED FLOOR COMPONENTS

CONCRETE FLOOR SLAB (SEE FLOOR PLAN-NEW CONSTRUCTION)). REMOVE ALL THREE

STEPS AT NORTH AND SOUTH SERIES OF STEPS AND PREPARE FOR IN-FILL.

AT MIDDLE LEVEL (RAISED FLOOR SHALL BE LOWERED TO 1'-0" ABOVE EXISTING

CONCRETE FLOOR SLAB (SEE FLOOR PLAN-NEW CONSTRUCTION)).

11. EXISTING RAISED FLOOR AT LOW LEVEL SHALL REMAIN AT PRESENT ELEVATION

(1'-0" ABOVE EXISTING CONCRETE FLOOR SLAB).

12. REMOVE EXISTING OVERHEAD COILING GRILLE ASSEMBLY.

13. REMOVE EXISTING BASE CABINETS (AND COUNTERTOPS); AND UPPER CABINETS.

14. REMOVE EXISTING IDS DOOR SENSOR ASSEMBLY, INCLUDING BOX; AND CONDUIT AND

16. REMOVE EXISTING PLASTIC LAMINATE DOORS AND PILASTERS.

17. REMOVE EXISTING DOUBLE DOORS AND HARDWARE. EXISTING FRAME SHALL REMAIN.

18. REMOVE EXISTING ALUMINUM PIVOT DOORS, FRAME, AND HARDWARE AND DRYWALL

RETURNS.

19. REMOVE EXISTING DOUBLE DOORS, FRAME, AND HARDWARE.

20. REMOVE EXISTING RAISED FLOOR COMPONENTS AS REQUIRED TO ALLOW NEW DRYWALL

PARTITION TO BEAR UPON AND BE ATTACHED TO EXISTING CONCRETE FLOOR SLAB.

21. REMOVE EXISTING STEPS AT EXISTING RAISED FLOOR AND PREPARE OPENING TO

RECEIVE IN-FILL.

22. REMOVE EXISTING GUARDRAILS/HANDRAILS.

23. EXISTING GUARDRAILS/HANDRAILS SHALL REMAIN.

24. REMOVE EXISTING BORROWED LITE (FRAME AND GLAZING) AND DRAPERY AS PART OF

PARTITION DEMOLITION.

25. REMOVE PORTION OF EXISTING DRYWALL PARTITION TO CREATE OPENING FOR NEW

FRAME. EXERCISE DUE CARE NOT TO DAMAGE (OR REMOVE MORE THAN REQUIRED)

EXISTING CERAMIC WALL TILES IN TOILET ROOMS.

26. REMOVE EXISTING VENT HOOD, FLUE, AND POWER SUPPLY.

U P

U P

100'-0"

102'-2"

101'-7"

101'-0"

05 05

AT HIGH LEVEL (RAISED FLOOR SHALL BE LOWERED TO 1'-0" ABOVE EXISTING

10. REMOVE AND SALVAGE FOR REINSTALLATION EXISTING RAISED FLOOR COMPONMENTS

CMU

SAWCUT

27. REMOVE EXISTING VCT FLOORING AND RUBBER BASE; SCRAPE/CLEAN SLAB TO RECEIVE

NEW FINISH FLOORING.

28. REMOVE EXISTING WATER COOLER; WATER SUPPLY AND DRAIN SHALL REMAIN TO SERVE

NEW KITCHEN SINK.

E X

T E

N T

O F

C M

U

100'-0"

INDICATED BY :xx

29. REMOVE EXISTING CASED OPENING AND PREPARE OPENING FOR IN-FILL.

OFFICE 1

OFFICE 2

OFFICE 3

OFFICE 4

OFFICE 5

ENTRY

AIRLOCK

MEN'S RR

WOMEN'S RR

STOR 1

JAN CLO

BREAK RM

KITCHENPANTRY

STOR 2

C O

R R

ID

O

R

ADMIN STAFF 1

ADMIN STAFF 2

C O

R R

BONUS RM 1 BONUS RM 2AUDITORIUM

LOBBY

BONUS RM 3MECHANICAL

COMMUNICATIONS

SOUTH VESTNORTH VEST COMMON ROOM

OFFICE 6

OFFICE 7

OFFICE 8 OFFICE 9

PARTITION LEGEND: INDICATED BY :xx

01. 5/8" GYPSUM BOARD BOTH SIDES ON 3 5/8" STEEL STUDS AT 16" OC; EXTENDS

02. 5/8" GYPSUM BOARD BOTH SIDES ON 3 5/8" STEEL STUDS AT 16" OC; EXTENDS

TO UNDERSIDE OF EXISTING ROOF DECK

03. 5/8" GYPSUM BOARD OVER 2X4 WOOD LATH BOTH SIDES ON 2x4 WOOD STUDS AT

16" OC; EXTENSION ABOVE EXISTING CEILING VARIES FROM 1'-0" TO 5'-0";

04. EXISTING 3 5/8" CMU'S WITH 3/8" GYPSUM BOARD ON 1-1/2" WOOD LATH ON

05. EXPOSED 3 5/8" CMU'S ON 'OFFICE 8' SIDE AND WITH 1/2" GYPSUM BOARD ON

07. 1/2" GYPSUM BOARD BOTH SIDES ON 2x4 WOOD STUDS AT 16" OC; EXTENDS 3"

ABOVE KITCHEN CEILING.

6" ABOVE EXISTING CEILING

VERTICALLY SAWCUT AND REMOVE EXSISTING 3 5/8" CMU'S WHERE SHOWN

'OFFICE 6' SIDE AND 1/2" GYPSUM BOARD ON 1-1/2" WOOD LATH ON 'OFFICE 7'

SIDE; EXTENDS 2" ABOVE EXISTING CEILING

3/4" WOOD LATH ON 'OFFICE 7' SIDE; EXTENDS 2" ABOVE EXISTING CEILING

06. 3 5/8" CMU WALL; EXTENDS WITHIN ONE FOOT OF EXISTING ROOF DECK

GENERAL NOTES:

01. EXISTING PARTITIONS SHOWN WITH DASHED LINES AND IN GRAYTONE SHALL BE

DEMOLISHED IN THEIR ENTIRETY. ANY WIRING DEVICES, ELEC OR COMM BOXES OR

APPURTENANCES MOUNTED IN OR ON THESE PARTITIONS, UNLESS INDICATED TO

BE REUSED OR RELOCATED, SHALL BE REMOVED; ANY ASSOCIATED CONDUIT AND

WIRING SHALL BE REMOVED TO SOURCES OF ORIGIN. EXISTING APPURTENANCES

INDICATED TO BE REUSED OR RELOCATED SHALL BE SALVAGED FOR REINSTALLATION.

03. ELEVATIONS SHOWN ARE EXISTING FLOOR ELEVATIONS; 100'-0" ELEVATION (CONCRETE

SLABE ELEVATION) IS DATUM ELEVATION. SEE FLOOR PLAN-NEW CONSTRUCTION, FOR

NEW ELEVATIONS AT RECONFIGURED RAISED FLOOR IN ADMIN STAFF 1 ROOM.

04. ROOM TITLES ARE PROVIDED ONLY FOR FIELD REFERENCE DURING CONSTRUCTION.

02. EXISTING CONSTRUCTION SHOWN WITH DASHED LINES AND/OR IN GRAYTONE,

INCLUDING DOOR ASSEMBLIES, SHALL BE REMOVED IN THEIR ENTIRETY, UNLESS

COMPONENTS ARE OTHERWISE INDICATED TO REMAIN.

NEW CARPET.

05. REMOVE EXISTING CHAIR RAILS AT WALLS OF OFFICES 1, 2, 3, 4, AND 5.

15. REMOVE EXISTING STAINLESS STEEL SINK UNIT; CAP DRAIN AND WATER SUPPLIES

AT WALL.

101'-0"

100'-7"

101'-2"

101'-9"

102'-4"

06. EXISTING DOORS AND FRAMES IN WORK AREA NOT INDICATED BY DOOR MARK TO BE

REMOVED SHALL BE REFINISHED/REPAINTED.

07. REMOVE EXISTING THRESHOLDS AND WEATHERSTRIPPING AT EXISTING DOORS AND

WITH NEW THRESHOLDS AND WEATHERSTRIPPING (TO MATCH EXISTING).

FRAMES IN WORK AREA NOT INDICATED BY DOOR MARK TO BE REMOVED AND REPLACE

30. REMOVE EXISTING DOOR AND HARDWARE; EXISTING FRAME SHALL REMAIN AND BE PREPARED

FOR REFINISHING. REMOVE CIPHER LOCK FOR GOVERNMENT SALVAGE.

V C

T C

P T 25

31. REMOVE ABANDONED PVC CONDENSATE PIPING AND CAP AT WALL.

32. REMOVE TOP TWO STEPS IN MIDDLE SERIES OF STEPS AND PREPARE FOR IN-FILL.

MEETING RM

100'-0"

100'-0"

100'-0"

101'-0"

101'-0"

101'-0" 101'-0"

33. NOT USED

02 02 02 02

08. EXISTING CMU WALL EXTENDS TO UNDERSIDE OF ROOF DECK.

08. REMOVE EXISTING INTERIOR ROOM SIGNAGE.

09. REMOVE EXISTING COMBINATION AND CIPHER/PUSH-BUTTON LOCKS FROM DOORS SHOWN

TO BE REMOVED; REMIT LOCKS TO BASE LOCKSMITH AS GOVERNMENT SALVAGE.

34. REMOVE EXISTING KEYPAD AND ASSOCIATED WIRING.

35. REMOVE EXISTING EXT PLATE TRIM AT EXISTING LOCK & PREPARE TO RECEIVE KEYED LOCK.

36. REMOVE EXISTING IDS PANELBOARDS AND ASSOCIATED WIRING AND CONDUIT.

37. REMOVE AND SALVAGE FOR REINSTALLATION EXISTING THERMOSTAT AND ASSOCIATED

WIRING.

38. REMOVE EXISTING "PUSH FOR EXIT" BUTTON AND ASSOCIATED CONDUIT AND WIRING.

39. REMOVE EXISTING 'CUBBY-HOLE' BUILT-IN AND ASSOCIATED WOOD TRIM AND PREPARE

OPENING FOR IN-FILL.

37 37 37 37

40. REMOVE EXISTING DRYWALL CHASE AND PREPARE CORNER FOR CONSTRUCTION OF

COLUMN BOX.

41. REMOVE 1'-0" WIDE VERTICAL STRIP OF EXISTING GYPSUM BOARD OVER EXISTING 1x4 LATH.

42. REMOVE EXISTING RUBBER BASE FROM CORNER-TO-CORNER OF ROOM.

STORAGE

SECURE RM

100'-0" 14

REMOVE EXISTING COMBINATION LOCK FOR GOVERNMENT SALVAGE.

AND WIRING BACK TO SOURCES OF ORIGIN.

10. COMPLETELY REMOVE EXISTING IDS SECURITY SYSTEM THRUOUT ENTIRE PROJECT AREA.

43. REMOVE EXISTING WATER HEATER; RETAIN EXISTING SUPPLY LINES AND ELEC SVC.

FA4608-17-R-0013

Attachment 2

P

P

P P

P P

P P

M M

PPP P

P PP

M PP M P

P

P P P

P

P

P

M

P

P

P

P P

P

P

P

DEMOLITION REFLECTED CEILING PLAN

SCALE: 1/8" = 1'-0"

01. REMOVE AND DISPOSE OF EXISTING LAY-IN CEILING GRID AND ACOUSTICAL PANELS IN

02. REMOVE EXISTING SECURE RACEWAY PDS AND ASSOCIATED SUSPENSION SYSTEM (TENSION

01 01

GENERAL NOTES

01. AT AREAS ENCOMPASSED BY BOLD BLACK LINES, EXISTING PARTITIONS, HEADERS, AND

CEILING FURRINGS, SHOWN IN GRAYTONE AND WITH DOUBLE DASHED LINES, SHALL BE

DEMOLISHED. SEE SHEET A01, DEMOLITION FLOOR PLAN, FOR ADDITIONAL INFORMATION.

02. ANY EXISTING CEILING GRID, ACOUSTICAL PANELS, OR APPURTENANCES INDICATED TO

REMAIN OR BE REUSED AND ARE DAMAGED BY THE CONTRACTOR SHALL BE REPLACED BY

CONTRACTOR AT NO ADDITIONAL COST TO THE GOVERNMENT.

03. CONTRACTOR SHALL PROVIDE 150 NEW ACOUSTICAL PANELS (TO MATCH EXISTING) TO

REPLACE PREVIOUSLY DAMAGED ACOUSTICAL PANELS IN AREAS WHERE EXISTING CEILING

ASSEMBLIES ARE TO REMAIN. DAMAGED PANELS TO BE REPLACED SHALL BE SELECTED BY

GOVERNMENT REPRESENTATIVE. THESE 150 NEW ACOUSTICAL PANELS ARE EXCLUSIVE

04. AT AREAS NOT ENCOMPASSED BY BOLD BLACK LINES, EXISTING CEILING ASSEMBLIES,

INCLUDING APPURTENANCES, SHALL REMAIN AS IS UNLESS OTHERWISE INDICATED BY

NOTE OR LEGEND.

05. ANY EXISTING FIRE SPRINKLER HEAD THAT IS TO BE RELOCATED IN AREAS ENCOMPASSED BY BOLD BLACK LINES SHALL BE POSITIONED IN TO CENTER OF ACOUSTICAL CEILING PANEL.

KEYNOTES

AREAS ENCOMPASSED BY BOLD BLACK LINES. EXISTING HANGER WIRES SUPPORTING

EXISTING CEILING ASSEMBLY MAY BE REUSED FOR NEW CEILING; AUGMENT HANGER WIRE

03. EXISTING PIPE SLEEVE ELBOWING THRU EXISTING WALL AND PENETRATING EXISTING

CEILING SHALL BE ENTIRELY REMOVED. PATCH WALL BOTH SIDES OF PENETRATION. SEE

04. REMOVE EXISTING CEILING ASSEMBLY, INCLUDING EXISTING APPURTENANCES (SALVAGE

FOR REINSTALLATION), TO EXTENT SHOWN AND AS ENCOMPASSED BY BOLD BLACK LINES TO

LET IN NEW DRYWALL PARTITION ABOVE CEILING. SEE SHEET A04, REFLECTED CEILING

PLAN - NEW CONSTRUCTION, FOR LOCATIONS OF NEW DRYWALL PARTITIONS.AS REQD TO FULLY SUPPORT LOADING. SEE APPURTENANCES LEGEND FOR DESIGNATIONS

OF ITEMS TO BE SALVAGED AND REINSTALLED/RELOCATED; AND ITEMS TO BE REMOVED

AND DISPOSED OF. TEMPORARILY SUSPEND ITEMS TO BE SALVAGED AND REINSTALLED/

RELOCATED HIGH ENOUGH ABOVE WORK AREA TO AVOID INTERFERENCE W/ NEW CEILING

ASSEMBLY INSTALLATION.

06. REMOVE AND DISPOSE OF EXISTING PUBLIC ADDRESS SYSTEM SPEAKERS THRUOUT PROJECT AREA. ALSO REMOVE ASSOCIATED ITEMS, SUCH AS CONDUIT & WIRING, BACK TO SOURCES OF ORIGIN.

APPURTENANCES LEGEND

SALVAGE FOR REINSTALLATION (0R TO REMAIN AS IS) EXISTING FIRE SPRINKLER HEAD

SALVAGE FOR REINSTALLATION (0R TO REMAIN AS IS) EXISTING SUPPLY AIR GRILLE

SALVAGE FOR REINSTALLATION (OR TO REMAIN AS IS) EXISTING RETURN AIR GRILLE

SALVAGE FOR REINSTALLATION EXISTING LIGHT TROFFER;

SALVAGE FOR REINSTALLATION EXISTING STRIP LIGHT FIXTURE

SALVAGE FOR REINSTALLATION EXISTING RECESSED CAN LIGHT

P REMOVE EXISTING PUBLIC ADDRESS SYSTEM SPEAKER

REMOVE EXISTING UNCLEAR LIGHT STROBE (ORANGE LENS)

REMOVE EXISTING IDS MOTION DETECTION STROBE

REMOVE EXISTING CEILING FAN

07. EXISTING CEILING HEIGHT AT EACH ROOM (MEASURED FROM EXISTING CONCRETE SLAB

05. EXISTING SLOPED CEILING ASSEMBLY TO REMAIN ONLY ABOVE AUDITORIUM 121. BRACE AS

REQUIRED FOR STRUCTURAL STABILITY.

TO UNDERSIDE OF EXISTING LAY-IN CEILING) IS SHOWN DOUBLE-UNDERLINED.

8'-0"

8'-1"

8'-1 1/2"

8'-1"

7'-11 1/2"

8'-0"

8'-0"

7'-11 1/2"

7'-11 1/2"

9'-3"

9'-9"

8'-0"

8'-1"

7'-9" 7'-6" 7'-9"

7'-9"

11'-0"

9'-11"

8'-0" 8'-0"

8'-0"

10'-11"

11'-0"

10'-1"

SHEET NO. Co01, DEMOLITION COMMUNICATIONS PLAN, FOR DISPOSITION OF EXISTING

SIPRNET CABLING IN SLEEVE.

REMOVE EXISTING SECURE RACEWAY PDS

SALVAGE FOR REINSTALLATION (OR TO REMAIN AS IS) EXISTING EMERGENCY LIGHTRODS AND UNISTRUTS). REPLACE ACOUSTICAL CEILING PANELS DAMAGED BY PDS.

S S A

St

A

A A

(A)

S 3(B)

S3(B)S

(C) B

B

C

C

C

C

S (D)

D

DD

S (E

)S (F

S

(G

F F

F F

E E

E E

E E

06. REMOVE EXISTING 'IN USE' LIGHT ABOVE DOOR AND ASSOCIATED CONDUIT, WIRING, AND

SWITCH MARK "G".

S (H)

H H

S (I)

S (J)

I,J

I,J

I,J

I,J

I,J

I,JI,JI,J

I,JI,JI,J

08. REMOVE ASSOCIATED WIRING AND CONDUITS FOR EXISTING SWITCHES INDICATED TO

BE REMOVED (SHOWN IN GRAYTONE).

S S t

X

X

S

S

St

(X)

REMOVE EXISTING SWITCH CONTROLLING UNCLEAR LIGHT STROBES

REMOVE EXISTING SWITCH CONTROLLING LIGHT FIXTURES MARKED "X"

S

3(X) REMOVE EXISTING 3-WAY SWITCH CONTROLLING LIGHT FIXTURES MARKED "X"

"X" DESIGNATES CONTROLLING SWITCH

FIXTURE: "X" DESIGNATES CONTROLLING SWITCH

EXISTING EXHAUST FAN TO REMAIN AS IS

SALVAGE FOR REINSTALLATION EXISTING EXHAUST FAN

D

REMOVE EXISTING CEILING-HUNG TV MOUNTING BRACKET

07. REMOVE EXISTING TV MOUNTING BRACKET AND ASSOCIATED MOUNTING POLE & UNISTRUTS.

ALSO REMOVE EXISTING ELECTRIC AND COMMUNICATIONS SERVICES TO SOURCES TO ORIGIN.

07 07 07

SALVAGE FOR REINSTALLATION EXISTING MNS/"BIG VOICE" LIGHT STROBE (GREEN LENS)

S (K

)S

S (K

S

K

K

K

S10

S (O)

O O O

S(N)

N N N

S3(M) S3(M)

M M M

S 3(L)

L

08. REMOVE EXISTING SWITCHING LEGS AT THESE LIGHT TROFFERS.

09. REMOVE EXISTING SINGLE-POLE SWITCH AND PREPARE EXISTING BOX TO RECEIVE NEW

3-WAY SWITCH.

10. REMOVE EXISTING SINGLE-POLE SWITCH AND PREPARE EXISTING BOX TO SERVE AS J-BOX

FOR NEW 3-WAY SWITCH ASSEMBLY.

11. REMOVE EXISTING PDS (TWO (2) EMT CONDUITS AND UNISTRUT WALL BRACKETS).

EXISTING LIGHT TROFFER TO REMAIN AS IS

M EXISTING MASS NOTIFICATION SYSTEM SPEAKER TO REMAIN AS IS

TO THOSE OTHERWISE TO BE REPLACED.

09. EXISTING MASS NOTIFICATION SYSTEM SPEAKERS AND ASSOCIATED ITEMS, SUCH AS BOXES AND

WIRING, SHALL REMAIN. TEST SPEAKERS FOR PROPER FUNCTIONING.

10. SOME EXISTING CEILING -MOUNTED APPURTENANCES ARE INDICATED IN LEGEND TO REMAIN AS IS WHILE OTHERS OF SAME TYPE ARE INDICATED TO BE SALVAGED FOR REINSTALLATION. COMPARE

REFLECTED CEILING PLANS ON SHEETS A02 AND A04 FOR PURPOSE OF DIFFERENTIATION.

M

P

PP

M P

FLOOR PLAN - NEW CONSTRUCTION

CONFERENCE RM

DEP CDR

EXEC DIR

EXEC OFFR

SEC/WAITING

VEST

LAVATORY

MEN'S TOILET

VEST

LAVATORY

111 WOMEN'S TOILET

JAN CLO

VEST

BREAK RM

CLASSROOM 1

AUDITORIUM

CLASSROOM 2

LOBBY

SIPR CAFE

C O

R R

ID

O

R

MEETING RM

ADMIN STAFF 2

138 HERITAGE RM

VEST

VEST

COMM RM

STORAGE 2

STORAGE 1

127DIV CHIEF 3

DIV CHIEF 2

DIV CHIEF 1

CHIEF

RESOURCE ADVISOR

ADMIN STAFF 1

6 23

1718192021

1" 1'

-4

6'-1 1/8" 5"

2'-4"

58'-11 3/4"

EQ

5" EQ 5" EQ 5" EQ

5" 3'-7"

5"

E Q

E Q

02 02 02

01 01 04

07 0707 05 05 05 05

N

100'-0"

100'-0"

101'-0" 101'-0" 101'-0"

100'-0"

KEYNOTES:

01. INFILL OPENING CREATED BY DOOR (OR BORROWED LITE OR PASS-THRU) REMOVAL

WITH 5/8" FIRE-RATED GYPSUM BOARD BOTH SIDES ON STEEL STUDS AT 16" OC MAX

SPACING; VERIFY WALL THICKNESS AT EACH IN-FILL LOCATION; USE OF DIFFERENT

STEEL STUD SIZES OR DOUBLE WYTHES OF STUDS MAY BE REQUIRED. ENSURE OUTER

FACES OF GYPSUM BOARD ARE FLUSH WITH EXISTING DRYWALL.

02. MIDDLE AND HIGH LEVELS OF EXISTING RAISED FLOOR TO BE SAME ELEVATION AS

EXISTING SUPPORTS & FRAMES AS PRACTICABLE. PROVIDE NEW SUPPORTS & FRAMES

AS REQUIRED FOR COMPLETE INSTALLATION.

03. PROVIDE NEW WEATHERSTRIPPING SET, THRESHOLD (FULL LENGTH OF OPENING),

04. IN-FILL FORMER LOCATION OF REMOVED STEPS (SEE SHEET A01, DEMOL FLOOR PLAN)

06. NOT USED

EXISTING STEEL COLUMN; MINIMIZE BOX FOOTPRINT.

08. PROVIDE LATCHES MISSING AT DOORS AT SEVEN (7) TOILET STALLS.

09. AFTER PREPARING CONC FLOOR SLAB, PROVIDE CULTURED MARBLE THRESHOLDS.

10. PROVIDE WALL-MOUNTED ALUMINUM HANDRAIL (TO MATCH EXISTING).

11. PROVIDE FLOOR-MOUNTED ALUMINUM GUARDRAIL (TO MATCH EXISTING).

07. CONSTRUCT BOX OF 5/8" FIRE-RATED GYPSUM BOARD ON 2-1/2" STEEL STUDS AROUND

INDICATED BY :xx

PARTITION LEGEND: INDICATED BY :xx

01. 5/8" FIRE-RATED GYPSUM BOARD BOTH SIDES ON 3 5/8" STEEL STUDS AT 16" OC;

02. 5/8" FIRE-RATED GYPSUM BOARD BOTH SIDES ON 3 5/8" STEEL STUDS AT 16" OC;

EXTEND TO 6" ABOVE CEILING.

03. NEW DRYWALL PARTITION SHALL BE ATTACHED TO EXISTING CONCRETE SLAB.

NEW PARTITION SHALL CONSIST OF 5/8" FIRE-RATED GYPSUM BOARD BOTH

05. 5/8" FIRE-RATED GYPSUM BOARD ON 2 -1/2" STEEL STUDS AT 16" OC OVER 1/2" AIR

EXTEND TO UNDERSIDE OF EXISTING ROOF DECK. JOINTS OF GYPSUM BOARD

SIDES ON 3 5/8" STEEL STUDS AT 16" OC. EXTEND PARTITION 6" ABOVE CEILING;

GAP OVER EXISTING CMU WALL; EXTEND GYPSUM BOARD AND STEEL STUD

ASSEMBLY 6" ABOVE CEILING. SECURE TOP TRACK TO CMU WALL WITH ANGLE

GENERAL NOTES:

01. ALL RAISED FLOOR WORK SHALL BE PERFORMED BY FIRM SPECIALIZING IN SUCH

WORK; FIRM SHALL HAVE MINIMUM FIVE (5) YEARS DOCUMENTED EXPERIENCE IN

RECONFIGURATION OF EXISTING INSTALLATIONS.

05. DIAGONALLY BRACE NEW PARTITIONS TO EXISTING ROOF STRUCTURE AT 4'-0" MAX

SPACING AND IN STAGGERED PATTERN.

04. SEE SHEET A06, SIGN SCHEDULE, FOR ROOM SIGNAGE.

LOW LEVEL (101'-0"). REINSTALL SALVAGED UNDAMAGEDFLOOR PANELS AND REUSE

040404

WITH MATCHING PANELS AND UNDERFLOOR STRUCTURE OF EXISTING RAISED FLOOR.

05. NO WORK IN THIS ROOM, UNLESS OTHERWISE NOTED

ABOVE CEILINGS SHALL BE TAPED.

REINSTALLED (OR PROVIDE NEW AS REQUIRED) RAISED FLOOR COMPONENTS

FOR NEW CONFIGURATION.

04. NEW DRYWALL PARTITION SHALL BE ATTACHED TO EXISTING CONCRETE SLAB.

NEW PARTITION SHALL CONSIST OF 5/8" FIRE-RATED GYPSUM BOARD BOTH

SIDES ON 3 5/8" STEEL STUDS AT 16" OC; EXTEND STEEL STUDS ABOVE CEILING

BRACE PARTITION TO EXISTING STRUCTURE. JOINTS OF GYPSUM BOARD ABOVE

BRACKETS AT 4'-0" MAXIMUM SPACING.

02. SEE SHEET A06, OPENING SCHEDULE, FOR WORK AT NEW DOOR ASSEMBLIES.

03. SEE SHEET A05, FINISH SCHEDULE, FOR ROOM FINISHES.

VESTIBULE

COMMON ROOM

12. PROVIDE VCT FLOORING (TO MATCH EXISTING).

1'-2"

101'-7"

102'-2"

102'-9"

103'-4"

COMMANDER

1'-2 1/2"

C O

R R

ID

O

R

NIPR RM

18'-6" 17'-4" 11'-6" 11'-6" 11'-6"

09. SEAL ALL AROUND PENETRATIONS BOTH SIDES OF GYPSUM BOARD AT EXISTING AND NEW

PARTITIONS (EXTENDING TO UNDERSIDE OF ROOF DECK) AT FOLLOWING ROOMS:

COMMANDER 102, AUDITORIUM 121, AND SIPR CAFE 117. APPLY CONTINUOUS 1/4" SEALANT

13. ARROWHEAD POINTS TO LOCATION OF SEPARATION BETWEEN PARTITION TYPES "03" & "04".

BEAD OR, WHERE ANNULAR SPACE OF PENETRATION IS TOO LARGE TO SEAT SEALANT BEAD,

USE EXPANDING FOAM SEALANT.

TO UNDERSIDE OF EXISTING ROOF DECK. BOTH SIDES OF GYPSUM BOARD SHALL

EXTEND FROM 10" ABOVE CONCRETE SLAB TO UNDERSIDE OF ROOF DECK.

CEILING SHALL BE TAPED.

5/8" FIRE-RATED GYPSUM BOARD BOTH SIDES ON 6" STEEL STUDS AT 16" OC) FROM

EXISTING TOP TRACK (APPROX 8" ABOVE CEILING) TO UNDERSIDE OF EXISTING ROOF

DECK. JOINTS OF GYPSUM BOARD (BOTH SIDES) ABOVE CEILING SHALL BE TAPED.

& 2 DOOR SWEEPS AT EA OPG. REPAINT EXISTING EXTERIOR DOORS & FRAMES (2 COATS).

020304

1' -0

09 10 11 12 13 14

SECURE RM

125A

14. EXTEND EXISTING DRYWALL PARTITION WITH NEW DRYWALL PARTITION (CONSISTING OF

10. WHERE EXISTING PARTITIONS ARE TO BE EXTENDED TO UNDERSIDE OF EXISTING ROOF

DECK, RELOCATE EXISTING ELECTRICAL COMPONENTS SUCH AS CONDUITS AND JUNCTION

BOXES FROM ATOP TOP PLATES/TRACKS.

BOARD BOTH SIDES) FROM EXISTING TOP PLATE TO UNDERSIDE OF EXISTING ROOF DECK

WITH NEW 5' HIGH DRYWALL PARTITION CONSISTING OF 3 5/8" STEEL STUDS AT 16" OC WITH- 5/8" FIRE-RATED GYPSUM BOARD BOTH SIDES. JOINTS OF GYPSUM BOARD (BOTH SIDES) ABOVE

15. EXTEND EXISTING DRYWALL PARTITION (CONSISTING OF 2x4 WOOD STUDS WITH 1/2" GYPSUM

CEILING SHALL BE TAPED.

AROUND AT DUCT PENETRATIONS WITHIN 1" OF INSULATION JACKET. PROVIDE 24 GAGE

GALVANIZED 3"x 3" ANGLE FLANGES ALL AROUND BOTH SIDES OF OPENING. SNUGLY FIT ANGLE

FLANGES ALL AROUND DUCT BUT DO NOT COMPRESS INSULATION.

16. IN-FILL OPENINGS AT EXISTING 4" CMU PARTITION WITH NEW 4"CMU'S; IN-FILL OPENINGS ALL

HIGH DRYWALL PARTITION CONSISTING OF 3 5/8" STEEL STUDS AT 16" OC WITH 5/8" FIRE-RATED

GYPSUM BOARD BOTH SIDES. JOINTS OF NEW GYPSUM BOARD ABOVE CEILING SHALL BE TAPED

BOTH SIDES.

17. EXTEND EXISTING 4" CMU PARTITION TO UNDERSIDE OF EXISTING ROOF DECK WITH NEW 4'

CORNER. IN-FILL THIS 1' WIDE x 4'HIGH OPENING WITH NEW DRYWALL PARTITION (CONSISTING OF 3 5/8" STEEL STUDS AT 16" OC WITH 5/8" FIRE-RATED GYPSUM BOARD BOTH SIDES. JOINTS OF

NEW GYPSUM BOARD ABOVE CEILING SHALL BE TAPED BOTH SIDES.

18. EXISTING DOUBLE-WYTHE CMU CAVITY WALL TERMINATES LATERALLY APPROX 1'-0" FROM

05 05

11. PROVIDE TRANSITION STRIPS WHERE DISSIMILAR MATERIALS JOIN. 06. PATCH HOLES IN EXISTG DRYWALL (TO REMAIN) CAUSED BY PAST DAMAGE OR REMOVAL

OF EXISTING CONSTRUCTION, INCLUDING HOLES LEFT BY REMOVAL OF WIRING OR

19. AFTER PERFORMING REQUIRED WORK AT EXISTING WALL, REINSTALL SALVAGED

THERMOSTAT AND ASSOCIATED CONDUIT AND WIRING. PROVIDE NEW CONDUIT AND

21. PROVIDE EXTERIOR KEYPAD/CARD READER AND INTERIOR "PUSH TO EXIT" BUTTON

05 05 05

20. REINSTALLED THERMOSTAT IN ROOM 103 SHALL CONTROL ROOMS 103, 104, AND 105.

WIRING AS REQUIRED FOR COMPLETE INSTALLATION.

22. REINSTALLED THERMOSTAT IN ROOM 129 SHALL CONTROL ROOMS 129 AND 130.

19 19

19 20

19 19 22

OTHER DEVICES. IF PATCHING IS NOT PRACTICABLE DUE TO FORWARD PLACEMENT OF

BOX IN HOLE, COVER HOLE WITH FACEPLATE OF APPROPRIATE SIZE.

CONCEAL ALL ITEMS ASSOCIATED WITH SWITCHES AND "PUSH TO EXIT" BUTTON.

23. CONSTRUCT CHASE (FOR BOXES FOR NEW SWITCHES & "PUSH TO EXIT" BUTTON) OF

12. PRIOR TO PAINTING WALLS, REMOVE EXISTING WALL-MOUNTED ITEMS SUCH AS SIGNS, SOUND

ABSORPTION PADS' BRACKETS, TV MOUNTING BRACKETS, KEY BOX, DEFIBRIATOR BOX, ETC.

12. SEE SHEET FA02 FOR WORK AT EXISTING SMOKE DETECTION SYSTEM UNDER RAISED FLOOR.

13. REPLACE EXISTING RAISED FLOOR PANELS PREVIOUSLY DAMAGED AND/OR WITH HOLES (FOR

GROMMETS, UTILITY BOXES, ETC.) WITH NEW PANELS (TO MATCH EXISTING).

28. PRIOR TO PAINTING WALL, REMOVE EXISTING TV MOUNTING BRACKET. REINSTALL

A C

T

IV

E

IN

A

C T

IV

E

A07

2'-6"

E Q

E Q

24. PROVIDE PHONE STORAGE CABINET; SEE ELEVATION 3, DRAWING SHEET 107.

25. PROVIDE TWO (2) PHONE STORAGE CABINETS; SEE ELEVATION 3, DRAWING SHEET 107.

3'-0"

A09

A09

A09

A09

A09

A09

A09

P C

T C

P T

PCTCPT

14. UNDERCUT DOORS AS REQUIRED TO ACCOMMODATE NEW CONSTRUCTION. 08. PROVIDE INSIDE AND OUTSIDE RUBBER BASE CORNERS.

26. SEE SHEET Co02 FOR PLYWOOD CLADDING AND PAINTING AT NIPR ROOM 139'S WALLS.

27. PROVIDE IN-FILL (5/8" FINISHED FIRE-RATED GYPSUM BOARD ON 3 5/8" STEEL STUDS

AT 16" OC) AT EXISTING PILASTERS AND COLUMNS.

AFTER PAINTING IS COMPLETE.

(CENTERLINE 48" AFF). PROVIDE ASSOCIATED ITEMS FOR COMPLETE INSTALLATION,

07. ALL INTERIOR DOORS AND FRAMES NOT INDICATED TO BE REPLACED AND THUS ARE

TO REMAIN SHALL BE REFINISHED.

5/8" FIRE-RATED GYPSUM BOARD OVER 2 1/2" STEEL STUDS AT 16" OC MAX SPACING.

MECH RM

CIPHER

BOTTOM EDGE OF GYPSUM BOARD SHALL BE 10" ABOVE CONCRETE SLAB. ADAPT

BUTTONS TO EXISTING IDS PANEL AT WEST END OF BUILDING.

SUCH AS CABLING, CONDUITS, & MODULES, TO CONNECT KEYPADS AND "PUSH TO EXIT"

29. PROVIDE TV MOUNTING BRACKET AT HEIGHT INDICATED BY GOVT REPRESENTATIVE.

SEE SHEET A09 FOR LOCATIONS OF OTHER CONTR-FURNISHED, CONTR-INSTALLED

MOUNTING BRACKETS.

30. PROVIDE ELECTRIC 50 GALLON WATER HEATER; REUSE/ADAPT EXISTING SUPPLY PIPING,

SHUT-OFF VALVE, AND ELEC SVC. PROVIDE ASSOCIATED ITEMS SUCH AS GALVANIZED DRAIN PAN, FLOAT SWITCHES, & DRAIN LINE (TO EXISTING FLOOR DRAIN) FOR COMPLETE INSTALLATION.

5"5"5"5"

M

S

S

S

MM

NEW GALVANIZED STEEL DUCT AS REQUIRED TO LIMIT FLEX DUCT DROPS TO 6' MAX LENGTH.

03. EXISTING FIRE SPRINKLER HEADS INSTALLED IN AREAS ENCOMPASSED BY BOLD BLACK LINES

WIRES, TO INSTALL SUPPLY- AND RETURN-AIR GRILLES AT NEW INDICATED LOCATIONS. PROVIDE

EXISTING FIRE SPRINKLER HEAD TO REMAIN AS IS

RELOCATE EXISTING FIRE SPRINKLER HEAD WHERE SHOWN

EXISTING RETURN AIR GRILLE TO REMAIN AS IS

EXISTING SUPPLY AIR GRILLE TO REMAIN AS IS

RELOCATE EXISTING SUPPLY AIR GRILLE WHERE SHOWN

S

RELOCATE EXISTING RETURN AIR GRILLE WHERE SHOWN

02. PAINT EXISTING GYPSUM BOARD (2 COATS) AT CEILING FURRING.

M

S

SCALE: 1/8" = 1'-0"

REFLECTED CEILING PLAN - NEW CONSTRUCTION

B

B

S S

C

C

TO INSTALL EXISTING LIGHT FIXTURES AT NEW INDICATED LOCATIONS. RELAMP THESE

SHALL BE RELOCATED AS INDICATED TO ACCOMMODATE CEILING RECONFIGURATION OR

FOR NEW CEILING RECONFIGURATION IN AREAS ENCOMPASSED BY BOLD BLACK LINES.

02. EXISTING LIGHT FIXTURES INSTALLED IN AREAS ENCOMPASSED BY BOLD BLACK LINES

INDICATED LOCATIONS. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH NFPA 13.

PROVIDE NEW RETURN AIR GRILLE WHERE SHOWN

PARTITIONS. PROVIDE ADDITIONAL ITEMS, SUCH AS DUCT, WRAP INSULATION, AND HANGER

EMCOMPASSED BY BOLD BLACK LINES FOR EVEN DISTRIBUTION THROUGHOUT ROOM.

GENERAL NOTES

ADDITIONAL ITEMS, SUCH AS PIPING AND JOINTS, AS REQUIRED TO INSTALL HEADS AT NEW

REMOVAL OF EXISTING PARTITIONS OR IMPOSITION OF NEW PARTITIONS. PROVIDE

REMOVAL OF EXISTING PARTITIONS OR IMPOSITION OF NEW PARTITIONS. PROVIDE

SHALL BE RELOCATED AS INDICATED TO ACCOMMODATE CEILING RECONFIGURATION OR

CEILING RECONFIGURATION OR REMOVAL OF EXISTING PARTITIONS OR IMPOSITION OF NEW

ADDITIONAL ITEMS, SUCH AS WHIPS, CONDUIT, WIRING, AND JUNCTION BOXES, AS REQUIRED

06. REBALANCE AIR SUPPLY VOLUME AT EACH EXISTING SUPPLY AIR GRILLE IN EACH ROOM IN AREAS

APPURTENANCES LEGEND

ENCOMPASSED BY BOLD BLACK LINES SHALL BE RELOCATED AS INDICATED TO ACCOMMODATE

04. EXISTING SUPPLY- AND RETURN-AIR GRILLES AND ASSOCIATED BOOTS INDICATED IN AREAS

07. EXISTING APPURTENANCES IN AREAS NOT ENCOMPASSED BY BOLD BLACK LINES SHALL REMAIN AS

01. PROVIDE NEW CEILING SUSPENSION GRID AND ACOUSTICAL PANELS (TO MATCH EXISTING)

IS UNLESS OTHERWISE INDICATED BY SYMBOLOGY IN APPURTENANCES LEGEND TO BE RELOCATED;

S 3(A)

A

(A

A A

A

B

B

B

B 3(C)

B

S

3(C)

C C

C

EXISTING LIGHT TROFFER TO REMAIN AS IS

RELOCATE EXISTING LIGHT TROFFER WHERE SHOWN

D

EXISTING STRIP LIGHT FIXTURE TO REMAIN AS IS

RELOCATE EXISTING STRIP LIGHT FIXTURE WHERE SHOWN

05. EXISTING FLEX DUCT DROPS EXCEEDING 6' MAXIMUM LENGTH SHALL REMAIN AND BE REUSED IN RELOCATION OF EXISTING SUPPLY AIR GRILLES. DO NOT INSTALL ADDITIONAL FLEX DUCT TO

S

DESIGNATED "X"

PROVIDE NEW SINGLE-POLE SWITCH TO CONTROL LIGHT

S

D

PROVIDE NEW 3-WAY SWITCH TO CONTROL LIGHT FIXTURES

EXISTING FLEX DUCT EXCEEDING 6' LENGTH. RELOCATE EXISTING FLEX DUCT TO MAINTAIN ITS

(G)

E

CIRCULAR CROSS-SECTIONAL PROFILE ALONG ITS ENTIRE LENGTH.

F

H

I

KEYNOTES

01. PROVIDE SWITCHBANK OF FOUR (4) SINGLE-POLE SWITCHES (ONE PER ROW OF LIGHT FIXTURES).

(J)

J J

I

L

J

J

M

J

M (L)

(N)4

S

N1

M

N3

(N)1

(N)2 N3

N1

N4 N4 N4

O2

O2

O2

O1O1

O2

A

S D(B)

A

A

C

B

B

S

D

3(D)

D

3(D)

08. RECONFIGURE SWITCHING ARRANGEMENT IN EACH ROOM AFFECTED BY REMOVAL OF EXISTING

D D

EXISTING EXHAUST FAN TO REMAIN AS IS

S (E) (F) S

E G

F G

S 3(X)

S

S

SINGLE-POLE SWITCH (TO ACTUATE EXISTING PORCH LIGHT FIXTURE). PROVIDE ASSOCIATED

D(X)

09. PROVIDE NEW SWITCHES, BOXES, CONDUITS, AND WIRING AS SHOWN AND AS REQUIRED FOR

(X)

PROVIDE NEW DIMMER SWITCH TO CONTROL LIGHT FIXTURES

DESIGNATED "X"

10. PROVIDE NEW RETURN AIR GRILLES WITH ALL ASSOCIATED ACCESSORIES, SUCH AS BOOTS, DUCTS, FIXTURES DESIGNATED "X"

X

"X" DESIGNATES CONTROLLING SWITCH

RELOCATE EXISTING RECESSED CAN LIGHT FIXTURE WHERE SHOWN;

X

OR BY KEYNOTE.

S 3(H)

S

H

3(H)

H

COMPLETE SWITCHING INSTALLATION.

INSULATION, AND MOUNTING FLANGES, AS REQUIRED FOR COMPLETE INSTALLATION.

H

S (I)

04. PATCH, REPAIR, RETEXTURE, AND REPAINT EXISTING GYPSUM BOARD BOTH SIDES AT EXISTING

J

S J

JJ

J

S

S

K

(K)

M

S (M)

M

(N)3

S S

S

N1 N1 N1

N2 N2

N3

N2 N2 N2

N3

N4

N3

N4 O2

S (O)2

O1

O2

O1 O1

O1

PARTITIONS AND/OR BY CONSTRUCTION OF NEW PARTITIONS.

RELOCATE EXISTING EXHAUST FAN WHERE SHOWN

S

"X" DESIGNATES CONTROLLING SWITCH

PARTITION WHERE PDS REMOVED.

03. PROVIDE NEW 3-WAY SWITCH (TO ACTUATE LIGHTTROFFERS IN VESTIBULE 107) AND NEW

CONDUITS, WIRING, J-BOX, SWITCH BOX, AND FACEPLATE.

S

EXISTING EMERGENCY LIGHT SHALL REMAIN WHERE SHOWN

RELOCATE EXISTING EMERGENCY LIGHT WHERE SHOWN

S

05 3

3 S

S

(S)

S

S

S

S (O)1

T Q

S (Q) S (R)

R R R

S (T)

T

(U) S

U U

SUPPLY AIR DUCTS SHALL ORIGINATE FROM COMMON VAV BOX. ALL RETURN AIR FROM SAME ROOM

11. ALL AIR VOLUMES DELIVERED TO PARTICULAR ROOM VIA EXISTING AND NEW TRUNK AND BRANCH

SHALL BE REMITTED VIA EXISTING AND NEW RETURN AIR DUCTS TO EXISTING AIR HANDLING UNIT

SERVING ABOVE-MENTIONED VAV BOX.

FIXTURES; AND 50w LED LAMPS FOR RECESSED CAN LIGHT FIXTURES.

FIXTURES: ENERGY SAVER 34w FLUORESCENT TUBES FOR LIGHT TROFFERS AND STRIP LIGHT

05. PROVIDE TWO (2) - NEW 3-WAY SWITCHES (TO ACTUATE EXISTING LIGHT TROFFERS AND EXHAUST FAN, RESPECTIVELY) IN EXISTING BOX IN LAVATORY AND TOILET ROOMS. REWIRE SWITCH LEGS FOR

3-WAY SWITCHING. PROVIDE ASSOCIATED ACCESSORIES FOR COMPLETE INSTALLATION.

06. PROVIDE TWO (2) - NEW 3-WAY SWITCHES AND ASSOCIATED BOX, CONDUIT, WIRING, & FACEPLATE

TOILET ROOMS. PROVIDE ASSOCIATED ACCESSORIES FOR COMPLETE INSTALLATION.

(TO ACTUATE EXISTING LIGHT TROFFERS AND EXHAUST FAN, RESPECTIVELY) IN LAVATORY AND

S 3

S 3

S

S

07. PROVIDE SUSPENDED MOUNTING BRACKET (& ASSOCIATED POLE, UNISTRUTS, FASTENERS, & COMM

OF MOUNTING BRACKET IS APPROXIMATE; A/V SUBCONTR SHALL DETERMINE EXACT LOCATION OF & ELECTRICAL SERVICES) FOR GOVT-FURNISHED, GOVT-INSTALLED PROJECTOR. SHOWN LOCATION

MOUNTING BRACKET. POLE'S PENETRATION OF ACOUST CLG PANEL SHALL BE CUT/FINISHED NEATLY.

07 07

REINSTALL EXISTING MNS/"BIG VOICE" LIGHT STROBE

(REPLACE GREEN LENS WITH AMBER LENS)

08. PROVIDE MOTORIZED PULL DOWN PROJECTION SCREEN; SEE SHEET A09, INTERIOR ELEVATIONS, FOR SPECIFICATIONS. FLUSH MOUNT CASE TO LAY-IN CEILING.

PROVIDE NEW LIGHT TROFFER (TO MATCH EXISTING) WITH

EMERGENCY BALLAST

09. EXISTING RECESSED CAN LIGHT FIXTURE SHALL REMAIN.

M

M

M EXISTING MASS NOTIFICATION SYSTEM SPEAKER TO REMAIN AS IS;

ADHERE "ALERT" LABEL TO BEZEL OF SPEAKER

FINISH SCHEDULE

BASEROOM TITLEMARK

ROOM

FLOOR NORTH SOUTH EAST WEST

WALLS

CEILING HT

CLG

REMARKS

RBCONFERENCE ROOM101 CPT EXGB/ GB/ EXGB/ EXGB/ LIC 8'-0"

PT&P TBT&P PT&P PT&P

RB102 CPT GB/ GB/ EXGB/ EXGB/ LIC 8'-0"

TBT&P TBT&P PT&P PT&P

COMMANDER

RBDEPUTY103 CPT GB/ GB/ EXGB/ GB/ LIC 8'0"

TBT&P TBT&P PT&P TBT&PCOMMANDER

RBEXECUTIVE 104 CPT GB/ GB/ EXGB/ GB/ LIC 8'-0"

TBT&P TBT&P PT&P TBT&PDIRECTOR

RBEXECUTIVE 105 CPT GB/ EXGB/ EXGB/ GB/ LIC 8'-0"

TBT&P PT&P PT&P TBT&POFFICER

RBSECRETARY/106 CPT GB/ GB/ EXGB/ LIC 8'-0"

TBT&P TBT&P PT&P

RBVESTIBULE 107 PCT EXGB/PT&P EXGB/ LIC 8'-0"

& GB/TBT&P PT&P

EXGB/

PT&P

EXGB/

PT&P

EXCBTMEN'S LAVATORY 108 EXCFT EXLIC

EXGB/

PT&P

EXCWT &

EXGB/

PT&P

EXCWT &

EXGB/

PT&P

EXCWT &

EXGB/

PT&P

EXCWT &

EXCBTMEN'S TOILET 109 EXCFT EXLIC

EXGB/

PT&P

EXCWT &

EXGB/

PT&P

EXCWT &

EXGB/

PT&P

EXCWT &

EXGB/

PT&P

EXCWT &

RBVESTIBULE 110 VCT EXGB/ LIC 8'-0"

PT&P

GB/TBT&P

EXGB/PT&P

EXGB/

PT&P

GB/TBT&P

EXGB/PT&P

EXCBTWOMEN'S LAVATORY 111 EXCFT EXLIC

EXGB/

PT&P

EXCWT &

EXGB/

PT&P

EXCWT &

EXGB/

PT&P

EXCWT &

EXGB/

PT&P

EXCWT &

EXCBTWOMEN'S TOILET 112 EXCFT EXLIC

EXGB/

PT&P

EXCWT &

EXGB/

PT&P

EXCWT &

EXGB/

PT&P

EXCWT &

EXGB/

PT&P

EXCWT &

RB JANITOR'S CLOSET113 EXVCT EXGB/ LIC 8'-0"

PT&P

GB/

TBT&P

EXGB/

PT&P

EXGB/

PT&P

RB &VESTIBULE114 VCT EXGB/ LIC 8'-0"

PT&PEXRB

GB/

TBT&P

EXGB/

PT&P

EXGB/

PT&P

RB BREAK ROOM115 VCT

GB/TBTP

LIC 8'-0"

EXGB/PT&P

EXGB/

PT&P

EXGB/

PT&P

3EXGB/

PT&P

MEETING ROOM116 EXRF EXLICEXGB/ EXGB/

PT&P

GB/TBT&P

EXGB/PT&P

SIPR CAFE117 LICRB VCT EXGB/PT&P &

GB/TBT&P

EXGB &

PT&P

GB/TBT&P

& EXGB/PT&P

CORRIDOR118 EXLICEXGB/

PT&P

RB VCT EXGB/

PT&P

EXGB/

PT&P

EXGB/

PT&P

CLASSROOM 1119 EXLIC & LICGB/

TBT&P

EXGB/

PT&P

EXRF EXGB/

PT&P

GB/

TBT&P

LOBBY120 EXLIC & LICGB/

TBT&P

EXGB/

PT&P

EXRF GB/

PBT&P

AUDITORIUM121 EXLIC & LIC GB/

TBT&P

EXGB/

PT&P

EXRF EXGB/

PT&P

GB/

TBT&P

CLASSROOM 2122 EXLIC & LICEXGB/

PT&P

EXRF EXGB/

PT&P

GB/

TBT&P

GB/

TBT&P

4, 6

4, 6

4, 6

HERITAGE ROOM123 EXLICEXGB/

PT&P

EXRF GB/TBT&P &

EXGB/PT&P

EXGB/

PT&P

COMM ROOM125 EXLIC EXRF 5

VESTIBULE126 EXLIC EXGB/

PT&P

EXRF EXGB/

PT&P

EXGB/

PT&P

VESTIBULE124 EXLIC EXGB/

PT&P

EXVCT EXGB/

PT&P

EXRB

& EXRF

EXGB/

PT&P

STORAGE 1127 EXLIC EXGB/

PT&P

EXGB/

PT&P

EXRF EXCMU

MECH ROOM128 EXLIC EXRF 5

RESOURCE ADVISOR129 LIC 7'-9"CPTRB EXGB/

PT&P

EXGB/

PT&P

EXGB/

PT&P

GB/

TBT&P

CHIEF130 LIC 7'-9"CPTRB EXGB/

PT&P

GB/

TBT&P

GB/

TBT&P

EXGB/

PT&P

DIVISION CHIEF 1131 LIC 7'-6"CPTRB

GB/TBT&P

GB/

TBT&P

GB/

TBT&P

GB/

TBT&P

DIVISION CHIEF 2132 LIC 7'-6"CPTRB GB/

TBT&P

GB/

TBT&P

GB/

TBT&P

DIVISION CHIEF 3133 LIC 7'-9"CPTRB EXGB/

PT&P

GB/

TBT&P

GB/

TBT&P

COMMON ROOM134 EXLICCPTRB EXGB/

PT&P

EXGB/

PT&P

EXGB/

PT&P

EXGB/

PT&P

VESTIBULE135 EXLICEXVCTEXRB EXGB/

PT&P

EXGB/

PT&P

EXGB/

PT&P

ADMIN STAFF 1136 EXLICEXVCTRB & EXGB/

PT&P

EXGB/PT&P EXGB/

PT&P& EXRF

EXGB/

PT&P

CORRIDOR137 EXLICEXRF EXGB/

PT&P

EXGB/

PT&P

EXGB/

PT&P

ADMIN STAFF 2138 EXLICEXGB/PT&P EXGB/

PT&P

EXRF EXGB/PT&P

& GB/TBT&P

LEGEND

BASE FLOOR

RB 4" COVE RUBBER BASE (TO MATCH EXISTING)

EXCBT EXISTING CERAMIC BASE TILE TO REMAIN, UNLESS

OTHERWISE INDICATED BY KEYNOTE OR NOTE IN

OPENING SCHEDULE TO BE REMOVED

EXRB EXISTING RUBBER BASE TO REMAIN

CPT 2'x2' CARPET TILE (PATTERN SELECTION BY USER)

EXVCT EXISTING VINYL COMPOSITION TILE TO REMAIN,

UNLESS OTHERWISE INDICATED BY KEYNOTE OR

NOTE IN DOOR SCHEDULE TO BE REMOVED

PCT 8"x8" PORCELAIN CERAMIC TILE (TILE & GROUT COLOR

SELECTION FROM STANDARD PALETTE BY USER);

VCT 12" x 12" VINYL COMPOSITION TILE (COLOR

SELECTION BY USER)

WALLS

GB 5/8" FIRE-RATED GYPSUM BOARD - EXTEND ABOVE CEILING AS INDICATED IN PARTITION LEGEND

EXGB EXISTING, PREVIOUSLY PAINTED GYPSUM BOARD TO REMAIN

PT&P PATCH HOLES AND OPENINGS WITH 5/8" FIRE-RATED GYPSUM BOARD; TEXTURE IMMEDIATE AREA AT EACH PATCH TO BLEND/FEATHER INTO EXISTING TEXTURE. APPLY ONE COAT OF PRIMER AT PATCHED AREAS AND TWO FINISH COATS OVER ENTIRETY OF EXPOSED WALL SURFACES; JOINTS OF GYPSUM BOARD ABOVE CEILINGS SHALL BE TAPED.

TBT&P TAPE, BED, TEXTURE, AND PAINT (3 COAT SYSTEM) ENTIRETY OF EXPOSED GYPSUM SURFACES; JOINTS OF GYPSUM BOARD

ABOVE CEILINGS SHALL BE TAPED.

CEILINGS

LIC LAY-IN CEILING OF 2' x 2' ACOUSTICAL PANELS IN PREFINISHED METAL SUSPENSION GRID (TO MATCH EXISTING)

EXLIC EXISTING LAY-IN CEILING ASSEMBLY TO REMAIN

REMARKS

1. ONE 2" x 2" CERAMIC FLOOR TILE IS MISSING. PROVIDE NEW TILE (TO MATCH EXISTING). GROUT TO MATCH EXISTING.

2. PROVIDE NEW 4" COVE RUBBER BASE (TO MATCH EXISTING) AT EAST WALL; AND AT NORTH AND SOUTH WALLS (FROM CORNER

3. EXISTING RUBBER BASE AT EXISTING, PREVIOUSLY PAINTED GYPSUM BOARD SHALL REMAIN. PROVIDE NEW RUBBER BASE (TO

MATCH EXISTING) AT NEW GYPSUM BOARD PARITIONS.

4. USE TO GREATEST POSSIBLE EXTENT EXISTING CEILING ASSEMBLY. AUGMENT WITH NEW CEILING COMPONENTS AT AREAS WHERE EXISTING SLOPED CEILING ASSEMBLIES ARE SHOWN TO BE REMOVED; NEW CEILING COMPONENTS (TO MATCH EXISTING)

SHALL BE PROVIDED.

5. NO WORK IN THIS ROOM - EXISTING FINISHES SHALL REMAIN (UNLESS OTHERWISE NOTED).

6. EXISTING, PREVIOUSLY PAINTED GYPSUM BOARD CLADDING AT COLUMNS SHALL REMAIN. PATCH HOLES AND OPENINGS WITH

APPLY ONE COAT OF PRIMER AT PATCHED AREAS AND TWO FINISH COATS OF OVER ENTIRETY OF EXPOSED WALL SURFACES;

JOINTS OF GYPSUM BOARD ABOVE CEILINGS SHALL BE TAPED.

5/8" FIRE-RATED GYPSUM BOARD; TEXTURE IMMEDIATE AREA AT EACH PATCH TO BLEND/FEATHER INTO EXISTING TEXTURE.

2, 6

NIPR ROOM139 EXLIC EXRF GB/TBT&P

EXGB/

PT&P

EXGB/PT&P

& GB/TBT&P

6, 7GB/TBT&P

WAITING

GB/

TBT&P

PT&P

EXCMU EXISTING, PREVIOUSLY PAINTED CMU - REPAINT (2 COATS)

EXPL EXISTING, PREVIOUSLY PAINTED PLASTER - REPAINT (2 COATS)

EXRF EXISTING RAISED FLOOR TO REMAIN, WITH

SECURE ROOM125A EXLIC EXRF 5

GB/

TBT&P

7. PROVIDE 3/4" INTERIOR PLYWOOD (GRADE BC - WITH B SIDE EXPOSED) BACKBOARD COVERING ALL GYPSUM BOARD WALLS FROM

RETARDANT PAINT.

2'-0" AFF TO CEILING; BOTTOM EDGE OF PLYWOOD SHALL BE 2'-0" AFF. PAINT PLYWOOD BACKBOARD WITH 2 COATS OF WHITE FIRE-

STORAGE 2140 EXLIC EXRF EXGB/PT&P EXGB/PT&P EXGB/PT&P EXGB/PT&P

GB/TBT&P

GB/TBT&P

EXRBEXRB

DALTILE SIERRA RAINIER-ABRASIVE OR

APPROVED EQUAL

ADAPTATION TO NEW LAYOUT

TO FOOT OF EACH RAMP).

9'-0"

DOOR TYPES

FRAME TYPES

D-1 D-2

DR WIDTH

F-1

2"

DR WIDTH

2"

D O

O R

H E

IG

H

T D

O O

R H

E

IG

H T

DR WIDTH

D O

O R

H E

IG

H

T

6" 6"

SIGN SCHEDULE

MARK ON SHEET A03

OPENING SCHEDULE

DOOR FRAME

GLAZ.

HDWE

LABEL REMARKSMATL WIDTH HT. THICK TYPE MAT. TYPE

1 SCWD 3'-0" 7'-0" 1 3 4" D-1 HM F-1 4

2 SCWD 3'-0" 7'-0" 1 3 4" D-1 HM F-1 2

3 SCWD 3'-0" 7'-0" 1 3 4" D-1 HM F-1 1

4 SCWD 3'-0" 7'-0" 1 3 4" D-1 HM F-1 2

5 SCWD 3'-0" 7'-0" 1 3 4" D-3 HM F-1 2

6 SCWD 3'-0" 7'-0" 1 3 4" D-3 HM F-1 2

7 SCWD 3'-0" 7'-0" 1 3 4" D-1 HM F-1 3

8 SCWD 3'-0" 7'-0" 1 3 4" D-1 HM F-1 3

9 SCWD 3'-0" 7'-0" 1 3 4" D-1 HM F-1 3

10 SCWD 3'-0" 7'-0" 1 3 4" D-1 HM F-1 3

11 SCWD 3'-0" 7'-0" 1 3 4" D-1 HM F-1 4

12 SCWD 3'-0" 7'-0" 1 3 4" D-2 HM F-1 5

13 SCWD (2) 3'-0" 7'-0" 1 3 4" D-2 HM F-2 6

14 SCWD 3'-0" 7'-0" 1 3 4" D-2 HM F-1 5

16 SCWD 3'-0" 7'-0" 1 3 4" D-1 HM F-1 4

17 SCWD 3'-0" 7'-0" 1 3 4" D-3 HM F-1 2

18 SCWD 3'-0" 7'-0" 1 3 4" D-3 HM F-1 2

19 SCWD 3'-0" 7'-0" 1 3 4" D-3 HM F-1 2

20 SCWD 3'-0" 7'-0" 1 3 4" D-3 HM F-1 2

21 SCWD 3'-0" 7'-0" 1 3 4" D-3 HM F-1 2

22 _

23 SCWD 3'-0" 7'-0" 1 3 4" D-1 HM F-1 2

24 SCWD (2) 3'-0" 7'-0" 1 3 4" D-2 HM F-2 7

25 -

26 HM (2) VARIES 7'-0" 1 3 4" D-1 EXHM F-2 8

2" DOOR WIDTH 2"

D O

O R

H E

IG

H

T

F-2

HARDWARE SETS

SET NO. 1: DOOR MARK 3:

1-1/2 PR BALL-BEARING HINGES

1 EA CLOSER

3 EA SILENCERS

1 EA QUARTER-DOME FLOOR STOP

1 EA CYLINDER LOCK (OFFICE FUNCTION)

1 EA CORE

SET NO. 2: DOOR MKS 2, 4, 5, 6, 11, 16, 17, 18, 19, 20, 21, AND 27:

1-1/2 PR BALL-BEARING HINGES

3 EA SILENCERS

1 EA QUARTER-DOME FLOOR STOP

1 EA CYLINDER LOCK (OFFICE FUNCTION)

1 EA CORE

SET NO. 3: DOOR MARKS 7, 8, 9, & 10:

1-1/2 PR BALL-BEARING HINGES

3 EA SILENCERS

1 EA QUARTER-DOME FLOOR STOP

1 SET PUSH PLATE/PULL HANDLE

1 EA CLOSER

SET NO. 4: DOOR MARKS 1 AND 27:

SET NO. 5: DOOR MARKS 12 AND 14:

1-1/2 PR BALL-BEARING HINGES

1 EA CLOSER

3 EA SILENCERS

1 EA QUARTER-DOME FLOOR STOP

1 EA PASSAGE LATCH

1 EA CORE

1 EA KICKPLATE

SET NO. 6: DOOR PAIR MARK 13:

3 PRS BALL-BEARING HINGES

2 EA CLOSERS

2 EA SILENCERS

2 EA QUARTER-DOME FLOOR STOPS

2 EA EXIT DEVICES WITH SURFACE-MOUNTED

2 EA KICKPLATES

VERTICAL RODS LESS BOTTOM RODS W/

TRIM (PLATE, LEVER, AND PUSHBUTTON

CIPHER LOCK ON LEAF INDICATED)

SET NO. 7: DOOR PAIR MARK 24:

3 PRS BALL-BEARING HINGES

2 EA CLOSERS

2 EA SILENCERS

2 EA QUARTER-DOME FLOOR STOPS

2 EA EXIT DEVICES WITH SURFACE-MOUNTED

2 EA KICKPLATES

VERTICAL RODS WITH TRIM (PLATE, LEVER,

AND PASSAGE LATCH FUNCTION)

SET NO. 8: DOOR MARK 26:

3 PRS BALL-BEARING HINGES

1 EA CLOSER (AT ACTIVE LEAF)

2 EA SILENCERS

1 EA KICKDOWN FLOOR STOP (AT INACTIVE LEAF)

1 EA EXIT DEVICE WITH SURFACE-MOUNTED VERTICAL

2 EA IDS DOOR SENSORS (WIRED TO CARD READER/

KEYPAD AND PUSH-TO-EXIT BUTTON)

2 EA KICKPLATES

ROD WITH TRIM (PLATE, LEVER, AND PASSAGE

LATCH FUNCTION) AT ACTIVE LEAF

1 SET WEATHERSTRIPPING

1 EA THRESHOLD

1 SET BRUSH ASTRAGALS

2 EA DOOR SWEEPS

SETMARK

HM

27 SCWD 3'-0" 7'-0" 1 3 4" D-1 HM F-1 4

F-1

SIGN

TYPE

SIGN ROOM NO.

NO. ON SIGN

TACTILE ROOM

REMARKSTACTILE LETTERING

PRIVATE

3/4" TACTILE LETTERS

W/ BRAILLE CHARACTERS

BELOW

FOR PRINTED PAPER

INSERTS

Name

Title

SIGN TYPE A

SIGN TYPE B

SIGN TYPE C

8"

8"

8"

8"

SIGN TYPE D

1 1/2" TACTILE ROOM NUMBERS

W/ BRAILLE CHARACTERS

BELOW

Name

Title

B 106 [NO NUMBER]

C 105 101

C 104 102

C 103 103

C 102 104

A 102 [NO NUMBER] "PRIVATE"

C 101 105

B 134 [NO NUMBER]

C 133 106

C 132 107

C 131 108

C 130 109

C 129 110

C 140 122

D 108 [NO NUMBER]

D 111 [NO NUMBER]

C 139 111

D 110 [NO NUMBER]

D 114 [NO NUMBER]

C 113 114

C 117 112

C 118 113

C 119 115

C 121 116

C 122 117

C 125A 118

C 125 119

C 125 119 C 127 120

E 136

REMARKS

1. SIGN SHALL BE ACRYLIC PLASTIC WITH GRAY BACKGROUND AND WHITE LETTERS, NUMBERS, AND/OR ARROWS (AS APPLICABLE).

LETTERS AND NUMBERS SHALL BE HELVETICA NEUE 55 ROMAN.

2. PAPER INSERTS BY GOVERNMENT.

3. SIGN SHALL BE SAME AS SIGN MARKS 15 AND 18, EXCEPT FOR SYMBOLOGY FOR WOMEN'S RESTROOM.

SEE SHEET A03 FOR LOCATIONS OF SIGNS:

INDICATED BY SOLID TRIANGLE SYMBOL

1, 2

1, 2

1, 2

1, 2 1, 2

1, 2

1, 2

1, 2

1, 2

1, 2 1, 2

1, 2 1, 2

1, 3

1, 2

1, 3 1, 2

1, 2

1, 2

1, 2 1, 2

1, 2 1, 2

1, 2

1, 2

1, 2

1/4" TEMPERED GLASS

(CLEAR TINT) IN

PAINTED METAL FRAME

REMARKS

1. ACTIVE LEAF SHALL BE 3'-0" WIDE; INACTIVE LEAF SHALL BE 2'-0" WIDE.

1, 4, 5, 6

2. STAIN NEW WOOD DOOR TO MATCH EXISTING; APPLY ONE (1) COAT SEALER AND TWO (2) COATS OF POLYURETANE (SHEEN TO MATCH EXISTING).

3. PAINT NEW HOLLOW METAL FRAME (3 COAT SYSTEM); COLOR TO MATCH EXISTING.

4. LEAVE EXISTING HOLLOW METAL FRAME IN PLACE; FILL HOLES AND VOIDS WITH BODY FILLER (3M BONDO OR APPROVED EQUAL). CLEAN AND SAND TO PREPARE FRAME FOR REPAINTING. TOUCH UP AND USE 2-COAT PAINT SYSTEM TO REPAINT; ENSURE COMPLETE HIDING.

5. PAINT NEW HOLLOW METAL DOOR (3 COAT SYSTEM); COLOR TO MATCH EXISTING.

6. NEW HOLLOW METAL DOOR SHALL BE INSULATED.

7. VENEER SHALL MATCH EXISTING.

2, 3, 7

EXHM 4, 8

2, 3, 7

2, 3, 7

2, 3, 7

2, 3, 7

2, 3, 7

2, 3, 7, 10

2, 3, 7

2, 3, 7, 10

2, 3, 7 2, 3, 7

2, 3, 7 2, 3, 7, 9

2, 3, 7

2, 3, 7

2, 3, 7

2, 3, 7

2, 3, 7

2, 3, 7 2, 3, 7

2, 3, 7 2, 3, 7

2, 3, 7

3, 8

(HARDWARE SHALL BE GRADE 1 AND MATCH EXISTING FINISH):

CLEAR ACRYLIC SLOTS

FOR PRINTED PAPER

INSERTS

CLEAR ACRYLIC SLOTS

SIGN TYPE E

1'-8"

Room Name

Room Name

Room Name

Room Name

Room Name

Room Name

Room Name

Room Name

Room Name

Room Name

D-3

DR WIDTH

2'-0" 6"

D O

O R

H E

IG

H

T

6"

[NO NUMBER] 1, 4

4. DIRECTIONAL SIGN IS SHOWN WITH MAXIMUM OF 10 - 3" 'GLUE-ON' MESSAGE PANELS. EACH MESSAGE PANEL SHALL CONTAIN 1 1/2" TACTILE ARROW; AND ROOM NAME IN 1" TACTILE TEXT. TEXT FOR EACH MESSAGE PANEL SHALL BE ANNOTATED BY

GOVERNMENT IN APPROVED SHOP DRAWINGS.

8. FILL HINGE AND STRIKEPLATE MORTISES WITH METAL, PAINT-GRIP BLANK PLATES.

1 EA KICKPLATE

1 SET BRUSH ASTRAGALS

KEYING SCHEDULE: CONTRACTOR SHALL PROVIDE KEYED CORES AS FOLLOWS:

1. MASTER KEY SHALL OPERATE ALL INTERIOR KEYED LOCKS, EXCEPT THOSE KEYED TO BASE COMMUNICATIONS KEY.

2. LOCKS FOR DOOR MARKS 2 AND 4 SHALL BE KEYED ALIKE.

3. LOCKS FOR DOOR MARKS 5. 6, 11, 17, 18, 20, 21, AND 23 SHALL BE KEYED SEPARATELY.

4. DOOR LOCKS FOR SECURE ROOM 125A AND EXTERIOR DOORS, UNLESS OTHERWISE INDICATED, SHALL REMAIN AS IS.

5. LOCK FOR EXISTING DOOR LOCK AT 'STORAGE ROOM 2' 140 SHALL BE KEYED SEPARATELY.

6. LOCK FOR DOOR MARK 16 SHALL BE KEYED TO BASE COMMUNICATIONS KEY.

3 PRS BALL-BEARING HINGES

1 EA CLOSER

3 EA SILENCERS

1 EA QUARTER-DOME FLOOR STOP

1 EA KICKPLATE

1 EA PUSHBUTTON CIPHER LOCK

MINIBLINDS (COLOR

(SELECTION BY USER)

W/ RETENTION RAIL

9. PROVIDE PUSHBUTTON CIPHER LOCK ON LEAF INDICATED WITH STRIKEPLATE ON OTHER LEAF.

1 EA COORDINATOR

10. PROVIDE NEW CERAMIC WALL TILE TO MATCH EXISTING 5' HIGH TILE WAINSCOT AT NEW DOOR FRAMES.

1 EA QUARTER-DOME FLOOR STOP

31 F 118 [NO NUMBER] 1, 5

RESTROOMS

1/2" TACTILE LETTERS

W/ BRAILLE CHARACTERS

BELOW

SIGN TYPE F

8"

"RESTROOMS"

5. CONSULT GOVT REPRESENTATIVE IN PLACEMENT OF SIGN MARK 31 IN RELATION TO SIGN MARK 22.

3'-0"

2'-0 3/4"

1'-0"

2"

CL-CL BULKHEADS

ELEVATION

SECTION

BREAK AREA CABINETRY SCALE: 1/2" = 1'-0" SCALE: 1/2" = 1'-0"

1 2

NOTES:

1. APPLY STAIN AT EXPOSED WOOD SURFACES TO MATCH EXISTING DOOR VENEER; THESE SURFACES SHALL RECEIVE

2. REMOVE EXISTING GYPSUM BOARD AT CHASE TO ACCESS AND CONNECT NEW DRAIN PIPE AT SINK TO EXISTING

3. CONNECT CW AND HW PIPING AT SINK TO NEARBY EXISTING CW AND HW PIPING. CONCEAL PIPING ABOVE CEILING

9'-3"

3'-2 1/2" 2'-10" 3'-2 1/2"

KEYNOTES: BREAK ROOM CABINETRY: INDICATED BY :

X

DRAIN LINE. PATCH, REPAIR, & PAINT GYPSUM BOARD AFTER PIPING CONNECTION IS MADE.

1. PROVIDE SINK (KRAUS KBU29 32" UNDERMOUNT 50/50 DOUBLE BOWL 18 GA STAINLESS STEEL OR

APPROVED EQUAL). PROVIDE ALL FITTINGS & PIPING REQUIRED FOR COMPLETE INSTALLATION, INCLUDING:

ONE FAUCET (KRAUS KPF-2250 SINGLE LEVER PULL-OUT KITCHEN FAUCET STAINLESS STEEL OR

APPROVED EQUAL);

TWO STRAINERS WITH BASKETS (MOEN 22036 3-1/2" COMPOSITE DRAIN ASSEMBLY STAINLESS STEEL

OR APPROVED EQUAL);

ONE P-TRAP;

TWO STOP VALVES;

TWO WATER SUPPLY PIPING.

2. CONSTRUCT UPPER CABINET OF SAME MATERIALS AS BASE CABINET.

3. PROVIDE 3/4" PLYWOOD BULKHEADS, SIDES, AND BOTTOM.

4. PROVIDE SOLID SURFACING (CORIAN OR APPROVED EQUAL) COUNTERTOP WITH INTEGRAL EDGE AND

BACK & SIDE SPLASHES. COLOR FROM MANUFACTURER'S STANDARD PALETTE SHALL BE SELECTED BY USER.

5. PROVIDE DRAWER WITH 1x SOLID WOOD FRONT, 1/4" PLYWOOD BOTTOM, 1/2" PLYWOOD SIDES

AND BACK, DUAL GUIDES, AND PULL (SIRO DESIGNS 3-3/4" CENTER-TO-CENTER FINE-BRUSHED STAINLESS

STEEL RECTANGULAR OR APPROVED EQUAL).

6. PROVIDE 1x SOLID WOOD STILES (HORIZONTAL AND VERTICAL); 2" WIDE UNLESS OTHERWISE INDICATED.

7. PROVIDE ADJUSTABLE MIDDLE SHELVES; 3/4" PLYWOOD WITH 3/4" x 1" SOLID WOOD EDGE.

8. PROVIDE RAISED PANEL, FLUSH-MOUNTED SOLID WOOD DOORS WITH PULLS AND CONCEALED HINGES.

9. PROVIDE TOE SPACE WITH 1/4" PLYWOOD VENEER FRONT.

10. PROVIDE 1x WOOD CLEATS.

11. PROVIDE 1/4" PLYWOOD BACKING.

ONE (1) COAT SEALER AND THREE (3) COATS POLYURETHANE.

AND/OR WITHIN WALL.

ELEVATION

PHONE STORAGE CABINET SC: 3/4" =1'-0"

SECTION

PHONE STORAGE CABINET SC: 3/4" =1'-0"

3'-9"

1/4" 5" 1/2"

KEYNOTES: PHONE STORAGE CABINET: INDICATED BY :

X

1. CONSTRUCT PERIMETER FRAME (TOP, BOTTOM, & SIDES) OF 3/4" INTERIOR

PLYWOOD (VENEER TO MATCH DOORS).

2. PROVIDE 1/2" DEEP x 3/4" WIDE HARDWOOD FACING ALL AROUND FRONT

EDGES OF PERIMETER FRAME.

3. SURFACE MOUNT CABINET TO EXISTING (OR NEW) STL STUD/GYP BOARD

PARTITION WITH PANHEAD SCREWS (PAINT SCREW HEADS TO MATH STAIN).

4. BACKING AND CUBBY-HOLE DIVIDERS SHALL BE 1/4" INTERIOR PLYWOOD

VENEER TO MATCH DOORS).

5. FINISH FLOOR (EXISTING RAISED FLOOR)

NOTES:

1. APPLY STAIN AT EXPOSED WOOD SURFACES TO MATCH EXISTING DOOR VENEER; THESE SURFACES SHALL RECEIVE

ONE (1) COAT SEALER AND THREE (3) COATS POLYURETHANE.

2. EACH CUBBY HOLE SHALL HAVE CLEAR DIMENSIONS OF 6" WIDE x 4" HIGH x 5" DEEP.

FURNITURE PLAN

GENERAL NOTES:

1. UNLESS OTHERWISE NOTED, FURNITURE AND EQUIPMENT ITEMS SHOWN ARE GOVERNMENT-FURNISHED, GOVERNMENT-INSTALLED.

THIS SHEET IS PROVIDED FOR INFORMATION ONLY.

CLASSROOM 1 ELEVATION

SCALE: 1/4" = 1'-0"

AUDITORIUM ELEVATION

SCALE: 1/4" = 1'-0"

CLASS ROOM 2 ELEVATION

SCALE: 1/4" = 1'-0"

CLASS ROOM 2 ELEVATION

SCALE: 1/4" = 1'-0"

CLASS ROOM 2 ELEVATION

SCALE: 1/4" = 1'-0"

CLASS ROOM 2 ELEVATION

SCALE: 1/4" = 1'-0"

CONFERENCE RM ELEVATION

SCALE: 1/4" = 1'-0"

KEYNOTES: INDICATED BY :

1. GOVERNMENT FURNISHED, GOVERNMENT INSTALLED 120" FIXED PROJECTION SCREEN; CONTRACTOR

2. CONTRACTOR FURNISHED, CONTRACTOR INSTALLED 4'X6' DRY ERASE BOARD WITH MARKER TRAY

3. GOVERNMENT FURNISHED, GOVERNMENT INSTALLED 60" LED ENERGY STAR CERTIFIED TELEVISION;

2 2

2 2 2 2

2 2

3 3

X

EQUAL EQUAL

CONTRACTOR SHALL PROVIDE TV MOUNTING BRACKET.

2'-0" 2'-0"

EQ 2'-0" EQ

6'-3"6'-0" EQ EQ

EQ

EQEQEQ

2 2

1'-0"EQ EQ

EQ EQ

4. CONTRACTOR FURNISHED, CONTRACTOR INSTALLED MOTORIZED PULL DOWN SCREEN; DRAPER

ACCESS/SERIES V OR APPROVED EQUAL (137" DIAGONAL; PURE WHITE MH1300V VIEWING SURFACE;

BLACK BACKING; 16:10 IMAGE FORMAT; 110v STANDARD MOTOR); CONTRACTOR SHALL PROVIDE

SUSPENSION SUPPORT APPARATUS; ELECTRIC POWER SERVICE, CONTROL SWITCH (DESIGNATED

"S ") AND ALL REQUIRED ACCESSORIES FOR COMPLETE INSTALLATION.

SHALL PROVIDE MOUNTING BRACKET.

S C

C

DEMOLITION COMMUNICATIONS PLAN

KEYNOTES:

01. REMOVE EXISTING SIPRNET CABLE (RED COLOR) AND 'TOP SECRET' CABLE (PURPLE

INDICATED BY :

OFFICE 1

OFFICE 2

OFFICE 3

OFFICE 4

M

ENTRY

AIRLOCK

MEN'S RR

WOMEN'S RR

STOR 1

JAN CLO

BREAK RM

KITCHEN

PANTRY

STOR 2

C O

R R

ID

O

R

ADMIN STAFF 1

ADMIN STAFF 2

C O

R R

BONUS RM 1 BONUS RM 2AUDITORIUM

LOBBY

BONUS RM 3MECHANICAL

COMMUNICATIONS

SOUTH VEST

NORTH VEST COMMON ROOM

OFFICE 6

OFFICE 7

OFFICE 8 OFFICE 9

GENERAL NOTES:

01. REMOVE COMPLETELY ALL REDUNDANT COMMUNICATIONS INFRASTRUCTURE

INSTALLED BENEATH EXISTING RAISED FLOOR AND IN EXISTING WALLS (TO REMAIN

AND TO BE REMOVED) AT AREAS INDICATED TO BE RENOVATED. REMOVE ANY AND

ALL APPARATUS, INCLUDING CAT-3 AND CAT-5 CABLING, FIBER OPTIC CABLES, BOXES,

TERMINAL BLOCKS, FACEPLATES, ETC. ALL COPPER AND FIBER OPTIC CABLES SHALL

BE REMOVED BACK TO SOURCES OF ORIGIN (TYPICALLY PATCH PANEL OR 66 STYLE

TERMINAL BLOCK) IN ACCORDANCE WITH NEC 800.154 800.3(c). CONTRACTOR SHALL

PROPERLY DISPOSE OF REDUNDANT COPPER CABLING.

MEETING RM

OFFICE 5

APPURTENANCES LEGEND

COLOR) AND ASSOCIATED CONDUITS TO SOURCES OF ORIGIN.

02. REMOVE EXISTING OPTICAL CABLE (YELLOW COLOR) AND ASSOCIATED BOX AND

CONDUIT TO SOURCE OF ORIGIN.

03. REMOVE EXISTING TELEPHONE PUNCH-DOWN PANELBOARD/BOX; REMOVE EXISTING

WIRING TO SOURCES OF ORIGIN.

04. REMOVE EXISTING MICROPHONE JACK AND ASSOCIATED BOX; REMOVE ASSOCIATED

CONDUIT AND WIRING TO SOURCE OF ORIGIN.

XX

AT EXISTING WALL/PARTITION TO BE REMOVED: REMOVE EXISTING SIPRNET/

NIPRNET QUAD OUTLET AND ASSOCIATED BOX, CONDUIT, AND WIRING

AT EXISTING WALL/PARTITION TO REMAIN: REMOVE EXISTING SIPRNET QUAD

OUTLET AND ASSOCIATED BOX, CONDUIT, AND WIRING; PREPARE OPENING

TO RECEIVE NEW NIPRNET DUPLEX OUTLET; OR OPENING TO BE FILLED WITH

GYPSUM BOARD PATCH OR COVERED WITH FACEPLATE

EXISTING REMOTED ANNUNCIATOR FOR UNDER-FLOOR SMOKE DETECTORS

SHALL REMAIN

SECURE RM

M

COMMUNICATIONS PLAN - NEW CONSTRUCTION

CONFERENCE RM

DEP CDR

EXEC DIR

EXEC OFFR

SEC/WAITING

VEST

LAVATORY

MEN'S TOILET

VEST

LAVATORY

111 WOMEN'S TOILET

JAN CLO

VEST

BREAK RM

CLASSROOM 1

AUDITORIUM

CLASSROOM 2

LOBBY

SIPR CAFE

C O

R R

ID

O

R

MEETING RM

ADMIN STAFF 2

138 HERITAGE RM

VEST

VEST

COMM RM

125MECH RM

STORAGE

127DIV CHIEF 3

DIV CHIEF 2

DIV CHIEF 1

CHIEF

RESOURCE ADVISOR

ADMIN STAFF 1

KEYNOTES:

01. PROVIDE (2) GOVERNMENT-FURNISHED, CONTRACTOR-INSTALLED EQUIPMENT RACKS.

(7'-0" HIGH). EXACT ARRANGEMENT AND LAYOUT SHALL BE COORDINATED WITH 2 CS

AT TIME OF INSTALLATION (CONTACT ALLEN PLAVNY (318-456-6617) OR GREG MCCALLIE

(318-456-4840)).

02. PROVIDE (3) CABLE MANAGEMENT CAGES (ORTRONICS P/N OR-MM6VMD706 OR

RACK. LABEL EACH GROUNDING AND BONDING CONDUCTOR IN ACCORDANCE WITH

04. PROVIDE PAINTED PLYWOOD AT WALLS; SEE SHEET A05, FINISH SCHEDULE.

05. PROVIDE (1) 12 STRAND SINGLE MODE FIBER OPTIC CABLE HOUSE CABLE FROM NIPR ROOM

TERMINATE FIBER OPTIC CABLE USING ST CONNECTORS AND ST LOADED 19" (1 RU) RACK-

MOUNTED FIBER PATCH PANELS. TEST AT 1310 AND 1550 NM IN BOTH DIRECTIONS; 100%

137 TO GOVERNMENT-FURNISHED, CONTRACTOR-INSTALLED SIPRNET SAFE IN SIPR CAFE 117.

INDICATED BY :xx

GENERAL NOTES:

01. ALL WALL-MOUNTED DUPLEX NIPRNET OUTLETS SHALL CONSIST OF TWO (2) CAT-6

CABLING AT EACH OUTLET UTILIZING 2-PORT FACEPLATE LOADED WITH TWO (2) IVORY

CAT-6 RJ-45 JACKS (P/N 61110-R16). FOR CONSISTENCY W/ BASE PRACTICES, USE LEVITON

02. INSTALL LABELS WITHIN 4" OF EACH END OF ALL HORIZONTAL CABLES (CAT-6 AND

FIBER OPTIC AT BOTH ENDS). NO PERMANENT MARKERS SHALL BE USED FOR LABELING

05. CAT-6 CABLES SHALL BE SECURED/BUNDLED TOGETHER WITH VELCRO STRAPPING

APPROVED EQUAL).

03. PROVIDE SINGLE-GANG RECESSED BOX WITH REDUCER PLATE FOR SINGLE GANG

04. ALL CAT-6 CABLES SHALL HAVE A 1 METER MAINTENANCE LOOP AT OUTLET END

VESTIBULE

COMMON ROOM

COMMANDER

C O

R R

ID

O

R

NIPR RM

06. ALL QUAD COMM OUTLETS SHALL CONSIST OF FOUR (4) CAT-6 CABLES (AKA QUAD COMM

DROPS). CAT-6 CABLING SHALL BE TERMINATED USING 568A STANDARD. ALL CABLES/

DROPS SHALL BE TESTED TO CAT-6 SPECIFICATIONS. TERMINATE CABLING AT EACH

OUTLET UTILIZING IVORY 4-PORT FACEPLATES LOADED WITH FOUR (4) IVORY CAT-6

J-STD-607-A, PARAGRAPH 5.1.5.1 (USE TAG P/N 01068 OR CALTA017). APPLY ANTIOXIDANT

SECURE RM

125A

03. PROVIDE 6 AWG INSULATED (GREEN COLORED SHEATH) GROUND AND 18" x 4" BUS BAR

MOUNTED ON STAND OFFS, CONNECTED TO FACILITY GROUND. MOUNT BAR ON

PLYWOOD BACKBOARD ALSO PROVIDE GROUND TO BASE OF EACH 19" EQUIPMENT

AT ALL CONNECTIONS.

CABLES; CAT-6 CABLING SHALL BE TERMINATED USING 568A STANDARD. ALL CABLES/

DROPS SHALL BE TESTED AND CERTIFIED TO CAT-6 SPECIFICATIONS. TERMINATE

PART NO. 42080-2IS (OR APPROVED EQUAL) SINGLE-GANG, TWO-PORT WALL PLATES

WITH DESIGNATION WINDOWS (LABELS SHALL BE MACHINE PRINTED AND PLACED

BEHIND PLASTIC WINDOWS); AND LEVITON CAT-6 RJ-45 JACKS (OR APPROVED EQUAL);

ALMOND COLOR.

FACEPLATE AT EACH DUPLEX COMM DROP. RUN 1" EMT CONDUIT FROM BOX TO

6" STUB-UP ABOVE CEILING; PROVIDE CONDUIT END BUSHING.

ABOVE CEILING AND 3 METER LOOP PROVIDED AT EQUIPMENT RACK END. METHOD

FOR INSTALLATION/RACKING OF 3 METER MAINTENANCE LOOP SHALL BE APPROVED

BY 2 CS (ALLEN PLAVNY (318-456-6617) OR GREG MCCALLIE (318-456-4840)).

(PER TIA/EIA-606-1, PARAGRAPH 5.1.2, PAGE 14 AND PARAGRAPH A4, PAGE 31).

(3/4" WIDE) CENTERED BETWEEN J-HOOK SUPPORTS. DO NOT USE PLASTIC CABLE TIES,

TIE WRAPS, OR ELECTRICAL TAPE ANYWHERE FOR CAT-6 CABLING.

07. ALL CABLE CONTAINMENT PROVIDED SHALL USE EITHER J-HOOKS (MAX SPACING OF 36"), WIRE BASKETS/TRAYS, AND/OR CONDUITS. RAISED FLOOR IS INSTALLED IN MUCH OF THE

FACILITY: WIRE TRAY SHALL BE REQUIRED BELOW RAISED FLOOR. CABLE CONTAINMENT

SHALL NOT EXCEED 50% FILL RATE (I. E., AFTER ALL CABLES HAVE BEEN INSTALLED, 50%

SPARE CAPACITY SHALL BE LEFT IN ALL CONTAINMENT DEVICES). WIRE BASKETS/TRAYS

SHALL BE INSTALLED IN CASED OPENING THROUGH WALLS WITH 1" MINIMUM ANNULAR

SPACE AROUND BASKET/TRAY (I. E., DRYWALL SHALL BE NO CLOSER THAN 1" MAXIMUM).

AFTER ALL CABLES HAVE BEEN INSTALLED, FILL ANNULAR SPACES & GAPS W/ REMOVABLE

FIRE-STOPPING MATERIAL (SOCK/BRICK OR PILLOW TYPES ARE ACCEPTABLE).

08. PROVIDE 50-PAIR HOUSE CABLE FROM BACKBOARD LOCATION OF FACILITY'S INCOMING

COMM. TERMINATE HOUSE CABLE ON SPLIT FIFTY STYLE 66 BLOCKS (TERMINATE ON LEFT

SIDE OF BLOCK ONLY) MOUNTED ON SB89 STANDOFF BRACKETS. TERMINATE AT EQUIPMENT

RACK ON 48 PORT PATCH PANEL, 1 PAIR PER PORT (WH/BL), EXCEPT AT 24TH AND 48TH PORTS

WHERE 2 PAIRS SHALL BE TERMINATED (WH/BL AND WH/OR).

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .