Building 120 AC Specs

- Must have 30 Ton cooling capability

- Must be floor mounted direct expansion rated for computer rooms

- Must have top return with bottom discharge into raised floor

- Must come with an adjustable 24” stand for unit

- Three blower motors rated at over 15,000 CFM

- Must be 460v 3 phase 60 hertz power

- BACnet MS/TP capable

- Factory mounted return air sensor

- UPS reheat and humidifier lockout contact

- E2- unit mount- large touch screen controller

- Black unit color

- 2 Scroll compressors

- Right hand top piping connection

- 4-251b/hr proportional steam humidifier

- 27 kW SCR reheat

- Free cooling coil must have three rows covering over 35 square feet of area

- DX cooling coil must have three rows covering over 35 square feet of area

- Backward curved direct driven fan

- Non-fused disconnect for evaporator

- 4" 30% Merv 8 filter (1 set)

- 3-way water regulating valve

- R410A compressor refrigerant