Attachment_I_-_Salient_Characteristics.pdf
PDF 49 KB Posted
- Attached to
- A/C Unit Minot AFB Federal contract opportunity
- Solicitation number
- FA452819QTR07
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FA4528-19-Q-TR07.pdf | ||
| Attachment_II_-_Quote_Sheet.xls | XLS spreadsheet |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FA4528-19-Q-TR07
Attachment I – Salient Characteristics
Building 120 AC Specs
- Must have 30 Ton cooling capability
- Must be floor mounted direct expansion rated for computer rooms
- Must have top return with bottom discharge into raised floor
- Must come with an adjustable 24” stand for unit
- Three blower motors rated at over 15,000 CFM
- Must be 460v 3 phase 60 hertz power
- BACnet MS/TP capable
- Factory mounted return air sensor
- UPS reheat and humidifier lockout contact
- E2- unit mount- large touch screen controller
- Black unit color
- 2 Scroll compressors
- Right hand top piping connection
- 4-251b/hr proportional steam humidifier
- 27 kW SCR reheat
- Free cooling coil must have three rows covering over 35 square feet of area
- DX cooling coil must have three rows covering over 35 square feet of area
- Backward curved direct driven fan
- Non-fused disconnect for evaporator
- 4" 30% Merv 8 filter (1 set)
- 3-way water regulating valve
- R410A compressor refrigerant
File details come from the government source that posted it.