PERFORMANCE WORK STATEMENT FOR THE
INSPECTION / MAINTENANCE, REPAIR, TESTING AND CERTIFICATION
OF THE
FIRE TRAINING SITE AT
JOINT BASE MCGUIRE-DIX-LAKEHURST
Joint Base McGuire-Dix-Lakehurst, New Jersey Revision No 2 25 July 2016
PERFORMANCE WORK STATEMENT (PWS) FOR THE
INSPECTION / MAINTENANCE, REPAIR, TESTING AND CERTIFICATION OF THE
FIRE TRAINING SITE AT
JOINT BASE MCGUIRE-DIX-LAKEHURST, NEW JERSEY
1.0. DESCRIPTION OF SERVICES. The contractor shall provide all supervision, tools, supplies, equipment and labor necessary for the inspection / maintenance, repair, testing, and certification of the fire training site at Joint Base McGuire-Dix-Lakehurst (JB MDL).
1. REQUIRED SERVICES:
1.1. BASIC SERVICES. The fire training site currently consists of two separate site modules: the Crash Fire Rescue Training Facility (CFRTF) and Smoke Training Facility (STF). The contractor shall maintain, repair, test, and certify the CFRTF and STF four (4) times a year. The items covered in the scope of work shall include but are not limited to the : air compressor, air dryer, filters, oil, refrigerant (annually), propane system, control stand, cathodic protection system, burn pit equipment, sump pit equipment, holding pond, re-weld / replace thin metal panels on mock aircraft hull as necessary, replace damaged equipment, rebuild faulty valves, analyze water samples from two Polyvinyl Chloride (PVC) monitor pipes for Aqueous Film Forming Foam (AFFF), and all associated components. The contractor shall maintain, repair, test and certify the CRRTF and STF in accordance with industry standards. A Helicopter Crash Trainer (HCT), Model # CH 571248, is tentatively slated to be installed and operational in Option Year 1. A Car Fire Trainer (CFT), Model WRG201, is tentatively slated to be installed and operational in Option Year 1. All fire training modules will be upgraded or installed in accordance with Operation & Maintenance Instruction Manual Aircraft Fire Training Facility (TO 35E1-2-13-1).
1.2 INSPECTION / MAINTENANCE. The contractor shall perform inspection / maintenance of the fire training modules four (4) times a year in accordance with manufacturers’ recommendations, industry standards, National Fire Protection Association (NFPA), Air Force Occupational Safety & Health Standard (AFOSHSTD), American National Standards Institute (ANSI), American Society of Mechanical Engineers (ASME), American Society of Safety Engineers (ASSE), Occupational Safety & Health Administration (OSHA), Fire Suppression Systems Association (FSSA) and Operation & Maintenance Instruction Manual Aircraft Fire Training Facility (TO 35E1-2-13-1) requirements. The following delineate major subsystems of the fire training modules are required actions:
| Propane system consisting of piping, fittings, tank (flanges, gaskets, valves, actuators Controlair Model Number 231-101-136, regulator General Equipment Manufacturer Co. Model Number 7A-73261-99, Quake Master Model Number 25, exterior tank surface, structural supports, paint, and water spray nozzles and sprinkler heads. |
| Compressed air system - check for leaks, service compressor, and dryer units |
| Cathodic protection system - test and record millivoltages per typical procedures |
Gravity drainage and weir Check berm liner and holding pond liner for leakage
| Two 200 GPM holding pond 3Hp fire pumps, inlet screens, foot valves, bronze strainers and check valves |
| 3/4Hp sump pump 10 GPM and actuation control of pump via holding pond level |
| Drainage pump |
Solenoid Actuators of pump water flow valves Verify control stand Norgren regulator valve settings and integrity
| Verify Co-Ax propane valves Model No. VMK202C140VTN3/4XX1VBXXP1 2/2 way including matching piston control actuator operation |
| Verify igniter operation Federal Stock Number 2920-00-776-4482 |
| Verify pigtail leads for igniters Champion Aviation Product P/N 204085 |
| Verify facility operation, ignition, and shutdown including emergency shutdown |
3/4Hp Sump pump and float and pump switch Inspect two fire pumps enclosure (house) and maintain its integrity.
Inspect rig’s accessories and fasteners for wear and weather damage Inspect facility for any loose material - to help keep airfield free from Foreign Object Damage.
SPECIFIC REQUIREMENTS.
IGNITOR SERVICE / REPLACEMENT. The contractor shall clean and/or remove and replace the igniters and pigtail leads in accordance with manufacturer’s instructions and industry practices. There are 18 igniters, 6 are located on the ground in the burn area and 12 are located on the mock-up.
CUTOUT PANEL REPAIR / REPLACEMENT. If the training scenario included forced entry extrication through the structure’s pre-installed cutout panels, the contractor shall remove cut section of sheet metal and provide and weld in place new patch and / or complete cutout panel. The contractor shall remove and replace damaged cutout panels in accordance with manufacturer’s instructions and standard industry practices. Cutout panels are located on the aft left and right sides of the mock-up. The panels are 36 inches wide and 84 inches high and constructed of .036 inch thick sheet metal.
WATER PUMP REPAIR / REPLACEMENT. The contractor shall remove and replace water pump(s) [two 3HP 200 gm self-priming 230V, one ¾ 10GPM self-priming close- coupled drain pump, one 3/4Hp sump pump] with same as necessary in accordance with manufacturer’s instructions and standard industry practices.
HIGH DENSITY POLYETHYLENE (HDPE) LINER MAINTENANCE. The 80- mil thick HDPE liners are located in the water conservation pond, burn area, and trench. The liners in the trench and burn pit are buried. The contractor shall take water samples from test pipes (between double layers) and have analyzed at a lab for detection of foam. If samples prove heavy concentrations of foam, the suspect liner(s) will need to be exposed and searched for leaks and patched. Locate the liner leak and repair in accordance with extrusion welder manufacturer’s instructions (Nation Seal Company, 1245 Corporate Blvd., Suite 300, Aurora, IL 60504. Telephone (708) 898-1161 or (800) 323-3820). The contractor shall submit the repair procedures, materials, and techniques to the Contracting Officer Representative (COR) for approval prior to initiating repairs.
REGULATOR ADJUSTMENT. The contractor shall adjust regulator pressure as follows:
| Burner Location | Optimal Flame Height |
| Engine burners | Fully Engulfed |
| Internal burners | 6-8 feet |
ACCESSORIES AND FASTENERS. Inspect rig’s bolts and pipe supports, connections and remove and replace those that visually show wear or damage making it suspect of failure.
WINTERIZATION. The contractor shall winterize the fire training modules during the final inspection / maintenance cycle prior to winter. The scope of winterization includes but not limited to: draining the above ground water supply pipes to nozzles / sprinkler heads, drain water lines containing solenoid valves / water pumps, electrically disconnect pumps, and cover controls from atmospheric winter elements.
1.3 REPAIRS. The contractor shall coordinate the repair of all mechanical / electrical deficiencies as a result of the inspection / maintenance with the COR
MINOR REPAIRS. The contractor shall make all repairs to the fire training site modules at the contractor’s labor expense if the material cost is less than $100.00 per module. The contractor shall ensure all minor repair work commences within two (2) days upon notification and shall ensure that all repairs are completed within four (4) days. The total time allotted to the contractor shall be six (6) days from CO approval to completion. The contractor is encouraged to keep equipment downtime to a minimum. The contractor shall provide a written report to include but not be limited to: all mechanical / electrical deficiencies, actual parts replaced, parts cost and man hours per repair. A copy of the repair report shall be provided to the COR and Contracting Officer (CO).
1.3.2 MAJOR REPAIRS. If the repair work for the fire training site modules is between $100.00 and $2,500.00 in total costs, the contractor shall provide a written repair cost estimate to the COR within two (2) days of finding the deficiency requesting authorization to proceed. The written repair cost estimate shall include, at a minimum, the following: the estimated cost of material, the labor hours (at the loaded rate stipulated in the bid schedule) needed to complete repairs, and the projected time the equipment will be out of service. The contractor shall be financially compensated for material and labor costs only if COR authorization is granted. At no time shall work in excess of $100.00 be completed without COR approval. If the work exceeds $2,500.00 in total costs, the contractor shall provide a written repair cost estimate directly to the Contracting Officer (CO) only (not to the COR) within two (2) days of finding the deficiency. The written repair cost estimate shall include, at a minimum, the following: the estimated cost of the material, the labor hours (at the loaded rate stipulated in the bid schedule) needed to complete the repairs, and the projected time the equipment will be out of service. The contractor shall be financially compensated for the material and labor costs only if CO authorization is granted. At no time shall work in excess of $2,500.00 be completed without CO approval. The contractor shall ensure all major repair work commences within three (3) days of COR or CO approval. The contractor shall ensure that all repair work is completed within seven (7) days of its commencement; however, the contractor is encouraged to keep equipment downtime to a minimum. The contractor shall provide a written repair completion report to include but not limited to: mechanical / electrical deficiencies found, actual parts replaced, parts cost, and actual man hours per repair. A copy of the repair report shall be provided to the COR.
TESTING. The fire training site modules shall be tested in accordance with the manufacturer’s recommendations, TO 35E1-2-13-1, and all applicable standards / regulations. The contractor shall conduct the testing in the presence of the COR and / or a member of the Fire Department. In the event that a necessary repair is found as a result of the testing process, the contractor shall be responsible to follow Paragraph 1.3. Repairs in order to correct the deficiency.
CERTIFICATION. The contractor shall certify that the fire site training modules passed all requirements as delineated in and accordance with the manufacturer’s recommendations, NFPA, AFOSHSTD, ANSI, ASME, ASSE, OSHA, FSSA, and TO 35E1-2-13-1 requirements. The contractor shall also physically attach a waterproof certification label or tag with legible print and with the pertinent information / data to each fire training site module control stand. The contractor shall provide written certification documents to the COR within seven (7) days.
SERVICE CALLS. In the event that a fire training site module or component fails or malfunctions, the contractor shall respond to a service call within two (2) business days upon notification by the COR or CO. The contractor shall inspect, repair, test and recertify the repaired the fire training site module in accordance with all established procedures within four
(4) days.
REPORTS / DOCUMENTATION. The contractor shall prepare and submit written reports after the completion of all inspection / maintenance, repairs, tests, and certification of each fire training site module. The reports and / or documentation shall be forwarded to the COR and CO within two (2) business days after the completion of work. The reports and / or documentation shall include but not be limited to: location, type of equipment with model number and manufacturer. In addition all reports shall note any work performed, repairs completed, date of repair, date of testing, date of certification, name of technician, company name with phone number and overall condition of the equipment.
2.0. SERVICE DELIVERY SUMMARY. The contract service requirements are summarized in performance objectives that relate directly to mission essential items. The performance threshold briefly describes the minimally acceptable levels of service required for each requirement. The SDS and the contractor’s Quality Control Plan provide information on contract requirements, the expected level of contractor performance and the expected method of Government surveillance and confirmation of services provided. These thresholds are critical to mission success. Procedures as set forth in the FAR 52.212-4 (a), Contract Terms and Conditions - Commercial Items, Inspection/Acceptance, will be used to remedy all deficiencies. During the first initial 30 days of the contract, two additional errors on each task shall be allowed in an effort to identify normal phase-in problems, except for any periodic cleaning service.
Performance Objectives Statement of Work Paragraph
Performance Thresholds Inspections / Maintenance. Inspect and maintain modules four times a year.
1.2 All modules shall be inspected / maintained 100% of the time.
Repairs. Perform repairs as required and authorized.
1.3 All repairs shall be completed within the allotted time frames 100% of the time.
Testing. Perform testing in accordance with the manufacturer’s recommendations, publications and industry standards and TO 35E1-2-13-1.
1.4 All tests shall be completed 100% of the time Certification. Certify that modules are functioning in accordance with the manufacturer’s recommendations, publications, industry standards, and TO 35E1-2-13-1.
1.5 All valid certifications shall be completed 100% of the time Service Calls. Respond to service request.
1.6 All repairs shall be completed within the allotted timeframes 100% of the time.
Reports / Documentation. Provides accurate reports and documentation.
1.7 All reports/documentation are current and available 100% of the time.
GOVERNMENT FURNISHED PROPERTY AND SERVICES. All reasonable quantities of utilities will be available to the contractor without charge. Any temporary lines and connections that may be required shall be installed, maintained and removed by the contractor at his / her expense and in a manner satisfactory to the COR.
POLICE PROTECTION. Base Security Forces shall provide initial law enforcement response and services to the contractor. The Base Security Operations Desk can be reached at phone numbers (609) 562-6001/2/3 (McGuire/Dix).
FIRE PROTECTION. Base Fire Department shall provide initial response and fire protection and emergencies services to the contractor. The Base Fire Alarm Control Center can be reached at phone number 911 from a base telephone. If dialing 911 from a cell phone, the location must be fully identified to ensure that the proper responder is notified.
PHYSICAL SECURITY. The contractor shall be held fully accountable for any failure to maintain the physical security of all base restricted areas, secured facilities or sites that they are responsible for providing services within. The contractor shall be responsible for the safekeeping and inventorying of all Government-furnished keys and combinations issued for the performance of services within secured areas. All losses or damages caused by the contractor, or by the contractor’s failure or negligence in maintaining proper security of these areas will be paid for by the contractor. Upon termination or completion of the contract, the contractor shall secure the previously issued keys and return them to the COR or CO within twenty-four (24) hours.
RESTRICTED AREA BADGES. The Government shall furnish an USAF Restricted Area Badge (AF Form 1199A) to all authorized contractor employees with proper security clearances and a validated need for access to flight line areas to perform maintenance services. The contractor shall coordinate the required request for restricted area badges with the CE COR or CO.
RESTRICTED AREA ESCORTS. The Government shall provide escort services for contractor employees to provide maintenance services within base restricted areas only until the contractor has been provided with the required AF Form 1199A (with escort authorization) to provide their own escorts. The contractor shall coordinate the necessary Government escort services with the CE COR or CO. The contractor is required to obtain restricted area badges for employees. The contractor shall obtain the appropriate number of employees with badges to escort the workforce.
AIRFIELD COORDINATION. The contractor shall coordinate all activities in the airfield area by contacting Airfield Management. Work will be accomplished only after Airfield Management has approved scheduled times.
FLIGHT LINE DRIVERS. Training must be completed prior to operating vehicles on the flight line. All employees working in airfield areas shall be required to have an AF Form IMT 483, Certificate of Competency (flightline driver’s license) with them at all times. Vehicles must have a valid POV pass issued by Airfield Management prior to operating on the flight line. The contractor shall be responsible for insuring that all foreign objects and debris are removed from vehicle tires prior to entering all taxiways, runways, and aircraft parking aprons.
GENERAL INFORMATION.
QUALITY CONTROL. The contractor shall develop, submit for CO review, and maintain a quality control program and the necessary quality control procedures to ensure that services are performed in accordance with the established commercial standards within two (2) weeks of award. The Government, through the COR, shall periodically evaluate the contractor’s work performance in accordance with the specific contract performance requirements.
HOURS OF OPERATION. The normal hours of operation for the contractor to perform normal maintenance and repair services required under this contract are 7:00 AM to 4:00 PM, Monday through Friday. The contractor is not required to provide normal service except for emergencies on the following days:
New Year’s Day - 1 January Martin Luther King Day - 3rd Monday in January Washington’s Birthday - 3rd Monday in February Memorial Day - last Monday in May Independence Day - 4 July Labor Day - 1st Monday in September Columbus Day - 2nd Monday in October Veteran’s Day - 11 November Thanksgiving Day - 4th Thursday in November Christmas Day - 25 December
If these holidays fall on Saturday, the preceding Friday will be observed. If these holidays fall on Sunday, the following Monday will be observed. If a holiday falls on a scheduled service day, the contractor will be responsible for rescheduling services for the first day post the holiday observance.
The COR or CO must approve in advance, excluding legal holidays, any exceptions to the normal work hours and designated workdays. The contractor shall submit their request to COR and CO no later than two (2) business days in advance of the requested change(s).
CONTRACTOR PERSONNEL. The contractor and their employees shall comply with all base regulations at all times and shall conduct themselves in a professional manner. Uniforms, badges, and good behavioral conduct will be mandatory. The contractor shall provide a complete and current employee roster to the COR and CO within ten (10) business days of the contract award. The contractor’s employee roster shall identify the primary and alternate site manager or foreman and the Quality Control inspector and their telephone or cell phone numbers. As required, the contractor shall provide updated copies of their employee roster to the COR and CO.
CONTRACTOR EMPLOYEE UNIFORMS AND IDENTIFICATION. All contractor employees shall wear a distinctive company logo on their outer garment at all times. The contractor employee shall be neat and professional in appearance and meet current commercial standards. In addition, the contractor’s employees shall wear a company-issued identification badge with the company’s name, employee’s name and employee’s photo prominently displayed on their outer clothing.
TOBACCO POLICY. The contractor shall ensure that all contractor employees do not use tobacco products within 50 ft. of any base facility, around fuel tanks and generators, within any clearly marked “No Smoking” areas or within 50 ft. of any flight line aircraft parking areas.
SAFETY AND ACCIDENT REPORTING. The contractor shall be responsible for providing services under this contract IAW all base, local, State and Federal occupational safety requirements. The contractor shall ensure that all services are conducted safely at all times. The contractor shall ensure that all contractor employees are issued and properly use all required safety personal protective equipment. The contractor shall use mechanically sound and safe vehicles and equipment in the performance of services under this contract. The contractors shall take necessary corrective actions if the contractor’s employees are conducting operations in an unsafe manner. In the event of an accident, the contractor shall contact the base emergency 911 service (see paragraph 3.2) and the COR immediately. If dialing 911 from a cell phone, the location must be fully identified to ensure that the proper responder is notified. Additionally, the contractor and contractor’s personnel will be knowledgeable of and comply with all other base incident-reporting procedures.
INCLEMENT WEATHER SCHEDULE. The contractor shall not provide operational service during periods of inclement weather.
HIRING GOVERNMENT PERSONNEL. The contractor is restricted from hiring the COR, inspectors, monitors or any other Government employees whose employment could result in conflict of interests in accordance with DOD 5500.7R.
SECURITY REQUIREMENTS / VEHICLES AND PASSES. All contractor or contractor employees’ vehicles used for the performance of this contract shall comply with all local, state and federal regulations. In addition, all vehicles described above must be registered through the Security Police Squadron, Pass and Registration and will comply with JB MDL directives. After award of contract, the contractor shall request through the COR, CO and Security Forces to be issued base passes and identification badges for their employees and work vehicles in accordance with the attached Contractor Security Appendix – 10 June 2015. Reference Appendix B.
PERFORMANCE OF SERVICES DURING CRISIS DECLARED BY THE NATIONAL COMMAND AUTHORITY OR THE LOCAL INSTALLATION COMMANDER. This service does not meet the criteria for continuation of performance during a crisis in accordance with Department of Defense Instruction (DODI) 1100.
EXECUTIVE ORDER (EO) 13423 (Strengthening Federal Environmental, Energy, and Transportation Management). The contractor shall assist in compliance with this EO through the:
| Use of products with post-consumer recycled content |
| Use of products that are recyclable |
| Use of low toxicity or non-toxic products |
| Use and installation of low-maintenance products |
The green procurement requirements related to the EO are available on Appendix C.
ENVIRONMENTAL COMPLIANCE. Contractor is required to comply with all applicable base, local, State and federal environmental laws and regulations, including Air Force Instructions in effect at the time of performance. Contractor shall be responsible for obtaining and complying with any required operating permits. Contractor shall be responsible and liable for penalties, fines, or environmental damage claims that may be required or assessed by the local, State or federal governments as a result of the contractor’s performance, or failure to perform, during the course of this contract. The government will inspect for environmental compliance at its discretion, and will notify the COR of any discrepancies found. In addition, contractor may be subject to contractual sanctions for environmental non-compliance including, but not limited to, termination, suspension, and debarment and adverse past performance assessment. Any damages incurred by the contractor’s operation or negligence shall be restored to their original condition by the contractor, at no additional cost to the government.
DISPOSAL OF WASTE. Contractor is responsible for the proper handling and disposal of solid waste. Contractor shall also be responsible for any enforcement action that may be taken by the State of New Jersey, other State or the Federal Government related to handling, transportation and the proper disposal of solid waste materials. If notification, certifications, documentation, manifests, permits or any other written materials are required by law to be obtained, prepared and/or submitted. Contractor shall prepare same and provide a written copy to the COR. Any action, which violates permit requirements for compliance, must be reported to 87 CES/CEAN at 754-6166 immediately.
NOTIFICATION OF ENVIRONMENTAL SPILLS. In the event contractor spills or releases any unpermitted substance, hazardous substance or hazardous waste into the environment, the contractor shall immediately report the incident to the Fire Department IAW paragraph 3.3, the COR, and the CO. Contractor shall be liable for the costs of clean up and remediation of any spills or the release of such substance into the environment. The government shall provide the contractor with the following utilities: electricity, and water. The government will only provide reasonable amounts in accordance with the PWS.
MATERIALS. All materials used in the performance of services on the installation shall be in compliance with TO 35E1-2-13-1, industry standards, local, federal and State laws, and will be used according to manufactures' recommendations. Materials will be used for intended purposes and will be stored and utilized in accordance with industry standards. Contractor will submit Safety Data Sheets on all materials to be used fifteen (15) days prior use for approval by the COR.
6.1 APPENDICES.
Estimated Workload Data
Security Requirements
Green Procurement Requirements
87th Safety Booklet for Civilian Contractors (June 2015)
Antiterrorism Awareness Guide for Civilian Contractors (July 15 v1)
APPENDIX A ESTIMATED WORKLOAD DATA
CRASH FIRE RESCUE TRAINING FACILITY (CFRTF) DRAWINGS AND TO 35E1-2-13-1 (FEB 2015) file_0.pdf
TO 35E1-2-13-1
TECHNICAL MANUAL
WORK PACKAGE
OPERATION AND MAINTENANCE INSTRUCTIONS
AIRCRAFT FIRE TRAINING FACILITY
DISTRIBUTION STATEMENT A - Approved for public release; distribution is unlimited. PA Case Number 05-07285. Other requests for this document shall be referred to 406 SCMS/GUEE, Robins AFB, GA 31098. Questions concerning technical content shall be referred to AFCEC/
CXF.
Published Under Authority of the Secretary of the Air Force
25 JUNE 2013 CHANGE 2 - 6 FEBRUARY 2015
BASIC AND ALL CHANGES HAVE BEEN MERGED TO MAKE THIS A COMPLETE PUBLICATION.
Dates of issue for original and changed pages are:
Original. . . . . . . .0 . . . . . . . 25 June 2013 Change . . . . . . . . 1 . . . . . . 9 August 2014
Change . . . . . . . . 2. . . . .6 February 2015
TOTAL NUMBER OF PAGES IN THIS PUBLICATION IS 256, CONSISTING OF THE FOLLOWING:
Page *Change No. No.
Title A i ii Blank iii - v vi Blank
LIST OF EFFECTIVE PAGES
INSERT LATEST CHANGED PAGES. DESTROY SUPERSEDED PAGES.
NOTE The portion of the text affected by the changes is indicated by a vertical line in the outer margins of the page. Changes to illustrations are indicated by shaded or screened areas, or by miniature pointing hands.
* Zero in this column indicates an original page.
A Change 2 USAF
NUMERICAL INDEX OF EFFECTIVE WORK PACKAGES
NOTE
Only those work packages and subordinate work packages assigned to this manual are listed in this index, therefore WP/SWP numbers may not be sequential. Insert Change No. 2, work packages and subordinate work packages, dated 6 February 2015. Dispose of superseded work packages and subordinate work packages. If change pages are issued to a work package or subordinate work package, insert the changed pages in the applicable work package or subordi-nate work package. The portion of the text affected in a change or revised WP or SWP is indicated by change bars in the outer margin of each column of text. Changes to illustrations and diagrams are indicated by pointing hands or shaded areas.
WP/SWP
No.
Change No.
Model Application Title
001 00 0 Alphabetical Index 002 00 2 Foreword 003 00 2 Master List of Special Tools, Test Equipment, and Consumables 004 00 1 Safety and Accident Prevention 005 00 1 Standard Operating Procedures 005 01 1 Winterization Procedures 006 00 1 Semi-Annual System Safety Inspection and Operational Checks 007 00 2 General Maintenance 007 01 0 Fault Isolation 007 02 0 Replacement Schedule 008 00 2 Facility Overviews 009 00 1 Goodfellow AFB Texas Operating Procedures 010 00 0 Thule AB Greenland Operating Procedures 010 01 0 Thule AB Greenland Winterization Procedures 011 00 1 AFTF Certification Performance Test
Change 2 i/(ii blank)
SAFETY SUMMARY
1 GENERAL SAFETY INSTRUCTIONS.
This manual describes physical and/or chemical processes which may cause injury or death to personnel, or damage to equipment, if not properly followed. This safety summary includes general safety precautions and instructions that must be understood and applied during operation and maintenance to ensure personnel safety and protection of equipment. Prior to performing any specific task, the WARNINGs, CAU- TIONs, and NOTEs included in that task shall be reviewed and understood.
2 WARNINGS, CAUTIONS, AND NOTES.
WARNINGs and CAUTIONs are used in this manual to highlight operating or maintenance procedures, practices, conditions, or statements which are considered essential to protection of personnel (WARNING) or equipment (CAU- TION). WARNINGs and CAUTIONs immediately precede the step or procedure to which they apply. WARNINGs and CAUTIONs consist of four parts: heading (WARNING, CAUTION, or icon), a statement of the hazard, minimum precautions, and possible results if disregarded. NOTEs are used in this manual to highlight operating or maintenance procedures, practices, conditions, or statements which are not essential to protection of personnel or equipment. NOTEs may precede or follow the step or procedure, depending upon the information to be highlighted. The headings used and their definitions are as follows:
Highlights an essential operating or maintenance procedure, practice, condition, statement, etc., which if not strictly observed, could result in in-jury to, or death of, personnel or long term health hazards.
procedure, practice, condition, statement, etc., which if not strictly observed, could result in dam-age to, or destruction of, equipment or loss of mis-sion effectiveness.
procedure, condition, or statement.
3 REGULATIONS.
These systems were developed in accordance with NFPA 1402-1992 and have been revalidated under NFPA 1402- 1997 as meeting all requirements for outside activities. This system has been revalidated by the Air Force based on the requirements of NFPA 1402-2002, and NFPA 1402-2007. All NFPA 1402-2007 Chapter 13 Outside Activities recommen-dations related to system and controls certification and label-ing by nationally recognized testing laboratories has been accomplished by the Air Force internal operational test and evaluation process (OT&E) conducted under the auspices of the independent Air Force Operational Test and Evaluation Center (AFOTEC). Compliance with this Technical Order is required to retain the certification identified in NFPA 1402.
3.1 Systems. Systems approved by AFCEC as complying
with the requirements of this Technical Order are in compli-ance with NFPA 1403-2007 Live Fire Training Evolutions, Chapter 7 Exterior Props and Chapter 8 Exterior Class-B Fires. All NFPA 1403 elements related to system and con-trols certification by nationally recognized testing laborato-ries has been accomplished by the Air Force internal opera-tional test and evaluation process (OT& E) conducted under the auspices of the independent Air Force Operational Test and Evaluation Center (AFOTEC). Compliance with this technical order is required to conduct live fire training evo-lutions in accordance with NFPA 1403.
3.2 Certification. All fire department personnel who in-
spect and operate the AFTF are required to be certified. To become certified, personnel are required to study the multi-media course material, entitled AFTF Inspection, Operation and Maintenance and pass the 50-question final exam with a minimum score of 80%. The test is called Liquid Propane Aircraft Fire Training Facility and is located in the most current version of CerTest. Upon completion of the academic portion personnel are required to pass the Performance Test and submit the Performance Test Record (see WP 011 00), the CerTest results and a cover letter signed by the Fire Chief requesting the training certificate.
iii
4 PROTECTIVE CLOTHING.
Wear Personal Protective Equipment (PPE); such as bunker gear, helmet, gloves, boots, Self Contained Breathing Appa-ratus (SCBA), etc. approved for use in actual firefighting incidents and the training exercises mentioned in this manual.
5 ELECTRICAL CIRCUITS.
Operating personnel must think safety at all times. Do not replace components or make adjustments inside of equip-ment with the electrical power supply turned on. To avoid injuries, always remove power from, discharge and ground a circuit before touching it. If a test connection to energized equipment is required, make the test connection ground con-nection before probing the voltage or signal to be tested. Do not attempt internal service or adjustment of equipment un-less another person capable of rendering aid and resuscita-tion is present.
6 LIVE FIREFIGHTER TRAINING.
The information in Paragraph 6 through Paragraph
6.5 is taken from USFA-TR-100 May 2003 Trends and Hazards in Firefighter Training - Special Re-port which is available on-line at: http://www.us-fa.fema.gov/downloads/txt/publications/tr-100.txt
The need for safe firefighter training must be balanced with sufficient challenge to prepare firefighters for the unpredict-able nature of the fire ground. Training must not be so con-trolled as to give firefighters a false sense of security, nor can it disregard established safety procedures for the sake of increased realism. To maintain an effective cadre of firefight-ers and officers, the fire service must find new and dynamic ways to train personnel to act in a safe, decisive manner that best supports the fire service’s mission to protect lives, prop-erty, and the environment.
This system is a live fire trainer intended to ex-pose the firefighter/trainee to the same thermal and direct fire exposure experience in an actual uncon-trolled fire emergency. The system is not a fire simulator; there is nothing simulated about the fires in the system. The potential for the training system fires to cause thermal injury is no less than that in an actual uncontrolled fire emergency.
6.1 Safety. Although generally considered an essential
part of firefighter training, practical evolutions utilizing live fire or smoke pose a significant risk to both trainees and instructors. The potential for injury is very real during this type of training and prudent instructors take numerous pre-cautions to ensure the safety of the participants.
6.2 Life-Threatening Fire Conditions. Modern protective
clothing may make life-threatening fire conditions less obvi-ous; fire fighters and instructors must be constantly alert to recognize the visual and physical clues to impending danger.
6.3 Firefighter Activities. Firefighting is, without question, a highly physical and demanding activity. The intensity and prolonged duration of firefighter training evolutions place substantial physical stress on trainees and instructors. Inju-ries that commonly occur during training evolutions involve knees, lower back, strains, and sprains. The best means for preventing these potential injuries is by promoting physical fitness and proper lifting techniques. Although it is impos-sible to completely prevent these types of injuries, increased fitness and conditioning helps to reduce the incidence of in-jury and enable firefighters to cope with the intense physical demands of practical training and tactical operations. Simple techniques, such as warm-up exercises to prevent muscle in-juries, although not routinely employed, should be done prior to any training.
During training, firefighters physical stress level should be monitored continuously to reduce train-ing- related heart attacks, strokes and heat stress emergencies.
6.4 Safety Discipline. The discipline and supervision ap-
plied during training can rarely be matched in actual fire-fighting operations. In many ways, training can and should constitute one of the safest aspects of a firefighter’s job.
However, training is sometimes compromised by compla-cency or by the diminished sense of danger suggested in a controlled training environment.
6.5 Building Construction and Detection/Suppression
Systems. The decrease in the incidence of fires, coupled with improvements in building construction and detection/ suppression systems, has led to a shortage of instructors with extensive experience under actual fire conditions. As experi-enced instructors retire, especially those in career fire depart-ments serving urban areas, they are being replaced with younger, less seasoned instructors. New instructors are often well educated and have usually achieved instructor certifica-tions through organizations that meet or exceed NFPA stan-dards for teaching and training. However, many of these in-structors do not have the same level of fireground experience as more seasoned fire instructors. While well-trained and competent leaders, they may not have the fire combat expe-rience of many of their predecessors that can help them to iv quickly recognize dangerously changing fire conditions. Lim-ited experience makes it even more imperative that firefight-ing instruction adheres strictly to established policies and standards.
Fire service instructors should ensure that training standards and procedures be followed closely, es-pecially when challenging tasks are assigned to recruits. To prevent injuries, instructors must know their material well, maintain a high ratio of in-structors to students and be vigilant about ensur-ing strict adherence to safety procedures. Instruc-tors should familiarize themselves with the backgrounds and experience of their students, and care should be taken to avoid situations for which the students are not yet prepared.
6.6 Attitude and Training. Attitude and the Training
Academy Way. One of the cornerstones of fire service train-ing is to impart the correct attitude towards firefighting from instructor to student. Failure to pass on the appropriate atti-tudes and force unit discipline in fire training can have a lasting effect on students. One problem consistently voiced by experienced fire service personnel is the attitude that there is a training academy way of doing things, and the real way of doing things (outside of training). The training academy way should be synonymous with the right way.
7 STRUCTURAL FAILURE REPORTING.
Any structural failure, collapse, damage, or significant defor-mation in the physical shape of the trainer mock-up, control/ safety tower, or propane storage facility shall be reported within 24 hours of occurrence to AFCEC/COS/CXF, 139 Barnes Drive, Tyndall AFB, FL, 32403-5319 or the AFCEC Reach Back Center. General warping of decks and panels which do not result in the deformation or shifting of the trainer’s general shape are considered normal in the course of use of the trainer.
8 COMPONENT FAILURE REPORTING.
Any component failure or malfunction which occurs in other than a safe mode shall be reported within 24 hours of occur-rence to AFCEC/COS/CXF, 139 Barnes Drive, Tyndall AFB, FL, 32403-5319 or the AFCEC Reach Back Center at ww-w.afcec.af.mil. All the components are designed to fail or not function in a safe mode - off, shut-down or not operate - any other failure condition must be reported.
9 CASUALTY REPORTING.
Any injury or death occurring during or following a training exercise using the an Air Force Fire Training Facility shall be reported within 6 hours using the Fire Incident Notifica-tion reporting process in AFI 32-2001. Copies of the final incident report shall be provided to AFCEC/COS/CXF, 139 Barnes Drive, Tyndall AFB, FL, 32403-5319 or the AFCEC Reach Back Center. As with any live training event, there is a potential for personnel injury. The following procedure shall be applied to all fire trainer systems regardless whether the system is COTS, Air Force Standard Design or unique design any time a firefighter suffers a reportable injury.
• The fire events in use at the time of the injury shall be locked and tagged out. Other events may con-tinue in use with the approval of the installation Fire Chief. Locked/tagged out fire events shall not be used until approved by AFCEC.
• All personal protective clothing and equipment used by the injured party shall be collected and secured for evaluation. Items shall remain secured by the installation Fire Chief until both MAJCOM and AFCEC have determined there is no further need for the items.
• The fire hose and nozzle being used in the training event shall be collected and secured. Items shall re-main secured by the installation Fire Chief until both MAJCOM and AFCEC have determined there is no further need for the items.
v/(vi blank)
ALPHABETICAL INDEX
EFFECTIVITY: AIRCRAFT FIRE TRAINING FACILITY
LIST OF EFFECTIVE WP PAGES
Total Number of Pages in this WP is 2 consisting of the following:
Page *Change Page *Change Page *Change No. No. No. No. No. No.
1. . . . . . . . . . . . . . . . . . . . . . . . . 0 2 Blank
ALPHABETICAL INDEX OF EFFECTIVE WORK PACKAGES
Only those work packages and subordinate work packages assigned to this manual are listed in this index.
Subject WP/SWP Subject WP/SWP
ALPHABETICAL INDEX . . . . . . . . . . . . . . . . 001 00
FACILITY OVERVIEWS . . . . . . . . . . . . . . . . . 008 00
FAULT ISOLATION . . . . . . . . . . . . . . . . . . . . 007 01
GENERAL MAINTENANCE . . . . . . . . . . . . . . 007 00
GOODFELLOW AFB TEXAS OPERATING
PROCEDURES . . . . . . . . . . . . . . . . . . . . . . 009 00
FOREWORD . . . . . . . . . . . . . . . . . . . . . . . . . 002 00
MASTER LIST OF SPECIAL TOOLS, TEST
EQUIPMENT AND CONSUMABLES . . . . . . 003 00
AFTF CERTIFICATION PERFORMANCE
TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 011 00
SEMI-ANNUAL SYSTEM SAFETY INSPEC-
TION AND OPERATIONAL CHECKS . . . . . . 006 00
SAFETY AND ACCIDENT PREVENTION . . . . 004 00
STANDARD OPERATING PROCEDURES . . . . 005 00
THULE AB GREENLAND OPERATING PRO-
CEDURES . . . . . . . . . . . . . . . . . . . . . . . . . 010 00
THULE AB GREENLAND WINTERIZATION
PROCEDURES . . . . . . . . . . . . . . . . . . . . . . 010 01
WINTERIZATION PROCEDURES . . . . . . . . . . 005 01
WP 001 00
1/(2 blank)
FOREWORD
OPERATION AND MAINTENANCE INSTRUCTION
Total Number of Pages in this WP is 12 consisting of the following:
1. . . . . . . . . . . . . . . . . . . . . . . . . 2 5 - 7. . . . . . . . . . . . . . . . . . . . . 2 10 - 11 2 - 4. . . . . . . . . . . . . . . . . . . . . . 0 8 - 9. . . . . . . . . . . . . . . . . . . . . 0 12
TABLE OF CONTENTS
Paragraph Page Paragraph Page
1 ABBREVIATIONS
2 RELATED PUBLICATIONS
3 PURPOSE
4 SCOPE
5 DESIGN, MODEL, AND DATE
6 MANUAL STRUCTURE
7 WP BREAKOUT
8 LOCATING INFORMATION
9 LEADING PARTICULARS
10 MAINTENANCE CONCEPT
11 USE OF SHALL, WILL, SHOULD AND
MAY
12 TIME COMPLIANCE TECHNICAL OR-
DERS (TCTO)
13 PRINCIPLES OF OPERATION
13.1 Description
13.2 Configuration
14 TOLERANCES, CLEARANCES AND
WEAR LIMITS
14.1 Wear Limits
15 PART IDENTIFICATION
16 ONE TIME USE ITEMS
17 IMPROVEMENT REPORTS
18 THEORY OF OPERATION - GEN-
ERAL
18.1 Burn Area
18.2 Control Stand
18.3 Liquid Propane System
19 WATER CONSERVATION POND
20 AFTF MODIFICATION
21 COMERCIAL-OFF-THE-SHELF (COTS)
TRAINING SYSTEMS
LIST OF ILLUSTRATIONS
Number Title Page Number Title Page
1 Generic AFTF 2 Mock-up Right Side and Aft View 3 Mock-up Left Side and Forward
View
4 LPG Burner Locations 5 LPG Burner, Ignitor and Sprinkler Loca-tions
WP 002 00
Change 2 1
LIST OF TABLES
1 Temperature and Pressure Relation
FOREWORD
1 ABBREVIATIONS.
All abbreviations used in this manual are in accordance with ASME Y14.38, Abbreviations and Acronyms for Use on Drawings and Related Documents.
AF Air Force AFCEC Air Force Civil Engineer Center (FOA) AFOSH Air Force Occupational Safety and Health AFTF Aircraft Fire Training Facility AFTO Air Force Technical Order AP Attaching Parts APU Auxiliary Power Unit AR As Required ARFF Aircraft Rescue Firefighting (vehicle) ASME American Society of Mechanical Engi-neers ASSY Assembly BTU British Thermal Unit CAGE Commercial and Government Entity CFE Contractor Furnished Equipment COTS Commercial-Off-the-Site DoD Department of Defense GFE Government Furnished Equipment HDPE High Density Polyethylene I&S Interchangeability and Substitution IPB Illustrated Parts Breakdown Kvac Kilovolts Alternating Current LPG Liquid Propane Gas MPL Maintenance Parts List N2 Nitrogen NFPA National Fire Protection Association NHA Next Higher Assembly NI Numerical Index NPGA National Propane Gas Association OS&Y (valve) Outside Screw and Yoke PPE Personal Protective Equipment PN Part Number Psi Pound Per Square Inch RDI Reference Designator Index REF Reference SCBA Self Contained Breathing Apparatus SMR Source, Maintenance, and Recoverability STANAG Standardization Agreement (NATO) SWP Subordinate Work Package UOC Usable on Code Vac Volts Alternating Current WP Work Package
2 RELATED PUBLICATIONS.
The following publications contain information in support of this technical manual.
List of Related Publications
Number Title AFM 91-201 Explosive Safety Standards ASME Y14.38 Abbreviations and Acronyms for Use on Drawings and Related Documents
DODI 5330.03_AFI 33-395 Document Automation and Production Service
(DAPS)
NFPA Standard on Fire Department Occupational Safety and Health Program
TO 00-5-1-WA-1 Air Force Technical Order System
TO 00-25-195-WA-1 Source, Maintenance, and Recoverability Coding of Air Force Weapons, Sys-tems, and Equipment
TO 00-25-234-WA-1 General Shop Practice Re-quirements for the Repair, Maintenance, and Test of Electrical Equipment
TO 00-105E-9/STANAG
Aerospace Emergency Res-cue and Mishap Response Information (Emergency Services)
3 PURPOSE.
This manual contains a series of Work Packages (WP) and Subordinate Work Packages (SWP) which provide operating instructions and instructions for intermediate and field level maintenance of the Aircraft Fire Training Facility. The intent of this system is to create a safe live fire training environ-ment for fire fighters.
4 SCOPE.
The complete set of work packages covers all approved op-erations, inspection, and fault isolation.
5 DESIGN, MODEL, AND DATE.
The AFTF design was originally referred to as the Crash Fire Rescue Training Facility (CFRTF). The original Technical Order was published under this title dated 19 November 1996 and changed to the AFTF on 1 June 2002 when this TO went to digital media. The following is the Design Modification Effective Dates:
Design Number Model Number Date CFRTF-3 Original 1991 CFRTF-3 Mod-1 14 June 1995 CFRTF-3 Mod-2 21 September 1995 CFRTF-3 Mod-3 22 December 1995 CFRTF-3 Mod-4 26 July 1996 CFRTF-3 Mod-5 9 August 1996 CFTRF-3-P N/A 1 October 1997 AFTF-P-4.0 N/A 1 December 2009
AFTF-P-4.1 N/A 2013
6 MANUAL STRUCTURE.
This manual is divided into WPs and SWPs. Each WP is an independent, task-oriented unit. Only essential information is provided. WPs cover the subjects of alphabetical indexes, foreword, theory of operation, operating instructions, trouble-shooting, inspection, and repair. A WP is subdivided into SWPs when one division by WP is not sufficient to maintain a logical sequence of data, for clarity, or to isolate specific maintenance level requirements.
7 WP BREAKOUT.
The Alphabetical Index (WP 001 00) provides a complete list of all WPs and SWPs.
8 LOCATING INFORMATION.
The Numerical Index of Effective Work Packages lists, in numerical order, all WPs and SWPs contained in this manual and provides the model application for each WP/SWP. The Alphabetical Index WP lists, in alphabetical order, all WPs and SWPs contained in this manual. Each WP/SWP contains a table of contents which lists all procedures contained in that WP/SWP. Reference to paragraphs, tables, or figures within a WP are made by number, e.g. “paragraph 7, table 2, or figure 3.” A reference to another WP merely includes the WP or SWP number, e.g., “WP 004 00 or SWP 004 01.” To find a particular procedure or topic, it is necessary to refer to that WP or SWP.
9 LEADING PARTICULARS.
Due to the nature and geographic diversity of each site, it would be impractical to list all leading particulars in this manual. Wherever possible, those items with a high prob-ability of site specific installation will be identified by the words, “if applicable”.
10 MAINTENANCE CONCEPT.
Civil Engineering or contractor personnel will maintain this facility. The replacement of valves, piping, etc., and clean-ing, painting, lubricating and corrosion control will be ac-complished utilizing established Civil Engineering proce-dures and per the manufacturer’s instruction. WP 007 00 contains excavation procedures for gaining access to and subsequent back fill of underground components. Inspection criteria for specific components will be as per this manual and manufacturer’s instruction.
11 USE OF SHALL, WILL, SHOULD AND MAY.
Use of the word “shall” indicates a mandatory provision that is binding. Use of the words “should” and “may” express non-mandatory provisions. The word “will” is used to ex-press a declaration of purpose. “Will” may also be used to show simple futurity, e.g., “Power for the meter will be pro-vided by the ship”.
12 TIME COMPLIANCE TECHNICAL ORDERS
(TCTO).
The following TCTOs are applicable to the Aircraft Fire Training Facility.
List of Time Compliance Technical Orders None
13 PRINCIPLES OF OPERATION.
13.1 Description. The Air Force Aircraft Fire…
This is the start of the file's text. The full file is on GovTribe.
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| SATELLITE_TV_COMBO_-_Amend_1.docx | DOCX document | |
| SEC_FORCES_APPENDIX.docx | DOCX document | |
| WD_Burlington_Co.pdf | ||