1. Air-handler Unit #5 Cooling Coil- Specification Data Diakin McQuay
Model# LSL137DV Serial# 35G01297-04
Part# 603614-060
a. Quantity: 2
b. Coil Type: Water
c. Circuiting: Double Circuit
d. Fins Per Inch: 6
e. Fins: 0.006”- 0.0095”
f. Rows Deep: 8
g. Fin Design: Corrugated Aluminum
h. Fin Height (inches): 24”
i. Finned Length (inches): 107.5”
j. Face Area (Sq. Ft): 35.9
k. Casing: 16 Gauge Galvanized Steel
l. OD Tubes: 0.625
m. Entering Air W/B D/B: 81.0
n. Leaving Air W/B D/B: 66.0
o. Total Output (min MBH): 512.7
p. Sensible Output (min MBH): 457.2
q. Air Flow Coil: Right Hand
r. CFM: 17,800
2. Air-handler Unit #6 Cooling Coil- Specification Data Diakin McQuay
Model# LSL114DV Serial# 35G01303-4
Part# 603614-070
a. Quantity: 1
b. Coil Type: Water
c. Circuiting: 1 ½ Circuit
d. Fins Per Inch: 6
e. Fins: 0.006”- 0.0095”
f. Rows Deep: 8
g. Fin Design: Corrugated Aluminum
h. Fin Height (inches): 30”
i. Finned Length (inches): 70.5”
j. Face Area (Sq. Ft): 14.7
k. Casing: 16 Gauge Galvanized Steel
l. OD Tubes: 0.625
m. Entering Air W/B D/B: 89.2
n. Leaving Air W/B D/B: 67.5
o. Total Output (min MBH): 247.6
p. Sensible Output (min MBH): 194.5
q. Air Flow Coil: Right Hand
r. CFM: 6,800
3. Air-handler Unit #7 Cooling Coil- Specification Data Diakin McQuay
Model# LSL141DH Serial# 35G01577-04
Part# 603614-080
a. Quantity: 2
b. Coil Type: Water
c. Circuiting: Double Circuit
d. Fins Per Inch: 6
e. Fins: 0.006”- 0.0095”
f. Rows Deep: 8
g. Fin Design: Corrugated Aluminum
h. Fin Height (inches): 27”
i. Finned Length (inches): 107.5”
j. Face Area (Sq. Ft): 40.4
k. Casing: 16 Gauge Galvanized Steel
l. OD Tubes: 0.625
m. Entering Air W/B D/B: 81.7
n. Leaving Air W/B D/B: 66.6
o. Total Output (min MBH): 657.9
p. Sensible Output (min MBH): 550.3
q. Air Flow Coil: Right Hand
r. CFM: 21,350
APPENDIX A
MECHANICAL SCHEDULE – COOLING COIL DATA AND FAN DATA
AHU #5 #6 #7
| Purchase Replacement Central Air handler Cooling Coils for Building 1385 BX Main Exchange located at 2180 REESE ST. |
| A. Mechanical Schedule- Cooling Coil Data and Fan Data |
| APPENDIX A |