FOR OFFICIAL USE ONLY

Statement of Work for the Uninterrupted Power Supply (UPS) Maintenance Agreement with the Guided Weapons Evaluation Facility (GWEF)

1. Background

The Guided Weapons Evaluation Facility (GWEF), 782d Test Squadron (782 TS), 96th Range Group (96 RANG), 96th Test Wing (96 TW) at Eglin AFB, FL, has a base of Eaton Uninterruptable Power Supply (UPS) systems installed throughout the facility to provide electrical filtering and backup for critical test systems that can be damaged by the unexpected loss of power or fluctuations (e.g. "brown-outs"and "spikes") in the commercial power.

Objective

The objective is to establish a service agreement for preventative and emergency maintenance of the UPS systems. Service provider shall use Eaton Certified Technicians with access to manufacturer proprietary diagnostic software and routines. ·

Services Required

Annual UPS Preventive Maintenance (PM) examination during normal business hours (Mon-Fri 8AM-SPM):

Provide trained repair personnel with manufacturer's proprietary system diagnostic tools for all PM visits
Repair and/or replace any damaged or defective components
Inspect all printed circuit board connections for cleanliness, swab contacts clean if necessary
Inspect all power connections for signs of overheating
Inspect all subassemblies, bridges and inverter legs for signs of component defects or stress
Inspect all AC and DC capacitors for signs of leakage
Review alarm logs to determine any chronic unusual events noted by the UPS
Provide input, output and internal voltage and current measurements via a detailed uniform format report for each UPS
Inspect for, and perform as required, any open engineering changes or manufacturer recommended firmware upgrades
Provide a Conttact Summary Report (Annual Maintenance) for each annual inspection (CDRL AOOl )

Annual Battery Preventive Maintenance examination of 5 of 8 battery strings (200 of 320 batteries) during normal business hours (Mon-Fri 8AM-5PM):

Examine the UPS alarm log for alarms relating to possible battery issues
Visually inspect all batteries for excessive case distortion or post corrosion
Note and clean any connections which appear dirty, sulfated or corroded
Record charger output current and voltage and total string voltage
Record isolated voltage and internal impedance of each battery
Check ambient temperature and connection resistance of at least one negative connection on each of 10 battery trays
Re-torque connections of and re-measure any battery whose impedance seems unusually high vs others in the string
Create well-formatted report noting measured parameters, corrective actions taken and any resulting recommendations
Provide a Contract Summary Report (Annual Maintenance) for each annual inspection (CDRL AOOl )

Emergency Repair Service:

Provide technically trained help desk services, 24 hrs/day, 7 days/week at no additional charge
Provide normal duty hour call-back services at no additional charge
Provide ONSITE emergency service response during THE NEXT BUSINESS DAY (Mon-Fri 8AM-5PM) after notification
Provide trained repair personnel with manufacturer's proprietary system diagnostic tools for all service visits
Provide parts replacement including faulty circuit boards, capacitors and fuses, etc., except faulty batteries
Provide battery diagnostic efforts in resolving any issue which may be battery related

Ifone to four batteries are faulty, remove one or four and re-index the UPS to operate .on

39 or 36 batteries

Include all travel, emergency parts' shipment and other expenses in the proposed cost
Maintain a complete parts inventory within one day transit distance of the site
Provide a Government Furnished Inspection Equipment Maintenance Report for each emergency repair service (CDRL A002)

Product Line to be Serviced

The GWEF currently has eight (8) Eaton Powerware UPS systems installed throughout the facility. Model and serial numbers follow.

a.Eaton Powenvare Model 9330-160-42 UPS
•SIN#: EF341CBB02 (UPS-9, R-229)
•SIN#: EE492CBB09 (UPS-11, R-226)

b. Eaton Powerware Model 9390-80-42 UPS

•SIN#: EF334CAB02 (UPS-3, R-146)
•SIN#: EF334CAB04 (UPS-4 R-109)
•SIN#: EF334CAB05 (UPS-7, R-210)
•SIN#: EF335CAB01 (UPS-8, R-224)
•SIN#: EF335CAB02 (UPS-2, R-106)
•SIN#: EB412CAA01 (UPS-10, R-134)

S. Place of Performance

Work required to accomplish this task will be conducted at the Government Facility located at 211 W. Eglin Blvd., Eglin AFB FL 32542-5429.

6. Period of Performance

One base year plus three option years