1. Describe your NEED: Facility 996. A commodity, “Chiller “machine that removes heat from a liquid via a vapor-compression or absorption refrigeration cycle. This liquid can then be circulated through a heat exchanger to cool air or equipment as required. As a necessary byproduct, refrigeration creates waste heat that must be exhausted to ambient or, for greater efficiency, recovered for heating purposes
Water Cooled Chiller CGWR-40ton Specifications TAG(S) CH-1 MAKE TRANE MODEL# CGWR MINIMUM CAPACITY (TONS) 40
COMPRESSOR TYPE/NO COMP SCROLL/3 ELECTRICAL (V/Phase/Hz) 208/3/60 TOTAL POWER (kW) 32.5
MCA (AMPS) 162 MOCP (AMPS) 225 NO. REFRIGERANT CKTS 2 REFRIGERANT R-410A REFRIGERANT CHARGE (CKT1/CKT2)
24/24 EVAPAPORATOR LWT/EWT (F) 44/54 CONDENSER LWT/EWT (F) 95/85 FLOW (GPM) EVAPORATOR/CONDENDESER
103.3/126.5 MAXIMUM PRESSURE DROP (ft. H20) EVAPORATOR/CONDENSER 6.53/8.13 FOULING FACTOR (HR-SQ FT-DEG
F/BTU) EVAPORATOR 0.000100 COOLING MEDIUM EVAP WATER
FOULING FACTOR (HR-SQ FT-DEG F/BTU) CONDENSER 0.000250 COOLING MEDIUM CONDENSER WATER
MAXIMUM OPERATING WEIGHT (LBS) 1577
NOTES: 1. PROVIDE SINGLE POINT POWER CONNECTION WITH CONTROL POWER TRANSFORMER
2. CONDENSER MUST BE SHELL AND TUBE. PLATE AND FRAME NOT ACCEPTABLE 3. PROVIDE LON CARD INTERFACE
CONNECTION TO EMCS. ALL POINTS LISTED ON THE ATTACHED PTS. LIST SHALL BE PASSED TO EMCS. 4. PROVIDE
CONDENSER WATER REGULATING VALVES. 5. FACTORY START UP SERVICES BY MANUFACTURER. 6. FACTORY
NEOPRENE ISOLATORS. 7. MINIMUM OF (2) REFRIGERANT CIRCUITS
8. FIVE YEAR MOTOR/COMPRESSOR PARTS WARRANTY 9. FACTORY INSTALLED FLOW SWITCH
10. CHILLER MUST MEET ASHRAE 90.1-2004 @ FULL ARI CONDITIONS. 11. FACTORY INSULATION - ALL COLD PARTS. 12.
FACTORY REFRIGERANT ISOLATION VALVES. 13. FUSED DISCONNECT SWITCH. 14. EVAPORATOR WYE STRAINER WITH
INSTALL KIT.