Item 0002 Chiller Model CGWR - 40 Ton Characteristics

View the file

Other files for this federal contract opportunity

Other files attached to Chillers bldg 996 & 425 PAFB, FL., newest first.
File Type Posted
Notice_of_Award_Phoeniz_Ltr.pdf PDF
FA252119QA002_Questions_&_Answers.pdf PDF
Salient_Chiller_RTWD_120_b.425.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. Describe your NEED: Facility 996. A commodity, “Chiller “machine that removes heat from a liquid via a vapor-compression or absorption refrigeration cycle. This liquid can then be circulated through a heat exchanger to cool air or equipment as required. As a necessary byproduct, refrigeration creates waste heat that must be exhausted to ambient or, for greater efficiency, recovered for heating purposes

Water Cooled Chiller CGWR-40ton Specifications TAG(S) CH-1 MAKE TRANE MODEL# CGWR MINIMUM CAPACITY (TONS) 40

COMPRESSOR TYPE/NO COMP SCROLL/3 ELECTRICAL (V/Phase/Hz) 208/3/60 TOTAL POWER (kW) 32.5

MCA (AMPS) 162 MOCP (AMPS) 225 NO. REFRIGERANT CKTS 2 REFRIGERANT R-410A REFRIGERANT CHARGE (CKT1/CKT2)

24/24 EVAPAPORATOR LWT/EWT (F) 44/54 CONDENSER LWT/EWT (F) 95/85 FLOW (GPM) EVAPORATOR/CONDENDESER

103.3/126.5 MAXIMUM PRESSURE DROP (ft. H20) EVAPORATOR/CONDENSER 6.53/8.13 FOULING FACTOR (HR-SQ FT-DEG

F/BTU) EVAPORATOR 0.000100 COOLING MEDIUM EVAP WATER

FOULING FACTOR (HR-SQ FT-DEG F/BTU) CONDENSER 0.000250 COOLING MEDIUM CONDENSER WATER

MAXIMUM OPERATING WEIGHT (LBS) 1577

NOTES: 1. PROVIDE SINGLE POINT POWER CONNECTION WITH CONTROL POWER TRANSFORMER

2. CONDENSER MUST BE SHELL AND TUBE. PLATE AND FRAME NOT ACCEPTABLE 3. PROVIDE LON CARD INTERFACE

CONNECTION TO EMCS. ALL POINTS LISTED ON THE ATTACHED PTS. LIST SHALL BE PASSED TO EMCS. 4. PROVIDE

CONDENSER WATER REGULATING VALVES. 5. FACTORY START UP SERVICES BY MANUFACTURER. 6. FACTORY

NEOPRENE ISOLATORS. 7. MINIMUM OF (2) REFRIGERANT CIRCUITS

8. FIVE YEAR MOTOR/COMPRESSOR PARTS WARRANTY 9. FACTORY INSTALLED FLOW SWITCH

10. CHILLER MUST MEET ASHRAE 90.1-2004 @ FULL ARI CONDITIONS. 11. FACTORY INSULATION - ALL COLD PARTS. 12.

FACTORY REFRIGERANT ISOLATION VALVES. 13. FUSED DISCONNECT SWITCH. 14. EVAPORATOR WYE STRAINER WITH

INSTALL KIT.