Here are the requirements for the Lap Pool Heater
1 lap pool heater that is at least a 1.8 million BTU heater powered by natural gas to heat 250,000 gallons of chorine water to a temperature of at least 78 degrees Fahrenheit
All fittings/pipes need to be made of galvanized metals since they will be exposed to the climate
Unit must be able to connect to existing piping located above ground level
Unit requires a ventilation kit
A new breaker to support new unit must be installed in an existing breaker box by the contractor
All labor, installation and delivery must be handled by contractor
A warranty of at least 1 year on labor and unit from date of install
Installers must be able to gain access to PAFB through for install. Security Forces will check backgrounds.