FT/LDH-1000 -4-10-18

Andrews AFB MODEL FT/LDH 1000 (4-10-18) 1000 Gallon Foam Resupply Trailer Specifications

TABLE OF CONTENTS

Section I - Trailer, Tank, and Compartments

Paragraph A-Trailer Frame

Paragraph B-Foam Tank

Paragraph C-Compartments

Section II - Pump

Paragraph A-Pump

Paragraph B- Pump Connections and Piping

Section III - Accessories

Paragraph A-Suction hose

Paragraph B- Filling accessories

Paragraph C- Manuals

Paragraph D – Wheel chocks

Section IV – Painting and lettering

Paragraph A – Trailer Painting

Paragraph B - Lettering

Section V – Warranties

Section VI – Options

Paragraph A – Tank Painting

Paragraph B – Generator and Light Package

SPECIFICATIONS

Mobile Foam Resupply Trailer

The following specifications are for a mobile foam resupply trailer of 1000 gallon capacity with accessories for use as a firefighting unit.

The trailer is intended to be towed by a support vehicle, of adequate capacity, to the scene of a fire and/or various types of spills for the purpose of fire suppression support. A one person operation shall allow for the transfer of foam to the fire at the scene of major incidents.

Product shall be completely brand new and of the best quality materials currently used in commercial practice for emergency vehicle fabrication. Materials that deteriorate when exposed to sunlight, extreme weather or operational conditions shall not be used or shall have a means of protection against such conditions that will not prevent compliance with performance standards. Protective coatings that chip, crack, or scale with age or extremes of climatic conditions or by exposure to heat or cold shall not be used.

Vendor shall demonstrate that the product offered for this bid is a proven foam resupply of a type that has been manufactured for (and successfully used by) other emergency services. The vendor shall be certified to the ISO 9000:2015 standard.

The foam resupply trailer offered shall comply with all applicable Motor Carrier Safety Regulations, as it pertains to municipal emergency firefighting, concerning size, weight, brakes, lights, load rating and balance. Conformance must meet FMVSS #108, FMVSS #115, FMVSS #120, and FMVSS #125 as stated in FCR title 49 in effect at time of delivery. The trailer shall comply with the NFPA 1901 chapter 26 standard on fire department trailers. Incoming exemptions applicable to municipal fire departments shall be permitted.

Weight shall be distributed as equally as practical over the axles and tires of the fully loaded vehicle. Fully loaded units that are unbalanced during stand alone operations or while being towed will not be accepted. Tires, wheels and axles shall be adequately sized for the load imposed by the in service weight of the completed trailer.

The use of proven nonmetallic materials in lieu of metal is permitted if that use contributes to reduced weight, lower cost or less maintenance and there is no degradation in performance or increase in long term operations and maintenance costs.

Foam resupply trailer must be constructed with lowest possible center of gravity when fully loaded with foam concentrate, tools and the appliances specified herein.

Performance must be commensurate with smooth and safe highway and moderate off highway operation. Proper weight and balance configuration is essential.

I. TRAILER, TANK, AND COMPARTMENTS

A. TRAILER FRAME

GVWR – Gross vehicle weight rating shall not exceed 14,000 pounds when fully loaded and equipped. Weight of foam shall not exceed 8.5 lbs/gallon

Size – Overall size of completed trailer (less packaging) not to exceed (approx.) 234” long, 88" wide, 80” high when measured from the ground surface.

Frame Weldment – The main trailer platform, cross members and a-frame hitch shall be constructed from rectangular tube steel and entirely MIG welded for maximum strength and torsional stiffness. Frame cross members shall be adequately spaced to support the load of the tank. A channel shaped rear bumper shall be included at the rear behind the tank to protect the rear of the tank. A .125 high bright aluminum diamond plate step area approximately 8” deep x 60” wide shall be provided for reaching the top of the foam tank. The A-Frame nose tubes shall under lap the main frame tubes for maximum strength in this area. A .187 thick steel plate shall be provided at the nose area of the trailer for the mounting of the transfer pump.

Lashing Points – There shall be (4) lashing points which shall allow the trailer to be safely lashed to the deck of a trailer should the trailer need to be moved other than towing

it. These lash points shall be made from ¾” diameter solid steel and bent to form a “V” and shall be positioned appropriately (2) each side of the main trailer frame tubes.

Fenders – Trailer fenders shall be heavy duty steel diamond plate type with center reinforcement supports. They shall support a firefighter in full turnout gear. The tops and slanted portions of the fenders shall have non-slip aluminum diamond plate surfaces.

Axles- There shall be two axles, each with a rated capacity of 7,000 lbs. properly located under the trailer frame. Each wheel is to have individual functioning electric brake.

Brakes shall have slack adjusters accessible from the back side of the backing plate. The bearings shall be sealed grease type. Hubs shall be cast type with pressed in wheel studs.

The suspension shall meet or exceed the capacity of the axles and shall have slipper type springs. The main equalizer pivot point of the suspension shall have grease fittings.

Tail, Clearance and License Plate Lights – The trailer lighting shall comply with FMVSS section 108 of FCR 49. There shall be two combination LED stop-tail-turn lights recess and shock mounted into a channel bumper at the rear of the trailer. Individual clearance lights on brackets shall mark the corners and rear of the trailer as required. A license plate light and bracket shall be located on the street side rear tapered plane of the fender.

Tires and Wheels – Tires to be minimum ST235-80R16 tires. Wheels to be 6” x 16” and rated for 3500 lbs. at 80 psi.

Draw bar – A 3” ID ring type drawbar shall be provided. Safety chains with slip hooks shall be rated for 14,000 lbs. each shall be provided at the front of the trailer. A break away line and trailer mounted battery shall be provided to activate brakes should the trailer become uncoupled from the tow vehicle.

“A” Frame Stand - One heavy duty, 5,000 lb. capacity crank down detachable type stand to support the loaded trailer during stand alone trailer operations shall be provided.

Trailer Electrical Plug – A round 7 pin male electrical circuit plug shall be provided at the extreme front of the nose tube with at least a 30” cord extending beyond the front of the trailer. The matching female plug shall be provided with a wiring diagram for proper interface between the tow vehicle and the trailer. The main power cord shall terminate into a main sealed junction box located under the nose of the trailer. All wiring shall extend from this box as required. Wiring shall be heavy duty all weather type insulated sized properly for all applied loads and protected from damage by foam concentrate overflow and normal use. An electrical schematic is to be provided for wiring tow vehicle. All wiring to be GXL cross linked with color coded function imprint every 4” wherever practical. All wiring shall be in protected channels or metal conduit.

Warning Lights - Two 3" x 7" LED red flashing lights shall be provided on the rear and each side of the trailer. These lights shall be powered from the vehicles emergency light circuit.

Work Lights – Two 2.5" x 6" clear LED lights shall be mounted (1) each side of the pump to illuminate all pump and piping controls for night operation. The switch for these lights shall be on the pump control panel. The power for these lights shall be from the main tail light circuit when the trailer is plugged into the tow vehicle.

B. FOAM TANK

Size – Capacity for 1000 U.S. gallons. Low center of gravity type with adequate baffles.

Construction - The foam tank shall be constructed from ½” and ¾” thick PT III E co-polymer sheet stock. The material shall be a non-corrosive stress relieved thermo-plastic, black in color and UV stabilized for maximum protection. The tank shall be designed to be an independent component of the completed vehicle. All joints shall be welded using Nitrogen shielding gas and tested for maximum weld integrity. The transverse partitions are to be fabricated from 3/8 polypropylene and shall be black in color and shall extend from within 4” of the tank floor to the underside of the covers. The longitudinal partitions shall be fabricated from ½” polypropylene (black in color) and extend from the floor thru the covers to allow for positive welding and maximum integrity. All partitions shall be equipped with vent and flow holes to permit proper flow of foam and air within the tank under all conditions. All partitions interlock with each other and are fully welded to the sidewalls of the tank as well as to each other. The tank covers shall be of a flush design to eliminate trapping of water or foam on the top surface.

Fill Tower - A fill tower shall be constructed which will allow the tank to be filled from 5 gallon foam cans. This tower shall be configured to allow two cans to be poured simultaneously into the foam tank. The tower shall have (2) recessed pockets which hold each of the 5 gallon cans in place. The design shall let the main tank vent as well as positioning the 5 gallon cans to fully self draining. The tower shall have a hinged lid and a retaining devise to stop the lid from folding over on itself. Two pressure/vacuum vents shall be installed in this tower lid to eliminate air exchange unless foam is pumped into or out of the main tank or if thermal expansion or contraction of the liquid occurs. A label on the outside of the tower shall read “FOAM CONCENTRATE ONLY”.

Sump

A sump shall be provided to trap any foreign items that may become trapped in the tank.

The sump shall be fabricated from ½” copolymer sheet stock and shall be permanently welded to the bottom of the tank.

Sump Drain

The floor of the sump shall be fitted with drain outlet. A 3” port in the sump shall be piped to a 1-1/2” ball valve to allow the tank to be drained. The outlet shall be a 1-1/2” NST female swivel with a tethered plug. The valve shall be labeled “DRAIN – FOAM

CONCENTRATE”.

Gauge – A vertical 2” wide translucent section of the tank shall be provided near the pump operator’s position to accurately monitor foam level within the tank. Tanks utilizing electronic level devises will not be acceptable.

C. COMPARTMENTS

Hose Compartments- There shall be two (2) cross lay type hose beds approximately 12”H x 13” W across the front of the tank. Each compartment shall have a minimum capacity of 200 feet of 1.75” double jacketed fire hose. These hose beds shall hold the hose to be used for foam concentrate transfer operations. Each cross lay shall be labeled “CROSS LAY – CONCENTRATE #1, AND CROSSLAY CONCENTRATE #2" respectively. A vinyl cover shall be provided over these hose beds.

Tool/Adapter/Accessory/Compartments – There shall be one compartment on top of the foam tank immediately behind the cross lay beds on the street side constructed of polypropylene. The compartment shall be fitted with a bright aluminum diamond plate cover and equipped with a hold open devise and a draw type latch. A weather resistant seal shall be provided on the cover. Drain provisions to allow any water entering the compartment to drain out shall be provided.

Large Diameter Hose bed – A hose bed open to the rear of the trailer shall be provided on top of the tank. It shall be the entire top width of the tank and shall occupy approximately two thirds of the total tank top surface. The bed shall have 3 sides to form the walls. The side walls shall be capped with 1” OD tubes with a rear 3” radius to allow hose to pay out without damage. This hose bed area shall have a capacity of 800 ft of 5” LDH or 1000 ft of 4” LDH. A vinyl cover shall prevent the accidental deployment of the rear hose.

II. PUMP

A. Pump

There shall be a 100 GPM self–priming gasoline driven pump for on loading and off loading the foam concentrate. Pump to be cast iron with foam resistant internal components. Pump is to have an electric start with recoil back-up, fuel tank and battery.

A battery box shall be fabricated from ¼” co-polymer polypropylene sheet stock to hose battery. This box shall have a removable cover and shall have 5” x 5” vented side panel.

The pump shall be mounted at front on the “A” frame portion of the trailer frame. A plastic isolator shall be installed under pump to eliminate contact of dissimilar metals.

Provisions to manually fill the pump initially shall be provided. This shall be labeled “FILL TO PRIME”. A yellow warning label shall be placed near the pump starter controls which reads. “DO NOT RUN ENGINE WITH PUMP DRY OR THE PUMP

SEAL WILL BE DAMAGED. FILL PRIME PORT PRIOR TO STARTING”.

B. Pump Connections and Piping

The permanently mounted pump shall be capable of pumping foam concentrate from the tank or from 55 gallon drums. All piping shall be stainless steel or high pressure foam resistant hose. All concentrate valves shall be bronze body full flow with chrome plated brass ball with a nylon seat. Valves shall have lever type handles for rapid opening and closing.

NOTE: All plumbing shall be designed for easy maintenance and/or replacement using grooved couplings or mechanical couplings.

1. Provide one (1) each 2" suction piping arrangement from the tank to the pump with a 1/4 turn tank isolation valve mounted at the tank. There shall be a label to identify this valve as “TANK TO PUMP”

2. Provide one (1) each 1.5" NSTM inlet on main tank to pump (suction) line to be used as an auxiliary suction port connection for a pick up tube device through the suction side of the pump. Also, provide cap and chain for the 1.5" inlet. This inlet shall be labeled “AUX. SUCTION”

3. Provide two (2) 1.5” gated concentrate outlets from discharge side of pump. Both shall be plumbed to the bottom of each of the two cross lay hose compartments for concentrate transfer operations. Each discharge shall terminate in a 1.5” 90° continuous type brass swivel device mounted below hose beds to facilitate left or right side deployment of foam supply hose without kinking.

from the pump. Each valve shall be labeled “CROSS LAY – CONCENTRATE #1, AND CROSS LAY CONCENTRATE #2", respectively.

4. Provide (1) gated concentrate outlet from the pump back to the tank to allow foam to be on loaded into the tank from the on-board pump. The inlet connection within the tank shall extend straight downward to within 1” of the floor to reduce foam agitation while filling.

III. Accessories

Provide the following accessories for use with the foam resupply trailer:

A. Suction Hose - Provide one (1) each approximately 72” long clear PVC 1.5" suction line with an 18” and a 40” PVC pipe pick up tube for drawing concentrate from 5gallon cans or from 55gallon barrels. This suction hose assembly shall also have a PVC 1-1/2” quarter turn ball valve located at the suction end of the hose to allow the pump operator to control foam flow into the pump while switching concentrate supply containers.

Provisions shall be made to safely carry these items on the trailer.

B. Fill Nozzles - Provide two fill nozzles for the end of each of the concentrate hose bed hoses. Each fill nozzle shall consist of a 1-1/2” quarter turn PVC ball valve with a 1- 1/2 NSTF swivel inlet x 1-1/2 NSTM outlet. These are to allow for direct bottom filling of foam tanks. Two 90degree pipe extensions shall be included that are approximately 42” in length and have a 1-1/2” NSTF swivel inlet connection. These can be added to the fill valves for top filling of other foam tanks through their fill towers. Provisions shall be made to safely carry these items on the trailer.

C. Manuals/Instruction - Technical manuals, parts manuals, and repair manuals for all installed equipment and accessories shall be provided with the trailer. They shall include all maintenance recommendations and full operational information for each function that the trailer is designed to perform.

D. Wheel Chocks - One set of wheel chocks shall be provided to allow the trailer to operate as a stand-alone unit. Provisions shall be made to safely carry these wheel chocks on the trailer.

IV. TREATING AND PAINTING

A. PAINTING AND LETTERING

A proven paint system shall be used to prime and paint the foam resupply trailer frame with appropriate color paint and shall be of an automotive quality finish. The trailer shall be sandblasted and painted Air Force red.

The tank shall be unpainted with a manufactured black smooth finish.

Lettering shall be provided on each side of the tank, on the stripe and shall not exceed 60 letters. All lettering shall be on the Scotchlite stripe.

A six-inch white Scotchlite stripe shall be provided on the front and sides of the trailer.

A 6” chevron pattern of red and yellow strips shall be provided on the rear of the trailer. (NFPA NPN) A 6” chevron pattern of red and yellow strips shall be provided on the rear of the trailer. (NFPA NPN)

B. LABELS:

All devices will have fixed weatherproof labels or tags. Instructional plates will be mounted directly adjacent to operational controls.

V. WARRANTIES

A. GENERAL WARRANTY

The contractor shall warranty the foam resupply trailer to be free from defects in material and workmanship under normal use and service for a period of two

(2) years. The obligation under this warranty is to cover minor materials and workmanship supplied that should fail within that two (2) year period. (See B.

and C. for other specific warranties) A copy of this warranty shall be provided with the trailer upon delivery.

B. TRAILER FRAME AND TANK WARRANTY

Provide a two (2) year warranty on the trailer frame and related parts. Items such as tires, brakes and other normal wear items are excluded from this warranty.

A lifetime warranty shall be provided for the foam tank which includes labor and materials should the tank fail. A copy of this warranty shall be provided with the trailer upon delivery.

C. OTHER WARRANTIES

All additional equipment such as pumps, valves, generators, appliances and equipment shall be warranted by its manufacturer per the applicable warranty provided by its manufacturer. The trailer manufacturer shall not extend these warranties if they are less than the standard two year warranty as described in section V. A.

VI. OPTIONS

A. TANK PAINT

A proven paint system shall be used to prime and paint the foam resupply trailer frame with appropriate color paint and shall be of an automotive quality finish.

The copolymer foam tank and the walls of the attached hose beds shall be painted to match the steel trailer frame. The tank process shall include special adhesion promoters and the proper primer and paint that is compatible with the copolymer material. Areas inside the hose beds and compartments shall not be painted.

B. GENERATOR AND LIGHT PACKAGE

A Honda 2000 watt / 12volt gasoline driven generator shall be mounted on the trailer using rubber isolators.

Two 120volt x 500watt Fire Research Focus light heads on telescopic aluminum poles, mounted one each side, shall be mounted to the side of the foam tank on external mounting blocks. The lights shall be switched at the light head and shall be hard wired to the generator. All wires shall be run in flexible conduit as practical. Each light head shall have a snap on wire frame shield to protect the lens.

C. FOAM MONITOR WITH NOZZLE

The trailer shall have a pre-piped 3” riser with a 5” Storz inlet located at the front of the trailer ahead of the tank. There shall be a cap for the 5” inlet connection with a chain to connect it to the trailer.

A 3” vertical pipe riser shall be permanently attached to the trailer frame.

A bronze 3” full flow valve shall be provided in this riser. A 500 gpm flow adjustable nozzle with a 3% mixture rate shall be mounted on the monitor and shall be connect to an internal foam tank pick up tube through a clear hose. The hose connection at the tank shall be a cam and groove coupler to allow for easy flushing of the hose.

1000 Gallon Foam Resupply Trailer Specifications
B. FOAM TANK
C. COMPARTMENTS
II. PUMP
B. Pump Connections and Piping
III. Accessories