Drawings OR Rewire.pdf

PDF 6 MB Posted

Attached to
Y1DA--PROJECT # 688-24-101 EMERGENCY REWIRE OR CIRCUITS Federal contract opportunity
Solicitation number
36C24524B0007
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 5

About this file

This is a solicitation for a construction project to rewire operating room circuits and install additional isolated power systems at the Veterans Affairs Medical Center in Washington D.C. The scope of work includes demolishing existing feeds from normal distribution and providing new feeds from emergency distribution for each of five operating rooms. It also requires installing five additional 7.5kVA isolated power systems to supplement seven existing systems, one for each operating room. The contractor must balance loads between new and existing systems, update panel schedules and device labeling, and certify the systems for patient use. Additional requirements include preserving and modifying operating room shielding, coordinating with facility staff, and obtaining independent certification of the isolated power systems. The period of performance is 180 calendar days from notice to proceed. The solicitation identifies various submittal and reporting requirements, safety protocols, infection control measures, hazardous material handling procedures, and other standard construction terms.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--PROJECT # 688-24-101 EMERGENCY REWIRE OR CIRCUITS, newest first.
File Type Posted
S05_RFI Response attachment_02.09.2024.pdf PDF
36C24524B0007 0002.docx DOCX document
36C24524B0007 0001.docx DOCX document
36C24524B0007_1.docx DOCX document
Specs OR Rewire_01.pdf PDF
RFI Submission 36C24524B0007.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

E101

OR #1 - ISOLATED POWER PLAN

Fi le

P at h

/1 5/

1:

:0

AM

FOR CONSTRUCTION

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

CORRECT CODE DEFICIENCY FOR

INCREASED ISOLATED POWER

688 - WASHINGTON D.C. VAMC

688-24-###

Project Director

NOV 1 2023 Chkd By DMWRevisions: Date:

1 DETAIL 1 - EXISTING

SCALE: 1/4" = 1' 2 DETAIL 2 - DEMOITION 3 DETAIL 3 - NEW WORK

GENERAL NOTES: (THIS SHEET)

KEYED NOTES: (THIS DETAIL)#

EXISTING TO REMAIN IPS IN OR #1.1

KEYED NOTES: (THIS DETAIL)#

PREPARE SPACE FOR NEW ADDITIONAL IPS; PROTECT

SHIELDING.

NOT USED.2

NOT USED.3

NOT USED.4

NOT USED.5

KEYED NOTES: (THIS DETAIL)#

PROVIDE NEW ADDITIONAL IPS IN OR #1 FED FROM 'ORNL'.1

DIVERSIFY LOADS BETWEEN EXISTING AND NEW IPS FOR MATCHED LEAKAGE

CURRENTS WITH FACILITY COORDINATION.

ONCE LOADS ARE BALANCED, CONTRACTOR TO UPDATE PANEL SCHEDULE AND

CIRCUIT IDENTIFIERS ON WIRING DEVICES.

NOT USED.4

NOT USED.5

1. CONTRACTOR SHALL COORDINATE ALL EFFORTS IN

ACCORDANCE WITH ENFORCED INFECTION CONTROL RISK

ASSESSMENT (ICRA) REQUIREMENTS.

2. ALL MATERIALS FURNISHED BY THE CONTRACTOR ARE

TO BE NEW AND APPROVED BY THE OWNER AS TO

MANUFACTURER AND TYPE.

3. ALL LOCATIONS AND DIMENSIONS SHOWN ARE

APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY

ALL ELECTRICAL EQUIPMENT LOCATIONS AND

EQUIPMENT DIMENSIONS. CONTRACTOR SHALL BE

RESPONSIBLE FOR PROVIDING EQUIPMENT THAT WILL

FIT IN THE SPACE ALLOTTED.

4. THE LOCATION OF UTILITIES AND STRUCTURES, BOTH

SURFACE AND SUBSURFACE, ARE SHOWN

ON THE PLANS FROM DATA AVAILABLE AT THE TIME OF

THE SURVEY AND ARE NOT NECESSARILY

COMPLETE OR CORRECT. THE EXACT LOCATION AND

PROTECTION OF UTILITIES AND STRUCTURES

IS THE RESPONSIBILITY OF THE CONTRACTOR. DURING

CONSTRUCTION THE CONTRACTOR SHALL

USE DILIGENCE TO PROTECT ALL EXISTING UTILITIES

AND STRUCTURES WHETHER SHOWN ON THE

PLANS OR NOT. IF DAMAGE IS CAUSED, THE

CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR

AND RESTORATION OF SAME IN ACCORDANCE WITH THE

DIRECTIONS OF THE ENGINEER AND FOR

ANY RESULTING CONTINGENT DAMAGES; GOVERNMENT

SHALL BEAR NO ADDITIONAL COSTS.

5. ONLY PULLBOXES SPECIFICALLY REQUIRED BY THE

ENGINEER IN LOCATIONS SHOWN ARE

IDENTIFIED. CONTRACTOR SHALL PROVIDE ALL

PULLBOXES REQUIRED TO MEET APPLICABLE

CODES.

6. CONTRACTOR TO COORDINATE WITH FACILITIES AND

BIOMEDICAL ENGINEERING FOR SEGREGATION AND

DIVERSITY OF LOADS BETWEEN THE EXISTING IPS AND

NEWLY INSTALLED IPS. CONTRACTOR TO BALANCE

LEAKAGE CURRENT. RE-LABEL PANEL SCHEDULES AND

FIELD DEVICES WITH ACCURATE CIRCUIT IDENTITY.

7. CONTRACTOR SHALL PRESERVE, REPAIR, AND

RE-CERTIFY ALL LEAD SHIELDING WHERE DAMAGED OR

AFFECTED WITHIN SCOPE OF WORK.

8. CONTRACTOR SHALL PRESERVE, PROTECT, AND REPAIR

ALL FINISHES SUBJECT TO DAMAGE WITHIN SCOPE OF

WORK. REPAIR OF DAMAGE MADE AT NO ADDITIONAL

COST TO THE GOVERNMENT.

NOT USED.2

NOT USED.3

NOT USED.4

NOT USED.5

SCALE: 1/4" = 1'SCALE: 1/4" = 1'

AutoCAD SHX Text

DICT

AutoCAD SHX Text 2E104C

AutoCAD SHX Text

MALE LOCKERS

AutoCAD SHX Text 2E104A

AutoCAD SHX Text

OPERATING RM OR-1

AutoCAD SHX Text 2E139

AutoCAD SHX Text

SPLINT PLASTER RM

AutoCAD SHX Text 2E138

AutoCAD SHX Text

SUB STERILE

AutoCAD SHX Text 2E137A

AutoCAD SHX Text G

AutoCAD SHX Text

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 19,21,23

AutoCAD SHX Text G

AutoCAD SHX Text

IPU#5

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

XIPU

AutoCAD SHX Text

3#10+1#10 EG

AutoCAD SHX Text

IN 3/4" CONDUIT

AutoCAD SHX Text J

AutoCAD SHX Text

3#6+1#10 EG

AutoCAD SHX Text

IN 1" CONDUIT

AutoCAD SHX Text

IPU#5

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text

IPU#5

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#5

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#5

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#5

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text 15,17

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

LIPU

AutoCAD SHX Text E

AutoCAD SHX Text J

AutoCAD SHX Text

IPU#5

AutoCAD SHX Text

DICT

AutoCAD SHX Text 2E104C

AutoCAD SHX Text

MALE LOCKERS

AutoCAD SHX Text 2E104A

AutoCAD SHX Text

OPERATING RM OR-1

AutoCAD SHX Text 2E139

AutoCAD SHX Text

SPLINT PLASTER RM

AutoCAD SHX Text 2E138

AutoCAD SHX Text

SUB STERILE

AutoCAD SHX Text 2E137A

AutoCAD SHX Text G

AutoCAD SHX Text

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 19,21,23

AutoCAD SHX Text G

AutoCAD SHX Text

IPU#5

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

XIPU

AutoCAD SHX Text

3#10+1#10 EG

AutoCAD SHX Text

IN 3/4" CONDUIT

AutoCAD SHX Text J

AutoCAD SHX Text

3#6+1#10 EG

AutoCAD SHX Text

IN 1" CONDUIT

AutoCAD SHX Text

IPU#5

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text

IPU#5

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#5

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#5

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#5

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text 15,17

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

LIPU

AutoCAD SHX Text E

AutoCAD SHX Text J

AutoCAD SHX Text

IPU#5

AutoCAD SHX Text

DICT

AutoCAD SHX Text 2E104C

AutoCAD SHX Text

MALE LOCKERS

AutoCAD SHX Text 2E104A

AutoCAD SHX Text

OPERATING RM OR-1

AutoCAD SHX Text 2E139

AutoCAD SHX Text

SPLINT PLASTER RM

AutoCAD SHX Text 2E138

AutoCAD SHX Text

SUB STERILE

AutoCAD SHX Text 2E137A

AutoCAD SHX Text G

AutoCAD SHX Text

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 19,21,23

AutoCAD SHX Text G

AutoCAD SHX Text

IPU#5

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

XIPU

AutoCAD SHX Text

3#10+1#10 EG

AutoCAD SHX Text

IN 3/4" CONDUIT

AutoCAD SHX Text J

AutoCAD SHX Text

3#6+1#10 EG

AutoCAD SHX Text

IN 1" CONDUIT

AutoCAD SHX Text

IPU#5

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text

IPU#5

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#5

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#5

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#5

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text 15,17

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

LIPU

AutoCAD SHX Text E

AutoCAD SHX Text J

AutoCAD SHX Text

IPU#5

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

E102

OR #2 - ISOLATED POWER PLAN

Fi le

P at h

/1 5/

1:

:0

AM

FOR CONSTRUCTION

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

CORRECT CODE DEFICIENCY FOR

INCREASED ISOLATED POWER

688 - WASHINGTON D.C. VAMC

688-24-###

Project Director

NOV 1 2023 Chkd By DMWRevisions: Date:

1 DETAIL 1 - EXISTING 2 DETAIL 2 - DEMOITION 3 DETAIL 3 - NEW WORK

GENERAL NOTES: (THIS SHEET)

KEYED NOTES: (THIS DETAIL)#

EXISTING TO REMAIN IPS IN OR #2.1

KEYED NOTES: (THIS DETAIL)#

PREPARE SPACE FOR NEW ADDITIONAL IPS; PROTECT

SHIELDING.

NOT USED.2

NOT USED.3

NOT USED.4

NOT USED.5

KEYED NOTES: (THIS DETAIL)#

PROVIDE NEW ADDITIONAL IPS IN OR #2 FED FROM 'ORNL'.1

DIVERSIFY LOADS BETWEEN EXISTING AND NEW IPS FOR MATCHED LEAKAGE

CURRENTS WITH FACILITY COORDINATION.

ONCE LOADS ARE BALANCED, CONTRACTOR TO UPDATE PANEL SCHEDULE AND

CIRCUIT IDENTIFIERS ON WIRING DEVICES.

NOT USED.4

NOT USED.5

1. CONTRACTOR SHALL COORDINATE ALL EFFORTS IN

ACCORDANCE WITH ENFORCED INFECTION CONTROL RISK

ASSESSMENT (ICRA) REQUIREMENTS.

2. ALL MATERIALS FURNISHED BY THE CONTRACTOR ARE

TO BE NEW AND APPROVED BY THE OWNER AS TO

MANUFACTURER AND TYPE.

3. ALL LOCATIONS AND DIMENSIONS SHOWN ARE

APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY

ALL ELECTRICAL EQUIPMENT LOCATIONS AND

EQUIPMENT DIMENSIONS. CONTRACTOR SHALL BE

RESPONSIBLE FOR PROVIDING EQUIPMENT THAT WILL

FIT IN THE SPACE ALLOTTED.

4. THE LOCATION OF UTILITIES AND STRUCTURES, BOTH

SURFACE AND SUBSURFACE, ARE SHOWN

ON THE PLANS FROM DATA AVAILABLE AT THE TIME OF

THE SURVEY AND ARE NOT NECESSARILY

COMPLETE OR CORRECT. THE EXACT LOCATION AND

PROTECTION OF UTILITIES AND STRUCTURES

IS THE RESPONSIBILITY OF THE CONTRACTOR. DURING

CONSTRUCTION THE CONTRACTOR SHALL

USE DILIGENCE TO PROTECT ALL EXISTING UTILITIES

AND STRUCTURES WHETHER SHOWN ON THE

PLANS OR NOT. IF DAMAGE IS CAUSED, THE

CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR

AND RESTORATION OF SAME IN ACCORDANCE WITH THE

DIRECTIONS OF THE ENGINEER AND FOR

ANY RESULTING CONTINGENT DAMAGES; GOVERNMENT

SHALL BEAR NO ADDITIONAL COSTS.

5. ONLY PULLBOXES SPECIFICALLY REQUIRED BY THE

ENGINEER IN LOCATIONS SHOWN ARE

IDENTIFIED. CONTRACTOR SHALL PROVIDE ALL

PULLBOXES REQUIRED TO MEET APPLICABLE

CODES.

6. CONTRACTOR TO COORDINATE WITH FACILITIES AND

BIOMEDICAL ENGINEERING FOR SEGREGATION AND

DIVERSITY OF LOADS BETWEEN THE EXISTING IPS AND

NEWLY INSTALLED IPS. CONTRACTOR TO BALANCE

LEAKAGE CURRENT. RE-LABEL PANEL SCHEDULES AND

FIELD DEVICES WITH ACCURATE CIRCUIT IDENTITY.

7. CONTRACTOR SHALL PRESERVE, REPAIR, AND

RE-CERTIFY ALL LEAD SHIELDING WHERE DAMAGED OR

AFFECTED WITHIN SCOPE OF WORK.

8. CONTRACTOR SHALL PRESERVE, PROTECT, AND REPAIR

ALL FINISHES SUBJECT TO DAMAGE WITHIN SCOPE OF

WORK. REPAIR OF DAMAGE MADE AT NO ADDITIONAL

COST TO THE GOVERNMENT.

NOT USED.2

NOT USED.3

NOT USED.4

NOT USED.5

SCALE: 1/4" = 1' SCALE: 1/4" = 1' SCALE: 1/4" = 1'

AutoCAD SHX Text

OR-2 ORTHOPEDIC OPERATING RM

AutoCAD SHX Text 2E137

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text E

AutoCAD SHX Text

OREP-

AutoCAD SHX Text 14,16,18

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text

OREP-

AutoCAD SHX Text 13,15,17

AutoCAD SHX Text

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 20,22,24

AutoCAD SHX Text M

AutoCAD SHX Text

WP

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 25,27,29

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

3#10+1#10 EG

AutoCAD SHX Text

IN 3/4" CONDUIT

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

XIPU

AutoCAD SHX Text

3#6+1#10 EG

AutoCAD SHX Text

IN1" CONDUIT

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text J

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

EF-6

AutoCAD SHX Text

ON ROOF.

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text

OR-2 ORTHOPEDIC OPERATING RM

AutoCAD SHX Text 2E137

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text E

AutoCAD SHX Text

OREP-

AutoCAD SHX Text 14,16,18

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text

OREP-

AutoCAD SHX Text 13,15,17

AutoCAD SHX Text

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 20,22,24

AutoCAD SHX Text M

AutoCAD SHX Text

WP

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 25,27,29

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

3#10+1#10 EG

AutoCAD SHX Text

IN 3/4" CONDUIT

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

XIPU

AutoCAD SHX Text

3#6+1#10 EG

AutoCAD SHX Text

IN1" CONDUIT

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text J

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

EF-6

AutoCAD SHX Text

ON ROOF.

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text

OR-2 ORTHOPEDIC OPERATING RM

AutoCAD SHX Text 2E137

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text E

AutoCAD SHX Text

OREP-

AutoCAD SHX Text 14,16,18

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text

OREP-

AutoCAD SHX Text 13,15,17

AutoCAD SHX Text

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 20,22,24

AutoCAD SHX Text M

AutoCAD SHX Text

WP

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 25,27,29

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

3#10+1#10 EG

AutoCAD SHX Text

IN 3/4" CONDUIT

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

XIPU

AutoCAD SHX Text

3#6+1#10 EG

AutoCAD SHX Text

IN1" CONDUIT

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text J

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

EF-6

AutoCAD SHX Text

ON ROOF.

IPU#4

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

E103

OR #3 - ISOLATED POWER PLAN

Fi le

P at h

/1 5/

1:

:0

AM

FOR CONSTRUCTION

U.S. Department of Veterans Affairs

A

B

C

D

E

F

5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

CORRECT CODE DEFICIENCY FOR

INCREASED ISOLATED POWER

688 - WASHINGTON D.C. VAMC

688-24-###

Project Director

NOV 1 2023 Chkd By DMWRevisions: Date:

1 DETAIL 1 - EXISTING 2 DETAIL 2 - DEMOITION 3 DETAIL 3 - NEW WORK

GENERAL NOTES: (THIS SHEET)

KEYED NOTES: (THIS DETAIL)#

EXISTING TO REMAIN IPS IN OR #3.1

KEYED NOTES: (THIS DETAIL)#

PREPARE SPACE FOR NEW ADDITIONAL IPS; PROTECT

SHIELDING.

NOT USED.2

NOT USED.3

NOT USED.4

NOT USED.5

KEYED NOTES: (THIS DETAIL)#

PROVIDE NEW ADDITIONAL IPS IN OR #3 FED FROM 'ORNL'.1

DIVERSIFY LOADS BETWEEN EXISTING AND NEW IPS FOR MATCHED LEAKAGE

CURRENTS WITH FACILITY COORDINATION.

ONCE LOADS ARE BALANCED, CONTRACTOR TO UPDATE PANEL SCHEDULE AND

CIRCUIT IDENTIFIERS ON WIRING DEVICES.

NOT USED.4

NOT USED.5

1. CONTRACTOR SHALL COORDINATE ALL EFFORTS IN

ACCORDANCE WITH ENFORCED INFECTION CONTROL RISK

ASSESSMENT (ICRA) REQUIREMENTS.

2. ALL MATERIALS FURNISHED BY THE CONTRACTOR ARE

TO BE NEW AND APPROVED BY THE OWNER AS TO

MANUFACTURER AND TYPE.

3. ALL LOCATIONS AND DIMENSIONS SHOWN ARE

APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY

ALL ELECTRICAL EQUIPMENT LOCATIONS AND

EQUIPMENT DIMENSIONS. CONTRACTOR SHALL BE

RESPONSIBLE FOR PROVIDING EQUIPMENT THAT WILL

FIT IN THE SPACE ALLOTTED.

4. THE LOCATION OF UTILITIES AND STRUCTURES, BOTH

SURFACE AND SUBSURFACE, ARE SHOWN

ON THE PLANS FROM DATA AVAILABLE AT THE TIME OF

THE SURVEY AND ARE NOT NECESSARILY

COMPLETE OR CORRECT. THE EXACT LOCATION AND

PROTECTION OF UTILITIES AND STRUCTURES

IS THE RESPONSIBILITY OF THE CONTRACTOR. DURING

CONSTRUCTION THE CONTRACTOR SHALL

USE DILIGENCE TO PROTECT ALL EXISTING UTILITIES

AND STRUCTURES WHETHER SHOWN ON THE

PLANS OR NOT. IF DAMAGE IS CAUSED, THE

CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR

AND RESTORATION OF SAME IN ACCORDANCE WITH THE

DIRECTIONS OF THE ENGINEER AND FOR

ANY RESULTING CONTINGENT DAMAGES; GOVERNMENT

SHALL BEAR NO ADDITIONAL COSTS.

5. ONLY PULLBOXES SPECIFICALLY REQUIRED BY THE

ENGINEER IN LOCATIONS SHOWN ARE

IDENTIFIED. CONTRACTOR SHALL PROVIDE ALL

PULLBOXES REQUIRED TO MEET APPLICABLE

CODES.

6. CONTRACTOR TO COORDINATE WITH FACILITIES AND

BIOMEDICAL ENGINEERING FOR SEGREGATION AND

DIVERSITY OF LOADS BETWEEN THE EXISTING IPS AND

NEWLY INSTALLED IPS. CONTRACTOR TO BALANCE

LEAKAGE CURRENT. RE-LABEL PANEL SCHEDULES AND

FIELD DEVICES WITH ACCURATE CIRCUIT IDENTITY.

7. CONTRACTOR SHALL PRESERVE, REPAIR, AND

RE-CERTIFY ALL LEAD SHIELDING WHERE DAMAGED OR

AFFECTED WITHIN SCOPE OF WORK.

8. CONTRACTOR SHALL PRESERVE, PROTECT, AND REPAIR

ALL FINISHES SUBJECT TO DAMAGE WITHIN SCOPE OF

WORK. REPAIR OF DAMAGE MADE AT NO ADDITIONAL

COST TO THE GOVERNMENT.

NOT USED.2

NOT USED.3

NOT USED.4

NOT USED.5

1 1

SCALE: 1/4" = 1'SCALE: 1/4" = 1'SCALE: 1/4" = 1'

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text

OR-3 OPERATING RM

AutoCAD SHX Text 2E135

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

XIPU

AutoCAD SHX Text

3#6+1#10 EG

AutoCAD SHX Text

IN 1" CONDUIT

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text J

AutoCAD SHX Text J

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 25,27,29

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

LIPU

AutoCAD SHX Text

3#10+1#10 EG

AutoCAD SHX Text

IN 3/4" CONDUIT

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 26,28,30

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text 31,33,35

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text

TO EF-3

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text J

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text

OR-3 OPERATING RM

AutoCAD SHX Text 2E135

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

XIPU

AutoCAD SHX Text

3#6+1#10 EG

AutoCAD SHX Text

IN 1" CONDUIT

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text J

AutoCAD SHX Text J

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 25,27,29

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

LIPU

AutoCAD SHX Text

3#10+1#10 EG

AutoCAD SHX Text

IN 3/4" CONDUIT

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 26,28,30

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text 31,33,35

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text

TO EF-3

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text J

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text

OR-3 OPERATING RM

AutoCAD SHX Text 2E135

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

XIPU

AutoCAD SHX Text

3#6+1#10 EG

AutoCAD SHX Text

IN 1" CONDUIT

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text J

AutoCAD SHX Text J

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 25,27,29

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

LIPU

AutoCAD SHX Text

3#10+1#10 EG

AutoCAD SHX Text

IN 3/4" CONDUIT

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 26,28,30

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text 31,33,35

AutoCAD SHX Text

IPU#4

AutoCAD SHX Text

TO EF-3

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

IPU#4

J

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

E104

OR #4 - ISOLATED POWER PLAN

Fi le

P at h

/1 5/

1:

:0

AM

FOR CONSTRUCTION

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

CORRECT CODE DEFICIENCY FOR

INCREASED ISOLATED POWER

688 - WASHINGTON D.C. VAMC

688-24-###

Project Director

NOV 1 2023 Chkd By DMWRevisions: Date:

1 DETAIL 1 - EXISTING 2 DETAIL 2 - DEMOITION 3 DETAIL 3 - NEW WORK

GENERAL NOTES: (THIS SHEET)

KEYED NOTES: (THIS DETAIL)#

EXISTING TO REMAIN IPS IN OR #4.1

KEYED NOTES: (THIS DETAIL)#

PREPARE SPACE FOR NEW ADDITIONAL IPS; PROTECT

SHIELDING.

NOT USED.2

NOT USED.3

NOT USED.4

NOT USED.5

KEYED NOTES: (THIS DETAIL)#

PROVIDE NEW ADDITIONAL IPS IN OR #4 FED FROM 'ORNL'.1

DIVERSIFY LOADS BETWEEN EXISTING AND NEW IPS FOR MATCHED LEAKAGE

CURRENTS WITH FACILITY COORDINATION.

ONCE LOADS ARE BALANCED, CONTRACTOR TO UPDATE PANEL SCHEDULE AND

CIRCUIT IDENTIFIERS ON WIRING DEVICES.

NOT USED.4

NOT USED.5

1. CONTRACTOR SHALL COORDINATE ALL EFFORTS IN

ACCORDANCE WITH ENFORCED INFECTION CONTROL RISK

ASSESSMENT (ICRA) REQUIREMENTS.

2. ALL MATERIALS FURNISHED BY THE CONTRACTOR ARE

TO BE NEW AND APPROVED BY THE OWNER AS TO

MANUFACTURER AND TYPE.

3. ALL LOCATIONS AND DIMENSIONS SHOWN ARE

APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY

ALL ELECTRICAL EQUIPMENT LOCATIONS AND

EQUIPMENT DIMENSIONS. CONTRACTOR SHALL BE

RESPONSIBLE FOR PROVIDING EQUIPMENT THAT WILL

FIT IN THE SPACE ALLOTTED.

4. THE LOCATION OF UTILITIES AND STRUCTURES, BOTH

SURFACE AND SUBSURFACE, ARE SHOWN

ON THE PLANS FROM DATA AVAILABLE AT THE TIME OF

THE SURVEY AND ARE NOT NECESSARILY

COMPLETE OR CORRECT. THE EXACT LOCATION AND

PROTECTION OF UTILITIES AND STRUCTURES

IS THE RESPONSIBILITY OF THE CONTRACTOR. DURING

CONSTRUCTION THE CONTRACTOR SHALL

USE DILIGENCE TO PROTECT ALL EXISTING UTILITIES

AND STRUCTURES WHETHER SHOWN ON THE

PLANS OR NOT. IF DAMAGE IS CAUSED, THE

CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR

AND RESTORATION OF SAME IN ACCORDANCE WITH THE

DIRECTIONS OF THE ENGINEER AND FOR

ANY RESULTING CONTINGENT DAMAGES; GOVERNMENT

SHALL BEAR NO ADDITIONAL COSTS.

5. ONLY PULLBOXES SPECIFICALLY REQUIRED BY THE

ENGINEER IN LOCATIONS SHOWN ARE

IDENTIFIED. CONTRACTOR SHALL PROVIDE ALL

PULLBOXES REQUIRED TO MEET APPLICABLE

CODES.

6. CONTRACTOR TO COORDINATE WITH FACILITIES AND

BIOMEDICAL ENGINEERING FOR SEGREGATION AND

DIVERSITY OF LOADS BETWEEN THE EXISTING IPS AND

NEWLY INSTALLED IPS. CONTRACTOR TO BALANCE

LEAKAGE CURRENT. RE-LABEL PANEL SCHEDULES AND

FIELD DEVICES WITH ACCURATE CIRCUIT IDENTITY.

7. CONTRACTOR SHALL PRESERVE, REPAIR, AND

RE-CERTIFY ALL LEAD SHIELDING WHERE DAMAGED OR

AFFECTED WITHIN SCOPE OF WORK.

8. CONTRACTOR SHALL PRESERVE, PROTECT, AND REPAIR

ALL FINISHES SUBJECT TO DAMAGE WITHIN SCOPE OF

WORK. REPAIR OF DAMAGE MADE AT NO ADDITIONAL

COST TO THE GOVERNMENT.

NOT USED.2

NOT USED.3

NOT USED.4

NOT USED.5

SCALE: 1/4" = 1'SCALE: 1/4" = 1'SCALE: 1/4" = 1'

AutoCAD SHX Text

OR-4 CARDIAC OPERATING RM

AutoCAD SHX Text 2E134

AutoCAD SHX Text

HEART PUMP RM

AutoCAD SHX Text 2E133

AutoCAD SHX Text

ORNP-3,35

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

XIPU

AutoCAD SHX Text

3#6+1#10 EG

AutoCAD SHX Text

IN 1" CONDUIT

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

1PU#2

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text 3#10 +1#10

AutoCAD SHX Text

EG IN 3/4"C.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ORNP-7,9,11

AutoCAD SHX Text

IPU#2

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#2

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text D,G

AutoCAD SHX Text D,G

AutoCAD SHX Text D,G

AutoCAD SHX Text

AutoCAD SHX Text D,G

AutoCAD SHX Text 10,12

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 26,28,30

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

OREP

AutoCAD SHX Text -7,9,11

AutoCAD SHX Text

OREP-

AutoCAD SHX Text 8,10,12

AutoCAD SHX Text G

AutoCAD SHX Text

IPU#2

AutoCAD SHX Text

IPU#2

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 31,33,35

AutoCAD SHX Text

IPU#2

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 8,10,12

AutoCAD SHX Text D,G

AutoCAD SHX Text M

AutoCAD SHX Text

WP

AutoCAD SHX Text

TO VSD

AutoCAD SHX Text J

AutoCAD SHX Text

EF-3 ON ROOF

AutoCAD SHX Text

11/2HP,480. 3%%C

AutoCAD SHX Text W.P.

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

IPU#2

AutoCAD SHX Text

ON

AutoCAD SHX Text

ROOF

AutoCAD SHX Text J

AutoCAD SHX Text

OR-4 CARDIAC OPERATING RM

AutoCAD SHX Text 2E134

AutoCAD SHX Text

HEART PUMP RM

AutoCAD SHX Text 2E133

AutoCAD SHX Text

ORNP-3,35

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

XIPU

AutoCAD SHX Text

3#6+1#10 EG

AutoCAD SHX Text

IN 1" CONDUIT

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

1PU#2

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text 3#10 +1#10

AutoCAD SHX Text

EG IN 3/4"C.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ORNP-7,9,11

AutoCAD SHX Text

IPU#2

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#2

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text D,G

AutoCAD SHX Text D,G

AutoCAD SHX Text D,G

AutoCAD SHX Text

AutoCAD SHX Text D,G

AutoCAD SHX Text 10,12

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 26,28,30

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

OREP

AutoCAD SHX Text -7,9,11

AutoCAD SHX Text

OREP-

AutoCAD SHX Text 8,10,12

AutoCAD SHX Text G

AutoCAD SHX Text

IPU#2

AutoCAD SHX Text

IPU#2

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 31,33,35

AutoCAD SHX Text

IPU#2

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 8,10,12

AutoCAD SHX Text D,G

AutoCAD SHX Text M

AutoCAD SHX Text

WP

AutoCAD SHX Text

TO VSD

AutoCAD SHX Text J

AutoCAD SHX Text

EF-3 ON ROOF

AutoCAD SHX Text

11/2HP,480. 3%%C

AutoCAD SHX Text W.P.

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

IPU#2

AutoCAD SHX Text

ON

AutoCAD SHX Text

ROOF

AutoCAD SHX Text J

AutoCAD SHX Text

OR-4 CARDIAC OPERATING RM

AutoCAD SHX Text 2E134

AutoCAD SHX Text

HEART PUMP RM

AutoCAD SHX Text 2E133

AutoCAD SHX Text

ORNP-3,35

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

XIPU

AutoCAD SHX Text

3#6+1#10 EG

AutoCAD SHX Text

IN 1" CONDUIT

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

1PU#2

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text 3#10 +1#10

AutoCAD SHX Text

EG IN 3/4"C.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ORNP-7,9,11

AutoCAD SHX Text

IPU#2

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#2

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text D,G

AutoCAD SHX Text D,G

AutoCAD SHX Text D,G

AutoCAD SHX Text

AutoCAD SHX Text D,G

AutoCAD SHX Text 10,12

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 26,28,30

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

OREP

AutoCAD SHX Text -7,9,11

AutoCAD SHX Text

OREP-

AutoCAD SHX Text 8,10,12

AutoCAD SHX Text G

AutoCAD SHX Text

IPU#2

AutoCAD SHX Text

IPU#2

AutoCAD SHX Text

IPU#3

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 31,33,35

AutoCAD SHX Text

IPU#2

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 8,10,12

AutoCAD SHX Text D,G

AutoCAD SHX Text M

AutoCAD SHX Text

WP

AutoCAD SHX Text

TO VSD

AutoCAD SHX Text J

AutoCAD SHX Text

EF-3 ON ROOF

AutoCAD SHX Text

11/2HP,480. 3%%C

AutoCAD SHX Text W.P.

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

IPU#2

AutoCAD SHX Text

ON

AutoCAD SHX Text

ROOF

J

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

E105

OR #5 - ISOLATED POWER PLAN

Fi le

P at h

/1 5/

1:

:0

AM

FOR CONSTRUCTION

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

CORRECT CODE DEFICIENCY FOR

INCREASED ISOLATED POWER

688 - WASHINGTON D.C. VAMC

688-24-###

Project Director

NOV 1 2023 Chkd By DMWRevisions: Date:

1 DETAIL 1 - EXISTING 2 DETAIL 2 - DEMOITION 3 DETAIL 3 - NEW WORK

GENERAL NOTES: (THIS SHEET)

KEYED NOTES: (THIS DETAIL)#

EXISTING TO REMAIN IPS IN OR #5.1

KEYED NOTES: (THIS DETAIL)#

PREPARE SPACE FOR NEW ADDITIONAL IPS; PROTECT

SHIELDING.

NOT USED.2

NOT USED.3

NOT USED.4

NOT USED.5

KEYED NOTES: (THIS DETAIL)#

PROVIDE NEW ADDITIONAL IPS IN OR #5 FED FROM 'ORNL'.1

DIVERSIFY LOADS BETWEEN EXISTING AND NEW IPS FOR MATCHED LEAKAGE

CURRENTS WITH FACILITY COORDINATION.

ONCE LOADS ARE BALANCED, CONTRACTOR TO UPDATE PANEL SCHEDULE AND

CIRCUIT IDENTIFIERS ON WIRING DEVICES.

NOT USED.4

NOT USED.5

1. CONTRACTOR SHALL COORDINATE ALL EFFORTS IN

ACCORDANCE WITH ENFORCED INFECTION CONTROL RISK

ASSESSMENT (ICRA) REQUIREMENTS.

2. ALL MATERIALS FURNISHED BY THE CONTRACTOR ARE

TO BE NEW AND APPROVED BY THE OWNER AS TO

MANUFACTURER AND TYPE.

3. ALL LOCATIONS AND DIMENSIONS SHOWN ARE

APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY

ALL ELECTRICAL EQUIPMENT LOCATIONS AND

EQUIPMENT DIMENSIONS. CONTRACTOR SHALL BE

RESPONSIBLE FOR PROVIDING EQUIPMENT THAT WILL

FIT IN THE SPACE ALLOTTED.

4. THE LOCATION OF UTILITIES AND STRUCTURES, BOTH

SURFACE AND SUBSURFACE, ARE SHOWN

ON THE PLANS FROM DATA AVAILABLE AT THE TIME OF

THE SURVEY AND ARE NOT NECESSARILY

COMPLETE OR CORRECT. THE EXACT LOCATION AND

PROTECTION OF UTILITIES AND STRUCTURES

IS THE RESPONSIBILITY OF THE CONTRACTOR. DURING

CONSTRUCTION THE CONTRACTOR SHALL

USE DILIGENCE TO PROTECT ALL EXISTING UTILITIES

AND STRUCTURES WHETHER SHOWN ON THE

PLANS OR NOT. IF DAMAGE IS CAUSED, THE

CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR

AND RESTORATION OF SAME IN ACCORDANCE WITH THE

DIRECTIONS OF THE ENGINEER AND FOR

ANY RESULTING CONTINGENT DAMAGES; GOVERNMENT

SHALL BEAR NO ADDITIONAL COSTS.

5. ONLY PULLBOXES SPECIFICALLY REQUIRED BY THE

ENGINEER IN LOCATIONS SHOWN ARE

IDENTIFIED. CONTRACTOR SHALL PROVIDE ALL

PULLBOXES REQUIRED TO MEET APPLICABLE

CODES.

6. CONTRACTOR TO COORDINATE WITH FACILITIES AND

BIOMEDICAL ENGINEERING FOR SEGREGATION AND

DIVERSITY OF LOADS BETWEEN THE EXISTING IPS AND

NEWLY INSTALLED IPS. CONTRACTOR TO BALANCE

LEAKAGE CURRENT. RE-LABEL PANEL SCHEDULES AND

FIELD DEVICES WITH ACCURATE CIRCUIT IDENTITY.

7. CONTRACTOR SHALL PRESERVE, REPAIR, AND

RE-CERTIFY ALL LEAD SHIELDING WHERE DAMAGED OR

AFFECTED WITHIN SCOPE OF WORK.

8. CONTRACTOR SHALL PRESERVE, PROTECT, AND REPAIR

ALL FINISHES SUBJECT TO DAMAGE WITHIN SCOPE OF

WORK. REPAIR OF DAMAGE MADE AT NO ADDITIONAL

COST TO THE GOVERNMENT.

NOT USED.2

NOT USED.3

NOT USED.4

NOT USED.5

SCALE: 1/4" = 1'SCALE: 1/4" = 1'SCALE: 1/4" = 1'

1 2

AutoCAD SHX Text

MED RM

AutoCAD SHX Text 2E140A

AutoCAD SHX Text

TOILET

AutoCAD SHX Text 2E110C

AutoCAD SHX Text

DICT

AutoCAD SHX Text 2E110B

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text

SUB- STERILE

AutoCAD SHX Text 2E131A

AutoCAD SHX Text

HOUSEKEEPING

AutoCAD SHX Text 2E132

AutoCAD SHX Text

OR-5 OPERATING RM

AutoCAD SHX Text 2E131

AutoCAD SHX Text

DICT

AutoCAD SHX Text 2E110A

AutoCAD SHX Text

AutoCAD SHX Text 15,17

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text D,G

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

IPU#1

AutoCAD SHX Text J

AutoCAD SHX Text

XIPU

AutoCAD SHX Text 3#6+1#10

AutoCAD SHX Text

EG IN

AutoCAD SHX Text

1" CONDUIT

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#1

AutoCAD SHX Text J

AutoCAD SHX Text

LIPU

AutoCAD SHX Text

3#10+1#10 EG IN

AutoCAD SHX Text

3/4" CONDUIT

AutoCAD SHX Text

IPU#1

AutoCAD SHX Text D,G

AutoCAD SHX Text D,G

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 13,15,17

AutoCAD SHX Text

IPU#1

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#1

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text D

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text

LASER ISPLATION

AutoCAD SHX Text

PANEL (LIPU)

AutoCAD SHX Text

MED RM

AutoCAD SHX Text 2E140A

AutoCAD SHX Text

TOILET

AutoCAD SHX Text 2E110C

AutoCAD SHX Text

DICT

AutoCAD SHX Text 2E110B

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text

SUB- STERILE

AutoCAD SHX Text 2E131A

AutoCAD SHX Text

HOUSEKEEPING

AutoCAD SHX Text 2E132

AutoCAD SHX Text

OR-5 OPERATING RM

AutoCAD SHX Text 2E131

AutoCAD SHX Text

DICT

AutoCAD SHX Text 2E110A

AutoCAD SHX Text

AutoCAD SHX Text 15,17

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text D,G

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

IPU#1

AutoCAD SHX Text J

AutoCAD SHX Text

XIPU

AutoCAD SHX Text 3#6+1#10

AutoCAD SHX Text

EG IN

AutoCAD SHX Text

1" CONDUIT

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#1

AutoCAD SHX Text J

AutoCAD SHX Text

LIPU

AutoCAD SHX Text

3#10+1#10 EG IN

AutoCAD SHX Text

3/4" CONDUIT

AutoCAD SHX Text

IPU#1

AutoCAD SHX Text D,G

AutoCAD SHX Text D,G

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 13,15,17

AutoCAD SHX Text

IPU#1

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#1

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text D

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text

LASER ISPLATION

AutoCAD SHX Text

PANEL (LIPU)

AutoCAD SHX Text

MED RM

AutoCAD SHX Text 2E140A

AutoCAD SHX Text

TOILET

AutoCAD SHX Text 2E110C

AutoCAD SHX Text

DICT

AutoCAD SHX Text 2E110B

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text

SUB- STERILE

AutoCAD SHX Text 2E131A

AutoCAD SHX Text

HOUSEKEEPING

AutoCAD SHX Text 2E132

AutoCAD SHX Text

OR-5 OPERATING RM

AutoCAD SHX Text 2E131

AutoCAD SHX Text

DICT

AutoCAD SHX Text 2E110A

AutoCAD SHX Text

AutoCAD SHX Text 15,17

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text D,G

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

IPU#1

AutoCAD SHX Text J

AutoCAD SHX Text

XIPU

AutoCAD SHX Text 3#6+1#10

AutoCAD SHX Text

EG IN

AutoCAD SHX Text

1" CONDUIT

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#1

AutoCAD SHX Text J

AutoCAD SHX Text

LIPU

AutoCAD SHX Text

3#10+1#10 EG IN

AutoCAD SHX Text

3/4" CONDUIT

AutoCAD SHX Text

IPU#1

AutoCAD SHX Text D,G

AutoCAD SHX Text D,G

AutoCAD SHX Text

ORNP-

AutoCAD SHX Text 13,15,17

AutoCAD SHX Text

IPU#1

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text

IPU#1

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text D

AutoCAD SHX Text +5'-0"

AutoCAD SHX Text

LASER ISPLATION

PANEL (LIPU)

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

E300

ONE-LINE DIAGRAM

Fi le

P at h

/1 5/

1:

:0

AM

FOR CONSTRUCTION

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

CORRECT CODE DEFICIENCY FOR

INCREASED ISOLATED POWER

688 - WASHINGTON D.C. VAMC

688-24-###

Project Director

NOV 1 2023 Chkd By DMWRevisions: Date:

GENERAL NOTES: (THIS SHEET)

1. CONTRACTOR SHALL COORDINATE ALL EFFORTS IN

ACCORDANCE WITH ENFORCED INFECTION CONTROL RISK

ASSESSMENT (ICRA) REQUIREMENTS.

2. ALL MATERIALS FURNISHED BY THE CONTRACTOR ARE

TO BE NEW AND APPROVED BY THE OWNER AS TO

MANUFACTURER AND TYPE.

3. ALL LOCATIONS AND DIMENSIONS SHOWN ARE

APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY

ALL ELECTRICAL EQUIPMENT LOCATIONS AND

EQUIPMENT DIMENSIONS. CONTRACTOR SHALL BE

RESPONSIBLE FOR PROVIDING EQUIPMENT THAT WILL

FIT IN THE SPACE ALLOTTED.

4. THE LOCATION OF UTILITIES AND STRUCTURES, BOTH

SURFACE AND SUBSURFACE, ARE SHOWN

ON THE PLANS FROM DATA AVAILABLE AT THE TIME OF

THE SURVEY AND ARE NOT NECESSARILY

COMPLETE OR CORRECT. THE EXACT LOCATION AND

PROTECTION OF UTILITIES AND STRUCTURES

IS THE RESPONSIBILITY OF THE CONTRACTOR. DURING

CONSTRUCTION THE CONTRACTOR SHALL

USE DILIGENCE TO PROTECT ALL EXISTING UTILITIES

AND STRUCTURES WHETHER SHOWN ON THE

PLANS OR NOT. IF DAMAGE IS CAUSED, THE

CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR

AND RESTORATION OF SAME IN ACCORDANCE WITH THE

DIRECTIONS OF THE ENGINEER AND FOR

ANY RESULTING CONTINGENT DAMAGES; GOVERNMENT

SHALL BEAR NO ADDITIONAL COSTS.

5. ONLY PULLBOXES SPECIFICALLY REQUIRED BY THE

ENGINEER IN LOCATIONS SHOWN ARE

IDENTIFIED. CONTRACTOR SHALL PROVIDE ALL

PULLBOXES REQUIRED TO MEET APPLICABLE

CODES.

6. ALL EQUIPMENT IS EXISTING TO REMAIN (ETR) UNLESS

NOTED OTHERWISE (UNO).

7. VA MEDICAL CENTER HAS FIRST RIGHT OF REFUSAL ON

ALL EQUIPMENT REMOVED FROM SERVICE. IF RETAINED,

COORDINATE FOR DELIVERY TO STORAGE LOCATION ON

SITE.

8. CONTRACTOR SHALL PHASE WORK IN SUCH A MANNER

TO MINIMIZE IMPACT TO MEDICAL CENTER OPERATIONS.

INTERRUPTION OF SERVICES REQUIRE 14 DAY NOTICE

TO COR.

9. ELECTRICAL REQUIREMENTS PER CONTRACT

DOCUMENTS; DRAWINGS AND SPECIFICATIONS, AND

CURRENT PUBLICATION OF NFPA 70, 99, 101, AND 110.

KEYED NOTES: (THIS SHEET)#

REMOVE FEEDER FROM NORMAL DISTRIBUTION. DEMOLISH COMPLETELY.1

PROVIDE FEEDER ON EMERGENCY DISTRIBUTION.2

IPS EXISTING IN OR 1 THRU 5 ARE ETR.3

PROVIDE ADDITIONAL 7.5kVA IP TO DIVERSIFY LOADS IN EACH OR.

BENDER LIM2010, 16 SPACE (2-POLE) OR EQUAL.

OR#4 IS OMITTED FROM ADDITIONAL IP. HAS ALREADY BEEN INSTALLED FROM OR#5.5

OR#5 REQUIRES (2) NEW IPS. REFERENCE KEYED NOTE 5.6

CONTRACTOR SHALL BALANCE LOADS BETWEEN EACH (2) IP SYSTEM PER OR.7

CONTRACTOR RESPONSIBLE FOR INDEPENDENT THIRD PARTY NFPA 99 CERTIFICATION.8

PANELS LOCATED IN MECHANICAL SPACE 2078, ADJACENT TO OR HVAC.9

PANELS LOCATED IN BASEMENT ELECTRICAL DISTRIBUTION ROOM; REFERENCE SHEET

E400.

BASEMENT

FIRST FLOOR

SECOND FLOOR

DP5

ORNL

75kVA

TX

ORNP

DPE2

E1PDP XRAY

IP

15kVA

OR1

IP

7.5kVA

OR2

IP

7.5kVA

OR3

IP

7.5kVA

OR4

IP

7.5kVA

OR5

IP

7.5kVA

LASER

IP

25kVA

480/277V 3PH 4W+G

225A MLO 22KAIC

480/277V 3PH 4W+G

225A MLO 22KAIC

DPE2

E1PDP XRAY

IP

15kVA

OR1

IP

7.5kVA

OR2

IP

7.5kVA

OR3

IP

7.5kVA

OR4

IP

7.5kVA

OR5

IP

7.5kVA

LASER

IP

25kVA

480/277V 3PH 4W+G

225A MLO 22KAIC

OR1

IP2

7.5kVA

OR2

IP2

7.5kVA

OR3

IP2

7.5kVA

OR4

IP2

7.5kVA

OR5

IP2

7.5kVA

SWBD

EMB

ORNL

75kVA

TX

ORNP

480/277V 3PH 4W+G

225A MLO 22KAIC

SUB 3

SWGR #3

ATS #9

1 DETAIL 1 - EXISTING

SCALE: NTS 2 DETAIL 2 - NEW WORK

SCALE: NTS

56 6

3 DETAIL 3 - UPDATED SCHEDULE

SCALE: NTS

OR #1 IP2

OR #2 IP2

OR #3 IP2

OR #4 IP2

OR #5 IP2

3.75

3.75

3.75

3.75

3.75

3.75

3.75

3.75

3.75 3.75

PROVIDE 2-POLE FEEDER BREAKERS AT MATCHING kAIC RATING OF ENCLOSURE IAW

MANUFACTURER REQUIREMENTS OF NEW IPS.

AutoCAD SHX Text

2#8, 1#10 EG 1"C

AutoCAD SHX Text

2#6, 1#8 EG 1-1/4"C

AutoCAD SHX Text

2#10, 1#12 EG 3/4"C (TYP.)

AutoCAD SHX Text

100A FEEDER (ORNL) 4#1/0, 1#6 EG 2"C

AutoCAD SHX Text

2#8, 1#10 EG 1"C

AutoCAD SHX Text

2#6, 1#8 EG 1-1/4"C

AutoCAD SHX Text

2#10, 1#12 EG 3/4"C (TYP.)

AutoCAD SHX Text

225A FEEDER (E1PDP) 4#250 KCMIL, 1#4 EG 3"C

AutoCAD SHX Text RELOCATE 'ORNL' FEEDER FROM DP5 TO SWBD 'EMB'. UTILIZE EXISTING PREPARED SPACE RATED FOR FEEDER. CONTRACTOR SHALL PROVIDE COORDINATION AND LABELING FOR NEW WORK IAW SPECIFICATION.

AutoCAD SHX Text PROVIDE SECOND FLUSH MOUNTED 7.5kVA ISOLATED POWER SYSTEM IN EACH OR ADJACENT TO EXISTING SYSTEM. CONTRACTOR TO DIVERSIFY LOADS BETWEEN THE TWO PANEL IN EACH OR.

AutoCAD SHX Text

2#10, 1#12 EG 3/4"C (TYP.)

AutoCAD SHX Text

NEW 225A FEEDER (ORNL) 4#250 KCMIL, 1#4 EG 3"C

SEQUENCE NOTE: PROVIDE NEW FEEDER PRIOR TO DEMOLITION OF OLD FEEDER TO THE PANEL TO REDUCE DOWNTIME TO THE MOST PRACTICAL EXTENTS.

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

E400

BASEMENT POWER PLAN

Fi le

P at h

/1 5/

1:

:0

AM

FOR CONSTRUCTION

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

CORRECT CODE DEFICIENCY FOR

INCREASED ISOLATED POWER

688 - WASHINGTON D.C. VAMC

688-24-###

Project Director

NOV 1 2023 Chkd By DMWRevisions: Date:

GENERAL NOTES: (THIS SHEET)

1. CONTRACTOR SHALL COORDINATE ALL EFFORTS IN

ACCORDANCE WITH ENFORCED INFECTION CONTROL RISK

ASSESSMENT (ICRA) REQUIREMENTS.

2. ALL MATERIALS FURNISHED BY THE CONTRACTOR ARE

TO BE NEW AND APPROVED BY THE OWNER AS TO

MANUFACTURER AND TYPE.

3. ALL LOCATIONS AND DIMENSIONS SHOWN ARE

APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY

ALL ELECTRICAL EQUIPMENT LOCATIONS AND

EQUIPMENT DIMENSIONS. CONTRACTOR SHALL BE

RESPONSIBLE FOR PROVIDING EQUIPMENT THAT WILL

FIT IN THE SPACE ALLOTTED.

4. THE LOCATION OF UTILITIES AND STRUCTURES, BOTH

SURFACE AND SUBSURFACE, ARE SHOWN

ON THE PLANS FROM DATA AVAILABLE AT THE TIME OF

THE SURVEY AND ARE NOT NECESSARILY

COMPLETE OR CORRECT. THE EXACT LOCATION AND

PROTECTION OF UTILITIES AND STRUCTURES

IS THE RESPONSIBILITY OF THE CONTRACTOR. DURING

CONSTRUCTION THE CONTRACTOR SHALL

USE DILIGENCE TO PROTECT ALL EXISTING UTILITIES

AND STRUCTURES WHETHER SHOWN ON THE

PLANS OR NOT. IF DAMAGE IS CAUSED, THE

CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR

AND RESTORATION OF SAME IN ACCORDANCE WITH THE

DIRECTIONS OF THE ENGINEER AND FOR

ANY RESULTING CONTINGENT DAMAGES; GOVERNMENT

SHALL BEAR NO ADDITIONAL COSTS.

5. ONLY PULLBOXES SPECIFICALLY REQUIRED BY THE

ENGINEER IN LOCATIONS SHOWN ARE

IDENTIFIED. CONTRACTOR SHALL PROVIDE ALL

PULLBOXES REQUIRED TO MEET APPLICABLE

CODES.

6. ALL EQUIPMENT IS EXISTING TO REMAIN (ETR) UNLESS

NOTED OTHERWISE (UNO).

7. VA MEDICAL CENTER HAS FIRST RIGHT OF REFUSAL ON

ALL EQUIPMENT REMOVED FROM SERVICE. IF RETAINED,

COORDINATE FOR DELIVERY TO STORAGE LOCATION ON

SITE.

8. CONTRACTOR SHALL PHASE WORK IN SUCH A MANNER

TO MINIMIZE IMPACT TO MEDICAL CENTER OPERATIONS.

INTERRUPTION OF SERVICES REQUIRE 14 DAY NOTICE

TO COR.

9. ELECTRICAL REQUIREMENTS PER CONTRACT

DOCUMENTS; DRAWINGS AND SPECIFICATIONS, AND

CURRENT PUBLICATION OF NFPA 70, 99, 101, AND 110.

10. ROUTE CONDUIT PARALLEL AND PERPENDICULAR TO

BUILDING STRUCTURES AND EQUIPMENT. COORDINATE

WITH OTHER TRADES FOR ACCESSIBILITY AND

SERVICEABILITY.

KEYED NOTES: (THIS SHEET)#

REMOVE FEEDER FROM 'DP5' TO 'ORNL'. REFERENCE ONE-LINE DRAWINGS.1

PROVIDE FEEDER FROM 'EMB' TO 'ORNL'. REFERENCE ONE-LINE DRAWINGS.2

NOT USED.3

NOT USED.4

NOT USED.5

1 DETAIL 1 - BASEMENT ELECTRICAL ROOM WORK PLAN

SCALE: NTS

Sheets and Views
E101
E102.pdf
Sheets and Views
E102
E103.pdf
Sheets and Views
E103
E104.pdf
Sheets and Views
E104
E105.pdf
Sheets and Views
E105
E300.pdf
Sheets and Views
E300
E400.pdf
Sheets and Views
E400

File details come from the government source that posted it. Updated .