Drawings OR Rewire.pdf
PDF 6 MB Posted
- Attached to
- Y1DA--PROJECT # 688-24-101 EMERGENCY REWIRE OR CIRCUITS Federal contract opportunity
- Solicitation number
- 36C24524B0007
About this file
This is a solicitation for a construction project to rewire operating room circuits and install additional isolated power systems at the Veterans Affairs Medical Center in Washington D.C. The scope of work includes demolishing existing feeds from normal distribution and providing new feeds from emergency distribution for each of five operating rooms. It also requires installing five additional 7.5kVA isolated power systems to supplement seven existing systems, one for each operating room. The contractor must balance loads between new and existing systems, update panel schedules and device labeling, and certify the systems for patient use. Additional requirements include preserving and modifying operating room shielding, coordinating with facility staff, and obtaining independent certification of the isolated power systems. The period of performance is 180 calendar days from notice to proceed. The solicitation identifies various submittal and reporting requirements, safety protocols, infection control measures, hazardous material handling procedures, and other standard construction terms.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| S05_RFI Response attachment_02.09.2024.pdf | ||
| 36C24524B0007 0002.docx | DOCX document | |
| 36C24524B0007 0001.docx | DOCX document | |
| 36C24524B0007_1.docx | DOCX document | |
| Specs OR Rewire_01.pdf | ||
| RFI Submission 36C24524B0007.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
E101
OR #1 - ISOLATED POWER PLAN
Fi le
P at h
/1 5/
1:
:0
AM
FOR CONSTRUCTION
U.S. Department of Veterans Affairs
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseDESIGNER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CORRECT CODE DEFICIENCY FOR
INCREASED ISOLATED POWER
688 - WASHINGTON D.C. VAMC
688-24-###
Project Director
NOV 1 2023 Chkd By DMWRevisions: Date:
1 DETAIL 1 - EXISTING
SCALE: 1/4" = 1' 2 DETAIL 2 - DEMOITION 3 DETAIL 3 - NEW WORK
GENERAL NOTES: (THIS SHEET)
KEYED NOTES: (THIS DETAIL)#
EXISTING TO REMAIN IPS IN OR #1.1
KEYED NOTES: (THIS DETAIL)#
PREPARE SPACE FOR NEW ADDITIONAL IPS; PROTECT
SHIELDING.
NOT USED.2
NOT USED.3
NOT USED.4
NOT USED.5
KEYED NOTES: (THIS DETAIL)#
PROVIDE NEW ADDITIONAL IPS IN OR #1 FED FROM 'ORNL'.1
DIVERSIFY LOADS BETWEEN EXISTING AND NEW IPS FOR MATCHED LEAKAGE
CURRENTS WITH FACILITY COORDINATION.
ONCE LOADS ARE BALANCED, CONTRACTOR TO UPDATE PANEL SCHEDULE AND
CIRCUIT IDENTIFIERS ON WIRING DEVICES.
NOT USED.4
NOT USED.5
1. CONTRACTOR SHALL COORDINATE ALL EFFORTS IN
ACCORDANCE WITH ENFORCED INFECTION CONTROL RISK
ASSESSMENT (ICRA) REQUIREMENTS.
2. ALL MATERIALS FURNISHED BY THE CONTRACTOR ARE
TO BE NEW AND APPROVED BY THE OWNER AS TO
MANUFACTURER AND TYPE.
3. ALL LOCATIONS AND DIMENSIONS SHOWN ARE
APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY
ALL ELECTRICAL EQUIPMENT LOCATIONS AND
EQUIPMENT DIMENSIONS. CONTRACTOR SHALL BE
RESPONSIBLE FOR PROVIDING EQUIPMENT THAT WILL
FIT IN THE SPACE ALLOTTED.
4. THE LOCATION OF UTILITIES AND STRUCTURES, BOTH
SURFACE AND SUBSURFACE, ARE SHOWN
ON THE PLANS FROM DATA AVAILABLE AT THE TIME OF
THE SURVEY AND ARE NOT NECESSARILY
COMPLETE OR CORRECT. THE EXACT LOCATION AND
PROTECTION OF UTILITIES AND STRUCTURES
IS THE RESPONSIBILITY OF THE CONTRACTOR. DURING
CONSTRUCTION THE CONTRACTOR SHALL
USE DILIGENCE TO PROTECT ALL EXISTING UTILITIES
AND STRUCTURES WHETHER SHOWN ON THE
PLANS OR NOT. IF DAMAGE IS CAUSED, THE
CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR
AND RESTORATION OF SAME IN ACCORDANCE WITH THE
DIRECTIONS OF THE ENGINEER AND FOR
ANY RESULTING CONTINGENT DAMAGES; GOVERNMENT
SHALL BEAR NO ADDITIONAL COSTS.
5. ONLY PULLBOXES SPECIFICALLY REQUIRED BY THE
ENGINEER IN LOCATIONS SHOWN ARE
IDENTIFIED. CONTRACTOR SHALL PROVIDE ALL
PULLBOXES REQUIRED TO MEET APPLICABLE
CODES.
6. CONTRACTOR TO COORDINATE WITH FACILITIES AND
BIOMEDICAL ENGINEERING FOR SEGREGATION AND
DIVERSITY OF LOADS BETWEEN THE EXISTING IPS AND
NEWLY INSTALLED IPS. CONTRACTOR TO BALANCE
LEAKAGE CURRENT. RE-LABEL PANEL SCHEDULES AND
FIELD DEVICES WITH ACCURATE CIRCUIT IDENTITY.
7. CONTRACTOR SHALL PRESERVE, REPAIR, AND
RE-CERTIFY ALL LEAD SHIELDING WHERE DAMAGED OR
AFFECTED WITHIN SCOPE OF WORK.
8. CONTRACTOR SHALL PRESERVE, PROTECT, AND REPAIR
ALL FINISHES SUBJECT TO DAMAGE WITHIN SCOPE OF
WORK. REPAIR OF DAMAGE MADE AT NO ADDITIONAL
COST TO THE GOVERNMENT.
NOT USED.2
NOT USED.3
NOT USED.4
NOT USED.5
SCALE: 1/4" = 1'SCALE: 1/4" = 1'
AutoCAD SHX Text
DICT
AutoCAD SHX Text 2E104C
AutoCAD SHX Text
MALE LOCKERS
AutoCAD SHX Text 2E104A
AutoCAD SHX Text
OPERATING RM OR-1
AutoCAD SHX Text 2E139
AutoCAD SHX Text
SPLINT PLASTER RM
AutoCAD SHX Text 2E138
AutoCAD SHX Text
SUB STERILE
AutoCAD SHX Text 2E137A
AutoCAD SHX Text G
AutoCAD SHX Text
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 19,21,23
AutoCAD SHX Text G
AutoCAD SHX Text
IPU#5
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
XIPU
AutoCAD SHX Text
3#10+1#10 EG
AutoCAD SHX Text
IN 3/4" CONDUIT
AutoCAD SHX Text J
AutoCAD SHX Text
3#6+1#10 EG
AutoCAD SHX Text
IN 1" CONDUIT
AutoCAD SHX Text
IPU#5
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text
IPU#5
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#5
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#5
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#5
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text 15,17
AutoCAD SHX Text G
AutoCAD SHX Text G
AutoCAD SHX Text G
AutoCAD SHX Text G
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
LIPU
AutoCAD SHX Text E
AutoCAD SHX Text J
AutoCAD SHX Text
IPU#5
AutoCAD SHX Text
DICT
AutoCAD SHX Text 2E104C
AutoCAD SHX Text
MALE LOCKERS
AutoCAD SHX Text 2E104A
AutoCAD SHX Text
OPERATING RM OR-1
AutoCAD SHX Text 2E139
AutoCAD SHX Text
SPLINT PLASTER RM
AutoCAD SHX Text 2E138
AutoCAD SHX Text
SUB STERILE
AutoCAD SHX Text 2E137A
AutoCAD SHX Text G
AutoCAD SHX Text
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 19,21,23
AutoCAD SHX Text G
AutoCAD SHX Text
IPU#5
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
XIPU
AutoCAD SHX Text
3#10+1#10 EG
AutoCAD SHX Text
IN 3/4" CONDUIT
AutoCAD SHX Text J
AutoCAD SHX Text
3#6+1#10 EG
AutoCAD SHX Text
IN 1" CONDUIT
AutoCAD SHX Text
IPU#5
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text
IPU#5
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#5
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#5
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#5
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text 15,17
AutoCAD SHX Text G
AutoCAD SHX Text G
AutoCAD SHX Text G
AutoCAD SHX Text G
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
LIPU
AutoCAD SHX Text E
AutoCAD SHX Text J
AutoCAD SHX Text
IPU#5
AutoCAD SHX Text
DICT
AutoCAD SHX Text 2E104C
AutoCAD SHX Text
MALE LOCKERS
AutoCAD SHX Text 2E104A
AutoCAD SHX Text
OPERATING RM OR-1
AutoCAD SHX Text 2E139
AutoCAD SHX Text
SPLINT PLASTER RM
AutoCAD SHX Text 2E138
AutoCAD SHX Text
SUB STERILE
AutoCAD SHX Text 2E137A
AutoCAD SHX Text G
AutoCAD SHX Text
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 19,21,23
AutoCAD SHX Text G
AutoCAD SHX Text
IPU#5
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
XIPU
AutoCAD SHX Text
3#10+1#10 EG
AutoCAD SHX Text
IN 3/4" CONDUIT
AutoCAD SHX Text J
AutoCAD SHX Text
3#6+1#10 EG
AutoCAD SHX Text
IN 1" CONDUIT
AutoCAD SHX Text
IPU#5
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text
IPU#5
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#5
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#5
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#5
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text 15,17
AutoCAD SHX Text G
AutoCAD SHX Text G
AutoCAD SHX Text G
AutoCAD SHX Text G
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
LIPU
AutoCAD SHX Text E
AutoCAD SHX Text J
AutoCAD SHX Text
IPU#5
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
E102
OR #2 - ISOLATED POWER PLAN
Fi le
P at h
/1 5/
1:
:0
AM
FOR CONSTRUCTION
U.S. Department of Veterans Affairs
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseDESIGNER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CORRECT CODE DEFICIENCY FOR
INCREASED ISOLATED POWER
688 - WASHINGTON D.C. VAMC
688-24-###
Project Director
NOV 1 2023 Chkd By DMWRevisions: Date:
1 DETAIL 1 - EXISTING 2 DETAIL 2 - DEMOITION 3 DETAIL 3 - NEW WORK
GENERAL NOTES: (THIS SHEET)
KEYED NOTES: (THIS DETAIL)#
EXISTING TO REMAIN IPS IN OR #2.1
KEYED NOTES: (THIS DETAIL)#
PREPARE SPACE FOR NEW ADDITIONAL IPS; PROTECT
SHIELDING.
NOT USED.2
NOT USED.3
NOT USED.4
NOT USED.5
KEYED NOTES: (THIS DETAIL)#
PROVIDE NEW ADDITIONAL IPS IN OR #2 FED FROM 'ORNL'.1
DIVERSIFY LOADS BETWEEN EXISTING AND NEW IPS FOR MATCHED LEAKAGE
CURRENTS WITH FACILITY COORDINATION.
ONCE LOADS ARE BALANCED, CONTRACTOR TO UPDATE PANEL SCHEDULE AND
CIRCUIT IDENTIFIERS ON WIRING DEVICES.
NOT USED.4
NOT USED.5
1. CONTRACTOR SHALL COORDINATE ALL EFFORTS IN
ACCORDANCE WITH ENFORCED INFECTION CONTROL RISK
ASSESSMENT (ICRA) REQUIREMENTS.
2. ALL MATERIALS FURNISHED BY THE CONTRACTOR ARE
TO BE NEW AND APPROVED BY THE OWNER AS TO
MANUFACTURER AND TYPE.
3. ALL LOCATIONS AND DIMENSIONS SHOWN ARE
APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY
ALL ELECTRICAL EQUIPMENT LOCATIONS AND
EQUIPMENT DIMENSIONS. CONTRACTOR SHALL BE
RESPONSIBLE FOR PROVIDING EQUIPMENT THAT WILL
FIT IN THE SPACE ALLOTTED.
4. THE LOCATION OF UTILITIES AND STRUCTURES, BOTH
SURFACE AND SUBSURFACE, ARE SHOWN
ON THE PLANS FROM DATA AVAILABLE AT THE TIME OF
THE SURVEY AND ARE NOT NECESSARILY
COMPLETE OR CORRECT. THE EXACT LOCATION AND
PROTECTION OF UTILITIES AND STRUCTURES
IS THE RESPONSIBILITY OF THE CONTRACTOR. DURING
CONSTRUCTION THE CONTRACTOR SHALL
USE DILIGENCE TO PROTECT ALL EXISTING UTILITIES
AND STRUCTURES WHETHER SHOWN ON THE
PLANS OR NOT. IF DAMAGE IS CAUSED, THE
CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR
AND RESTORATION OF SAME IN ACCORDANCE WITH THE
DIRECTIONS OF THE ENGINEER AND FOR
ANY RESULTING CONTINGENT DAMAGES; GOVERNMENT
SHALL BEAR NO ADDITIONAL COSTS.
5. ONLY PULLBOXES SPECIFICALLY REQUIRED BY THE
ENGINEER IN LOCATIONS SHOWN ARE
IDENTIFIED. CONTRACTOR SHALL PROVIDE ALL
PULLBOXES REQUIRED TO MEET APPLICABLE
CODES.
6. CONTRACTOR TO COORDINATE WITH FACILITIES AND
BIOMEDICAL ENGINEERING FOR SEGREGATION AND
DIVERSITY OF LOADS BETWEEN THE EXISTING IPS AND
NEWLY INSTALLED IPS. CONTRACTOR TO BALANCE
LEAKAGE CURRENT. RE-LABEL PANEL SCHEDULES AND
FIELD DEVICES WITH ACCURATE CIRCUIT IDENTITY.
7. CONTRACTOR SHALL PRESERVE, REPAIR, AND
RE-CERTIFY ALL LEAD SHIELDING WHERE DAMAGED OR
AFFECTED WITHIN SCOPE OF WORK.
8. CONTRACTOR SHALL PRESERVE, PROTECT, AND REPAIR
ALL FINISHES SUBJECT TO DAMAGE WITHIN SCOPE OF
WORK. REPAIR OF DAMAGE MADE AT NO ADDITIONAL
COST TO THE GOVERNMENT.
NOT USED.2
NOT USED.3
NOT USED.4
NOT USED.5
SCALE: 1/4" = 1' SCALE: 1/4" = 1' SCALE: 1/4" = 1'
AutoCAD SHX Text
OR-2 ORTHOPEDIC OPERATING RM
AutoCAD SHX Text 2E137
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text E
AutoCAD SHX Text
OREP-
AutoCAD SHX Text 14,16,18
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text
OREP-
AutoCAD SHX Text 13,15,17
AutoCAD SHX Text
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 20,22,24
AutoCAD SHX Text M
AutoCAD SHX Text
WP
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 25,27,29
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
3#10+1#10 EG
AutoCAD SHX Text
IN 3/4" CONDUIT
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
XIPU
AutoCAD SHX Text
3#6+1#10 EG
AutoCAD SHX Text
IN1" CONDUIT
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text J
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
EF-6
AutoCAD SHX Text
ON ROOF.
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text
OR-2 ORTHOPEDIC OPERATING RM
AutoCAD SHX Text 2E137
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text E
AutoCAD SHX Text
OREP-
AutoCAD SHX Text 14,16,18
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text
OREP-
AutoCAD SHX Text 13,15,17
AutoCAD SHX Text
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 20,22,24
AutoCAD SHX Text M
AutoCAD SHX Text
WP
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 25,27,29
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
3#10+1#10 EG
AutoCAD SHX Text
IN 3/4" CONDUIT
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
XIPU
AutoCAD SHX Text
3#6+1#10 EG
AutoCAD SHX Text
IN1" CONDUIT
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text J
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
EF-6
AutoCAD SHX Text
ON ROOF.
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text
OR-2 ORTHOPEDIC OPERATING RM
AutoCAD SHX Text 2E137
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text E
AutoCAD SHX Text
OREP-
AutoCAD SHX Text 14,16,18
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text
OREP-
AutoCAD SHX Text 13,15,17
AutoCAD SHX Text
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 20,22,24
AutoCAD SHX Text M
AutoCAD SHX Text
WP
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 25,27,29
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
3#10+1#10 EG
AutoCAD SHX Text
IN 3/4" CONDUIT
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
XIPU
AutoCAD SHX Text
3#6+1#10 EG
AutoCAD SHX Text
IN1" CONDUIT
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text J
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
EF-6
AutoCAD SHX Text
ON ROOF.
IPU#4
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
E103
OR #3 - ISOLATED POWER PLAN
Fi le
P at h
/1 5/
1:
:0
AM
FOR CONSTRUCTION
U.S. Department of Veterans Affairs
A
B
C
D
E
F
5 6 7 8 9 10
PhaseDESIGNER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CORRECT CODE DEFICIENCY FOR
INCREASED ISOLATED POWER
688 - WASHINGTON D.C. VAMC
688-24-###
Project Director
NOV 1 2023 Chkd By DMWRevisions: Date:
1 DETAIL 1 - EXISTING 2 DETAIL 2 - DEMOITION 3 DETAIL 3 - NEW WORK
GENERAL NOTES: (THIS SHEET)
KEYED NOTES: (THIS DETAIL)#
EXISTING TO REMAIN IPS IN OR #3.1
KEYED NOTES: (THIS DETAIL)#
PREPARE SPACE FOR NEW ADDITIONAL IPS; PROTECT
SHIELDING.
NOT USED.2
NOT USED.3
NOT USED.4
NOT USED.5
KEYED NOTES: (THIS DETAIL)#
PROVIDE NEW ADDITIONAL IPS IN OR #3 FED FROM 'ORNL'.1
DIVERSIFY LOADS BETWEEN EXISTING AND NEW IPS FOR MATCHED LEAKAGE
CURRENTS WITH FACILITY COORDINATION.
ONCE LOADS ARE BALANCED, CONTRACTOR TO UPDATE PANEL SCHEDULE AND
CIRCUIT IDENTIFIERS ON WIRING DEVICES.
NOT USED.4
NOT USED.5
1. CONTRACTOR SHALL COORDINATE ALL EFFORTS IN
ACCORDANCE WITH ENFORCED INFECTION CONTROL RISK
ASSESSMENT (ICRA) REQUIREMENTS.
2. ALL MATERIALS FURNISHED BY THE CONTRACTOR ARE
TO BE NEW AND APPROVED BY THE OWNER AS TO
MANUFACTURER AND TYPE.
3. ALL LOCATIONS AND DIMENSIONS SHOWN ARE
APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY
ALL ELECTRICAL EQUIPMENT LOCATIONS AND
EQUIPMENT DIMENSIONS. CONTRACTOR SHALL BE
RESPONSIBLE FOR PROVIDING EQUIPMENT THAT WILL
FIT IN THE SPACE ALLOTTED.
4. THE LOCATION OF UTILITIES AND STRUCTURES, BOTH
SURFACE AND SUBSURFACE, ARE SHOWN
ON THE PLANS FROM DATA AVAILABLE AT THE TIME OF
THE SURVEY AND ARE NOT NECESSARILY
COMPLETE OR CORRECT. THE EXACT LOCATION AND
PROTECTION OF UTILITIES AND STRUCTURES
IS THE RESPONSIBILITY OF THE CONTRACTOR. DURING
CONSTRUCTION THE CONTRACTOR SHALL
USE DILIGENCE TO PROTECT ALL EXISTING UTILITIES
AND STRUCTURES WHETHER SHOWN ON THE
PLANS OR NOT. IF DAMAGE IS CAUSED, THE
CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR
AND RESTORATION OF SAME IN ACCORDANCE WITH THE
DIRECTIONS OF THE ENGINEER AND FOR
ANY RESULTING CONTINGENT DAMAGES; GOVERNMENT
SHALL BEAR NO ADDITIONAL COSTS.
5. ONLY PULLBOXES SPECIFICALLY REQUIRED BY THE
ENGINEER IN LOCATIONS SHOWN ARE
IDENTIFIED. CONTRACTOR SHALL PROVIDE ALL
PULLBOXES REQUIRED TO MEET APPLICABLE
CODES.
6. CONTRACTOR TO COORDINATE WITH FACILITIES AND
BIOMEDICAL ENGINEERING FOR SEGREGATION AND
DIVERSITY OF LOADS BETWEEN THE EXISTING IPS AND
NEWLY INSTALLED IPS. CONTRACTOR TO BALANCE
LEAKAGE CURRENT. RE-LABEL PANEL SCHEDULES AND
FIELD DEVICES WITH ACCURATE CIRCUIT IDENTITY.
7. CONTRACTOR SHALL PRESERVE, REPAIR, AND
RE-CERTIFY ALL LEAD SHIELDING WHERE DAMAGED OR
AFFECTED WITHIN SCOPE OF WORK.
8. CONTRACTOR SHALL PRESERVE, PROTECT, AND REPAIR
ALL FINISHES SUBJECT TO DAMAGE WITHIN SCOPE OF
WORK. REPAIR OF DAMAGE MADE AT NO ADDITIONAL
COST TO THE GOVERNMENT.
NOT USED.2
NOT USED.3
NOT USED.4
NOT USED.5
1 1
SCALE: 1/4" = 1'SCALE: 1/4" = 1'SCALE: 1/4" = 1'
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
OR-3 OPERATING RM
AutoCAD SHX Text 2E135
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
XIPU
AutoCAD SHX Text
3#6+1#10 EG
AutoCAD SHX Text
IN 1" CONDUIT
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 25,27,29
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
LIPU
AutoCAD SHX Text
3#10+1#10 EG
AutoCAD SHX Text
IN 3/4" CONDUIT
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 26,28,30
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text 31,33,35
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text
TO EF-3
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text J
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
OR-3 OPERATING RM
AutoCAD SHX Text 2E135
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
XIPU
AutoCAD SHX Text
3#6+1#10 EG
AutoCAD SHX Text
IN 1" CONDUIT
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 25,27,29
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
LIPU
AutoCAD SHX Text
3#10+1#10 EG
AutoCAD SHX Text
IN 3/4" CONDUIT
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 26,28,30
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text 31,33,35
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text
TO EF-3
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text J
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
OR-3 OPERATING RM
AutoCAD SHX Text 2E135
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
XIPU
AutoCAD SHX Text
3#6+1#10 EG
AutoCAD SHX Text
IN 1" CONDUIT
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 25,27,29
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
LIPU
AutoCAD SHX Text
3#10+1#10 EG
AutoCAD SHX Text
IN 3/4" CONDUIT
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 26,28,30
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text 31,33,35
AutoCAD SHX Text
IPU#4
AutoCAD SHX Text
TO EF-3
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
IPU#4
J
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
E104
OR #4 - ISOLATED POWER PLAN
Fi le
P at h
/1 5/
1:
:0
AM
FOR CONSTRUCTION
U.S. Department of Veterans Affairs
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseDESIGNER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CORRECT CODE DEFICIENCY FOR
INCREASED ISOLATED POWER
688 - WASHINGTON D.C. VAMC
688-24-###
Project Director
NOV 1 2023 Chkd By DMWRevisions: Date:
1 DETAIL 1 - EXISTING 2 DETAIL 2 - DEMOITION 3 DETAIL 3 - NEW WORK
GENERAL NOTES: (THIS SHEET)
KEYED NOTES: (THIS DETAIL)#
EXISTING TO REMAIN IPS IN OR #4.1
KEYED NOTES: (THIS DETAIL)#
PREPARE SPACE FOR NEW ADDITIONAL IPS; PROTECT
SHIELDING.
NOT USED.2
NOT USED.3
NOT USED.4
NOT USED.5
KEYED NOTES: (THIS DETAIL)#
PROVIDE NEW ADDITIONAL IPS IN OR #4 FED FROM 'ORNL'.1
DIVERSIFY LOADS BETWEEN EXISTING AND NEW IPS FOR MATCHED LEAKAGE
CURRENTS WITH FACILITY COORDINATION.
ONCE LOADS ARE BALANCED, CONTRACTOR TO UPDATE PANEL SCHEDULE AND
CIRCUIT IDENTIFIERS ON WIRING DEVICES.
NOT USED.4
NOT USED.5
1. CONTRACTOR SHALL COORDINATE ALL EFFORTS IN
ACCORDANCE WITH ENFORCED INFECTION CONTROL RISK
ASSESSMENT (ICRA) REQUIREMENTS.
2. ALL MATERIALS FURNISHED BY THE CONTRACTOR ARE
TO BE NEW AND APPROVED BY THE OWNER AS TO
MANUFACTURER AND TYPE.
3. ALL LOCATIONS AND DIMENSIONS SHOWN ARE
APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY
ALL ELECTRICAL EQUIPMENT LOCATIONS AND
EQUIPMENT DIMENSIONS. CONTRACTOR SHALL BE
RESPONSIBLE FOR PROVIDING EQUIPMENT THAT WILL
FIT IN THE SPACE ALLOTTED.
4. THE LOCATION OF UTILITIES AND STRUCTURES, BOTH
SURFACE AND SUBSURFACE, ARE SHOWN
ON THE PLANS FROM DATA AVAILABLE AT THE TIME OF
THE SURVEY AND ARE NOT NECESSARILY
COMPLETE OR CORRECT. THE EXACT LOCATION AND
PROTECTION OF UTILITIES AND STRUCTURES
IS THE RESPONSIBILITY OF THE CONTRACTOR. DURING
CONSTRUCTION THE CONTRACTOR SHALL
USE DILIGENCE TO PROTECT ALL EXISTING UTILITIES
AND STRUCTURES WHETHER SHOWN ON THE
PLANS OR NOT. IF DAMAGE IS CAUSED, THE
CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR
AND RESTORATION OF SAME IN ACCORDANCE WITH THE
DIRECTIONS OF THE ENGINEER AND FOR
ANY RESULTING CONTINGENT DAMAGES; GOVERNMENT
SHALL BEAR NO ADDITIONAL COSTS.
5. ONLY PULLBOXES SPECIFICALLY REQUIRED BY THE
ENGINEER IN LOCATIONS SHOWN ARE
IDENTIFIED. CONTRACTOR SHALL PROVIDE ALL
PULLBOXES REQUIRED TO MEET APPLICABLE
CODES.
6. CONTRACTOR TO COORDINATE WITH FACILITIES AND
BIOMEDICAL ENGINEERING FOR SEGREGATION AND
DIVERSITY OF LOADS BETWEEN THE EXISTING IPS AND
NEWLY INSTALLED IPS. CONTRACTOR TO BALANCE
LEAKAGE CURRENT. RE-LABEL PANEL SCHEDULES AND
FIELD DEVICES WITH ACCURATE CIRCUIT IDENTITY.
7. CONTRACTOR SHALL PRESERVE, REPAIR, AND
RE-CERTIFY ALL LEAD SHIELDING WHERE DAMAGED OR
AFFECTED WITHIN SCOPE OF WORK.
8. CONTRACTOR SHALL PRESERVE, PROTECT, AND REPAIR
ALL FINISHES SUBJECT TO DAMAGE WITHIN SCOPE OF
WORK. REPAIR OF DAMAGE MADE AT NO ADDITIONAL
COST TO THE GOVERNMENT.
NOT USED.2
NOT USED.3
NOT USED.4
NOT USED.5
SCALE: 1/4" = 1'SCALE: 1/4" = 1'SCALE: 1/4" = 1'
AutoCAD SHX Text
OR-4 CARDIAC OPERATING RM
AutoCAD SHX Text 2E134
AutoCAD SHX Text
HEART PUMP RM
AutoCAD SHX Text 2E133
AutoCAD SHX Text
ORNP-3,35
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
XIPU
AutoCAD SHX Text
3#6+1#10 EG
AutoCAD SHX Text
IN 1" CONDUIT
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
1PU#2
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text 3#10 +1#10
AutoCAD SHX Text
EG IN 3/4"C.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ORNP-7,9,11
AutoCAD SHX Text
IPU#2
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#2
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text D,G
AutoCAD SHX Text D,G
AutoCAD SHX Text D,G
AutoCAD SHX Text
AutoCAD SHX Text D,G
AutoCAD SHX Text 10,12
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 26,28,30
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
OREP
AutoCAD SHX Text -7,9,11
AutoCAD SHX Text
OREP-
AutoCAD SHX Text 8,10,12
AutoCAD SHX Text G
AutoCAD SHX Text
IPU#2
AutoCAD SHX Text
IPU#2
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 31,33,35
AutoCAD SHX Text
IPU#2
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 8,10,12
AutoCAD SHX Text D,G
AutoCAD SHX Text M
AutoCAD SHX Text
WP
AutoCAD SHX Text
TO VSD
AutoCAD SHX Text J
AutoCAD SHX Text
EF-3 ON ROOF
AutoCAD SHX Text
11/2HP,480. 3%%C
AutoCAD SHX Text W.P.
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
IPU#2
AutoCAD SHX Text
ON
AutoCAD SHX Text
ROOF
AutoCAD SHX Text J
AutoCAD SHX Text
OR-4 CARDIAC OPERATING RM
AutoCAD SHX Text 2E134
AutoCAD SHX Text
HEART PUMP RM
AutoCAD SHX Text 2E133
AutoCAD SHX Text
ORNP-3,35
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
XIPU
AutoCAD SHX Text
3#6+1#10 EG
AutoCAD SHX Text
IN 1" CONDUIT
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
1PU#2
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text 3#10 +1#10
AutoCAD SHX Text
EG IN 3/4"C.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ORNP-7,9,11
AutoCAD SHX Text
IPU#2
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#2
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text D,G
AutoCAD SHX Text D,G
AutoCAD SHX Text D,G
AutoCAD SHX Text
AutoCAD SHX Text D,G
AutoCAD SHX Text 10,12
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 26,28,30
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
OREP
AutoCAD SHX Text -7,9,11
AutoCAD SHX Text
OREP-
AutoCAD SHX Text 8,10,12
AutoCAD SHX Text G
AutoCAD SHX Text
IPU#2
AutoCAD SHX Text
IPU#2
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 31,33,35
AutoCAD SHX Text
IPU#2
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 8,10,12
AutoCAD SHX Text D,G
AutoCAD SHX Text M
AutoCAD SHX Text
WP
AutoCAD SHX Text
TO VSD
AutoCAD SHX Text J
AutoCAD SHX Text
EF-3 ON ROOF
AutoCAD SHX Text
11/2HP,480. 3%%C
AutoCAD SHX Text W.P.
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
IPU#2
AutoCAD SHX Text
ON
AutoCAD SHX Text
ROOF
AutoCAD SHX Text J
AutoCAD SHX Text
OR-4 CARDIAC OPERATING RM
AutoCAD SHX Text 2E134
AutoCAD SHX Text
HEART PUMP RM
AutoCAD SHX Text 2E133
AutoCAD SHX Text
ORNP-3,35
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
XIPU
AutoCAD SHX Text
3#6+1#10 EG
AutoCAD SHX Text
IN 1" CONDUIT
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
1PU#2
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text 3#10 +1#10
AutoCAD SHX Text
EG IN 3/4"C.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ORNP-7,9,11
AutoCAD SHX Text
IPU#2
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#2
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text D,G
AutoCAD SHX Text D,G
AutoCAD SHX Text D,G
AutoCAD SHX Text
AutoCAD SHX Text D,G
AutoCAD SHX Text 10,12
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 26,28,30
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
OREP
AutoCAD SHX Text -7,9,11
AutoCAD SHX Text
OREP-
AutoCAD SHX Text 8,10,12
AutoCAD SHX Text G
AutoCAD SHX Text
IPU#2
AutoCAD SHX Text
IPU#2
AutoCAD SHX Text
IPU#3
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 31,33,35
AutoCAD SHX Text
IPU#2
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 8,10,12
AutoCAD SHX Text D,G
AutoCAD SHX Text M
AutoCAD SHX Text
WP
AutoCAD SHX Text
TO VSD
AutoCAD SHX Text J
AutoCAD SHX Text
EF-3 ON ROOF
AutoCAD SHX Text
11/2HP,480. 3%%C
AutoCAD SHX Text W.P.
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
IPU#2
AutoCAD SHX Text
ON
AutoCAD SHX Text
ROOF
J
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
E105
OR #5 - ISOLATED POWER PLAN
Fi le
P at h
/1 5/
1:
:0
AM
FOR CONSTRUCTION
U.S. Department of Veterans Affairs
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseDESIGNER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CORRECT CODE DEFICIENCY FOR
INCREASED ISOLATED POWER
688 - WASHINGTON D.C. VAMC
688-24-###
Project Director
NOV 1 2023 Chkd By DMWRevisions: Date:
1 DETAIL 1 - EXISTING 2 DETAIL 2 - DEMOITION 3 DETAIL 3 - NEW WORK
GENERAL NOTES: (THIS SHEET)
KEYED NOTES: (THIS DETAIL)#
EXISTING TO REMAIN IPS IN OR #5.1
KEYED NOTES: (THIS DETAIL)#
PREPARE SPACE FOR NEW ADDITIONAL IPS; PROTECT
SHIELDING.
NOT USED.2
NOT USED.3
NOT USED.4
NOT USED.5
KEYED NOTES: (THIS DETAIL)#
PROVIDE NEW ADDITIONAL IPS IN OR #5 FED FROM 'ORNL'.1
DIVERSIFY LOADS BETWEEN EXISTING AND NEW IPS FOR MATCHED LEAKAGE
CURRENTS WITH FACILITY COORDINATION.
ONCE LOADS ARE BALANCED, CONTRACTOR TO UPDATE PANEL SCHEDULE AND
CIRCUIT IDENTIFIERS ON WIRING DEVICES.
NOT USED.4
NOT USED.5
1. CONTRACTOR SHALL COORDINATE ALL EFFORTS IN
ACCORDANCE WITH ENFORCED INFECTION CONTROL RISK
ASSESSMENT (ICRA) REQUIREMENTS.
2. ALL MATERIALS FURNISHED BY THE CONTRACTOR ARE
TO BE NEW AND APPROVED BY THE OWNER AS TO
MANUFACTURER AND TYPE.
3. ALL LOCATIONS AND DIMENSIONS SHOWN ARE
APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY
ALL ELECTRICAL EQUIPMENT LOCATIONS AND
EQUIPMENT DIMENSIONS. CONTRACTOR SHALL BE
RESPONSIBLE FOR PROVIDING EQUIPMENT THAT WILL
FIT IN THE SPACE ALLOTTED.
4. THE LOCATION OF UTILITIES AND STRUCTURES, BOTH
SURFACE AND SUBSURFACE, ARE SHOWN
ON THE PLANS FROM DATA AVAILABLE AT THE TIME OF
THE SURVEY AND ARE NOT NECESSARILY
COMPLETE OR CORRECT. THE EXACT LOCATION AND
PROTECTION OF UTILITIES AND STRUCTURES
IS THE RESPONSIBILITY OF THE CONTRACTOR. DURING
CONSTRUCTION THE CONTRACTOR SHALL
USE DILIGENCE TO PROTECT ALL EXISTING UTILITIES
AND STRUCTURES WHETHER SHOWN ON THE
PLANS OR NOT. IF DAMAGE IS CAUSED, THE
CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR
AND RESTORATION OF SAME IN ACCORDANCE WITH THE
DIRECTIONS OF THE ENGINEER AND FOR
ANY RESULTING CONTINGENT DAMAGES; GOVERNMENT
SHALL BEAR NO ADDITIONAL COSTS.
5. ONLY PULLBOXES SPECIFICALLY REQUIRED BY THE
ENGINEER IN LOCATIONS SHOWN ARE
IDENTIFIED. CONTRACTOR SHALL PROVIDE ALL
PULLBOXES REQUIRED TO MEET APPLICABLE
CODES.
6. CONTRACTOR TO COORDINATE WITH FACILITIES AND
BIOMEDICAL ENGINEERING FOR SEGREGATION AND
DIVERSITY OF LOADS BETWEEN THE EXISTING IPS AND
NEWLY INSTALLED IPS. CONTRACTOR TO BALANCE
LEAKAGE CURRENT. RE-LABEL PANEL SCHEDULES AND
FIELD DEVICES WITH ACCURATE CIRCUIT IDENTITY.
7. CONTRACTOR SHALL PRESERVE, REPAIR, AND
RE-CERTIFY ALL LEAD SHIELDING WHERE DAMAGED OR
AFFECTED WITHIN SCOPE OF WORK.
8. CONTRACTOR SHALL PRESERVE, PROTECT, AND REPAIR
ALL FINISHES SUBJECT TO DAMAGE WITHIN SCOPE OF
WORK. REPAIR OF DAMAGE MADE AT NO ADDITIONAL
COST TO THE GOVERNMENT.
NOT USED.2
NOT USED.3
NOT USED.4
NOT USED.5
SCALE: 1/4" = 1'SCALE: 1/4" = 1'SCALE: 1/4" = 1'
1 2
AutoCAD SHX Text
MED RM
AutoCAD SHX Text 2E140A
AutoCAD SHX Text
TOILET
AutoCAD SHX Text 2E110C
AutoCAD SHX Text
DICT
AutoCAD SHX Text 2E110B
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
SUB- STERILE
AutoCAD SHX Text 2E131A
AutoCAD SHX Text
HOUSEKEEPING
AutoCAD SHX Text 2E132
AutoCAD SHX Text
OR-5 OPERATING RM
AutoCAD SHX Text 2E131
AutoCAD SHX Text
DICT
AutoCAD SHX Text 2E110A
AutoCAD SHX Text
AutoCAD SHX Text 15,17
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text D,G
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
IPU#1
AutoCAD SHX Text J
AutoCAD SHX Text
XIPU
AutoCAD SHX Text 3#6+1#10
AutoCAD SHX Text
EG IN
AutoCAD SHX Text
1" CONDUIT
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#1
AutoCAD SHX Text J
AutoCAD SHX Text
LIPU
AutoCAD SHX Text
3#10+1#10 EG IN
AutoCAD SHX Text
3/4" CONDUIT
AutoCAD SHX Text
IPU#1
AutoCAD SHX Text D,G
AutoCAD SHX Text D,G
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 13,15,17
AutoCAD SHX Text
IPU#1
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#1
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text D
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text
LASER ISPLATION
AutoCAD SHX Text
PANEL (LIPU)
AutoCAD SHX Text
MED RM
AutoCAD SHX Text 2E140A
AutoCAD SHX Text
TOILET
AutoCAD SHX Text 2E110C
AutoCAD SHX Text
DICT
AutoCAD SHX Text 2E110B
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
SUB- STERILE
AutoCAD SHX Text 2E131A
AutoCAD SHX Text
HOUSEKEEPING
AutoCAD SHX Text 2E132
AutoCAD SHX Text
OR-5 OPERATING RM
AutoCAD SHX Text 2E131
AutoCAD SHX Text
DICT
AutoCAD SHX Text 2E110A
AutoCAD SHX Text
AutoCAD SHX Text 15,17
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text D,G
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
IPU#1
AutoCAD SHX Text J
AutoCAD SHX Text
XIPU
AutoCAD SHX Text 3#6+1#10
AutoCAD SHX Text
EG IN
AutoCAD SHX Text
1" CONDUIT
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#1
AutoCAD SHX Text J
AutoCAD SHX Text
LIPU
AutoCAD SHX Text
3#10+1#10 EG IN
AutoCAD SHX Text
3/4" CONDUIT
AutoCAD SHX Text
IPU#1
AutoCAD SHX Text D,G
AutoCAD SHX Text D,G
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 13,15,17
AutoCAD SHX Text
IPU#1
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#1
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text D
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text
LASER ISPLATION
AutoCAD SHX Text
PANEL (LIPU)
AutoCAD SHX Text
MED RM
AutoCAD SHX Text 2E140A
AutoCAD SHX Text
TOILET
AutoCAD SHX Text 2E110C
AutoCAD SHX Text
DICT
AutoCAD SHX Text 2E110B
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
SUB- STERILE
AutoCAD SHX Text 2E131A
AutoCAD SHX Text
HOUSEKEEPING
AutoCAD SHX Text 2E132
AutoCAD SHX Text
OR-5 OPERATING RM
AutoCAD SHX Text 2E131
AutoCAD SHX Text
DICT
AutoCAD SHX Text 2E110A
AutoCAD SHX Text
AutoCAD SHX Text 15,17
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text D,G
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
IPU#1
AutoCAD SHX Text J
AutoCAD SHX Text
XIPU
AutoCAD SHX Text 3#6+1#10
AutoCAD SHX Text
EG IN
AutoCAD SHX Text
1" CONDUIT
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#1
AutoCAD SHX Text J
AutoCAD SHX Text
LIPU
AutoCAD SHX Text
3#10+1#10 EG IN
AutoCAD SHX Text
3/4" CONDUIT
AutoCAD SHX Text
IPU#1
AutoCAD SHX Text D,G
AutoCAD SHX Text D,G
AutoCAD SHX Text
ORNP-
AutoCAD SHX Text 13,15,17
AutoCAD SHX Text
IPU#1
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
IPU#1
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text D
AutoCAD SHX Text +5'-0"
AutoCAD SHX Text
LASER ISPLATION
PANEL (LIPU)
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
E300
ONE-LINE DIAGRAM
Fi le
P at h
/1 5/
1:
:0
AM
FOR CONSTRUCTION
U.S. Department of Veterans Affairs
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseDESIGNER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CORRECT CODE DEFICIENCY FOR
INCREASED ISOLATED POWER
688 - WASHINGTON D.C. VAMC
688-24-###
Project Director
NOV 1 2023 Chkd By DMWRevisions: Date:
GENERAL NOTES: (THIS SHEET)
1. CONTRACTOR SHALL COORDINATE ALL EFFORTS IN
ACCORDANCE WITH ENFORCED INFECTION CONTROL RISK
ASSESSMENT (ICRA) REQUIREMENTS.
2. ALL MATERIALS FURNISHED BY THE CONTRACTOR ARE
TO BE NEW AND APPROVED BY THE OWNER AS TO
MANUFACTURER AND TYPE.
3. ALL LOCATIONS AND DIMENSIONS SHOWN ARE
APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY
ALL ELECTRICAL EQUIPMENT LOCATIONS AND
EQUIPMENT DIMENSIONS. CONTRACTOR SHALL BE
RESPONSIBLE FOR PROVIDING EQUIPMENT THAT WILL
FIT IN THE SPACE ALLOTTED.
4. THE LOCATION OF UTILITIES AND STRUCTURES, BOTH
SURFACE AND SUBSURFACE, ARE SHOWN
ON THE PLANS FROM DATA AVAILABLE AT THE TIME OF
THE SURVEY AND ARE NOT NECESSARILY
COMPLETE OR CORRECT. THE EXACT LOCATION AND
PROTECTION OF UTILITIES AND STRUCTURES
IS THE RESPONSIBILITY OF THE CONTRACTOR. DURING
CONSTRUCTION THE CONTRACTOR SHALL
USE DILIGENCE TO PROTECT ALL EXISTING UTILITIES
AND STRUCTURES WHETHER SHOWN ON THE
PLANS OR NOT. IF DAMAGE IS CAUSED, THE
CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR
AND RESTORATION OF SAME IN ACCORDANCE WITH THE
DIRECTIONS OF THE ENGINEER AND FOR
ANY RESULTING CONTINGENT DAMAGES; GOVERNMENT
SHALL BEAR NO ADDITIONAL COSTS.
5. ONLY PULLBOXES SPECIFICALLY REQUIRED BY THE
ENGINEER IN LOCATIONS SHOWN ARE
IDENTIFIED. CONTRACTOR SHALL PROVIDE ALL
PULLBOXES REQUIRED TO MEET APPLICABLE
CODES.
6. ALL EQUIPMENT IS EXISTING TO REMAIN (ETR) UNLESS
NOTED OTHERWISE (UNO).
7. VA MEDICAL CENTER HAS FIRST RIGHT OF REFUSAL ON
ALL EQUIPMENT REMOVED FROM SERVICE. IF RETAINED,
COORDINATE FOR DELIVERY TO STORAGE LOCATION ON
SITE.
8. CONTRACTOR SHALL PHASE WORK IN SUCH A MANNER
TO MINIMIZE IMPACT TO MEDICAL CENTER OPERATIONS.
INTERRUPTION OF SERVICES REQUIRE 14 DAY NOTICE
TO COR.
9. ELECTRICAL REQUIREMENTS PER CONTRACT
DOCUMENTS; DRAWINGS AND SPECIFICATIONS, AND
CURRENT PUBLICATION OF NFPA 70, 99, 101, AND 110.
KEYED NOTES: (THIS SHEET)#
REMOVE FEEDER FROM NORMAL DISTRIBUTION. DEMOLISH COMPLETELY.1
PROVIDE FEEDER ON EMERGENCY DISTRIBUTION.2
IPS EXISTING IN OR 1 THRU 5 ARE ETR.3
PROVIDE ADDITIONAL 7.5kVA IP TO DIVERSIFY LOADS IN EACH OR.
BENDER LIM2010, 16 SPACE (2-POLE) OR EQUAL.
OR#4 IS OMITTED FROM ADDITIONAL IP. HAS ALREADY BEEN INSTALLED FROM OR#5.5
OR#5 REQUIRES (2) NEW IPS. REFERENCE KEYED NOTE 5.6
CONTRACTOR SHALL BALANCE LOADS BETWEEN EACH (2) IP SYSTEM PER OR.7
CONTRACTOR RESPONSIBLE FOR INDEPENDENT THIRD PARTY NFPA 99 CERTIFICATION.8
PANELS LOCATED IN MECHANICAL SPACE 2078, ADJACENT TO OR HVAC.9
PANELS LOCATED IN BASEMENT ELECTRICAL DISTRIBUTION ROOM; REFERENCE SHEET
E400.
BASEMENT
FIRST FLOOR
SECOND FLOOR
DP5
ORNL
75kVA
TX
ORNP
DPE2
E1PDP XRAY
IP
15kVA
OR1
IP
7.5kVA
OR2
IP
7.5kVA
OR3
IP
7.5kVA
OR4
IP
7.5kVA
OR5
IP
7.5kVA
LASER
IP
25kVA
480/277V 3PH 4W+G
225A MLO 22KAIC
480/277V 3PH 4W+G
225A MLO 22KAIC
DPE2
E1PDP XRAY
IP
15kVA
OR1
IP
7.5kVA
OR2
IP
7.5kVA
OR3
IP
7.5kVA
OR4
IP
7.5kVA
OR5
IP
7.5kVA
LASER
IP
25kVA
480/277V 3PH 4W+G
225A MLO 22KAIC
OR1
IP2
7.5kVA
OR2
IP2
7.5kVA
OR3
IP2
7.5kVA
OR4
IP2
7.5kVA
OR5
IP2
7.5kVA
SWBD
EMB
ORNL
75kVA
TX
ORNP
480/277V 3PH 4W+G
225A MLO 22KAIC
SUB 3
SWGR #3
ATS #9
1 DETAIL 1 - EXISTING
SCALE: NTS 2 DETAIL 2 - NEW WORK
SCALE: NTS
56 6
3 DETAIL 3 - UPDATED SCHEDULE
SCALE: NTS
OR #1 IP2
OR #2 IP2
OR #3 IP2
OR #4 IP2
OR #5 IP2
3.75
3.75
3.75
3.75
3.75
3.75
3.75
3.75
3.75 3.75
PROVIDE 2-POLE FEEDER BREAKERS AT MATCHING kAIC RATING OF ENCLOSURE IAW
MANUFACTURER REQUIREMENTS OF NEW IPS.
AutoCAD SHX Text
2#8, 1#10 EG 1"C
AutoCAD SHX Text
2#6, 1#8 EG 1-1/4"C
AutoCAD SHX Text
2#10, 1#12 EG 3/4"C (TYP.)
AutoCAD SHX Text
100A FEEDER (ORNL) 4#1/0, 1#6 EG 2"C
AutoCAD SHX Text
2#8, 1#10 EG 1"C
AutoCAD SHX Text
2#6, 1#8 EG 1-1/4"C
AutoCAD SHX Text
2#10, 1#12 EG 3/4"C (TYP.)
AutoCAD SHX Text
225A FEEDER (E1PDP) 4#250 KCMIL, 1#4 EG 3"C
AutoCAD SHX Text RELOCATE 'ORNL' FEEDER FROM DP5 TO SWBD 'EMB'. UTILIZE EXISTING PREPARED SPACE RATED FOR FEEDER. CONTRACTOR SHALL PROVIDE COORDINATION AND LABELING FOR NEW WORK IAW SPECIFICATION.
AutoCAD SHX Text PROVIDE SECOND FLUSH MOUNTED 7.5kVA ISOLATED POWER SYSTEM IN EACH OR ADJACENT TO EXISTING SYSTEM. CONTRACTOR TO DIVERSIFY LOADS BETWEEN THE TWO PANEL IN EACH OR.
AutoCAD SHX Text
2#10, 1#12 EG 3/4"C (TYP.)
AutoCAD SHX Text
NEW 225A FEEDER (ORNL) 4#250 KCMIL, 1#4 EG 3"C
SEQUENCE NOTE: PROVIDE NEW FEEDER PRIOR TO DEMOLITION OF OLD FEEDER TO THE PANEL TO REDUCE DOWNTIME TO THE MOST PRACTICAL EXTENTS.
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
E400
BASEMENT POWER PLAN
Fi le
P at h
/1 5/
1:
:0
AM
FOR CONSTRUCTION
U.S. Department of Veterans Affairs
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseDESIGNER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CORRECT CODE DEFICIENCY FOR
INCREASED ISOLATED POWER
688 - WASHINGTON D.C. VAMC
688-24-###
Project Director
NOV 1 2023 Chkd By DMWRevisions: Date:
GENERAL NOTES: (THIS SHEET)
1. CONTRACTOR SHALL COORDINATE ALL EFFORTS IN
ACCORDANCE WITH ENFORCED INFECTION CONTROL RISK
ASSESSMENT (ICRA) REQUIREMENTS.
2. ALL MATERIALS FURNISHED BY THE CONTRACTOR ARE
TO BE NEW AND APPROVED BY THE OWNER AS TO
MANUFACTURER AND TYPE.
3. ALL LOCATIONS AND DIMENSIONS SHOWN ARE
APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY
ALL ELECTRICAL EQUIPMENT LOCATIONS AND
EQUIPMENT DIMENSIONS. CONTRACTOR SHALL BE
RESPONSIBLE FOR PROVIDING EQUIPMENT THAT WILL
FIT IN THE SPACE ALLOTTED.
4. THE LOCATION OF UTILITIES AND STRUCTURES, BOTH
SURFACE AND SUBSURFACE, ARE SHOWN
ON THE PLANS FROM DATA AVAILABLE AT THE TIME OF
THE SURVEY AND ARE NOT NECESSARILY
COMPLETE OR CORRECT. THE EXACT LOCATION AND
PROTECTION OF UTILITIES AND STRUCTURES
IS THE RESPONSIBILITY OF THE CONTRACTOR. DURING
CONSTRUCTION THE CONTRACTOR SHALL
USE DILIGENCE TO PROTECT ALL EXISTING UTILITIES
AND STRUCTURES WHETHER SHOWN ON THE
PLANS OR NOT. IF DAMAGE IS CAUSED, THE
CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR
AND RESTORATION OF SAME IN ACCORDANCE WITH THE
DIRECTIONS OF THE ENGINEER AND FOR
ANY RESULTING CONTINGENT DAMAGES; GOVERNMENT
SHALL BEAR NO ADDITIONAL COSTS.
5. ONLY PULLBOXES SPECIFICALLY REQUIRED BY THE
ENGINEER IN LOCATIONS SHOWN ARE
IDENTIFIED. CONTRACTOR SHALL PROVIDE ALL
PULLBOXES REQUIRED TO MEET APPLICABLE
CODES.
6. ALL EQUIPMENT IS EXISTING TO REMAIN (ETR) UNLESS
NOTED OTHERWISE (UNO).
7. VA MEDICAL CENTER HAS FIRST RIGHT OF REFUSAL ON
ALL EQUIPMENT REMOVED FROM SERVICE. IF RETAINED,
COORDINATE FOR DELIVERY TO STORAGE LOCATION ON
SITE.
8. CONTRACTOR SHALL PHASE WORK IN SUCH A MANNER
TO MINIMIZE IMPACT TO MEDICAL CENTER OPERATIONS.
INTERRUPTION OF SERVICES REQUIRE 14 DAY NOTICE
TO COR.
9. ELECTRICAL REQUIREMENTS PER CONTRACT
DOCUMENTS; DRAWINGS AND SPECIFICATIONS, AND
CURRENT PUBLICATION OF NFPA 70, 99, 101, AND 110.
10. ROUTE CONDUIT PARALLEL AND PERPENDICULAR TO
BUILDING STRUCTURES AND EQUIPMENT. COORDINATE
WITH OTHER TRADES FOR ACCESSIBILITY AND
SERVICEABILITY.
KEYED NOTES: (THIS SHEET)#
REMOVE FEEDER FROM 'DP5' TO 'ORNL'. REFERENCE ONE-LINE DRAWINGS.1
PROVIDE FEEDER FROM 'EMB' TO 'ORNL'. REFERENCE ONE-LINE DRAWINGS.2
NOT USED.3
NOT USED.4
NOT USED.5
1 DETAIL 1 - BASEMENT ELECTRICAL ROOM WORK PLAN
SCALE: NTS
| Sheets and Views |
| E101 |
| E102.pdf |
| Sheets and Views |
| E102 |
| E103.pdf |
| Sheets and Views |
| E103 |
| E104.pdf |
| Sheets and Views |
| E104 |
| E105.pdf |
| Sheets and Views |
| E105 |
| E300.pdf |
| Sheets and Views |
| E300 |
| E400.pdf |
| Sheets and Views |
| E400 |
File details come from the government source that posted it. Updated .