This memorandum outlines requirements for a solicitation seeking four diesel generators. The Department of the Air Force Oklahoma City Air Logistics Complex at Tinker Air Force Base requests generators producing 72KW of continuous 400Hz power from diesel fuel without diesel exhaust fluid. Generators must meet MIL-STD-704E and include 60-foot cables, 28.5VDC and 270VDC outputs, electric starting, fault detection, lighted controls, and an enclosed trailer. The related solicitation posted by the Air Force Sustainment Center seeks these generators set aside for small business, with quotes due by the closing date on page one. Responders should complete forms, certifications, and pricing and explain how they meet technical criteria.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Solicitation - FA812522Q0053.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEPARTMENT OF THE AIR FORCE
OKLAHOMA CITY AIR LOGISTICS COMPLEX (OC-ALC)
TINKER AIR FORCE BASE OKLAHOMA
Item Description
MEMORANDUM FOR RECORD
SUBJECT: Item Description, A22-053 Diesel Generators
1. 76 AMXG request the purchase of four (4) Diesel Generators used for multiple processes during the maintenance of KC-135, E-3, E-6, B-1, and B-52 weapon systems.
2. The requested descriptions/specifications are outlined below.
A. Four (4) Each Diesel Generators that meet the following specifications:
• 72 KW, 400 Hz continuous load at 0.8 power factor, at rated voltage
• Shall run on Diesel Fuel without using Diesel Exhaust Fluid (DEF)
• AC OUTPUT VOLTAGE:
Three phase, four wire, 115 volts line-to-neutral and 200 volts line-to-line:
(115/200 volts) Reconnectable: 230/400 Volts. Must Meet MIL-STD-704E
• AC OUTPUT CABLE:
A 60 foot or greater length AC output cable with a MS25486 plug (with a replaceable contact section).
• 28.5 VDC OUTPUT:
Nominal Voltage: 28.5 Volts DC Steady State Voltage: .5 Volts DC ± 1% Amperage: 600 Amps, 2,250 Amps peak
• 270 VDC OUTPUT:
Nominal Voltage: 270 Volts DC Steady State Voltage: 270 Volts DC ± 1% Amperage: 267 Amps Continuous
• Electric starter powered by the onboard battery/batteries.
• A fault system with a solid state Generator Fault Detector and an Engine Speed and Fault Detector.
• All operating controls and instrumentation necessary for proper operation of the generator located on the control panel.
• Illumination lighting on the control panel for night operation.
• A leaf spring suspension trailer with four pneumatic tires, steerable type with a tow bar with a three inch Inside Diameter (ID) lunette eye (pintle) for connecting to a tow vehicle.