Attachment A
Specification
DE-SOL-0009752
March 2015
TECHNICAL SPECIFICATION FOR
WESTERN AREA POWER ADMINISTRATION
OPERATION AND MAINTENANCE PURCHASE OF
GLUED LAMINATED STRUCTURES
1 March 2015
TABLE OF CONTENTS
Page
Number
SECTION 1.1--GLUED LAMINATED STRUCTURES
1.1 GENERAL
1. STRUCTURES
1.2 CONTRACTOR-FURNISHED DATA AND DRAWINGS
1. GENERAL
2. DESIGN DATA SHALL INCLUDE
3. APPROVAL DRAWINGS
4. FINAL ORIGINAL DRAWINGS
1.3 DESIGN REQUIREMENTS
1. GENERAL
2. SPECIFIC REQUIREMENTS
3. EMBEDMENT DESIGN
1.4 MATERIAL
1. GENERAL
2. HARDWARE AND ASSOCIATED MATERIAL
3. WEST COAST REGION DOUGLAS FIR OR SOUTHERN PINE GLUED LAMINATED WOOD
POLES
1.5 QUALITY CONTROL
1. GENERAL
2. FRAMING
3. HUMIDITY
4. ADHESIVES
1.6 MANUFACTURE
1. EDGE JOINTS
2. END JOINTS
3. REPAIRS
4. SECOND STAGE GLUING
5. PROOF-LOADING
6. END JOINT SPACING
7. DIMENSIONS AND TOLERANCES
8. APPEARANCE
1.7 POLE MARKING AND CODE LETTERS
1.8 TESTING AND INSPECTION
1. REQUIREMENTS
2. MATERIAL
3. VOID-FILLING COMPOUNDS
4. RECORDS
5. QUALITY CONTROL SYSTEM
1.9 STORAGE, HANDLING, AND TRANSPORTING
1. ACCEPTANCE
1.10 INSTALLATION
GLUE LAMINATED STRUCTURES
2 March 2015
SECTION 1--GLUED LAMINATED STRUCTURES
1.1 GENERAL:
1. STRUCTURES: Designing, detailing, and furnishing glued laminated wood pole structures complete with foundation designs and embedment depths and the following:
(1) Poles, crossarms, and braces as applicable.
(2) Attachment hardware, connection bolts, nuts, and locknuts.
(3) Guying requirements including guy assemblies when guying is permitted. One guy, either single or double guy strand, shall include the length of guy assembly; with strand and fittings for guy attachment to connect the guys to the pole bands and to the anchor rods. The Contractor will not receive extra payment for guys longer than shown on the drawings.
(4) Guy anchors, including copper-clad anchor rods, and anchor accessories when guying is permitted.
(5) Structure grounding including staples, hardware grounding clips, and ground wire.
(6) Overhead ground wire support assemblies.
1.2 CONTRACTOR-FURNISHED DATA AND DRAWINGS:
1. GENERAL: Use United States standard units of measurement and English words, signs, and symbols. Submit data and drawing of structures. Include design calculations for all structural components. Drawings shall be new originals. Reproducibles of specification drawings are not acceptable.
Data and drawings shall be thoroughly checked for accuracy and completeness before submittal.
Western will not check details and intermediate dimensions.
Western will return one set of the design data sheets which require changes and one print of each drawing marked to indicate approved or not approved and any required changes. The Contractor shall change the designs and details which Western determines necessary to make the finished structures conform to these specifications.
Western approval shall not relieve the Contractor from meeting the specifications requirements nor the responsibility for design and drawing correctness. Fabrication prior to design data and drawing approval shall be at the Contractor’s risk.
2. DESIGN DATA SHALL INCLUDE:
(1) General dimensions and weight.
(2) Total ultimate loads and moments including the ultimate moment capacity at ground line and splices.
(3) Maximum deflection at top of structure.
(4) Camber requirements. Raking of the poles will be permitted.
(5) Species of timber.
3 March 2015
(6) Type of preservative.
(7) Quantity of structures.
(8) Certification that the Contractor has:
1) Successfully designed and supplied manufactured items of comparable magnitude and purpose for a 3-year period.
2) Manufacturing facilities used to supply glued laminated structures are adequate for the type and size of structures required.
3. APPROVAL DRAWINGS: Prior to fabrication, submit for approval, the drawings for the structures.
Note: design calculations/drawings should not be included as part of this package, they will be requested if needed. The submittal shall include:
(1) Erection drawings showing the following:
1) Dimensions.
2) A complete bill of material, including hardware and weights, listing all material for one structure or the portion shown thereon. Total weight of one complete structure shall be noted.
3) Weight, center of gravity, lifting location or lifting method for entire structure.
4) Camber orientation as it relates to direction of transmission line.
5) Foundation auger diameter, embedment depth, and rake of pole if required.
4. FINAL ORIGINAL DRAWINGS: Prior to pole shipment, furnish originals or positive reproducibles and electronic copies in AutoCAD version 2008.
1.3 DESIGN REQUIREMENTS:
1. GENERAL: Design using published theories accepted by the industry as good engineering practice.
Construction shall be Grade B. Overload factors shall be in accordance with NESC C2-2012.
Structure and attachments shall be designed for the simultaneous application of dead loads, wind on the structure and wire loads as shown in the enclosed spreadsheet. If other load cases are provided, a 1.1 overload factor shall be used. X-braces may be used if the overall structure cost is less with them.
2. SPECIFIC REQUIREMENTS: Design consistent with the following:
(1) Include proper theory to accommodate stresses from structure deflection (secondary bending).
(2) Camber or rake structures so that the structure axis are vertical after the conductors are strung. In multi-pole angle structures, all poles shall be aligned and oriented on the bisector of the angle being turned.
(3) The Pole Supplier shall be fully responsible for the structure designs and the satisfactory performance under acceptance tests. Approval by Western does not relieve the Pole Supplier of responsibility for the adequacy of the designs and drawings.
4 March 2015
3. EMBEDMENT DESIGN:
(1) Auger Diameter: Auger diameter shall be the maximum pole base dimension plus a minimum of 12 inches.
(2) Embedment Depth: The bearing capacity of the soil shall be assumed to be 5,500 psf (Class
6). The Contractor shall determine the embedment depth.
(3) Pole Supplier shall determine if a foundation reinforcement system is required. If required, the foundation system shall be an integral part of the structure and shall be included in the structure unit price.
(4) Western’s position is that each laminated pole (and foundation reinforcement, if required) will be placed in an augered hole as described above and backfilled with thoroughly compacted, well-graded, washed or unwashed, 2-inch minus rock. The pole supplier should also provide their recommended backfill material, if different than above. If the pole supplier’s installation instructions contain additional foundation requirements (i.e. caissons, culverts, etc.), Western will determine its costs in acquiring and installing those additional requirements and those costs will be added onto the submitted bid price.
1.4 MATERIAL:
1. GENERAL: Furnish all material in accordance with the drawings and the requirements of this specification. In addition to the laminated poles and foundation reinforcement (if required), the pole supplier shall provide all hardware and fasteners necessary to attach all conductors, overhead ground wires and optical ground wires to the structure as outlined in the referenced structure drawing. Dead end tees shall be furnished in lieu of pole bands as shown in drawing 41 6138.
Holes necessary for installing the hardware shall be drilled at the appropriate locations prior to preservative treatment.
2. HARDWARE AND ASSOCIATED MATERIAL:
(1) Bolts, Nuts, and Locknuts: Bolts and nuts shall be square headed and in accordance with ANSI C135.1. Unless otherwise specified, rolled or cut threads of the American Standard coarse thread series shall be furnished. The double arming bolts shall be furnished with four square nuts and threaded 6 inches at each end. Locknuts shall be Type MF.
3. WEST COAST REGION DOUGLAS FIR OR SOUTHERN PINE GLUED LAMINATED WOOD
POLES: Conforming to the following:
(1) General: Poles shall be in accordance with ANSI 05.2 including the following clarification revisions and all applicable AWPA specifications, including C28 and C32, for the preparation and treatment except as modified in this specification.
All referenced specifications and Standards shall be of the latest revision.
This specification is to be used in conjunction with the AWPA Standard C1 and M6. Structural Glue Laminated Timber is an engineered, product comprised of assemblies of specifically selected and prepared wood laminates bonded with adhesives. These assemblies are prepared under AITC Standards 110, 111, and 200.
Lumber shall be West Coast Region Douglas Fir or Southern Pine as defined in Section 4.1
ANSI 05.2.
5 March 2015
All Laminating lumber shall be graded in accordance with applicable grading rules of the West Coast Lumber Inspection Bureau (WCLIB) for Douglas fir as supplemented by the requirements of ANSI A190.1 and AITC 117.
All glue laminated poles shall have been glued with a wet use adhesive as specified in ANSI/AITC Standard A190.1
1) Flaws: All lumber for laminating poles shall be free of timber breaks.
2) Soundness: Decay in any form is not permitted, including decay in knots in any form.
3) Moisture Content: Shall be per Section 4.3 of ANSI 05.2. The mean equilibrium moisture content shall be 12 percent.
(2) Incising and Radial Drilling: Laminated poles constructed of Douglas Fir shall be incised prior to treatment. This incising shall be for the full pole length and on all four sides with a minimum depth of 5/8 inch. The pattern shall minimize any damage to the surface of the pole by splintering and shall be a sufficiently dense pattern to assure uniform treatment.
All laminated poles constructed of Douglas Fir shall be incised and through bored prior to treatment. This drilling is in the zone extending 2’ above and 3’ below the standard groundline (as defined in ANSI 05.1), or as otherwise designated. For drilling, the boring shall be 3/16” diameter by 3” long and shall be spaced in a diamond pattern so that holes within a given diamond are approximately 6” apart. Drilled holes on the edge faces shall be omitted for the first 2 laminations on each side. Care shall be taken on the edge faces to ensure that drill holes do not penetrate along glue lines. All laminated poles constructed with Southern Pine shall be drilled with this pattern on the two constant pole faces only.
For best results, all cuts and drilling should be done prior to treatment. This shall include a mechanism (i.e. internal grooves) for allowing wood preservative to flow longitudinally through the entire length of each internal joint of the pole. Care should be taken to avoid mechanical damage in both handling and in service. When mechanical damage occurs, field treatment should be in accordance with AWPA Standard M4. All poles shall be inspected after treatment in accordance with the applicable sections of AWPA Standard M2.
(3) Treatment of Poles:
1) General: All poles shall be treated in accordance with AWPA specifications C1, C4, M2, and especially C32, except as modified or changed in this paragraph.
2) Preservatives:
The preservative used in the treatment of the poles shall be one of the following:
a. Copper Naphthenate meeting the requirement of AWPA specification P8 (Section 2, Copper Naphthenate). The petroleum shall be hydrocarbon solvent, Type A only, meeting the requirements of AWPA specification P9.
The Copper Naphthenate petroleum solution shall contain not less than one percent (1 percent), by weight, of Copper Naphthenate and not less than two percent (2 percent) copper as metal.
6 March 2015
b. Pentachlorophenol petroleum solution consisting of pentachlorophenol meeting the requirements of AWPA specifications P8 (Section 1, Pentachlorophenol) dissolved in suitable petroleum oil meeting the requirements for Type A solvent of AWPA specification P9.
The concentration of pentachlorophenol, as determined in accordance with AWPA specification A5, shall be not less than 5 percent by weight.
3) Penetration: Penetration shall be determined from increment borer cores taken 1 to 2 feet below the brand from each piece of the charge. These cores shall be used to check penetration of the preservative. Additional cores in through-bored members shall be taken from a zone approximately 1 foot above the intended ground line and 1 foot below the top of the drilled zone. These cores shall be assayed for retention. If 90 percent of the boring meet the penetration requirements, the charge shall be accepted, but the non-conforming poles in the charge will be retreated.
Penetration of preservative shall be 100 percent in the ground line bored area.
4) Retention: The pole shall be treated so as to maintain the minimums noted below
(AWPA C4). Retention shall be determined with borer cores taken at the same points as for penetration determination.
a. For the Copper Naphthenate treatments, the minimum retention of preservative shall be:
Inches From
Surface (Incised zone)
Pole
Height
Copper
Naphthenate
LB/FT3
0.5 to 1.0
All
0.15
2.0 to 2.5
0.075
b. For pentachlorophenol solutions, the minimum retention of preservation shall be:
Inches From
Surface (Incised zone)
Pole
Height
Pentachorophenol
LB/FT3
0.5 to 1.0
0.60
2.0 to 2.5
0.30
c. Color: Upon completion of the treating process, all poles shall be as light colored as reasonably possible to obtain a light to medium brown; color chart range three to seven poles darker than chart seven may be rejected. Poles shall be clean and dry, without excess surface oil.
7 March 2015
1.5 QUALITY CONTROL:
1. GENERAL: The supplier shall have defined quality control methods and functions available for review and approval. Maintain permanent records on material specifications. The supplier shall eliminate all material that would be considered defective according to these specifications.
2. FRAMING: Drilling, if any, shall be as specified according to the drawings included with the order.
Drilling on specified poles and square cut roofing on all poles shall be completed BEFORE the treatment process.
3. HUMIDITY: The relative humidity of the manufacturing area shall be maintained at such a level that the moisture content will not change substantially during the manufacturing process. All bonding shall be performed as soon as practical after checking moisture content.
4. ADHESIVES: Adhesives for structural laminating shall conform to all applicable requirements of
ANSI A190.1 to comply with wet conditions of use and be compatible with the selected preservative solution to be used. Adhesives containing urea shall not be used.
1.6 MANUFACTURE:
The selection, preparation, assembly, and bonding of the laminations shall be in accordance with ANSI A190.1 and as specified herein.
1. EDGE JOINTS: Unglued edge joints shall be permitted for multiple width lamination lay-up as permitted by ANSI A190.1. The non-cut edge joint gaps shall be limited to 1/4 inch and occasionally to a maximum of 3/8 inch. The cut edge joint gap shall be limited to 3/8” inch for a nominal width of 10” and less, ½” for a nominal width of 10” to 12”, ¾” for a nominal width of 12” to 14”, 7/8” for a nominal width of 14” to 16”, and 1” for nominal widths over 16”.
2. END JOINTS: End joints of laminations shall be pre-glued and cured before assembly of face joint into structural members. Spacing of the end joints shall be as specified in ANSI A190.1.
3. REPAIRS: Structural repairs as defined in ANSI A190.1 are allowed. End blocks as defined in
ANSI A190.1 are prohibited.
4. SECOND STAGE GLUING: When two or more laminated members that are over 2 inches in net thickness are glued together, a gap-filling adhesive shall be used in accordance with ANSI A190.1.
5. PROOF-LOADING: Proof loading shall be in accordance with ANSI A190.1. All laminated stock in high stress area shall be E-rated lumber.
6. END JOINT SPACING: When proof loading is performed in accordance with ANSI A190.1, end joint spacing is not required.
7. DIMENSIONS AND TOLERANCES: Allowable variations from specified dimensions are as follows:
(1) Sizes and tolerances for poles shall be in accordance with the following:
1) Depth: ±1/2 inch.
2) Width: ±1/4 inch.
3) Squareness: ±3/8 inch per foot of depth.
8 March 2015
4) Length of poles under 50 feet: +6 inches, -3 inches.
5) Length of poles over 50 feet: +12 inches, -6 inches.
(2) Unless specified otherwise on the plans, drawings, or purchase order, holes shall be a minimum of 1/16 inch and a maximum of 1/8 inch larger than the bolt diameter.
(3) Hole locations: ±1/8 inch.
(4) The camber or straightness tolerance for poles is ±1/2 inch for members up to 20 feet. For members over 20 feet, the tolerance is increased by ±1/2 inch per each additional 20 feet, or fraction thereof, but should not exceed ±2 inches. These tolerances are at the time of manufacture without allowance for dead load deflection and should be used for straight or slightly cambered members and not more sharply curved members.
8. APPEARANCE: Glued laminated structural members shall be manufactured in accordance with the industrial appearance grade as defined in AITC 110 and as required in 1 through 6 as follows.
(1) Poles shall be eased to a minimum of 3/4 inch and a maximum of 1 inch.
(2) After gluing, all members shall be surfaced, at least on the two sides where glue lines are exposed.
(3) Splintering around the holes caused by drilling, shall be kept to a minimum. Holes shall be drilled perpendicular to the starting and finishing faces of members with a uniform cross section unless otherwise specified, or as specified on the plans and drawings of members with a variable cross section.
(4) Occasional laminations may contain wane, may be scant of the specified width, or both.
These conditions in a lamination shall not be more than 3/16 inch in width.
(5) Medium splits in the outside laminations of vertical mounted members and short splits in the top laminations of horizontal and diagonally mounted members, developing at the laminating plant after gluing, are permitted.
(6) All voids in the roof of poles shall be filled (after treating) with a void-filling compound unless otherwise specified. The compound shall be sanded or scraped smooth after patching. Wood dowels may be used to repair improperly drilled holes, as long as the defect does not affect the structural integrity of the member.
1.7 POLE MARKING AND CODE LETTERS:
The following information shall be included on a metal tag affixed thereto.
1. The supplier's code or trademark.
2. The plant location and the year of treatment.
3. Code letters denoting the pole's species and preservative used. The size designation and/or equivalent class and the length of the pole.
4. Poles shall be marked with two aluminum discs in accordance with ANSI 05.1. The discs shall be made of 24-gauge aluminum and approximately 2 inches in diameter. The discs shall be punched
9 March 2015 for nails, placed in the marking disc recesses, and attached with two twisted 2-inch aluminum twist nails. Marking on the face shall be approximately 6 feet above the ground line.
5. The approximate treated weight of the pole shall be marked at the balancepoint of the pole.
1.8 TESTING AND INSPECTION:
1. REQUIREMENTS: Testing and inspection shall be in accordance with ANSI A190.1 and AITC 200.
2. MATERIAL: Testing and inspection shall be performed on the material and from the production that is supplied on the purchase order and produced in accordance with this standard. Samples for physical testing shall be taken at random.
3. VOID-FILLING COMPOUNDS: Physical tests of void-filling compounds shall be made on samples of daily production in accordance with AITC test 110, as included in AITC 200 to establish compliance with 5.6.6.1 of AITC 200 standard.
4. RECORDS: The results of all strength and wood failure tests of face, edge, and end joints and test of void-filling compounds conducted on material produced in accordance with AITC 200 shall be sent to the purchaser within 5 working days, if requested by the purchaser. Legible copies of hand written records shall suffice.
5. QUALITY CONTROL SYSTEM: The quality control system shall be as specified in ANSI A190.1.
Daily records of the material produced under this standard shall be submitted to the purchaser within 5 working days. Daily records shall include, at least, the requirements established in the Manufacturer's Procedures Manual and Quality Control Manual and any others required in this standard.
(1) Inspection: Treated laminated poles shall be inspected after treatment in accordance with the applicable sections of AWPA Standard M2.
(2) Penetration: Penetration determination shall be made on 100 percent of the poles regardless of the specie. Penetration determination of the Douglas Fir shall be from one (1) boring per pole at the same location as noted in specification paragraph 1.4.2 and between the marking disc and the ground line. Part of these borings may be used for retention analysis.
1.9 STORAGE, HANDLING, AND TRANSPORTING:
Shipments are to be made by truck, and all applicable Federal and State rules and regulations shall be followed. No pole shall be permitted to protrude above the top of the side stakes. Unloading of poles is the responsibility of the Contractor unless otherwise stated.
1. ACCEPTANCE: Final inspection and acceptance of each pole will be made by Western at the destination. In case such inspection shows that material does not meet the specifications or have been damaged in transit, then before accepting them from the transportation company and before unloading, Western will report to the Contractor by telephone or fax, who will provide instruction on how to proceed. The Contractor shall pay transportation costs both ways on all rejected poles.
Neither inspection, waiving of inspection, nor Western’s acceptance shall relieve the processor from obligations to furnish poles to meet the requirements of this specification.
1.10 INSTALLATION:
Install structures in accordance with manufacturer's instructions.
eray Rectangle
| 05. Specifications.pdf |
| TABLE OF CONTENTS |
| SECTION 1--GLUED LAMINATED STRUCTURES |
| 1.1 GENERAL: |
| 1. STRUCTURES: Designing, detailing, and furnishing glued laminated wood pole structures complete with foundation designs and embedment depths and the following: |
| 1.2 CONTRACTOR-FURNISHED DATA AND DRAWINGS: |
| 1. GENERAL: Use United States standard units of measurement and English words, signs, and symbols. Submit data and drawing of structures. Include design calculations for all structural components. Drawings shall be new originals. Reproducibles of s... |
| 2. DESIGN DATA SHALL INCLUDE: |
| 3. APPROVAL DRAWINGS: Prior to fabrication, submit for approval, the drawings for the structures. Note: design calculations/drawings should not be included as part of this package, they will be requested if needed. The submittal shall include: |
| 4. FINAL ORIGINAL DRAWINGS: Prior to pole shipment, furnish originals or positive reproducibles and electronic copies in AutoCAD version 2008. |
| 1.3 DESIGN REQUIREMENTS: |
| 1. GENERAL: Design using published theories accepted by the industry as good engineering practice. Construction shall be Grade B. Overload factors shall be in accordance with NESC C2-2012. Structure and attachments shall be designed for the simulta... |
| 2. SPECIFIC REQUIREMENTS: Design consistent with the following: |
| 3. EMBEDMENT DESIGN: |
| 1.4 MATERIAL: |
| 1. GENERAL: Furnish all material in accordance with the drawings and the requirements of this specification. In addition to the laminated poles and foundation reinforcement (if required), the pole supplier shall provide all hardware and fasteners ne... |
| 2. HARDWARE AND ASSOCIATED MATERIAL: |
| 3. WEST COAST REGION DOUGLAS FIR OR SOUTHERN PINE GLUED LAMINATED WOOD POLES: Conforming to the following: |
| a. Copper Naphthenate meeting the requirement of AWPA specification P8 (Section 2, Copper Naphthenate). The petroleum shall be hydrocarbon solvent, Type A only, meeting the requirements of AWPA specification P9. |
| b. Pentachlorophenol petroleum solution consisting of pentachlorophenol meeting the requirements of AWPA specifications P8 (Section 1, Pentachlorophenol) dissolved in suitable petroleum oil meeting the requirements for Type A solvent of AWPA specifica... |
| a. For the Copper Naphthenate treatments, the minimum retention of preservative shall be: |
| b. For pentachlorophenol solutions, the minimum retention of preservation shall be: |
| c. Color: Upon completion of the treating process, all poles shall be as light colored as reasonably possible to obtain a light to medium brown; color chart range three to seven poles darker than chart seven may be rejected. Poles shall be clean and... |
| 1.5 QUALITY CONTROL: |
| 1. GENERAL: The supplier shall have defined quality control methods and functions available for review and approval. Maintain permanent records on material specifications. The supplier shall eliminate all material that would be considered defective... |
| 2. FRAMING: Drilling, if any, shall be as specified according to the drawings included with the order. Drilling on specified poles and square cut roofing on all poles shall be completed BEFORE the treatment process. |
| 3. HUMIDITY: The relative humidity of the manufacturing area shall be maintained at such a level that the moisture content will not change substantially during the manufacturing process. All bonding shall be performed as soon as practical after chec... |
| 4. ADHESIVES: Adhesives for structural laminating shall conform to all applicable requirements of ANSI A190.1 to comply with wet conditions of use and be compatible with the selected preservative solution to be used. Adhesives containing urea shall ... |
| 1.6 MANUFACTURE: |
| 1. EDGE JOINTS: Unglued edge joints shall be permitted for multiple width lamination lay-up as permitted by ANSI A190.1. The non-cut edge joint gaps shall be limited to 1/4 inch and occasionally to a maximum of 3/8 inch. The cut edge joint gap shal... |
| 2. END JOINTS: End joints of laminations shall be pre-glued and cured before assembly of face joint into structural members. Spacing of the end joints shall be as specified in ANSI A190.1. |
| 3. REPAIRS: Structural repairs as defined in ANSI A190.1 are allowed. End blocks as defined in ANSI A190.1 are prohibited. |
| 4. SECOND STAGE GLUING: When two or more laminated members that are over 2 inches in net thickness are glued together, a gap-filling adhesive shall be used in accordance with ANSI A190.1. |
| 5. PROOF-LOADING: Proof loading shall be in accordance with ANSI A190.1. All laminated stock in high stress area shall be E-rated lumber. |
| 6. END JOINT SPACING: When proof loading is performed in accordance with ANSI A190.1, end joint spacing is not required. |
| 7. DIMENSIONS AND TOLERANCES: Allowable variations from specified dimensions are as follows: |
| 8. APPEARANCE: Glued laminated structural members shall be manufactured in accordance with the industrial appearance grade as defined in AITC 110 and as required in 1 through 6 as follows. |
| 1.7 POLE MARKING AND CODE LETTERS: |
| 1. The supplier's code or trademark. |
| 2. The plant location and the year of treatment. |
| 3. Code letters denoting the pole's species and preservative used. The size designation and/or equivalent class and the length of the pole. |
| 4. Poles shall be marked with two aluminum discs in accordance with ANSI 05.1. The discs shall be made of 24-gauge aluminum and approximately 2 inches in diameter. The discs shall be punched for nails, placed in the marking disc recesses, and attach... |
| 5. The approximate treated weight of the pole shall be marked at the balancepoint of the pole. |
| 1.8 TESTING AND INSPECTION: |
| 1. REQUIREMENTS: Testing and inspection shall be in accordance with ANSI A190.1 and AITC 200. |
| 2. MATERIAL: Testing and inspection shall be performed on the material and from the production that is supplied on the purchase order and produced in accordance with this standard. Samples for physical testing shall be taken at random. |
| 3. VOID-FILLING COMPOUNDS: Physical tests of void-filling compounds shall be made on samples of daily production in accordance with AITC test 110, as included in AITC 200 to establish compliance with 5.6.6.1 of AITC 200 standard. |
| 4. RECORDS: The results of all strength and wood failure tests of face, edge, and end joints and test of void-filling compounds conducted on material produced in accordance with AITC 200 shall be sent to the purchaser within 5 working days, if reques... |
| 5. QUALITY CONTROL SYSTEM: The quality control system shall be as specified in ANSI A190.1. Daily records of the material produced under this standard shall be submitted to the purchaser within 5 working days. Daily records shall include, at least,... |
| 1.9 STORAGE, HANDLING, AND TRANSPORTING: |
| 1. ACCEPTANCE: Final inspection and acceptance of each pole will be made by Western at the destination. In case such inspection shows that material does not meet the specifications or have been damaged in transit, then before accepting them from the... |
1.10 INSTALLATION: