This solicitation concerns repair and hydrostatic testing of underground storage tank systems at multiple facilities. Brockton facilities require repairs to one sump and spill bucket, with hydrotesting of eight sumps and seven spill buckets. Jamaica Plain facilities require repairs to one sump and associated components, with hydrotesting of two sumps and spill buckets. West Roxbury facilities require hydrotesting of four sumps and spill buckets, with one sump passing previously. The related federal contract opportunity is solicitation number 36C241-23-AP-2837 for underground storage tank sump hydrostatic repair and testing issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1. The document provides details on underground storage tank systems and components requiring repair or hydrostatic retesting at various facilities.

View the file

Other files for this federal contract opportunity

Other files attached to Underground Storage Tank (UST) Sump Hydro Repair & Testing, newest first.
File Type Posted
VA Brockton UST Sump 3 images.pdf PDF
Wage Determination 2015-4047 Rev 24 Dated 6.30.2023.pdf PDF
Past Performance Worksheet.xlsx XLSX spreadsheet
36C24123Q0903.pdf PDF
LOS Certification.pdf PDF
VA JP UST Sump 4 images.pdf PDF
VA W Roxbury UST Sump 7 images.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Brockton USTs Solicitation # 36C24123Q0628 - UST Sump Repair & Hydro Testing

Brockton USTsBldg. 40 #2 Fuel Oil 30,000 gal. Unit 1 TankBldg. 40 #2 Fuel Oil 30,000 gal. Unit 2 TankBldg. 51 4000 gal. Diesel TankBldg. 51 3000 gal. Gasoline TankBldg. 67 4000 gal. Ultra-Low Sulfur Diesel TankBldg. 68 2,500 gal. Ultra-Low Sulfur Diesel TankBldg. 69 2,500 gal. Ultra-Low Sulfur Diesel TankBldg. 70 2,500 gal. Ultra-Low Sulfur Diesel Tank
Sump11111111
Spill Bucket11111111

Pass

Fail; requires hydrostatic retest

Brockton - 8 sumps / 4 passed
8 spill buckets. 1 needs repaired and retested. 7 of the 8 spill buckets passed

Jamaica Plain USTs Solicitation # 36C24123Q0628 - UST Sump Repair & Hydro Testing

Jamaica Plain USTsBldg. 5 Boiler Plant Low Ultra-Low Sulfur Diesel Tank 10,000 gal. TankBldg. 1A Research Ultra-Low Sulfur Diesel 4,000 gal. Tank
Sump11
Spill Bucket11
Pass
Failed; required hydrostatic retest
Jamaica Plain - 2 sumps and 2 spill buckets. Bldg. 1A diesel sump by the parking garage is missing 3 clamps to secure test boots, junction box is corroded and needs repairs and retesting. Bldg. 5 Sump needs no repairs but needs testing.

West Roxbury USTs Solicitation # 36C24123Q0628 - UST Sump Repair & Hydro Testing

West Roxbury USTsBldg. 8 Boiler Plant #2 Fuel Oil 25,000 gal. Tank #1Bldg. 8 Boiler Plant #2 Fuel Oil 25,000 gal. Tank #2Bldg. 2 #2 Fuel Oil 4,000 gal. TankBldg. 1 #2 Fuel Oil 3,000 gal. Tank
Sump1111
Spill Bucket1111
Pass
Failed; required hydrostatic retest
W. Roxbury - 4 sumps / 1 passed
4 spill buckets/4 passed