SCALE OF MILES
20 0
PARK HEADQUARTERS
VISITOR CENTER
LEGEND
V.C.
STE. GENEVIEVE NATIONAL HISTORICAL PARK
STATE
NATIONAL PARK SERVICE
DENVER SERVICE CENTER REGION COUNTY
DEPARTMENT OF THE INTERIOR
UNITED STATES LOCATION WITHIN PARK
NAME OF PARK
TITLE OF DRAWING
DELASSUS-KERN HOUSE
STE. GENEVIEVE MISSOURI
QUALITY DESIGN CERTIFICATION
Prepared in Accordance with Design Development (Title I)
OR
Variance from Design Development (Title I) Approved by Superintendent on
OR
Construction Drawing Not Preceded by Design Development (Title I)
Project Manager Date
Mark Sheet REVISION Date Initial x x x xx.xx.xx XXX
A/E FIRM
RATHS, RATHS &
JOHNSON, INC.
500 Joliet Road, Suite 200
Willowbrook, Illinois 60527-5618
STABILIZATION AND SHORINGPRIME/ARCH:
STE. GENEVIEVE, MISSOURI
HQ.
HQ.
STE. GENEVIEVE, MO
5001000 0
010002000
SCALE OF METERS
SCALE OF FEET
PROJECT SITE
G0.0 COVER SHEET
G0.1 GENERAL NOTES
G0.2 SITE PLAN
G.03 REPRESENTATIVE PHOTOS
G.04 REPRESENTATIVE PHOTOS
S1.0 FOUNDATION SHORING PLAN
S1.1 BASEMENT SHORING PLAN
S1.2 FIRST FLOOR SHORING PLAN
S1.3 SECOND FLOOR SHORING PLAN
S2.0 EAST ELEVATION
S3.0 LONGITUDINAL SECTION
S3.1 LATERAL SECTION
S3.2 ENLARGED LATERAL SECTION
S5.0 DETAILS
La st
S av ed : L m bl an k
(M ay
, 2
3)
Au to C
AD
L
T
G :\1
.1 7\
D ra w in gs \S
TG
E\ pm is
9b
\c ad
V
D ra w in gs
\G en
\G
C O
VE
R
.d w g
CONSTRUCTION DRAWINGS
MIDWEST
STE. GENEVIEVE NHP
OF
PMIS/PKG NO.
SHEET
DRAWING NO.
331639B
19071 US-61, STE. GENEVIEVE, MISSOURI 63670
DELASSUS-KERN HOUSE
STABILIZATION AND SHORING
PMIS 331639B
V.C.
PARK BOUNDARIES
PARK BOUNDARIES
HW
Y U.S. 61
500 1000 2000
500 1000
LIST OF DRAWINGS
DELASSUS-KERN HOUSE PROJECT SITE
10 0
SCALE OF METERS
SCALE OF FEET
100 10050 50
2030 10 20 30
APPROXIMATE PROPERTY LINE
NO CONTRACTOR USE OR
ACCESS OF EAST PARCEL
NO CONTRACTOR
USE OR ACCESS
VIA ROADS
PRIVATELY HELD
BY OTHERS
US-61
May 10, 2023
53'-4"
'-6
U P
CRAWLSPACE
(FLOOR FRAMING
NOT SHOWN)
S2.0
CONCRETE
PORCH
1' -6
S3.1
S3.0
EXISTING CONCRETE
BLOCKS 2'-6 x 2'-6"x5'-0"
CONTINUOUS FOOTING
AND WOOD SILL
MEMBERS, MAY NEED
TO BE BROKEN UP DUE
TO TERRAIN.
CONTINUOUS FOOTING
AND WOOD SILL
MEMBERS, MAY NEED
TO BE BROKEN UP DUE
TO TERRAIN.
2' -0
" 1' -6
2'-0"3'-0"4'-0"2'-0"4'-0"4'-0"4'-0"3'-0"3'-0"4'-0"
7' -6
'-0
NEW CONCRETE
BLOCKS 2'-6 x 2'-6"x5'-0"
EXISTING CONCRETE
BLOCKS 2'-6 x 2'-6"x5'-0"
2'-10"3'-3"2'-11"2'-11"2'-5"2'-6"3'-4"
3'-11" ±
NEW CONCRETE
BLOCKS 2'-6 x 2'-6"x5'-0"
NEW DAYTON
SUPERIOR T14 HEAVY
LOAD BRACE (APP 3
FEET ON CENTER), TYP.
10"
HISTORIC WOOD WINE
PRESS STORED ON WOOD
PALLETS, RELOCATE PER
COR DIRECTION SPACING OF SHORING
IS PRELIMINARY AND
MAY BE ADJUSTED TO
ACCOMMODATE
EXISTING CONDITIONS
AND AVOID CONFLICTS
WITH EXISTING WOOD
BRACING IN BASEMENT.
CONSULT WITH
ENGINEER-OF-RECORD
PRIOR TO MODIFYING
SPACING.
EXISTING 2x6 BRACE AND
LEDGER BOARD INSIDE
BASEMENT, TYP.
FOUNDATION
SHORING PLANS1.0
TITLE OF SHEET
OF
PMIS/PKG NO.
SHEET
DRAWING NO.A/E FIRM
RATHS, RATHS &
JOHNSON, INC.
500 Joliet Road, Suite 200
Willowbrook, Illinois 60527-5618
STE. GENEVIEVE NATIONAL HISTORICAL PARK
80001
SUB SHEET NO.DESIGNED:
GRM
CADD:
AM/WPB
TECH. REVIEW:
LMB/GRM
DATE:
05-10-2023
PRIME/ENG:
La st
S av ed : L m bl an k
(M ay
0, 3)
Au to
C
AD
L T
G
:\1
.1
7\ D ra w in gs
\S
TG
E\ pm is
9b \c ad V
D ra w in gs \S tru ct
\S
F O
U N
D
AT
IO
N
P
LA
N .d w g
331639B
#STABILIZATION AND SHORING DELASSUS-KERN HOUSE
SCALE: 1
4" = 1'-0"
FOUNDATION SHORING PLAN1
S1.0
SHORING GENERAL NOTES
1. Design Loads:
a. Dead Loads
i. Exterior East Wall Load 200 lb/ft
ii. Second Floor 10 psf
iii. First Floor 16 psf
b. Live Loads
i. Construction Live Loads 20 psf
ii. Minimum Roof Loads 20 psf
iii. Existing Wall Load due to Snow 150 lb/ft.
iv. Allowable Soil Bearing Pressure 1,500psf
2. Submittals
a. Delegated Design
i. Contractor shall submit the shoring delegated design package sealed by a Professional Engineer licensed in the State of Missouri for review prior to the commencement of the shoring installation.
1.) Calculations 2.) Drawings including connection and assembly details.
3.) Shoring Scope
b. Design, install and maintain shoring and temporary structural supports as required to preserve stability and prevent unexpected or uncontrolled movement, settlement, or collapse of existing construction and finishes to remain.
4. Miscellaneous
a. These general notes supplement the project specifications. Refer to project specifications for additional requirements.
b. The contractor is responsible for coordinating requirements from other documents into their shop drawings and calculations.
c. The contractor shall follow all applicable standards including Occupational Safety and Health (OSHA) and American National Standards Institute (ANSI) standards and be familiar with and follow the safety guidelines recommended by the Scaffolding, Shoring and Forming Institute.
Local, state and federal statutes or regulations shall supersede the above-mentioned guidelines if there is a conflict and it is the responsibility of the contractor to comply with these statutes and regulations.
d. The stabilization and protection of all in-place surfaces and materials in this building structure is paramount. The contractor must take all measures of care possible to protect the in-place building surfaces and materials from damage during shoring installation and construction. Do not mechanically fasten to in-place building materials without prior written approval from the project architect-of-record.
e. Any detail titled as a typical detail is applicable throughout the drawings. These details are defined as general standards that are usually not identified by specific reference within the drawings. These details may be modified or superseded by specific details that are referenced within the drawings.
f. Do not scale the drawings. Use specified dimensions.
g. Contractor to verify all dimensions in the field prior to performing the calculations and submitting the shop drawings and calculations.
h. No cutting, notching or openings shall be made in any shoring member without the prior written approval of the delegated shoring engineer-of-record.
i. Provide temporary bracing as required to maintain the alignment and security of all shoring during installation and construction.
j. The contractor is responsible for limiting the amount of construction load imposed upon the shoring framing. Construction loads shall not exceed the design capacity of the framing at the time the loads are imposed.
k. The shoring is to be designed to function as a unit upon completion. The contractor is responsible for furnishing all temporary bracing and/or support that may be required as the result of the contractor's construction methods and/or sequences.
l. It is the contractor's sole responsibility to determine erection procedures and sequences and to ensure the safety of the shoring and its component parts during its use. This includes the addition of any shoring, sheeting, temporary bracing, guys, or tie downs that may be necessary.
Review of the shoring construction by any design professional is for conformance with the design only, not to review the contractor's construction procedures. Lack of comments by the design professional regarding construction means and methods shall not be interpreted as approval of any construction procedures.
m. Job safety shall be the sole responsibility of the contractor.
n. In cases where material or members specified is not readily available, the contractor may submit the use of alternate material or members for review by the shoring engineer-of-record. The alternate material or members proposed must minimally provide the same strength and stiffness as the original design. The contractor shall be responsible for verifying that any substitutions do not conflict with the project specifications. Any additional costs associated with any proposed substitutions shall be borne by the contractor.
o. The contractor shall inform the shoring engineer-of-record in writing of any deviations from the contract documents. The contractor shall not be relieved of the responsibility of such deviations by the shoring engineer-of-record's review of shop drawings, product data, etc., unless the contractor has specifically informed the shoring engineer-of-record of such deviation at the time of submission, and the shoring engineer-of-record has given written approval for the specific deviation.
2'-1" 2'-4" 2'-5" 2'-6" 2'-5" 2'-8" 2'-4" 2'-8" 2'-6" 2'-7" 2'-4" 2'-3" 2'-5" 2'-5" 2'-2" 1'-10"1'-9" 2'-4" 2'-4" 2'-8" 1'-10" J1
J2 J3 J4 J5 J6 J7 J8 J9 J1
J1
J1
J1
J1
J1
J1
J1
J1
J1
J2
J2
53'-4"
'-6
U P
CRAWLSPACE
(FLOOR FRAMING
NOT SHOWN)
B1
S2.0
CONCRETE
PORCH
1' -6
1'
-6
2'-8"
NEW DAYTON
SUPERIOR T14 HEAVY
LOAD BRACE (APP 3
FEET ON CENTER), TYP.
EXISTING CONCRETE
BLOCKS 2'-6 x 2'-6"x5'-0"
EXISTING 2x6 BRACE, TYP.
7' -6
'-0
NEW CONCRETE
BLOCKS 2'-6 x 2'-6"x5'-0"
EXISTING CONCRETE
BLOCKS 2'-6 x 2'-6"x5'-0"
NEW CONCRETE
BLOCKS 2'-6 x 2'-6"x5'-0"
EXISTING ROCK WALL
S3.1
2'-0"3'-0"4'-0"2'-0"4'-0"4'-0"3'-0"3'-0"4'-0"
S3.0
EXISTING 2x6 BRACE
INSIDE BASEMENT, TYP.
BASEMENT
SHORING PLANS1.1
TITLE OF SHEET
OF
PMIS/PKG NO.
SHEET
DRAWING NO.A/E FIRM
RATHS, RATHS &
JOHNSON, INC.
500 Joliet Road, Suite 200
Willowbrook, Illinois 60527-5618
STE. GENEVIEVE NATIONAL HISTORICAL PARK
80001
SUB SHEET NO.DESIGNED:
GRM
CADD:
AM/WPB
TECH. REVIEW:
LMB/GRM
DATE:
05-10-2023
PRIME/ENG:
La st
S av ed : L m bl an k
(M ay
0, 3)
Au to
C
AD
L T
G
:\1
.1
7\ D ra w in gs
\S
TG
E\ pm is
9b \c ad V
D ra w in gs \S tru ct
\S
B
SM
T
PL
AN
.d w g
331639B
#STABILIZATION AND SHORING DELASSUS-KERN HOUSE
SCALE: 1
4" = 1'-0"
BASEMENT SHORING PLAN1
S1.1
SHEET NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND
DIMENSIONS. DO NOT SCALE FROM DRAWINGS.
2. GRAPHICAL AND NARRATIVE DESCRIPTIONS OF WORK CONTAINED
WITHIN THESE DRAWINGS ARE INTENDED TO CONVEY THE
GENERAL EXTENTS OF THE WORK AND ESTIMATED QUANTITIES
FOR THE CONTRACTOR'S CONVENIENCE FOR PREPARATION OF A
PROPOSAL. ADDITIONAL COMPONENTS OR ACCESSORIES
BEYOND THOSE SHOWN AND NECESSARY FOR A COMPLETE
INSTALLATION OF WORK (E.G.: FASTENERS, SHIMS, ETC) ARE THE
RESPONSIBILITY OF THE CONTRACTOR.
BASEMENT FF
- 6'-0" ±
(VARIES AT INTERIOR)
FIRST FLOOR FF
0'-0"
SECOND FLOOR FF
+9'-8" ±
ATTIC
+20'-8 1/2" ±
ROOF
+26'-10 1/2" ±
APPROX AVG GRADE
- 4'-0" ±
105 106
201 203 204202
4'-0" 3'-0" 4'-0" 4'-0" 2'-0" 4'-0" 3'-0" 2'-0"
SPLICES SHOWN OVER
SHORING SUPPORTS
ONLY
LONGITUDINAL SECTIONS3.0
TITLE OF SHEET
OF
PMIS/PKG NO.
SHEET
DRAWING NO.A/E FIRM
RATHS, RATHS &
JOHNSON, INC.
500 Joliet Road, Suite 200
Willowbrook, Illinois 60527-5618
STE. GENEVIEVE NATIONAL HISTORICAL PARK
80001
SUB SHEET NO.DESIGNED:
GRM
CADD:
AM/WPB
TECH. REVIEW:
LMB/GRM
DATE:
05-10-2023
PRIME/ENG:
La st
S av ed : L m bl an k
(M ay
0, 3)
Au to
C
AD
L T
C
:\U se rs \lm bl an k\ on ed riv e
- R at hs
, R at hs
J oh ns on
, I nc
\D es kt op
\k er n Fi na l D oc um en ts
\S
TG
E\ pm is
9b \c ad V
D ra w in gs \S tru ct
\S
L O
N G
S
EC
T.
dw g
331639B
#STABILIZATION AND SHORING DELASSUS-KERN HOUSE
SCALE: 1
4" = 1'-0"
LONGITUDINAL SECTION1
S3.0 0 2' 4' 8'