Statement of Work: HVAC Service S.O. Conte Anadromous Fish Research Laboratory, Turners Falls, MA
1. Introduction: The Conte Anadromous Fish Research Laboratory (CAFRC) has a requirement to establish an HVAC service contract. The contract will include four main parts:
A.) Performance of annual periodic maintenance (PM) tasks on various HVAC systems at the facility. Regular preventative and predicative maintenance will also be covered in this part of the contract. (HVAC systems include but may not be limited to Hot Water boiler and accessories, forced hot air systems, air handling systems, direct expansion Air Conditioning units, walk in cooler and freezer, propane and electric unit heaters, VAV systems and Automated Logic Building Automation System (ALC BAS).)
B.) An agreement to respond to service and repair calls throughout the year at a fixed hourly rate for labor plus the cost of parts or materials. A fixed hourly rate will be provided for emergency response and afterhours/weekend work.
C.) An agreement to monitor and perform simple programming in Automated Logic Controls (ALC) building automation system (BAS) when such requests are made from the Facility Manager (FM) to ensure proper operation and to make modifications in the system to accommodate changing environmental conditions. A fixed hourly rate will be determined for controls work.
D.) An agreement to use authorized ALC contractors to replace proprietary equipment, add new equipment and perform complex programming and maintenance to BAS.
ALC will bill the client for these services.
A site visit will be scheduled for interested parties. Attendance is not mandatory but is highly recommended. Some equipment is in remote spaces, and some have special access requirements.
2. Background: CAFRC has numerous HVAC systems which differ greatly in age, some being recent upgrades and some original to the facility’s construction in 1990. It is essential to the mission of the facility to have these systems working properly to ensure the success of their vital work. The facility consists of four main buildings and one outbuilding, wherein all HVAC systems are to be included in this bid. All systems must be regularly inspected, serviced and monitored and any downtime must be as minimal as possible. The contractor must be experienced in the ALC BAS system and be able to troubleshoot and make adjustments to schedules, setpoints and other minor changes in programming. Service calls to complete repairs may occur outside of normal business hours. The contractor must be committed to making the facility’s proper operation a high priority and have the necessary resources to fulfill this requirement.
3. Scope of Work: The following is a list of all the buildings and the equipment which are to be included in this bid and the required periodic maintenance where noted. All regular maintenance will be performed during quarterly visits.
The periodic maintenance (PM) visits will be scheduled for September, December, March and June. The equipment list is marked with the initial of the month in which the PM is to be performed (S, D, M, J).The contractor will be responsible for adhering to this schedule, and contact the COR via email to determine dates for service.
A.) Research Lab Building (RLB) or Building 1
1. (S) PK Mach condensing hot water boiler, propane fired.
1. Clean and inspect flue passages and piping. Reseal when completed.
2. Clean and Inspect burner assembly and all associated parts.
3. Lubricate all moving damper linkages.
4. Clean and inspect low water safety cut off device.
5. Flush and clean with approved solvent to remove scale
6. Verify proper operation of all operating and safety devices.
7. Perform combustion analysis and adjust burner to proper fuel air ratio minimizing CO output. Results to be included in report.
8. Clean, inspect and verify operation of all boiler system components and accessories
2. (S) Hot Water heating system pumps and accessories.
1. Grease motor and pump bearings yearly prior to heating season.
2. Inspect pump seals and couplings.
3. Inspect, and tighten connections in pump motor starters.
4. Verify proper operation.
3. (M) Walk in Freezer.
1. Clean and inspect condenser and evaporator coils.
2. Check refrigerant charge and check for refrigerant leaks.
3. Inspect and clean evaporator drains.
4. Check all electrical connections.
5. Verify proper operation.
4. (M) Walk in cooler.
1. Clean and inspect condenser and evaporator coils.
2. Check refrigerant charge and check for refrigerant leaks.
3. Inspect and clean evaporator drains.
4. Check all electrical connections.
5. (J) (2) McQuay air handlers Heating and Cooling (AHU-1) with VSD and Heating (HV-1) with VSD.
1. Inspect and grease motor and blower bearings.
2. Clean evaporator and heating coils.
3. Inspect coils and piping for refrigerant and hot water leaks.
4. Clean and lubricate all dampers and damper actuator linkages.
5. Clean and inspect drain pans and drain lines.
6. (J, D) Change V belts twice a year (belts provided by government).
7. Verify proper operation of VSD, all operating and safety devices.
8. Filters will be provided by government and changed by contractor.
6. (M) Trane 10-ton packaged air conditioning unit with humidity controls
(mounted on ground)
1. Clean condenser coils prior to Spring start up.
2. Inspect refrigeration circuits for leaks.
3. Inspect and tighten all electrical connections.
4. Inspect fan motors and blades.
5. Clean condensate pan and drain, inspect for clogs or leaks.
6. Verify proper operation.
7. (M, S) Change V-belts twice yearly (belts provided by government.)
8. Air filters will be provided by government and installed by contractor.
7. (M) McQuay 30-ton Air conditioning condensing unit.
1. Clean condenser coils.
2. Inspect refrigeration circuits for leaks.
3. Inspect and tighten all electrical connections.
4. Inspect fan motors and blades.
8. (S) (10) Enviro Tec VAV boxes w/ reheat.
1. Verify proper operation of VAV system.
2. Clean heating coils as needed.
3. Clean or replace air filters (filters provided by government).
4. Inspect heating valves and piping for leaks.
9. (D) (2) Rinnai tankless hot water heaters.
1. Flush with approved solvent to remove scale.
2. Check propane connections for leaks.
3. Check supply and control wiring.
10. (M) Hitachi Mini-split AC system (phone room).
1. Clean or replace filters.
2. Remove and clean indoor air quality (IAQ) components
3. Clean evaporator coils.
4. Inspect and clean condensing unit.
5. Inspect refrigeration and insulation wraps.
11. (D) Champion air compressor with air dryer.
1. Change oil and filters.
2. Check for air leaks.
3. Check for integrity of wiring.
12. (D) Champion vacuum pump.
(Same as A.10)
13. Automated Logic Controls BAS.
1. Verify proper function of system
B.) Fish Passage Complex (FPC) or Building 2
1. (J) McQuay roof top heating and air conditioning unit.
1. Inspect and grease motor and blower bearings.
2. Clean evaporator and condenser coils prior to spring start up.
3. Inspect refrigeration circuits for refrigerant leaks.
4. Clean and lubricate all dampers and damper actuator linkages.
5. Clean and inspect drain pans and drain lines.
6. (J, D) Change V belts twice a year (belts provided by government).
7. Verify proper operation of all operating and safety devices.
8. Perform combustion analysis and adjust burner to proper fuel air ratio minimizing CO output. Results to be included in report.
9. Clean and inspect heat exchanger for leakage and corrosion.
10. Verify proper operation of all operating and safety devices.
11. Air filters will be provided by the government and changed by contractor.
2. (S) (7) Enviro Tec VAV boxes.
1. Verify proper operation of VAV system.
2. Verify operation of dampers, tighten, adjust and repair linkage.
3. Check for leaks or damage in duct.
3.(D) GE hybrid electric hot water heater.
1. Clean or replace air filter.
2. Clean evaporator.
3. Check condensate drain pans and lines for leaks or clogs.
4. Check water and gas piping for leaks.
5. Check for integrity of wiring.
6. Ensure proper operation of all components.
4. (D) Champion air compressor.
1. Change oil and filters.
2. Check for air leaks.
3. Check for integrity of wiring.
5. Automated Logic BAS
C.) Vehicle Storage Building (VSB) or Building 3
1. (S) (3) Reznor propane fired unit heaters
1. Clean and inspect ignition system
2. Clean and inspect fan and heat exchanger
3. Check gas piping and wiring for integrity
D.) Solar Roof Building (SRB) or building 4
1. (M) York packaged AC unit with humidity controls (mounted on ground)
9. Clean condenser coils prior to Spring start up.
10. Inspect refrigeration circuits for leaks.
11. Inspect and tighten all electrical connections.
12. Inspect fan motors and blades.
13. Clean condensate pan and drain, inspect for clogs or leaks.
14. Verify proper operation.
15. (M, S) Change V-belts twice yearly (belts provided by government.)
16. Air filters will be provided by government and installed by contractor.
2. (S) (2) Modine propane fired unit heaters
1. Clean and inspect ignition system.
2. Clean and inspect fan and heat exchanger.
3. Check gas piping and wiring for integrity.
4. Clean or replace air filters.
3. (M) (7) Trane 5hp heat pumps used as water chillers.
1. Clean condenser coils.
2. Check for coolant leaks.
3. Verify proper operation.
4. Automated Logic Controls BAS
E.) Antenna Research Building or Building 5
1. (M) (2) Amana hotel HVAC units
1. Clean condenser coils.
2. Clean heat exchanger coils.
3. Clean or replace air filter.
4. Check fan for proper operation.
5. Inspect wiring and control board for integrity and proper operation.
2. (S) Modine propane fired unit heater
1. Check and clean ignition system.
2. Inspect gas piping for leaks.
Equipment may be added or removed from this list during construction and remodeling projects.
4. Applicable Documents: Any contractor must be licensed in the state of Massachusetts to perform HVAC work and be fully insured to be considered for this bid. Contractor must provide license information for any technician performing work at facility where such a requirement exists. Any technician working on the automation system must be certified and authorized by Automated Logic Controls. All work must be performed in accordance with Federal, state and local regulations. All chemicals used in cleaning, lubricating or other routine tasks must be clearly labeled and MSDS provided, all spills of these chemicals must be contained and cleaned properly, and all excess removed or disposed of properly. Any refrigerant which is added or removed from equipment must be accompanied with a report detailing type and amount of material used.
5. Deliverables: Contractor must provide documentation of all work performed at the facility. Any visits to the facility must be scheduled in advance and approved by the FM or designated representative and must not disrupt normal operations. After Spring and Winter start-up visits the contractor will provide a full report on the status of the mechanical equipment that is in their scope of work. All routine periodic maintenance will be performed during the visits and any additional work must be detailed in a proposal including estimated cost of parts and labor and must be approved by the FM.
Contractor will complete service report forms supplied by the facility manager. Contractor will primarily coordinate service with FM but may also work with other staff members as becomes necessary.
All routine work is to be performed during regular business hours (7:30am-4:00pm) unless other arrangements are made. All service calls require prior notification and confirmation from FM or other staff member. Tools and materials may be stored during service visits in designated areas, but the center assumes no liability for stolen or damaged items.