Attch 4 - South Wing Cassion Reports.pdf
PDF 6 MB Posted
- Attached to
- Project # 667-086 - A/E DESIGN Expand Radiology & SPS Federal contract opportunity
- Solicitation number
- 36C25620R0142
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attch 2 - Asbuilts for Basement and 1-South.pdf | ||
| Attch 3 - As-Builts for 2-South.pdf | ||
| Attch 7 - South Wing Soils Report - Feb 6 2009.pdf | ||
| 36C25620R0142.docx | DOCX document | |
| Attch 5 - South Wing Soils Report - Dec 16 2008.pdf | ||
| Attch 8 - PSDM Mission Critical Waiver Response - Draft Final.pdf | ||
| Attch 1 - SPS and Radiology Expansion - Final SOW.docx | DOCX document | |
| Attch 6 - AE Submission Requirements.doc | DOC document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Build.On n#rc*ryrGcmulffilErlbdlg
Professional Service Industries, lnc.
4123 Curtis Lane Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Goncrete Field RePort Report No: FC:0275169-8
Thsse test results apply only to the specific lo€tions andfiaterialsnoted and may not represini'any other locations or elevations This rePorl may not be r6produi€d, except in full, without written Permission by Professional Servie Industties, Inc.
lfrr"-+-/c*- Approved Signatory: Michael Car (Department Manager)
Date of lssue: 412612010 rrrnet-nruO-pnVCO CORPORATION CC: ARCHIE LANHAM
+TOZ CNOUSH OAK DR DONNIE JONES
LANSING, MI 48911 JUSTIN PARK
RANDY FRITZ
VA OVERTON BROOKS MENTAL HLTH
SHREVEPORT, LA
General Field Data Technician: Jesi Hoover Test Date: 412212010
Informotinn bBuild,On
E rgrrcertng r GoruulUqg r lbcdng
Mix Data Mix Data Submifted BY Supplier Mix ldentification Specified Design Strength (Psi)
Design Unit Weight (Pcf) Gement Factor (Sackst!d3) Water-Gement Ratio (lb/lb)
Professional Service Industries, lnc.
4123 Curtis Lane Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Buildeis SupplY Buildefs SuPPIY 733570 3800 at age 28 daYs
DateReceived 412312010
Material Cement 1 (lb) Cement 2 (lb) Fly Ash (lb)
Coarse Agg 1 (lb) Coarse Agg 2 (lb)
Fine Agg (lb) Admix 1 (oz) Admix 2 (oz) Admix 3 (oz) Water (gal)
SlumP (in) Slump w/ Plasticizer (in)
AirTemP ('F) Concrete TemP ('F)
Air Content (%) Unit Weight (PcO Batch Size (Yd3)
Water Added (gal)
Time Batched Time SamPled
Time Placed Time In Truck (mins)
Amount Moisture N/A N/A N/A
Measured Specified 8.50 N/A
10:45 1' l :30 11'.40 6E
ASTM G 39
Compressive Required Strength (Psi) Strength (Psi)
Details of SamPle Date Sampled 412212010
Specimen lD Date Tested
General Location Drilled Piers
SamPle Location Pier El3 &Dl2
Curing Method One day Field/Laboratory Cure
Field Sample No Field cure Temp ('F) High Low
Contractor Case Atlantic Truck No. 444 Ticket No.
Sampled By Jesi Hoover Submitted BY Jesi Hoover Weather PartlY CloudY Est. Wnd (mph) 10 Est. Rh (%) 78
Yd3 Placed 8.0
Oornpressive Strength of Goncrete Cylinders
ASTM C 1064
ASTM C 231
ASTM C 138
Age (days)
Dimensions (in) Area (in'z) Diameter Height
Type of cap
Ultimate Load (lbO
Before After
Type of Fracture
Concrete Test RePort Report No: GON:0275{'69'8'C1
These test results apply only to the sp&ific localions and materials noted and mav not represent any other locations or elevations. This rePort may not be ;produced, except in full, without written permission by Professional Seryice Industries, Inc.
Approved Signatory: Michael Car (Department Manags)
Date of lssue: 512012010
WIELAND-DAVCOCORPORATION CC:
4162 ENGLISH OAK DR
LANSING, MI 48911
VA OVERTON BROOKS MENTAL HLTH
SHREVEPORT, LA
0275169-8-C1\'t 04129110 0275169-8-Clu 05120t10 0275169-8-C1\3 05t20t10
0275169-8-C1\4 05t20t10
U u U U
4.01 4.01 4.00 4.00
8.01 8.01 8.00 8.00
12.63 12.63 12.57 12.57
53990 61760 68350 66570
I
Remarks Fai luroMode:3=C39:Vertcrackingy'nocones;C1314:Cone&Spl i t '5=C39:Side iraaure-opposite ends; C1314: Semi4onical Break
Notes l.SamDlino toASTM C 172 z.soecimen(s) Prepared to ASTM C 31 ;.;fi;;';f=ffi;; n-snt,t c otz, u=unbonded ASrM c 1231, c = combined
Build.On Eiryfrrglrfirg r Gomuffilg r lbd€l
Professional Service Industries, Inc.
4123 Curtis Lane Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Goncrete Field RePort Report No: FG:0275169-10
These tesl results apply only to the specific locations and matorialsnoled and may not represent any other loetions or elevations. This reporl may not be rbproduced, except in tull, without writlen petmission by
Professional Service Industries, Inc.
IN+*f c*- Approved Signatory: Michael Car (Department Managil)
Date of fssue: 4127l2o1o
WIELAND.DAVCO CORPORATION GG:
4162 ENGLISH OAK DR
LANSING, MI 48911
VA OVERTON BROOKS MENTAL HLTH
SHREVEPORT, LA
General Field,Data Technician: Jesi Hoover
Test Date: 412612010
T+st Result$ Set No. SPecimens
Made
0275169-10-C1 "
0275169-10-C2 4 l 0275169-10-C3 0
0275169-10-C4 0
0275169-10-c5 4
Ticket ir oir sa 2102160 dionii,g iio3g3i i 17938112 1 703831 3
Time Batched
1O.'24- -f O:Zg
". io.loo 14:15 14:25 il,so
Time Unloaded
11"20 i r'r,ds , 1 t ; ! 0 .
i 15 :15
' f S:+O ; 15:35
Cubic Yards Placed
8.0 ro.o-zi,.p -
3r.o 40.0^ ;8.0
Slump (in)
8.50 e.oo a.oo s.oo 8.50
LOO
Air Temp. (oF) Concrete fF)
7 9 i . ' l
8 2 ; 7 7 8 3 i 8 4 i g 4 : z e
Lodion & Remarks Set No. Location......,,'.. -,;:,, General Location: Drilled Piers
0275169-1O-Cl Pier C/5
0275169-10-C2 Pier C/5 & Bottom of E/4
0275169-10-C4 Pier ClZ
0275169-10-C5 Pier C/2 & Bottom of D/4
0275169-1 Dt4
02751 69-1 0-C3\Pier E/4
Phone: (31 8) 631-5547 Fax: (318) 631-1546
Goncrete Test RePort Report No.. GON:02751 69-1 0-C5
These test results apPly only to the specific locations andfiaterialsnoted and may not represent any other locations or elevations This reporl may not be rboroduied, except in full, without written permission by
Professional Service Industries, Inc.
id+*#U- Approved Signatory: Michael Can (Department Manager)
Date of lssue: 5l24l2o1o
Wrn-qNOOnVCO CORPORATION GC: ARCHIE LANHAM
+TOZ ENCIISH OAK DR DONNIE JONES
LANSING, MI 48911 JUSTIN PARK
RANDY FRITZ
VA OVERTON BROOKS MENTAL HLTH
SHREVEPORT, LA
5g'ry&HFJfirrg r Goneirlfiqglr lbcfin$
Professional Service lndustries, Inc.
4123 Curtis Lane Shreveport, LA 71109
MiN Data Mix Data Submitted BY Supplier
Buildeis SuPPIY Builde/s SuPPIY
Material Cement 1 (lb) Cement 2 (lb) Fly Ash (lb)
Coarse Agg 1 (lb) Coarse Agg 2 (lb)
Fine Agg (lb) Admix 1 (oz) Admix 2 (oz) Admix 3 (oz) Water (gal)
SlumP (in) Slump w/ Plasticizer (in)
Air TemP ('F) Concrete TemP ('F)
Air Content (%) Unit Weight (Pcfl Batch Size (Yd")
Water Added (gal)
Time Batched Time SamPled
Time Placed Time In Truck (mins)
Amount Moisture N/A N/A N/A
Measured SPecified 8.50 N/A
I
14:25 15:00 15:40
ASTM C 39
Compressive Required Strength (Psi) Strength (PSi)
Mix ldentification 733570 Specified Design Strength (psi) 3800 at age 28 days
Design Unit Weight (Pcfl
Cement Factor (Sacks/Yd3) Water-Cement Ratio (lb/lb)
Details of SamPle Date Sampled 4l26t2O1O Date Received 412712010
General Location Drilled Piers
Sampfe Location Pier Cl2 & Bottom of D/4
Guring Method One day Field/Laboratory Cure
Field Sample No Field Cure Temp ('F) High Low
Contractor Case Atlantic Truck No. 417 Ticket No. 17038312
Sampled BY Jesi Hoover Submitted BY Jesi Hoover Weather SunnY Est. Wnd (mPh) 10 Yd'Placed 40'0
Est. Rh (%) 68
Gornpressive Strength of Colcrete Cylinders
ASTM C 1064
ASTM C 231
ASTM C138
Before After
Specimen lD Date Tested Dimensions (in) Area (in') Diameter Height
Age (days)
Type of cap
Ultimate Load (lbO
Type of Fracture
0275169-10-C5\1 05/03/10 0275169-10-c512 05124110
0275169-10-C5\3 05t24110
0275169-10-C5\4 05124110
4.00 4.00 4.01 4.00
8.00 8.00 8.01 8.00
12.57 12.57 12.63 12.57
55060 59040 63870 66470
U u U U c
Remarks Fai lureMode:1=c39:Conesonbothends;c1314:ConicatBreak4=c39:Diagonal f raclure;
biiiii?l,i-.iJ. ai;, s , bsg, sia" f,"aure-opposite endsi c1314: semi-conical Break
Notes ' l.sampling to ASTM C 172 z.Soeiimen(s) Prepared to ASTM c 31 i.6!ppi"g ilb"ndA ASTM c 617, u=unbonded ASTM c 1231' c = combined bBuildOn F*ngfltrlertng r Goneirlffnglr lbsffqg
Professional Service Industries' |nc.
4123 Curtis Lane Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Goncrete Field RePort Report No: FC:0275169-14
Thess test results apply only to the specific locations and materials noted and mav not represent any other lo€lions or elevations This report may not be r;produied, excepi in full, without written permission by
Professional Service Industries, Inc.
$i-j"J Approved Signatory: Michael Car (Department Manager)
Dateoflssue: 4l3ol2o1o
WIELAND-DAVCO CORPORATION GC: ARCHIE LANHAM
+ioz rNcusH oAK DR DoNNIE JoNES
LANSING, MI 4891T JUSTIN PARK
RANDY FRITZ
Proiect: VA OVERTON BROOKS MENTAL HLTH-
SHREVEPORT, LA
Technician: Jesi Hoover Test Date: 412912010
Test Results Set No. SPecimens
Made
027516g-14-c1 4
0275169-14-C2 0
0275199]14-c3 0
0275169-14-c4 4 ozts1.6s4q-cs 0
Ticket zsozspi +osisoi )iozqao itoiiiz 2102435
Time Batched
. tO:ZO 11 :08 litt't) 13 :18 15:35
Time Unloaded
'11:25
11 :55
1J,45
Cubic Yards Placed
8 o 1 6 0 24.0 33.0 42.0
Slump (in)
8 5 0 8.00 e.5o e.5o 8.s0
Air Temp. ("F) Concrete T fF) es ti 8 3 i 8 5 ' 8 2
Uocition & Remarks --- pe!.No, Location
General Location: Drilled Piers
0275169-14-C1 Pier C.7 13
0275169-'14-C2 Pier C.713 & D'3/3
0275169-14-C3
0275169-14-C4 Pier Cl4
0275169-14-CS Pier Cl4 &8,12.1
Mix Data
- SetNo.
0275169-14-C1 oitsta's4a-C2 oz?tr6sii+-cs 0275169-14-C4 oizsiog-ra-cs
Supplier Builde/s SupPlY Build-e.r:s Sllpp-ly Builder's SuPPIY Bu!lde|s SuPPIY Builde/s SuPPIY
Mix
733570 3800 PSI
733570 3800 Psl
733570 3800 PSI
zgisio ssoo Pst zgCs?o 3aoo PSt
Design Strength (Psi)
.390.0 .
B4gllncafing r Gorcrrffng t l€rfftng
Professional Service Industries, Inc.
4123 Cudis Lane Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Mix Data Mix Data Submitted BY Supplier Mix ldentification Specified Design Strength (Psi)
Design Unit Weight (PcD Cement Factor (Sacks/Yd3) Water-Cement Ratio (lb/lb)
Details of SamPle Date Sampled 412912010 contractor Case Atlantic Truck No. 416 Sampled BY Jesi Hoover Submitted By Jesi Hoover Weather PartlY CloudY Est. Wind (mPh) 25 Est. Rh (%) 70
Builde/s SupplY Buildefs Supply 733570 3800 at age 28 daYs
DateReceived 413012010
TicketNo. 2102432
Yd'Placed 33.0
Material Cement 1 (lb) Cement 2 (lb) Fly Ash (lb)
Coarse Agg I (lb) Coarse Agg 2 (lb)
Fine Agg (lb) Admix 1 (oz) Admix 2 (oz) Admix 3 (oz) Water (gal)
SlumP (in) Slump w/ Plasticizer (in)
Air TemP ('F) Concrete TemP ('F)
Air Content (%) Unit Weight (PcO Batch Size (Yd3)
Water Added (gal)
Time Batched Time Sampled
Time Placed Time ln Truck (mins)
Amount
Measured Specified 8.50 N/A
AsrM c 1064 82
ASTM C 231
ASTM C138
I
Before After
13 :18 14:20 14:35
Moisture N/A N/A N/A
General Location Drilled Piers
SamPle Location Pier C/4
Guring Method One day Field/Laboratory Cure
Field Sample No Field Gure Temp ('F) High Low
Gompressive Strength of Concrete Gylinders . -.
specimen rD Date rested tj"gr?r o,l#i.1".TjllL, Area (in')
ASTM C 39
Tvpe of GomPressive Required Fiacture Strength (psi) Strength (psi)Type of
Gap Ultimate Load (lbf)
Goncrete Test RePort Report No: GoN :02-'::"t"-J ff i These test results apply only to the specific locations and materials noted and may not represent any other locatims or elevations. This report may not be rbproduced, except in full, without written permission by
Professional Serui@ lndustries, Inc.
lfri#Ju- Approved Signatory: Michael Can (Department Mmager)
Date of fssue: 512712010
ARCHIE LANHAM
DONNIE JONES
JUSTIN PARK
RANDY FRITZ
WIELAND.DAVCO CORPORATION CC:
4162 ENGLISH OAK DR
LANSING, MI 48911
VA OVERTON BROOKS MENTAL HLTH
SHREVEPORT,I.A
0275169-14-C4\1 05/06/10 0275169-14-C4\2 05127110 0275169-14-C4\3 05127110
0275169-14-C4\4 05127110
4.01 4.00 4.0'l 4.00
8.01 8.00 8.00 8.00
12.63 12.57 12.60 12.57
56260 61630 62590 59470
U U U U
I
Remarks FaitureMode: 1 = C39: Cones on both ends; c1314: conical Braak, 3 = C39: Verl cracklng/no cones: C1314: Cone & Split Notes l.sampling toASTM C 172 2.Speiimen(s) prePared to ASTM C 31 A:d';il;B'=itilA ASTIV! c 617, u=unbonded ASrM c 1231, c = combined
Report No: DPR:0275169-1-C1
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
VA OVERTON BROOKS MENTAL HLTH
SHREVEPORT LA
Client: WIELAND-DAVCO CORPORATION
4162 ENGLISH OAK DR
LANSING, MI
Approved Signatory: Michael Carr (Department Manager) Date of Issue: 5/19/2010
CC: ARCHIE LANHAM,
DONNIE JONES,
JUSTIN PARK,
RANDY FRITZ
These test results apply only to the specific locations and materials noted and may not represent any other locations or elevations. This report may not be reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: J.2/2.3 Date: 3/31/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drill Caisson feet
Equipment Code
Slump Cone:
Thermometer:
Air Meter:
04SC275
04CT275
Shaft Pier
Diameter:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
Length Auger Drilled:
Length Rock Cored:
24.00
85.50
83.00
83.00
28.00
28.00
55.00 inches feet feet feet feet feet feet feet feet
Dates
Date Started:
Date Completed:
Date(s) Observed:
Date Concrete
Placed:
5/5/2010
Pier Concrete
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
Design Strength (psi):
Ticket Number(s):
11:20
11:35
2102323
Concrete Testing
Amt. of Concrete in Load (yd
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
Air Temp. (°F):
Cylinder Set No.:
8.5
2102823
733570
0275169-1-C1
Water
Water Present Prior to Pumping :
Water Present Prior to Concrete
Placement :
1.00
Bearing Surface
Level:
Clean:
Sound:
Rock Socket Length :
Probe Hole Length :
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
Size:
Spacing:
#6
18.00
53.00
#4
16.00
If no concrete testing was performed on this pier, cylinder set represents the concrete for this pier.
Other Concrete Areas:
Probe Hole Description:
H/2.3
Remarks: Concrete placed by tremy. Shoring sieve was used.
All grade elevations are approximate.
Report No: DPR:0275169-1-C3
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: K.2/7.6 Date: 3/31/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Pier feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
35.00 feet feet feet feet feet feet feet
Date(s) Observed:
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
15:10
15:30
2102867
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
733570
0275169-1-C3
Water
Water Present Prior to Pumping :
20.00
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
18.00
33.00 concrete for this pier.
Other Concrete Areas:
J.2/7.6 & H/7.2
Remarks: Concrete placed by tremy. Shoring sieve was used. Slurry method was used.
Report No: DPR:0275169-1-C4
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: J.7/7.6 Date: 3/31/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Caisson feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
feet feet feet feet feet feet feet
Date(s) Observed:
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
15:30
15:40
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
2102866
733570
0275169-1-C4
Water
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
18.00
33.00 concrete for this pier.
Other Concrete Areas:
Report No: DPR:0275169-1-C5
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: H/7.2 Date: 3/31/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Caisson feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
36.00
83.00
23.00
23.00
60.00 feet feet feet feet feet feet feet
Date(s) Observed:
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
15:45
16:15
2102866
17038815
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
17058815
733570
0275169-1-C5
Water
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
#8
30.00
58.00 concrete for this pier.
Report No: DPR:0275169-6-C1
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
Date of Issue: 4/22/2010
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: G-2 Date: 4/20/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Caisson
40.00 feet
Equipment Code
Slump Cone:
04PM275
Shaft Pier
Diameter:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
94.00
90.84
90.84
50.84
50.84
40.00 feet feet feet feet feet feet feet
Date(s) Observed:
4/20/2010
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
14:00
14:35
210832
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
210182
733570
0275169-6-C1
Water
Water Present Prior to Pumping :
30.00
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
30.00
38.00 concrete for this pier.
Remarks: Piers drilled per slurry method. Concrete pumped & tremmied to bottom of pier. Reinforcing steel per S301 Detail B dated 1/20/10.
Report No: DPR:0275169-7-C1
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: G/3 Date: 4/21/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Caisson feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
90.84
50.84
50.84 feet feet feet feet feet feet feet
Date(s) Observed:
4/21/2010
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
11:30
11:45
2101891
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
2101891
733570
0275169-7-C1
Water
Water Present Prior to Pumping :
0.50
0.50
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
30.00
38.00 concrete for this pier.
Remarks: Pier Drilled per Slurry Method
Concrete Pumped & Tremmied from Bottom of Pier
Report No: DPR:0275169-7-C2
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: F/2 Date: 4/21/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Caisson feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
90.84
50.84
50.84 feet feet feet feet feet feet feet
Date(s) Observed:
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
15:40
16:20
2101938
2101942
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
2101938
733570
0275169-7-C2
Water
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
30.00
38.00 concrete for this pier.
Other Concrete Areas:
E/2
Remarks:
Report No: DPR:0275169-7-C7
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: F/3 Date: 4/21/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Caisson feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
93.30
93.30
53.30
53.30 feet feet feet feet feet feet feet
Date(s) Observed:
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
11:55
12:45
NP
2101914
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
733570
0275169-7-C7
Water
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
30.00
38.00 concrete for this pier.
Report No: DPR:0275169-7-C8
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: E/2 Date: 4/21/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Caisson feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
90.84
50.84
50.84 feet feet feet feet feet feet feet
Date(s) Observed:
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
16:30
17:20
2101942
2101949
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
0275169-7-C8
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
30.00
38.00 concrete for this pier.
Report No: DPR:0275169-8-C2
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
Date of Issue: 4/26/2010
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: F/4 Date: 4/22/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Caisson feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
93.30
53.30
53.30 feet feet feet feet feet feet feet
Date(s) Observed:
4/22/2010
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
16:20
16:40
NP &
2102070
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
0275169-8-C2
Water
Water Present Prior to Pumping :
2.00
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
30.00
38.00 concrete for this pier.
Other Concrete Areas:
F/5
Remarks: Concrete placed by tremy method.
Report No: DPR:0275169-8-C3
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: D/2 Date: 4/22/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Caisson feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
90.84
50.84
50.84 feet feet feet feet feet feet feet
Date(s) Observed:
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
12:30
12:45
2102016 &
NP
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
0275169-8-C3
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
30.00
38.00 concrete for this pier.
Remarks: Drilled by slurry method. Concrete placed by tremy method.
Report No: DPR:0275169-8-C4
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: F/5 Date: 4/22/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Caisson feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
94.50
93.30
53.30 feet feet feet feet feet feet feet
Date(s) Observed:
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
16:00
16:15
NP
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
0275169-8-C4
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
30.00
38.00 concrete for this pier.
Report No: DPR:0275169-9-C1
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: D/5 Date: 4/23/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Caisson feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
90.80
90.80
50.80
50.80 feet feet feet feet feet feet feet
Date(s) Observed:
4/23/2010
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
10:30
11:05
4057325
4057326
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
4057325
733570
0275169-9-C1
Water
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
30.00
38.00 concrete for this pier.
Other Concrete Areas:
E/5
Report No: DPR:0275169-9-C3
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: E/5 Date: 4/23/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Caisson feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
90.80
50.80
50.80 feet feet feet feet feet feet feet
Date(s) Observed:
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
11:10
11:30
4057326
4057327
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
4057327
733570
0275169-9-C3
Water
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
30.00
38.00 concrete for this pier.
Report No: DPR:0275169-10-C2
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
Date of Issue: 4/27/2010
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: C/5 Date: 4/26/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Caison feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
90.50
90.50
50.80
50.50 feet feet feet feet feet feet feet
Date(s) Observed:
4/26/2010
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
11:05
11:25
2102160
2102158
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
2102160
733570
0275169-10-C2
Water
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
30.00
38.00 concrete for this pier.
Other Concrete Areas:
E/4
Remarks: Slurry Method was used. Concrete placed by tremy.
Report No: DPR:0275169-10-C3
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: E/4 Date: 4/26/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Builders Supply feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
93.30
53.30 feet feet feet feet feet feet feet
Date(s) Observed:
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
11:30
11:55
2102160
2102158
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
2102159
733570
0275169-10-C3
Water
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
30.00
38.00 concrete for this pier.
Remarks: Concrete placed by tremy.
Report No: DPR:0275169-10-C4
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
Date of Issue: 4/28/2010
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: C/2 Date: 4/26/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Caissons feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
90.80
50.80
50.80 feet feet feet feet feet feet feet
Date(s) Observed:
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
15:00
15:30
17038311
17038312
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
17038311
733570
0275169-10-C4
Water
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
30.00
38.00 concrete for this pier.
Remarks: Concrete placed by tremy. Slurry method used.
Report No: DPR:0275169-10-C5
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: D/4 Date: 4/26/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Caisson feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
93.50
93.50
53.50
53.50 feet feet feet feet feet feet feet
Date(s) Observed:
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
15:30
15:55
17038312
17038313
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
17038312
733570
0275169-10-C5
Water
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
30.00
38.00 concrete for this pier.
Other Concrete Areas:
C/2
Report No: DPR:0275169-12-C1
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
Date of Issue: 4/29/2010
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: B/4 Date: 4/27/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Caisson feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
89.00
89.00
29.00
29.00 feet feet feet feet feet feet feet
Date(s) Observed:
4/27/2010
4/2/2010
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
12:00
12:30
2102211
2102212
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
2102211
733570
0275169-12-C1
Water
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
#9
30.00
58.00 concrete for this pier.
Remarks: Concrete placed by tremy. Slurry method was used.
Report No: DPR:0275169-12-C3
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: B.2/5 Date: 4/27/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Caisson feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
91.80
91.80
56.80
56.80 feet feet feet feet feet feet feet
Date(s) Observed:
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
16:05
16:30
2102237
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
2102237
733570
0275169-12-C3
Water
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
18.00
34.00 concrete for this pier.
Report No: DPR:0275169-13-C1
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: B/3 Date: 4/28/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Caisson feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
89.80
89.80
29.80
29.80 feet feet feet feet feet feet feet
Date(s) Observed:
4/28/2010
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
11:40
12:05
4057442
4057444
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
4057442
733570
0275169-13-C1
Water
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
#9
30.00
58.00 concrete for this pier.
Report No: DPR:0275169-13-C3
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: B/4.9 Date: 4/28/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drillied Caisson feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
92.00
92.00
57.00
57.00 feet feet feet feet feet feet feet
Date(s) Observed:
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
15:50
16:05
17038479
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
17038479
733570
0275169-13-C3
Water
Water Present Prior to Pumping :
15.00
15.00
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
18.00
32.00 concrete for this pier.
Report No: DPR:0275169-14-C1
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
Date of Issue: 4/30/2010
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: C.7/3 Date: 4/29/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Caisson feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
93.30
53.30
53.30 feet feet feet feet feet feet feet
Date(s) Observed:
4/29/2010
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
11:15
11:30
2102395
4057501
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
2102395
733570
0275169-14-C1
Water
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
30.00
38.00 concrete for this pier.
Other Concrete Areas:
D.3/3
Report No: DPR:0275169-14-C2
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: D.3/3 Date: 4/29/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Caisson feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
93.30
53.30
53.30 feet feet feet feet feet feet feet
Date(s) Observed:
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
12:15
4057501
2102400
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
4057501
733570
0275169-14-C2
Water
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
30.00
38.00 concrete for this pier.
Report No: DPR:0275169-14-C4
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: C/4 Date: 4/29/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Caisson feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
90.80
50.80
50.80 feet feet feet feet feet feet feet
Date(s) Observed:
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
16:10
16:30
2102452
2102435
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
2102432
733570
0275169-14-C4
Water
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
30.00
38.00 concrete for this pier.
Other Concrete Areas:
B/2.1
Report No: DPR:0275169-14-C5
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: Date: 4/29/2010 Technician:
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Builder's Supply
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
feet feet feet feet feet feet feet
Date(s) Observed:
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
2102435
733570
0275169-14-C5
Water
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
concrete for this pier.
Report No: DPR:0275169-15-C1
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: C/3 Date: 4/30/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Caisson feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
90.80
50.80
50.80 feet feet feet feet feet feet feet
Date(s) Observed:
4/30/2010
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
12:05
2102506
2102508
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
2102506
733570
0275169-15-C1
Water
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
30.00
38.00 concrete for this pier.
Other Concrete Areas:
B.2/2
Report No: DPR:0275169-15-C2
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: B.2/2 Date: 4/30/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Caissons feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
89.00
89.00
54.00
54.00 feet feet feet feet feet feet feet
Date(s) Observed:
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
12:10
12:25
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
733570
0275169-15-C2
Water
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
18.00
32.00 concrete for this pier.
Report No: DPR:0275169-18-C1
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
Date of Issue: 6/2/2010
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: S/22/3 Date: 5/5/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drill Caisson feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
83.00
28.00
28.00 feet feet feet feet feet feet feet
Date(s) Observed:
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
11:20
11:35
2102323
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
733570
0275169-18-C1
Water
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
18.00
53.00 concrete for this pier.
Other Concrete Areas:
H/2.3
Remarks: Concrete placed by tremy. Shoring sleeve was used.
Report No: DPR:0275169-18-C2
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: H/2.3 Date: 5/5/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Caisson feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
83.00
28.00
28.00 feet feet feet feet feet feet feet
Date(s) Observed:
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
12:05
17038786
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
9.5
17038786
733570
0275169-18-C2
Water
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
18.00
53.00 concrete for this pier.
Report No: DPR:0275169-18-C3
Issue No: 1 Drilled Pier Report
Professional Service Industries, Inc.
4123 Curtis Lane
Shreveport, LA 71109
Phone: (318) 631-5547 Fax: (318) 631-1546
Project:
No:
CC: ARCHIE LANHAM,
DONNIE JONES,
reproduced, except in full, without written permission by Professional Service Industries, Inc.
Log of Pier: K.2/7.6 Date: 5/5/2010 Technician: Jesi Hoover
Drilling Contractor:
Concrete Supplier:
Pier Type:
Auger Refusal Depth:
Case Atlantic
Builder's Supply
Drilled Pier feet
Equipment Code
Slump Cone:
Bell Diameter:
Existing Grade Elevation:
Plan Top Elevation:
Actual Elevation Top:
Plan Elevation Bottom:
Actual Elevation Bottom:
Length of Pier:
feet feet feet feet feet feet feet
Date(s) Observed:
Total Amt. of Concrete
(yd
Initial Time of Placement:
Time of Completion:
15:10
15:30
Ticket No.:
Truck No.:
Mix No.:
No. of Cylinders:
Slump (in):
Air (%):
Concrete Temp. (°F):
733570
0275169-18-C3
Water
Water Present Prior to Pumping :
Level:
Clean:
Sound:
Reinforcing Steel
Vertical No. of bars:
Size:
Cage Diameter:
Cage Length:
Horizontal: No. of bars:
18.00
33.00 concrete for this pier.
Other Concrete Areas:
J.2/7.6 & H/7.2
Remarks: Concrete