Attachment II - Drawings.pdf
PDF 20 MB Posted
- Attached to
- Z1DA--Project No. 610A4-20-107 - Replace Fire Alarm System. Federal contract opportunity
- Solicitation number
- 36C25025B0025
About this file
The provided document is a comprehensive set of architectural and engineering drawings for a fire alarm system replacement project at the VA Northern Indiana Health Care System in Fort Wayne, Indiana. The drawings, labeled as VA Project No. 610A4-20-107, cover multiple buildings (Buildings 1-6, 16, 17, and a Modular Building) and include detailed fire alarm and speaker plans for each building's lower level, first, second, third, fourth, fifth, and sixth floors.
The drawings provide extensive technical details, including floor-specific layouts, fire alarm device placements, speaker locations, and construction notes. Key aspects include replacing existing fire alarm systems, installing new fire alarm control panels, conduits, cables, speakers, and notification appliances across the campus. The project involves a phased approach, with specific instructions for each building, emphasizing careful demolition of existing systems, installation of new equipment, and maintaining operational continuity during the replacement process. The drawings are prepared by Viridian Architectural Design and FRC Consultants, with the project being managed by the VA's Office of Construction and Facilities Management.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment I - Q and A.pdf | ||
| 36C25025B0025 0001.docx | DOCX document | |
| Attachment II - Site Viste Sign in Sheet.pdf | ||
| Attachment I - DBA WD.pdf | ||
| Attachment IV - RFI Form.pdf | ||
| Attachment III - Specifications.pdf | ||
| 36C25025B0025_1.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY
SPRINKLED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDSTAMPFIRE PROTECTION CONSULTANT
321 4 5 6 7 8 9 10
All Concepts, ideas, design elements, plans, and details as shown on this document are the sole property of Viridian Architectural Design, Inc. and shall not be used for any purpose without prior expressed written consent.
The Owner shall be permitted to retain copies for information and reference.
2020 E. Washington Boulevard Suite 200 Fort Wayne, Indiana 46803
PH: 260.424.4830
www.viridian-design.net
NORTH
REFERENCE
PROJECT # SIGNATURE DATE
Director Associate Director Chief of Staff Associate Director for Patient Services Associcate C.O.S. for Mental Health Chief, FMS Chief, Engineering Section Chief, Environmental Management Section Infectious Control Officer Patient Safety Manager GEMS Coordinator Safety Specialist Chief, Police Service Chief, Fire Station Union Safety Representative Contracting Officer Contracting Officer Representative
VA NORTHERN INDIANA HEALTH CARE SYSTEM: FORT WAYNE, IN
VA NORTHERN INDIANA
HEALTH CARE SYSTEM
2121 LAKE AVENUE
FORT WAYNE, INDIANA 46805
VA PROJECT NO.:
FINAL BID
DOCUMENTS
01 53OF
RA
ND
AL
LI
A
DR
IV
E
LAKE AVENUE
LAKE AVENUE
CA
RE
W S
TR
EE
T
E. STATE BLVD.
LOCATION
OF PROJECT
LOCATION MAP VICINITY MAP
RA
ND
AL
LI
A
DR
IV
E
BE
AC
O N
ST
RE
ET
1520 Main Street Indianapolis, Indiana 46224
PH: 317.486.5188
www.fpc-consultants.com
Z:
\V iri di an \P ro je ct s\
\0
D R
AW
IN
G S\
R
EV
IT
\L
O C
AL
F
IL
ES
\6
A4 -2
0-
7_ B1
_C
EN
TR
AL
_R
_a m or ta ki s.
rv t
6/
/2
:4 1:
A
M
GI001
COVER SHEET REPLACE FIRE ALARM SYSTEM 610A4-20-107
BUILDING 1
06/06/2022 TWT JAH
REPLACE FIRE ALARM SYSTEM
610A4-20-107
610A4-20-107
FORT WAYNE VAMC
INDEX OF WORKING DRAWINGS
SHEET NO DRAWING TITLE DRAWING N0
01.ES001 BUILDING 1 - LOWER LEVEL SPEAKER PLAN - A 30
01.ES002 BUILDING 1 - LOWER LEVEL SPEAKER PLAN - B 31
01.ES003 BUILDING 1 - LOWER LEVEL SPEAKER PLAN - C 32
01.ES101 BUILDING 1 - FIRST FLOOR SPEAKER PLAN - A 33
01.ES102 BUILDING 1 - FIRST FLOOR SPEAKER PLAN - B 34
01.ES103 BUILDING 1 - FIRST FLOOR SPEAKER PLAN - C 35
01.ES201 BUILDING 1 - SECOND FLOOR SPEAKER PLAN - A 36
01.ES202 BUILDING 1 - SECOND FLOOR SPEAKER PLAN - B 37
01.ES203 BUILDING 1 - SECOND FLOOR SPEAKER PLAN - C 38
01.ES301 BUILDING 1 - THIRD FLOOR SPEAKER PLAN - A 39
01.ES302 BUILDING 1 - THIRD FLOOR SPEAKER PLAN - B 40
01.ES303 BUILDING 1 - THIRD FLOOR SPEAKER PLAN - C 41
01.ES401 BUILDING 1 - FOURTH FLOOR SPEAKER PLAN - A 42
01.ES402 BUILDING 1 - FOURTH FLOOR SPEAKER PLAN - B 43
01.ES501 BUILDING 1 - FIFTH FLOOR SPEAKER PLAN - A 44
01.ES502 BUILDING 1 - FIFTH FLOOR SPEAKER PLAN - B 45
01.ES601 BUILDING 1 - SIXTH FLOOR SPEAKER PLAN 46
02.ES100 BUILDING 2 - LOWER LEVEL AND FIRST FLOOR SPEAKER PLAN 47
03.ES100 BUILDING 3 - LOWER LEVEL AND FIRST FLOOR SPEAKER PLAN 48
04.ES100 BUILDING 4 - LOWER LEVEL AND FIRST FLOOR SPEAKER PLAN 49
05.ES100 BUILDING 5 - LOWER LEVEL, FIRST, AND SECOND FLOOR SPEAKER PLAN 50
06.ES100 BUILDING 6 - LOWER LEVEL, FIRST, AND SECOND FLOOR SPEAKER PLAN 51
16.ES100 BUILDING 16 - FIRST FLOOR SPEAKER PLAN 52
17.ES100 BUILDING 17 - FIRST FLOOR SPEAKER PLAN 53
INDEX OF WORKING DRAWINGS
SHEET NO DRAWING TITLE DRAWING N0
GENERAL
GI001 COVER SHEET 01
GI002 ICRA DETAILS 02
GI003 ELECTRICAL ABBREVIATIONS & SYMBOLS 03
GI004 CAMPUS PLAN 04
ELECTRICAL
01.FA001 BUILDING 1 - LOWER LEVEL FIRE ALARM PLAN - A 05
01.FA002 BUILDING 1 - LOWER LEVEL FIRE ALARM PLAN - B 06
01.FA003 BUILDING 1 - LOWER LEVEL FIRE ALARM PLAN - C 07
01.FA101 BUILDING 1 - FIRST FLOOR FIRE ALARM PLAN - A 08
01.FA102 BUILDING 1 - FIRST FLOOR FIRE ALARM PLAN - B 09
01.FA103 BUILDING 1 - FIRST FLOOR FIRE ALARM PLAN - C 10
01.FA201 BUILDING 1 - SECOND FLOOR FIRE ALARM PLAN - A 11
01.FA202 BUILDING 1 - SECOND FLOOR FIRE ALARM PLAN - B 12
01.FA203 BUILDING 1 - SECOND FLOOR FIRE ALARM PLAN - C 13
01.FA301 BUILDING 1 - THIRD FLOOR FIRE ALARM PLAN - A 14
01.FA302 BUILDING 1 - THIRD FLOOR FIRE ALARM PLAN - B 15
01.FA303 BUILDING 1 - THIRD FLOOR FIRE ALARM PLAN - C 16
01.FA401 BUILDING 1 - FOURTH FLOOR FIRE ALARM PLAN - A 17
01.FA402 BUILDING 1 - FOURTH FLOOR FIRE ALARM PLAN - B 18
01.FA501 BUILDING 1 - FIFTH FLOOR FIRE ALARM PLAN - A 19
01.FA502 BUILDING 1 - FIFTH FLOOR FIRE ALARM PLAN - B 20
01.FA601 BUILDING 1 - SIXTH FLOOR FIRE ALARM PLAN 21
02.FA100 BUILDING 2 - LOWER LEVEL AND FIRST FLOOR FIRE ALARM PLAN 22
03.FA100 BUILDING 3 - LOWER LEVEL AND FIRST FLOOR FIRE ALARM PLAN 23
04.FA100 BUILDING 4 - LOWER LEVEL AND FIRST FLOOR FIRE ALARM PLAN 24
05.FA100 BUILDING 5 - LOWER LEVEL, FIRST, AND SECOND FLOOR FIRE ALARM PLAN 25
06.FA100 BUILDING 6 - LOWER LEVEL, FIRST, AND SECOND FLOOR FIRE ALARM PLAN 26
16.FA100 BUILDING 16 - FIRST FLOOR FIRE ALARM PLAN 27
17.FA100 BUILDING 17 - FIRST FLOOR FIRE ALARM PLAN 28
MB.FA100 MODULAR BUILDING - FIRST FLOOR FIRE ALARM PLAN 29
FW VAMC CAMPUS
Revisions: Date:
A
O
V
E
PROVIDE STICKY MATS
(CHANGED END OF SHIFT OR
MORE IF NECESSARY TO
MAINTAIN CLEANLINESS).
INDICATOR MUST BE AT -.01 OR GREATER
(VERIFY DAILY), IF NOT VERIFY ALL OPENINGS
SUCH AS DOORS ARE CLOSED AND/OR CHANGE
OUT NEGATIVE AIR PRE-FILTER.
POST ICRA, ILSM, FIRE
INSPECTION SHEETS
VISIBLE TO PUBLIC.
FIRE EXTINGUISHER
ON PORTABLE FLOOR
BRACKET (ISLM MAY
REQUIRE MORE THAN
ONE).
TAPE ALL SERVICES
TO PROTECT AGAINST
CONTAMINATION.
COVER ALL RETURNS AT
THE GRATE / DIFFUSERS
SUPPLY DUCTS EITHER
KEEP RUNNING OR
COVER WHEN RUNNING
TO KEEP DUST OUT.
OUTSIDE OF BUILDING
SUSPENDED PLASTIC ZIPPER
WALL CURTAIN BARRIER
OPTIONAL EXHAUST
DUCTS (COVER THE
GRATES AND THE
DIFFUSERS)
EXIT
CLOSED FOR
CONSTRUCTION
PROVIDE AND DISPLAY ICRA REQUIREMENT
DOCUMENTATION. COORDINATE WITH COR.
5-PLY SOLID CORE FLUSH DOORS SHALL BE
SECURED, AND HAVE LIMITED, ZIPPERED ACCESS,
AND MASKED OFF / SEALED AND PROTECTED PER
INFECTION CONTROL REQUIREMENTS PRIOR TO
DEMOLITION AND FOR DURATION OF
CONSTRUCTION. COORDINATE EGRESS
REQUIREMENTS WITH COR. SEE SPECIFICATIONS
FOR ADDITIONAL INFORMATION.
USE ALTERNATIVE
EXITS
CAUTION
THIS AREA CLOSED
OFF
ICRA
REQUIREMENTS
NO ENTRY
DUST BARRIER
PROVIDE AND DISPLAY ICRA REQUIREMENT
DOCUMENTATION. COORDINATE WITH COR.
5-PLY SOLID CORE FLUSH DOORS SHALL BE
SECURED, AND HAVE LIMITED, ZIPPERED ACCESS,
AND MASKED OFF / SEALED AND PROTECTED PER
INFECTION CONTROL REQUIREMENTS PRIOR TO
DEMOLITION AND FOR DURATION OF
CONSTRUCTION. COORDINATE EGRESS
REQUIREMENTS WITH COR. SEE SPECIFICATIONS
FOR ADDITIONAL INFORMATION.
FLEX DUCT
PLASTIC WINDOW
(ON ALL SIDES)
HEPA NEGATIVE AIR UNIT
MOBILE CONTAINMENT
CART WITH CANVAS /
1-1/4" SQUARE STEEL
TUBULAR FRAME
FLEX DUCT
SWIVEL CASTERS
ZIPPER SIDE ENTRY
AD
JU
ST
AB
LE
HE
IG
HT
UNIT SHALL BE VENTED
TO OUTSIDE
AD
JU
ST
AB
LE
HE
IG
HT
XXXXX
XXXXX
XXXXX
INDICATOR MUST MAINTAIN -0.01 INCHES OF WATER
GAUGE (VERIFY DAILY) AIR PRESSURE, IF NOT VERIFY
ALL OPENING SUCH AS DOORS ARE CLOSED AND/OR
CHANGE OUT NEGATIVE AIR PRE-FILTER.
INDICATOR
(REFER TO
PLAN AND
ELEVATION)
POST ICRA, ILSM,
FIRE INSPECTION
SHEETS VISIBLE
TO PUBLIC
SUSPENDED
PLASTIC ZIPPER
WALL CURTAIN
BARRIER
COMING SOON!!!
ICRA, ILSM
FIRE WATCH
MISC. FORMS
PAPER
CADDY
PERSONNEL ENTERING MUST HAVE: HARD HAT,
SAFETY GLASSES AND PROPER I.D.
-DESCRIPTION OF NEWLY PROPOSED OCCUPANCY-
THIS IS A
RESTRICTED AREA
AREA UNDER CONSTRUCTION
CONST. SUPERVISOR
NAME & CELL PHONE
CONTACT PHONE #####
FIRE EMERGENCY DIAL 911
XXXXXX
XXXX
FRAMED
PICTURE OF
C.O.R.WITH
CONTACT
INFORMATION
AP
PR
OX
. 4
8" A
.F .F
TYPE A TYPE B
4" RUBBER COVE
TO MATCH EXISTING AREA
BASE AT BOTH SIDES
4" RUBBER COVE
TO MATCH EXISTING AREA
BASE AT BOTH SIDES
SUSPENDED
ACOUSTICAL CEILING
AS SCHEDULED
ON FLOOR PLAN.
ALL TEMPORARY CONSTRUCTION
BARRIER - INFECTION/ DUST CONTROL
PARTITION(S) SHALL BE SEALED TO EXISTING
FLOOR, CEILING, WALL, AND DOOR/ WINDOW
FRAME CONSTRUCTION AS APPLICABLE, PER
INFECTION CONTROL REQUIREMENTS PRIOR
TO DEMOLITION AND FOR DURATION OF
CONSTRUCTION. SEE SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
TEMPORARY CONSTRUCTION "SMOKE
TIGHT" BARRIER - INFECTION/ DUST
CONTROL PARTITION: 4" , 20 GA.
METAL STUDS @ 16" O.C., SECURED
TO FLOOR, CEILING, WALL, AND DOOR/
WINDOW FRAME INTERSECTIONS
FOR STRUCTURAL STABILITY, W/ 1/2"
GYP. BD. EA. SIDE, W/ ALL JOINTS
TAPED AND SEALED FOR INFECTION/
DUST CONTROL (NOT MUDDED).
SUSPENDED
ACOUSTICAL CEILING
AS SCHEDULED
ON FLOOR PLAN.
ALL TEMPORARY CONSTRUCTION
BARRIER - INFECTION/ DUST CONTROL
PARTITION(S) SHALL BE SEALED TO
EXISTING FLOOR, CEILING, WALL, AND
DOOR/ WINDOW FRAME
CONSTRUCTION AS APPLICABLE, PER
INFECTION CONTROL REQUIREMENTS
PRIOR TO DEMOLITION AND FOR
DURATION OF CONSTRUCTION. SEE
SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
4 7/8"
W
AL
L H
EI
GH
T
VE
RI
ES
F
IEL
D
VE
RI
FY
CE
ILI
NG
H
EI
GH
T 8'
-0
" 3 5/8" 16 GA. METAL
STUDS AT 16" O.C.
WITH 5/8" GYPSUM
BOARD EACH SIDE.
4 7/8"
CE
ILI
NG
H
EI
GH
T 8'
-0
W
AL
L H
EI
GH
T
VE
RI
ES
F
IEL
D
VE
RI
FY
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY
SPRINKLED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDSTAMPFIRE PROTECTION CONSULTANT
321 4 5 6 7 8 9 10
All Concepts, ideas, design elements, plans, and details as shown on this document are the sole property of Viridian Architectural
Design, Inc. and shall not be used for any purpose without prior expressed written consent. The Owner shall be permitted to retain copies for information and reference.
2020 E. Washington Boulevard Suite 200 Fort Wayne, Indiana 46803
PH: 260.424.4830
www.viridian-design.net
FINAL BID
DOCUMENTS
OF02 53
1520 Main Street Indianapolis, Indiana 46224
PH: 317.486.5188
www.fpc-consultants.com
Z:
\V iri di an \P ro je ct s\
\0
D R
AW
IN
G S\
R
EV
IT
\L
O C
AL
F
IL
ES
\6
A4 -2
0-
7_ B1
_C
EN
TR
AL
_R
_a m or ta ki s.
rv t
6/
/2
:1 8:
A
M
GI002
ICRA DETAILS REPLACE FIRE ALARM SYSTEM
FORT WAYNE VAMC
610A4-20-107
BUILDING 1
06/06/2022 TWT JAH
LOW RISK MEDIUM RISK HIGH RISK HIGHEST RISK
• OFFICE AREAS • CARDIOLOGY
• ECHOCARDIOGRAPHY
• ENDOSCROPY
• NUCLEAR MEDICINE
• PHYSICAL THERAPY
• RADIOLOGY / MRI
• RESPIRATORY THERAPY
• CCU
• EMERGENCY ROOM
• LABOR AND DELIVERY
• LABORATORY (SPECIMEN)
• NEWBORN NURSEY
• OUTPATIENT SURGERY
• PEDIATRICS
• PHARMACY
• POST ANESTHESIA CARE UNIT
• SURGICAL UNITS
• ANY AREA CARING FOR
IMMUNOCOMPROMISED PATIENTS
• BURN UNIT
• CARDIAC CATH LAB
• CENTRAL STERILE SUPPLY
• INTENSIVE CARE UNITS
• MEDICAL UNIT
• NEGATIVE PRESSURE ISOLATION ROOMS
• ONCOLOGY
• OPERATING ROOMS INCLUDING
C-SECTION ROOMS
PATIENT RISK GROUPS
APPLICABILITY OF GENERAL CONSTRUCTION NOTES:
THESE NOTES APPLY TO ALL WORK DESCRIBED IN THESE DRAWINGS AND SPECIFICATIONS AND TO ALL CONTRACTORS AND / OR SUBCONTRACTORS THAT WORK IN, ON, OR AROUND THIS BUILDING OR THE ADJACENT SITE. FOR ADDITIONAL SCOPE OF WORK DESCRIBED IN DETAIL, SEE THE RESPECTIVE DISCIPLINE DRAWINGS AND
SPECIFICATIONS.
1. EXISTING BUILDING UTILITIES: PRIOR TO THE COMMENCEMENT OF ANY / ALL WORK, VERIFY THE LOCATION AND INSURE THE OBVIOUS MARKING OF ALL EXISTING UTILITIES (PRIVATE / PUBLIC) AND RELATED EQUIPMENT ON, ABOVE, OR BENEATH THE ADJACENT WORK AREA, WHETHER INDICATED TO REMAIN, TO BE MODIFIED, OR TO BE REMOVED. COORDINATE ALL VERIFICATION AND MARKING WORK WITH THE COR.
2. BUILDING DUST AND INFECTION CONTROL: THE BUILDING WILL REMAIN FULLY OCCUPIED DURING ALL PHASES OF THIS WORK. THEREFORE, PROVIDE, INSTALL, AND MAINTAIN ALL CONSTRUCTION DUST, DEBRIS AND INFECTION CONTROL MEASURES OUTLINED. SEE INFECTION CONTROL PLAN AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION. COORDINATE SPECIFIC INFORMATION WITH THE COR.
3. BUILDING ACCESS AND SECURITY: THE BUILDING WILL REMAIN FULLY OCCUPIED DURING ALL PHASES OF THIS WORK. THEREFORE, PROVIDE, INSTALL, AND MAINTAIN ALL TEMPORARY MEASURES REQUIRED TO MAINTAIN ACCESS AND SECURITY OF THE EXISTING BUILDING AND THE WORK AREA FOR THE DURATION
OF THE CONSTRUCTION PROJECT. COORDINATE SPECIFIC INFORMATION WITH THE COR. SEE
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
4. EXISTING WORK AREA AND BUILDING CONDITION: PROVIDE, INSTALL, AND MAINTAIN PROTECTIVE MEASURES TO KEEP THE EXISTING BUILDING ADJACENT TO THE WORK AREA AND PATH OF DEMOLITION
TRAVEL FROM CONSTRUCTION DAMAGE DURING WORK. RESTORE ANY PORTION OF THE EXISTING
BUILDING OR ADJACENT SITE INADVERTENTLY DAMAGED BY, OR AS A RESULT OF THIS WORK, AT NO
ADDITIONAL COST TO THE VA. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
5. EXITS TO BE MAINTAINED: MAINTAIN A MINIMUM OF 3' OF MAIN WARD ACCESS / EXIT THROUGHOUT THE
CONSTRUCTION PERIOD.
6. GENERAL DEMOLITION NOTES AND INFORMATION: SEE DISCIPLINE DRAWINGS AND SPECIFICATIONS FOR
GENERAL DEMOLITION NOTES AND INFORMATION INCLUDING DISPOSAL AND / OR SALVAGE OF
DEMOLISHED MATERIALS. COORDINATE SPECIFIC INFORMATION WITH THE COR.
7. GENERAL CONSTRUCTION NOTES AND INFORMATION: SEE DISCIPLINE DRAWINGS AND SPECIFICATIONS
FOR GENERAL CONSTRUCTION NOTES AND INFORMATION INCLUDING STORAGE AND STAGING OF
CONSTRUCTION MATERIALS. COORDINATE SPECIFIC INFORMATION WITH THE COR.
8. EXISTING PLUMBING SUPPLY AND DWV SYSTEMS AND EQUIPMENT: THE BUILDING WILL REMAIN FULLY
OCCUPIED DURING CONSTRUCTION. THEREFORE, COORDINATE ALL TEMPORARY AND PERMANENT
DISCONNECTING, MODIFICATIONS TO, REROUTING OF, AND RECONNECTING OF EXISTING PLUMBING SUPPLY AND DRAIN WASTE VENT SYSTEMS (DWV) AND EQUIPMENT WITH THE COR. SEE DEMOLITION, ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
9. EXISTING MECHANICAL SYSTEMS AND EQUIPMENT: THE BUILDING WILL REMAIN FULLY OCCUPIED DURING CONSTRUCTION. THEREFORE, COORDINATE ALL TEMPORARY AND PERMANENT DISCONNECTING AND RECONNECTING OF EXISTING MECHANICAL SYSTEMS, STEAM PIPING AND EQUIPMENT WITH THE COR. SEE DEMOLITION, ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
10. EXISTING ELECTRICAL POWER SUPPLIES AND EQUIPMENT: THE BUILDING WILL REMAIN FULLY OCCUPIED DURING CONSTRUCTION. THEREFORE, COORDINATE ALL TEMPORARY AND PERMANENT DISCONNECTING AND RECONNECTING OF EXISTING POWER SUPPLIES AND EQUIPMENT WITH THE COR. SEE DEMOLITION, ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS, AND SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
11. FIRE-PROTECTION SYSTEMS AND EQUIPMENT: THE BUILDING WILL REMAIN FULLY OCCUPIED DURING CONSTRUCTION. THEREFORE, COORDINATE ALL NEW ROUTING OF FIRE-PROTECTION SYSTEMS AND EQUIPMENT WITH THE COR. SEE DEMOLITION, ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS, AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
GENERAL CONSTRUCTION AND PHASING NOTES
COORDINATE WITH NORTHEAST INDIANA VAMC CONTRACTING OFFICER'S REPRESENTATIVE (COR) TO COMPLETE AN INFECTION CONTROL RISK ASSESSMENT MATRIX AND OBTAIN AN INFECTION CONTROL CONSTRUCTION PERMIT FOR EACH PHASE OF WORK OUTLINED IN THESE DOCUMENTS PRIOR TO THE START OF DEMOLITION AND CONSTRUCTION. COMPLY WITH ALL INFECTION CONTROL REQUIREMENTS FOR THE DURATION OF THE CONSTRUCTION PROJECT. SEE ITEMS LISTED BELOW AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
1. REFER TO SPECIFICATIONS FOR MEDICAL CENTER "INFECTION CONTROL RISK ASSESSMENT MATRIX OF
PRECAUTIONS FOR CONSTRUCTION & RENOVATION" FOR INFECTION CONTROL INFORMATION AND
REQUIREMENTS.
2. USING THE "INFECTION CONTROL RISK ASSESSMENT MATRIX OF PRECAUTIONS FOR CONSTRUCTION &
RENOVATION" COORDINATE WITH COR TO DETERMINE THE FOLLOWING PROJECT CONDITIONS:
· PATIENT RISK GROUPS (LOW, MEDIUM, HIGH, HIGHEST)
· TYPE OF CONSTRUCTION PROJECT ACTIVITY (A, B, C, OR D)
· CLASS OF PRECAUTION/ LEVEL OF INFECTION CONTROL ACTIVITIES REQUIRED (CLASS II REQUIRED)
3. ONCE THE "CLASS OF PRECAUTION" HAS BEEN DETERMINED IN COORDINATION WITH THE COR, COMPLETE THE "INFECTION CONTROL CONSTRUCTION PERMIT." PROCEED WITH DEMOLITION AND CONSTRUCTION WORK ONLY AFTER THE PERMIT HAS BEEN AUTHORIZED BY THE COR. ONCE THE PERMIT
IS AUTHORIZED, POST THE PERMIT AS DIRECTED BY THE COR.
4. USING THE "DESCRIPTION OF REQUIRED INFECTION CONTROL PRECAUTIONS BY CLASS" AS OUTLINED BELOW, COORDINATE WITH THE COR TO DETERMINE THE SPECIFIC EXTENT AND APPLICATION METHODS OF THE REQUIRED INFECTION CONTROL PRECAUTIONS. PRECAUTIONS LISTED BELOW ARE TO BE
CONFIRMED WITH THE COR:
1.1. DURING CONSTRUCTION PROJECT PHASE:
1.1.1. ISOLATE THE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION
OF DUCT SYSTEM.
1.1.2. COMPLETE ALL CRITICAL BARRIERS TO SEAL WORK AREA FROM NON-WORK AREA BEFORE
DEMOLITION OR CONSTRUCTION BEGINS.
1.1.3. MAINTAIN NEGATIVE AIR PRESSURE OF -0.1" W.C. WITHIN WORK SITE UTILIZING HEPA EQUIPPED
AIR FILTRATION UNITS. CONTRACTOR SHALL PROVIDE MAGNOMETER TO MEASURE AIR
PRESSURE.
1.1.4. SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES APPROPRIATELY.
1.1.5. CONSTRUCT ANTEROOM AND REQUIRE ALL PERSONNEL TO PASS THROUGH THIS ROOM
SO THEY CAN BE VACUUMED USING A HEPA VACUUM CLEANER BEFORE LEAVING WORK SITE OR
THEY CAN WEAR CLOTH OR PAPER COVERALLS THAT ARE REMOVED EACH TIME THEY LEAVE THE
WORK SITE.
1.1.6. ALL PERSONNEL ENTERING WORK SITE ARE REQUIRED TO WEAR SHOE COVERS. SHOE COVERS
MUST BE EXCHANGED EACH TIME WORKER EXITS THE WORK AREA.
1.1.7. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS INSPECTED BY THE
SAFETY OFFICE AND INFECTION CONTROL AND THOROUGHLY CLEANED BY ENVIRONMENTAL
MANAGEMENT SERVICE.
1.2. UPON COMPLETION OF PROJECT PHASE:
1.2.1. REMOVE BARRIER MATERIAL CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS
ASSOCIATED WITH CONSTRUCTION.
1.2.2. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.
1.2.3. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS SOLID LID.
1.2.4. VACUUM WORK AREA WITH HEPA FILTERED VACUUMS.
1.2.5. WET MOP AREA WITH DISINFECTANT.
1.2.6. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE WORK HAS BEEN PERFORMED.
5. DURING THE CONSTRUCTION PROJECT PHASE, PROVIDE, INSTALL, & MAINTAIN THE SPECIFIC INFECTION
CONTROL PRECAUTIONS AS DETERMINED BY COORDINATION WITH COR.
6. UPON COMPLETION OF THE CONSTRUCTION PROJECT PHASE, REMOVE THE SPECIFIC INFECTION
CONTROL PRECAUTIONS AS DETERMINED BY COORDINATION WITH COR.
7. IAQ (INDOOR AIR QUALITY) CONTROL MEASURES DURING CONSTRUCTION NOTES:
INFECTION CONTROL PLAN GENERAL NOTES
TYPE A
INCLUDES, BUT IS NOT LIMITED TO:
• REMOVABLE OF CEILING TILES FOR VISUAL INSPECTION LIMITED TO 1 TILE PER 50 SQUARE FEET.
• PAINTING (BUT NOT SANDING).
• WALL COVERING, ELECTRICAL TRIM, MINOR PLUMBING, AND ACTIVITIES WHICH DO NOT GENERATE DUST OR
REQUIRE CUTTING OF WALLS OR ACCESS TO CEILINGS OTHER THAN FOR VISUAL INSPECTION.
INFECTION CONTROL RISK ASSESSMENT (ICRA)
MATRIX OF PRECAUTIONS FOR
CONSTRUCTION AND RENOVATION
INSPECTION AND NON-INVASIVE ACTIVITIES
TYPE B
INCLUDES, BUT IS NOT LIMITED TO:
• INSTALLATION OF TELEPHONE AND COMPUTER CABLING.
• ACCESS TO CHASE SPACES.
• CUTTING OF WALLS OR CEILING WHERE DUST MIGRATION CAN BE CONTROLLED.
SMALL SCALE, SHORT DURATION ACTIVITIES
WHICH CREATES MINIMAL DUST
TYPE C INCLUDES, BUT IS NOT LIMITED TO:
• SANDING OF WALLS FOR PAINTING OR WALL COVERING.
• REMOVAL OF FLOOR COVERINGS, CEILING TILES OR CASEWORK.
• NEW WALL CONSTRUCTION.
• MINOR DUCT WORK OR ELECTRICAL WORK ABOVE CEILINGS.
• MAJOR CABLING ACTIVITIES.
• ANY ACTIVITY WHICH CANNOT BE COMPLETED WITHIN A SINGLE WORK SHIFT.
WORK THAT GENERATES A MODERATE TO HIGH LEVEL
OF DUST OR REQUIRES DEMOLITION OR REMOVAL OF
ANY FIXED BUILDING COMPONENTS OR ASSEMBLIES
TYPE D INCLUDES, BUT IS NOT LIMITED TO:
• ACTIVITIES WHICH REQUIRE CONSECUTIVE WORK SHIFTS.
• REQUIRE HEAVY DEMOLITION OR REMOVAL OF A COMPLETE CABLING SYSTEM.
• NEW CONSTRUCTION.
MAJOR DEMOLITION AND CONSTRUCTION PROJECTS
RISK RELATED GROUP
LOW RISK GROUP
MEDIUM RISK GROUP
HIGH RISK GROUP
HIGHEST RISK GROUP
TYPE A
I
I
I
II
TYPE B
II
II
II
III / IV
TYPE C
II
III
III / IV
III / IV
TYPE D
III / IV
IV
IV
IV
NOTE:
INFECTION CONTROL APPROVAL WILL BE REQUIRED WHEN THE CONSTRUCTION ACITIVITY AND RISK LEVEL INDICATE THAT CLASS IV CONTROL
PROCEDURES ARE NECESSARY.
IC MATRIX - CLASS OF PRECAUTIONS:
CONSTRUCTION PROJECT BY PATIENT RISK
CONSTRUCTION PROJECT TYPE
CL
AS
S I
CLASS I WORK ITEMS NOTES:
1. EXECUTE WORK METHODS TO MINIMIZE RAISING DUST FROM CONSTRUCTION OPERATIONS.
2. IMMEDIATELY REPLACE CEILING TILE DISPLACED FOR VISUAL INSPECTION.
CL
AS
S
II
CLASS II WORK ITEMS NOTES:
1. PROVIDE ACTIVE MEANS TO PREVENT AIRBORNE DUST FROM DISPERSING INTO ATMOSPHERE.
2. WATER MIST WORK SURFACES TO CONTROL DUST WHILE CUTTING.
3. SEAL UNUSED DOORS WITH DUCT TAPE.
4. BLOCK OFF AND SEAL AIR VENTS.
5. PLACE DUST MAT AT ENTRANCE AND EXIT WORK AREAS.
6. REMOVE OR ISOLATE H.V.A.C. SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.
PRIOR TO ANY CONSTRUCTION:
1. WIPE WORK SURFACES TO CONTROL DUST WHILE CUTTING.
2. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.
3. WET MOP AND / OR VACUUM WITH HEPA FILTERED VACUUM BEFORE LEAVING WORK AREA.
4. REMOVE ISOLATION OF H.V.A.C. SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.
POST CONSTRUCTION:
SCALE: 3/8" = 1'-0"
GI002
CLASSI & II TYPICAL CONSTRUCTION LAYOUT
SCALE: 1/2" = 1'-0"
GI002
EXIT CLOSED FOR CONSTRUCTION
SCALE: 1/2" = 1'-0"
GI002
INFECTION / DUST CONTROL DOOR
SCALE: 3/8" = 1'-0"
GI002
MOBILE CONTAINMENT CART
SCALE: 3/8" = 1'-0"
GI002
ROOM ELEVATION
SCALE: 1/2" = 1'-0"
GI002
WALL CONSTRUCTION TYPES
FW VAMC CAMPUS
SEQUENCE OF CONSTRUCTION NOTES
APPLICABILITY OF SEQUENCE OF CONSTRUCTION NOTES:
THESE NOTES APPLY TO THE SEQUENCE AND ORDER OF CONSTRUCTION OF THE NEW FIRE ALARM SYSTEM AND SPEAKERS IN THIS PROJECT. ALL WORK SHALL BE COORDINATED WITH THE PRIOR TO STARTING.
BUILDING 1 WORK:
1. INSTALL NEW FIRE ALARM CONTROL PANELS, POWER SUPPLIES AND PANEL RISER IN BUILDING 1.
2. 6TH FLOOR: STARTING WITH THE 6TH FLOOR, TEMPORARY ALL ELEVATOR CONTROLS TO MAINTAIN RECALL FUNCTIONS. PROVIDE TEMPORARY PULL-STATION, SPEAKER AND STROBE AS PER DETAIL 2 ON SHEET 01.FA001. PROVIDE PLENUM-RATED CABLE FROM TEMPORARY STATION TO NEW PANEL ON FLOOR 5 AND TEST FOR PROPER OPERATION. TEMPORARY ALL SPRINKLER FLOW, TAMPER OR PRESSURE SWITCHES FROM EXISTING SYSTEM TO NEW. INSTALL NEW DEVICES AS SHOWN ON DRAWINGS, BEGIN DEMOLITION OF EXISTING DEVICES AND INSTALLATION OF NEW DEVICES AS SHOWN ON DRAWINGS, INSTALL NEW CABLE AND CONDUIT TO NEW DEVICE LOCATIONS AND ANY EXISTING DEVICES TO BE
REUSED AS SHOWN MAKING ALL TERMINATIONS. TEST 6TH FLOOR ON NEW SYSTEM.
3. 5TH FLOOR: PROVIDE TEMPORARY DEVICES AS SHOWN IN DETAIL 2 ON SHEET 01.FA001 INCLUDING SPEAKER, STROBE AND PULL STATION. INSTALL CABLE IN EYELET ABOVE CEILING GRID, RUN PLENUM
RATED CABLE FROM TEMPORARY STATIONS TO NEW FIRE ALARM PANEL AND TEST FOR PROPER
OPERATION. TEMPORARY ALL SPRINKLER, FLOW, TAMPER OR PRESSURE SWITCHES FROM OLD SYSTEM TO NEW. TEMPORARY ANY AND ALL DOOR HOLDERS FROM EXISTING SYSTEM TO NEW. DEMO EXISTING FLOOR CABLES AND CONDUIT. CONDUIT BEING RE-USED SHALL BE RE-SUPPORTED ON EXISTING STRUCTURE.
INSTALL NEW CABLE AND CONDUIT TO NEW DEVICE LOCATIONS AND ANY EXISTING DEVICES TO BE REUSED AS SHOWN. ALL NEW CONDUIT SHALL BE RED IN COLOR AS PER SPEFICIATIONS. PULL NEW CABLE
AND MAKE ALL TERMINATIONS. TEST 5TH FLOOR ON NEW SYSTEM. CORRECT ANY ERRORS OR
MALFUNCTIONS IN SYSTEM.
4. WORK DETAILED IN BUILDING 1, ITEM #3 SHALL BE REPEATED ON EACH FLOOR WORKING FROM TOP TO
BOTTOM UNTIL BUILDING 1 INSTALLATION IS COMPLETED, TESTED, AND COMMISSIONED.
5. CONTRACTOR SHALL PATCH, REPAIR, REPAIN WALLS AND CEILINGS FOR DEMOLISHED OR REMOVED DEVICES TO SHOW NO EVIDENCE OF CONSTRUCITON. PROVIDE BRUSHED STAINLESS STEEL COVER PLATES WITH ROUNDED CORNERS AND NO ROUGH EDGES FOR ALL ABANDONDED BACK BOXES. TYPICAL
FOR ALL BUILDINGS.
OUTLYING BUILDINGS - NOTE - EACH BUILDING SHALL BE DOWN FOR NO MORE THAN 5 CONSECUTIVE DAYS
UNLESS WRITTEN PERMISSION FROM COR IS RECEIVED:
1. BUILDING 2: INSTALL NEW PANEL, PROVIDE NEW FIBER OPTIC CABLE FROM PANEL TO BUILDING 1, USING EXISTING CONDUIT AND MANHOLES AS SHOWN ON SITE PLAN. DEMO EXISTING DEVICES, CONDUIT, CABLE AND ALLAPPURTENANCES IN THEIR ENTIRETY AS SHOWN ON DRAWINGS, INSTALL NEW DEVICES, CONDUIT
AND CABLE, TEST AND COMMISSION SYSTEM FOR PROPER OPERATION.
2. BUILDINGS 3,4,5 & 6: DEMO EXISTING DEVICES, CONDUIT, CABLE AND ALL APPURTENANCES IN THEIR
ENTIRETY AS SHOWN ON DRAWINGS, INSTALL NEW DEVICES, CONDUIT AND CABLE, TEST AND
COMMISSION SYSTEM FOR PROPER OPERATION.
3. BUILDINGS 16 & 17: INSTALL NEW CIRCUITS IN EXISTING CONDUIT FROM BUILDING 1 AS SHOWN ON CONSTRUCTION DRAWINGS. EXISTING CONDUITS SHALL BE CLEANED AND PREPPED PER SPECIFIFCIATIONS PRIOR TO REUSE. INSTALL NEW DEVICES, CONDUIT AND CABLES AS SHOWN, TEST AND COMMISSION SYSTEM FOR PROPER OPERATION, DEMO EXISTING DEVICES, CONDUIT, CABLE AND ALL APPURTENANCES
IN THEIR ENTIRETY.
FIRE ALARM COMMISSIONING
AE SHALL BE RESPONSIBLE FOR COMMISSIONING FIRE ALARM SYSTEM FOR ALL BUILDINGS.
CONTRACTOR SHALL COORDINATE WITH AE FOR COMMISSIOING.
1PH SINGLE-PHASE
1P SINGLE POLE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE-PHASE
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC FREQUENCY
CONTROL, OR AVAILABLE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB OR A AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISH FLOOR
BIL BASIC INSULATION LEVEL
BLDG BUILDING
BPIP BOILER PLANT INSTRUMENTATION PANEL
BRKR BREAKER
BYP BY PASS
C CONDUIT
CAB CABINET
CALC CALCULATE
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
CD CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER
CLF CURRENT LIMITING FUSE
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAX CABLE
COMM COMMUNICATION
COMPT COMPARTMENT
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
CUR CURRENT
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DISTR PNL DISTRIBUTION PANEL
DMR SW DIMMER SWITCH
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMCP EMERGENCY MONITORING CONTROL PANEL
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
EPRF EXPLOSION PROOF
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST EXISTING
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABL FIRE ALARM BELL
FABX FIRE ALARM BOX
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FI FILM ILLUMINATOR
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FLT FLOODLIGHT
FLUOR FLUORESCENT
FLUOR FIX FLUORESCENT FIXTURE
FOUTT TELEPHONE FLOOR OUTLET
FP FIRE PROTECTION
FT FEET OR FOOT
FU SW FUSED SWITCH
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G OR GND GROUND OR GENERATOR
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
IESNA ILLUMINATION ENGINEERING SOCIETY OF NORTH AMERICA
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT AMPERE
KVAH KILOVOLT AMPERE PER HOUR
KVAR KILOVOLT AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
KWHM KILOWATT HOUR METER
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LM LUMEN
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LTCP LOCAL TEMPERATURE CONTROL PANEL
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MT MOUNT
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT MICROWAVE
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NEUT OR N NEUTRAL
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, PULL BOX, OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PCB POLYCHLORINATED BIPHENYL
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
POD POWER OPERATED DAMPER
PT POTENTIAL TRANSFORMER
PTRV POWER TYPE ROOF VENTILATION
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
RCP REFLECTED CEILING PLAN
REC RECESSED
RECPT RECEPTACLE
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
REQD REQUIRED
SCC SHORT CIRCUIT CAPACITY
SES SERVICE ENTRANCE SECTION
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TC TIME CLOCK
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
W WATT
WH WATER HEATER
WP WEATHERPROOF
XFER TRANSFER
XFMR TRANSFORMER
ELECTRICAL ABBREVIATIONS ELECTRICAL SYMBOLS - DIAGRAM COMMUNICATION SYMBOLS
N
TTB
S
A
J
M
N
R M
C
A
B
A
B
D
E
E
PB
TC
R
T
S
S
VFD
R
R M
NCS
NCT
S
SWITCH, MULTIPOSITION
SWITCH, NORMALLY CLOSED FLOAT
SWITCH, NORMALLY CLOSED FOOT OPERATED
SWITCH, NORMALLY CLOSED LIMIT
SWITCH, NORMALLY CLOSED TIME DELAY
SWITCH, NORMALLY CLOSED TEMPERATURE ACTIVATED
SWITCH, NORMALLY OPEN FLOAT
SWITCH, NORMALLY OPEN LIMIT
SWITCH, NORMALLY OPEN TEMPERATURE ACTIVATED
SWITCH, NORMALLY OPEN TIME DELAY
SWITCH, SINGLE BREAK
FUSE WITH RATING
NORMALLY CLOSED RELAY CONTACT
NORMALLY OPEN RELAY CONTACT
MOLDED CASE CIRCUIT BREAKER
LOW-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER
HIGH-VOLTAGE OIL CIRCUIT BREAKER
HIGH-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER
SWITCH AND FUSE UNIT
FUSED DRAWOUT POTENTIAL TRANSFORMER
MOTOR, SINGLE-PHASE
MOTOR, THREE-PHASE
DELTA CONNECTION
TRANSFORMER
WYE CONNECTION
EARTH GROUND
JUNCTION BOX
PULL BOX
PRESSURE SWITCH-CLOSE ON INCREASE
PRESSURE SWITCH-OPEN ON INCREASE
FUSIBLE LINK
TIME CLOCK
GENERATOR, POWER
BATTERY
CAPACITOR
LIGHTNING ARRESTOR
RECTIFIER, CATHODIC PROTECTION SANITARY
RELAY
50 = INSTANTANEOUS OVERCURRENT OR RATE-OF-
RISE
51 = AC-TIME OVERCURRENT
67 = AC-DIRECTIONAL OVERCURRENT
86 LOCKING OUT
DISCONNECT SWITCH, FUSED
DISCONNECT SWITCH, UNFUSED
STARTER, COMBINATION WITH DISCONNECT SWITCH
STARTER OR MOTOR CONTROLLER
POTHEAD
STRESS CONE
METER
AMMETER
VOLTMETER
WATTMETER
WATT-HOUR METER
TIME CLOCK
RECTIFIER, CATHODIC PROTECTION SANITARY
ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" [610mm] CENTERS
OR AS
DESIGNATED ON DRAWINGS), MTD 3'-6" [1067mm] AFF OR AS
INDICATED.
3-GANG COMPARTMENT BOX IN FLOOR FOR TELEPHONE, DATA & RECEPTACLE.
DISCONNECT SWITCH, FUSED
DISCONNECT SWITCH, UNFUSED
STARTER, COMBINATION WITH DISCONNECT SWITCH
STARTER OR MOTOR CONTROLLER
POTHEAD
STRESS CONE
VENTILATOR OR FAN COIL UNIT OUTLET
CONDUIT TERMINATED 6" [152mm] AFF IN STANDARD BOX FOR
EXTENSION TO EQUIPMENT AS DIRECTED.
CONDUIT TERMINATED W/COUPLING (FLUSH W/FINISHED FLOOR) FOR
EXTENSION TO EQUIPMENT AS DIRECTED.
JUNCTION BOX
TRANSFORMER, PLAN
MOTOR, SINGLE-PHASE
MOTOR, THREE-PHASE
WYE CONNECTION
DUCT, CELL FLOOR HEADER
DUCT, TROLLEY
DUCT, UNDERFLOOR JUNCTION BOX
EARTH GROUND
LADDER CABLE TRAY
BRANCH CIRCUIT HOMERUN. LINES INDICATE NUMBER OF
CIRCUITS, NEUTRAL, AND SWITCH LEG CONDUCTORS.
ONE SEPARATE GREEN GROUNDING CONDUCTOR SHALL BE
PROVIDED FOR EACH HOMERUN; NOT SHOWN
PULL BOX
WIREWAY
RIGID CONDUIT LINE = RC
SUBSTATION
BUSWAY
FLOOR OUTLET, DATA COMMUNICATION
OUTLET, DATA COMMUNICATION
PUSH BUTTON
DISTRIBUTION PANEL
LIGHTING PANEL
PANELBOARD CABINET, FLUSH MOUNTED
PANELBOARD CABINET, SURFACE MOUNTED
RECEPTACLE, CLOCK HANGER
RECEPTACLE, DUPLEX
RECEPTACLE, DUPLEX ON EMERGENCY POWER
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT INTERRUPTER
RECEPTACLE, QUADRAPLEX
RECEPTACLE, SINGLE
RECEPTACLE, SINGLE WITH SWITCH
RECEPTACLE, SPECIAL PURPOSE
A = 120V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 5-20R.
B = 208V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R.
C = 120V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 5-30R.
D = 208V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R.
E = 208V, 60A, 1 PHASE, 3-POLE, 4W, NEMA
14-60R.
F = 208V, 30A, 3 PHASE, 3-POLE 4W, NEMA
15-30R.
G = 208V, 50A, 3 PHASE, 3 POLE, 4W, NEMA
15-30R.
H = 208V, 60A, 3 PHASE, 3 POLE, 4W, NEMA
15-60R.
RECEPTACLE, SWITCHED DUPLEX
DIRECT BURIAL CABLE = DB
POWER DUCT = P
HI VOLTAGE SWITCH ON CONCRETE PAD
LOW VOLTAGE SWITCH ON CONCRETE PAD
DUAL POWER AND TELECOMMUNICATIONS MANHOLE
DROP CORD, SINGLE CONVENIENCE OUTLET, 3-WIRE, GROUNDING
TYPE, 20A, W/#12 CONDUCTORS IN FLEXIBLE CORD (CENTER LINE
OF OUTLET: 6'-6" [1981mm] AFF. MINIMUM).
ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" [610mm] CENTERS OR AS DESIGNATED ON DRAWINGS), MTD 3'-6" [1067mm] AFF
OR AS INDICATED.
3-GANG COMPARTMENT BOX IN FLOOR FOR TELEPHONE, DATA & RECEPTACLE.
RELAY; LETTER INDICATES RELAY TYPE
50 = INSTANTANEOUS OVERCURRENT OR RATE-OF-
RISE
51 = AC-TIME OVERCURRENT
67 = AC-DIRECTIONAL OVERCURRENT
86 = LOCK OUT
SWITCH
F = FUSED SWITCH
L = LOCK
M = MANUAL MOTOR STARTING
MP= MOTOR SNAP WITH PILOT LIGHT
(THERMAL TYPE)
WP=WEATHER PROOF
K = KEY OPERATED
LM=LOW VOLTAGE MASTER
MC=MOMENTARY CONTACT
P = WITH PILOT LIGHT
RC=REMOTE CONTROL
X = EXPLOSION PROOF
VARIABLE FREQUENCY DRIVE
SWITCH, CEILING MOUNTED PULL
SWITCH (# SUBSCRIPT AS INDICATED BELOW):
BLANK = SINGLE POLE 2 = DOUBLE POLE
3 = THREE-WAY 4 = FOUR-WAY
D = DIMMER K = KEY OPERATED
LV= LOW VOLTAGE P = WITH PILOT LIGHT
LM= LOW VOLTAGE MASTER RC= REMOTE CONTROL
PB= PUSH BUTTON STATION WP= WEATHER PROOF
T = TIMER OPERATED Mo= OCCUPANCY SENSOR
RECESSED DOWNLIGHT FIXTURE, LETTER INDICATES TYPE.
LIGHT FIXTURE, RECESSED FLUORESCENT, 610x1220mm (2'x4');
LETTER INDICATES TYPE.
LIGHT FIXTURE, RECESSED FLUORESCENT, 305x1220mm (1'x4');
LETTER INDICATES TYPE.
LIGHT FIXTURE, SURFACE MOUNTED FLUORESCENT, 610x1220mm (2'x4');
LETTER INDICATES TYPE.
LIGHT FIXTURE, SURFACE MOUNTED FLUORESCENT, 305x1220mm (1'x4'); LETTER INDICATES TYPE.
LIGHT FIXTURE, FLUORESCENT EMERGENCY;
LETTER INDICATES TYPE.
LIGHTING, ONE HEAD EMERGENCY BATTERY POWER
LIGHTING, TWO HEAD EMERGENCY BATTERY POWER
LIGHTING, THREE HEAD EMERGENCY BATTERY POWER
EXIT SIGN, WALL MOUNTED WITH DIRECTIONAL ARROWS AND FACES AS SHOWN
EXIT SIGN, CEILING MOUNTED WITH DIRECTIONAL ARROWS AND FACES AS SHOWN
LIGHT FIXTURE, RECESSED FLUORESCENT, 610x610mm (2'x2'); LETTER INDICATES TYPE.
LIGHT FIXTURE, SURFACE MOUNTED FLUORESCENT, 2'x2' [610x610mm]; LETTER INDICATES TYPE.
LIGHT TRACK WITH HEADS AS SHOWN
LIGHT FIXTURE, STRIP/INDUSTRIAL FLUORESCENT; LETTER INDICATES TYPE.
LIGHT FIXTURE, WALL MOUNTED
LIGHT FIXTURE, BOLLARD
LIGHT FIXTURE, DIRECTIONAL
LIGHT FIXTURE, WALL MOUNTED
OUTLET, COMBINATION TELEPHONE/DATA COMMUNICATION
CABLE TELEVISION LINE = CATV
CLOSED CIRCUIT TELEVISION LINE = CCTV. MINIMUM 1" [25mm] CONDUIT
FIBEROPTICS LINE = FO
FLOOR RECEPTACLE, TELEPHONE
OUTLET TELEPHONE; LETTER INDICATES AS FOLLOWS:
J = JACK TYPE W = WALL TYPE
OUTLET DATA ONLY
TELEPHONE LINE = T
INTERCOM LINE = I. MINIMUM 3/4" [19mm] CONDUIT.
SOUND LINE = S
NURSE CALL LINE = NC. MINIMUM 3/4" [19mm] CONDUIT.
OUTLET; LETTER INDICATES AS FOLLOWS:
A = AUDIO V = VIDEO I = INTERCOM
RADIO CONDUIT RUN, MINIMUM 3/4" [19mm] CONDUIT.
RADIO CHANNEL SELECTOR FACILITIES, MTD. 4'-6" [1372mm] AFF UNLESS OTHERWISE NOTED.
SPEAKER PROGRAM SELECTOR SWITCH & VOLUME CONTROL MTD.
4'-6" [1372mm] AFF UNLESS OTHERWISE NOTED.
OUTLET, TELEVISION
BLANK = 4 11/16" [119mm] MASTER ANTENNA OUTLET BOX W/BLANK COVER, MTD. 18"
[457mm] AFF UNLESS OTHERWISE NOTED.
C = CAMERA (CCTV SYSTEM), MTD. 18" [457mm] AFF
M = MONITOR (CTTV SYSTEM).
NURSE'S CALL MASTER STATION MTD ON NURSE'S COUNTER TOP UNLESS OTHERWISE NOTED.
NURSE CALL TERMINAL CABINET.
NURSE CALL STATION.
2 = DUPLICATE FACILITIES FOR TWO BEDS (SEPERATE INDICATORS AT MASTER STATION) MTD 5'-0" [1524mm] AFF UNLESS OTHERWISE NOTED.
D = DUTY STATION. MTD 5'-0" [1524mm] AFF UNLESS NOTED OTHERWISE.
E = MTD. 6'-0" [1829mm] AFF FOR SHOWER LOCATION, MTD 4'-6" [1372mm] AFF FOR TUB LOCATION, & MTD 3'-0" [914mm] AFF FOR TOILET LOCATION.
P = PSYCHIATRIC CORRIDOR STATION WITH KEY SWITCH.
S = AUDIO VISUAL MALL STATION (STAFF) MTD 5'-0" [1524mm] AFF UNLESS OTHERWISE NOTED.
U = UTILITY CALL STATION, MTD 5'-0" [1524mm] AFF UNLESS OTHERWISE NOTED.
NURSE CALL STATION.
2 = NURSE'S CALL DOME LIGHT (SUFFIX INDICATED No OF LAMP) MTD 6" [152mm] ABOVE DOOR.
D = CORRIDOR DOME LIGHT.
I = AUXILIARY INTERSECTIONAL DOME LIGHT.
TELEPHONE TERMINAL CABINET
TELEPHONE BACKBOARD (WALL MOUNTED)
3-POLE TWIST-LOCK RECEPTACLE FOR MICROPHONE, MTD. 4'-6" [1372mm] AFF.
REMOTE DICTATING OUTLET MTD 1'-6" [457mm] AFF. UNLESS OTHERWISE NOTED.
INTERCOM STATION (REFER TO SPECS. FOR FUNCTIONAL OPERATION OF INSTRUMENT & TYPE REQUIRED).
INTERCOM STAFF STATION.
TELECOMMUNICATIONS MANHOLE
G
R
PB
S
HVS
LVS
P T
DP#
LP
R
TC
R
R
NC
S
I
T
FO
CCTV
CATV
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY
SPRINKLED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDSTAMPFIRE PROTECTION CONSULTANT
321 4 5 6 7 8 9 10
All Concepts, ideas, design elements, plans, and details as shown on this document are the sole property of Viridian Architectural
Design, Inc. and shall not be used for any purpose without prior expressed written consent. The Owner shall be permitted to retain copies for information and reference.
2020 E. Washington Boulevard Suite 200 Fort Wayne, Indiana 46803
PH: 260.424.4830
www.viridian-design.net
FINAL BID
DOCUMENTS
OF03 53
1520 Main Street Indianapolis, Indiana 46224
PH: 317.486.5188
www.fpc-consultants.com
Z:
\V iri di an \P ro je ct s\
\0
D R
AW
IN
G S\
R
EV
IT
\L
O C
AL
F
IL
ES
\6
A4 -2
0-
7_ B1
_C
EN
TR
AL
_R
_a m or ta ki s.
rv t
6/
/2
:1 8:
A
M
GI003
ELECTRICAL ABBREVIATIONS &
SYMBOLS
REPLACE FIRE ALARM SYSTEM
FORT WAYNE VAMC
610A4-20-107
BUILDING 1
06/06/2022 TWT JAH
S
X
HT
S-S
SD
S
SR
FIRE ALARM SYMBOLS:
F
F
F
F
F
F
K
FS
TS
PS
H/LPS
PIV
DEC
F
RL
DH
FACC
FACP
FAAP
FPCP
RLCP
FAPS
ERLR
ERCR
EPSR
EGCP
UPS
BAT
CHR
CRT
FAP
TC
FB
DC
FC
F/SD
SR
EP
EC
KS
CR
MR
ML
RT
X
THE FOLLOWING DEVICE NOTATIONS, LOCATED AT THE LOWER LEFT
CORNER OF THE SYMBOL, APPLY TO ALL DEVICES AND / OR EQUIPMENT
LISTED ABOVE:
N - NEW
E - EXISTING TO BE REUSED
R - EXISTING TO BE REPLACED
D - EXISTING TO BE REMOVED (DELETED)
F - FUTURE DEVICE TO BE INSTALLED UNDER DIFFERENT PROJECT
EXAMPLES:
MANUAL FIRE ALARM STATION - EXISTING TO BE REPLACEDF
R
F N
DH
D
FS
F
SMOKE DETECTOR - NEW
DOOR HOLDER - EXISTING TO BE REMOVED
FLOW SWITCH - FUTURE
MANUAL FIRE ALARM STATION
RESIDENTIAL TYPE SMOKE DETECTOR
SMOKE DETECTOR
IN-DUCT SMOKE DETECTOR
SOUNDER SMOKE DETECTOR
HEAT DETECTOR
KITCHEN HOOD FIRE SUPPRESSION SYSTEM
FLOW SWITCH
VALVE SUPERVISORY SWITCH
PRESSURE SWITCH
HIGH/LOW AIR PRESSURE SUPERVISORY
POST INDICATOR VALVE
DELAYED EGRESS CONTROL
STROBE
REMOTE INDICATOR LAMP
DOOR HOLDER
FIRE ALARM COMMAND CONSOLE
FIRE ALARM CONTROL PANEL
FIRE ALARM ANNUNCIATOR PANEL
FIRE PUMP CONTROL PANEL
REMOTELY LOCATED CONTROL PANEL
FIRE ALARM POWER SUPPLY
ELEVATOR RECALL LIGHT RELAYS
ELEVATOR RECALL CONTROL RELAYS
ELEVATOR POWER SHUTDOWN RELAYS
EMERGENCY GENERATOR CONTROL PANEL
UNINTERRUPTIBLE POWER SUPPLY
FIRE ALARM BATTERIES
FIRE ALARM BATTERIES CHARGER
CRT WITH KEYBOARD - OPERATOR'S TERMINAL
FIRE ALARM PRINTER
FIRE ALARM TERMINAL CABINET
FIBER OPTICS BREAKOUT BOX
DAMPER CONTROL
FAN CONTROL
COMBINATION FIRE AND SMOKE DAMPER
FIRE SHUTTER RELAY
ELECTRICAL PANEL
ELEVATOR CONTROLLER
KEY TEST SWITCH
CONTROL MODULE RELAY
MONITORING MODULE RELAY
MAGNETIC DOOR LOCK RELEASE
REMOTE TEST
TEMPORARY FIRE ALARM STATION
NAC NOTIFICATION APPLIANCE CIRCUIT
JUNCTION BOXJ
FS
E
FLOW SWITCH - EXISTING TO BE REUSED.
SP-HL
SP-X
SP-HX
H-X
S
SP-H
SP-DC
SP-C
SP-B
SP
SP
SPEAKER SYMBOLS:
F
P
P
P
P
P
THE FOLLOWING DEVICE NOTATIONS, LOCATED AT THE LOWER LEFT
CORNER OF THE SYMBOL, APPLY TO ALL DEVICES AND / OR EQUIPMENT
LISTED ABOVE:
N - NEW
E - EXISTING TO BE REUSED
R - EXISTING TO BE REPLACED
D - EXISTING TO BE REMOVED (DELETED)
F - FUTURE DEVICE TO BE INSTALLED UNDER DIFFERENT PROJECT
EXAMPLES:
MANUAL FIRE ALARM STATION - EXISTING TO BE REPLACEDF
R
F N
DH
D
FS
F
SMOKE DETECTOR - NEW
DOOR HOLDER - EXISTING TO BE REMOVED
FLOW SWITCH - FUTURE
SPEAKER (1/2 WATT UNLESS NOTED)
PAGING SPEAKER
SPEAKER - BOX TYPE
SPEAKER - CAN TYPE
SPEAKER - DOUBLE CAN
SPEAKER - HORN TYPE
F
F
F
HORN - STROBE
OLD SPEAKER STROBE
SPEAKER - STROBE
F FIRE ALARM SPEAKER LIGHT COMBINATION
PACP PA CONTROL PANEL
HC
HC
HC
HC
HC
HC
HC
HC
HC
CB
CB
D
CB
D
D
D
S
S
D
D
D
C
SP
TF
W
LP
PIV
PIV PIV
C
G
LP
LP
LP
C
LP
EBC
W
W
CB
CB
CB
CB
D
CB
W
W
LP
LP
LP
LP
LP
LP
LP
W
C
EB
C C
CB
D
CB
S
CB
LP
LP
LP
FLAG POLE
YL
YL
YL
CO
B
B
B
B
LP
LP
EB
LP
LP
LP
LP
LP
YL
YL
YL
YL YL
LP
FLAG POLE
FLAG POLE
FLAG POLE
FLAG POLE
FLAG POLE
LP
LP
LP
LP
LPC
PED
LP
LP
LP
LP
LP
LP
LP
LP
LP
LP
LP
CO
CO
CO
W
LP
W
LP
W
PIV
PIV
D
CB
CB
S
S
D
CB
CB
LP
LP
W
CS
PIV
W
W
W
EB
EB
LP
LP
LP
LP
LP
LP
LP
LP
CO
C
E
B B B B B B B B B B
BBBBBB
CB
CB
CB
S
CB
CB
CB
CB
CB
CB
CB
CB
B B B B
W
W
S
D
EB
C
W
C C
LP
D
CB
CB
CB
CB
CB
D
LP
W
CB
C E
CB
LP
EB
G
EB
C
PED
CB
EB
PIV
PIV
PIV
D CB
D
D
YD
C
PED
C
PED
C
PED
C
PED
C
PED
C C
EB
EB
AC
EB
LP
LP
LP
EB EB
LP
AC
EB
CB
C C
C
CB
EB
M
CB
CB
CB
G
CS
C
EBEB
LP
M
W
CS
LP
LP
LP
LP
EB
LP
D
CB
CB
D
LP
LP
CO CO
W CO CO
CO
CO
YD
YD
YD
YD
YD
YD
YD
YD
YDYD
YD YD
C
YD
YD
S
LP
LP
LP
LP
S
CB
W
CS
C
LP
LP
LP
LP
CB CB
CB
CO
LP
EB
EB
E
PIV
CB
CB
S
D
CB
CB
CB
D
C
CO
G
C
EB
EB
LP
LP
C E
PIV
C
E
C
M
M
M
E M
M
M
M
MCO
M
MM M
CO
M
CO
EBEB EBEBEBEBEBEB
BB B
W
CS
EB
EBEB
EB
EBEB
EB
M
S
LP
B B
B B
B
E
B
CB
CB
CB
S
S
LP
LP
EBEB
C
EB
G
C
LP
CB
EB
C C
EBEB
CO
W
E
E
EB
EB
EB
B B
B B
B B B
B B
B B
B B
B
LP
LP
LPLP
E E
W
W
LP
LP
IP
IP
IP
IP
IP
IP
IP
IPIP
IP
IP
W
EB
C
E
EB
E E
LP
LP
E
E
LP
EB
EB
CO
CB
CB
EB
EB
CB
CB
CB
M
EB
W
IP
CB
S
S
EB
CB
D
CB
LP
LP
CB
D
CB
CB
D
S
S
S
S
S
S
S
S
S
S
S
S
D
D
CB
CB
CB
D
D
CB
CB
CB
CB
CB
D
D
D
D
D
D
D
CB
CB
CB
CB
CB
D
CB
CB
CB
CB
CB
D
CB
D
CB
CB
CB
CB
D
D
D
CB
CB
CB
CB
D
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
DCB
D
CB
D
D
S
CB
CB
CB
CB
CB
CB
CB
CB
VLTE
VLTE
312274
313522
MH
762.977 39074
MH
MH
MH 42IN DIA
MH
MH 42IN DIA
MH
MH
MH 42IN DIAMH 42IN DIA
MH 42IN DIAMH MH 16IN DIA
MH INTERCEPTOR
766.958
767.003
767.021
766.839
766.780
766.773
766.630
766.818767.040
767.137767.150 767.274
767.293
311373
311374
311375
311377
311378
311379
311380
311381311383
311384311385 311386
311406
OHC B
OHC E
OHC B
OHC E LN B EXPOSED COMM LINE NO ELEV
304879
304882
313299
313310
BLIND TAP
PER BLOODHOUND
OXYGEN
LINE
GTE-NORTH
UTILITY ESMT. PER
DOC.#92-061268GTE-NORTH
UTILITY ESMT. PER
DOC.#92-061268
G
TE
-N O
R
TH
U
TI
LI
TY
E
SM
T.
P
ER
D
O C
-0
G
TE
-N O
R
TH
U
TI
LI
TY
E
SM
T.
P
ER
D
O C
-0
CLEAN-OUT
INV.:766.71'
RIM:760.9±
RIM:761.4±
TRENCH DRAIN
10"VCP INV.:757.37
"R
C P
"R
C P
4"PVC
EXPOSED
COMM. LINE
24'LID (WIRES INSIDE)
RIM:766.96
18"LID
RIM:767.00
18"LID (PUMP)
RIM:766.84
42"LID (VALVES)
RIM:766.78
18"LID
RIM:766.77
24"LID
RIM:766.63
42"LID
RIM:767.02
42"PLASTIC LID
RIM:767.04
OIL INTERCEPTOR
MANHOLE
RIM:767.29
18"LID
RIM:767.15
42"LID
RIM:767.14
14"PLASTIC LID
RIM:767.27
42"PLASTIC LID
RIM:766.82
GTE-NORTH
UTILITY ESMT. PER
DOC.#92-061268
STEAMLINE
STEAMLINE
STEAMLINE
STR.#2
RIM:752.15
STR.#3
RIM:752.15
STR.#5
RIM:751.85
TRENCH
DRAIN
RIM:764.4±
I.E.:758.28'
STR.#1
RIM:752.62
STR.#4
RIM:752.49
STR.#28
RIM:753.21
STR.#107
RIM:766.53
STR.#108
RIM:759.00
STR.#30
RIM:759.20
STR.#29
RIM:753.39
STR.#26
RIM:763.42
STR.#27
RIM:765.11
STR.#31
RIM:758.49
STR.#32
RIM:761.29
STR.#40
RIM:762.26
STR.#39
RIM:762.36
STR.#41
RIM:762.73
STR.#23
RIM:761.53
STR.#24
RIM:767.31
STR.#20
RIM:767.90
STR.#25
RIM:770.18
STR.#109
RIM:766.58
STR.#22
RIM:767.38
STR.#114
RIM:769.76
STR.#18
RIM:770.73
STR.#17
RIM:771.37
STR.#110
RIM:767.13
STR.#14
RIM:769.17
STR.#21
RIM:769.60
STR.#12
RIM:768.43
STR.#13
RIM:768.56
STR.#51
RIM:769.96
STR.#54
RIM:769.80
STR.#57
RIM:770.86
STR.#59
RIM:770.33
STR.#62
RIM:769.64
STR.#63
RIM:769.59
STR.#53
RIM:770.08
STR.#52
RIM:772.26
STR.#58
RIM:771.99
STR.#56
RIM:771.16
STR.#55
RIM:769.79
STR.#112
RIM:771.57
I.E.:772.86'
STR.#37
RIM:772.09
STR.#34
RIM:770.28
STR.#33
RIM:770.33
STR.#35
RIM:770.54
STR.#10
RIM:770.64
STR.#80
RIM:763.76
STR.#11
RIM:771.58
STR.#111
RIM:769.95
STR.#50
RIM:772.47
6"INCH DRAIN
RIM:768.67
STR.#38
RIM:773.86
12"RCP - I.E.:770.34'
STR.#42
RIM:762.60
STR.#78
RIM:768.27'
STR.#77
RIM:761.63'
STR.#43
RIM:763.68
STR.#76
RIM:762.90
STR.#44
RIM:779.33
STR.#46
RIM:777.65
STR.#47
RIM:777.20
STR.#48
RIM:777.09
STR.#87
RIM:758.52
STR.#113
RIM:775.30
STR.#49
RIM:776.93
STR.#115
RIM:785.46
STR.#16
RIM:768.95
STR.#64
RIM:769.84
STR.#66
RIM:769.84
ROOF DRAIN
RIM:772.61RIM:772.65
RIM:772.18
STR.#68
RIM:766.40
STR.#71
RIM:759.22
STR.#74
RIM:755.07
STR.#73
RIM:755.02
STR.#72
RIM:755.56
STR.#75
RIM:757.51
STR.#101
RIM:769.18
TRENCH DRAIN
10"VCP INV.:757.37
RIM:760.9±
RIM:761.4±
STR.#102
RIM:763.76
STR.#70
RIM:762.98
STR.#81
RIM:762.58
STR.#67
RIM:769.34
STR.#60
RIM:769.29
STR.#61
RIM:769.11
STR.#103
RIM:765.28
STR.#104
RIM:768.83
STR.#85
RIM:759.06
STR.#86
RIM:762.01
STR.#84
RIM:758.42
STR.#83
RIM:762.74
STR.#82
RIM:762.65
STR.#9
RIM:760.18
STR.#8
RIM:760.62
12"PVC - INV.:763.13
STR.#6
RIM:754.29
RIM:772.26
RIM:772.60
RIM:772.26
RIM:772.26
RIM:772.57
RIM:772.33
RIM:772.32
RIM:772.31
RIM:772.61
RIM:772.30
STR.#7
RIM:753.91
RIM:765.0±
STR.#69
RIM:757.06
STR.#106
RIM:767.64
STR.#105
RIM:766.73
6"PVC PIPE ON
SIDE OF WALL
INV.:768.24
STR.#65
RIM:769.10
STR.#19
RIM:771.60
STR.#15
RIM:769.30
STR.#36
RIM:771.99
WATER
PUMP
HOUSE
34"WATER
MANHOLE
WATER
PUMP
HOUSE
WATER
VAULT
WATER
VAULT
34"WATER MANHOLE
RIM:766.73'
OLD
WATER
LINE
PRIVATE HYDRANT
TRENCH
DRAIN
RIM:764.4±
I.E.:758.28'
RIM:765.0±
ROOF DRAIN
RIM:772.61
RIM:772.65
RIM:772.18
RIM:772.26
RIM:772.60
RIM:772.26
RIM:772.26
RIM:772.57
RIM:772.33
RIM:772.32
RIM:772.31
RIM:772.61
RIM:772.30
STM. STR.#5
BEEHIVE
Rim. Elev.=751.85 Inv. 749.80, 12" HDPE~S.
STM. STR.#4
MANHOLE
Rim. Elev.=752.49 Inv. 749.64, 12" HDPE~N.
Inv. 745.79, 12" HDPE~SW.
STM. STR.#3
CURB CAST INLET
Rim. Elev.=752.15 Inv. 747.85, 12" HDPE~E.
STM. STR.#2
CURB CAST INLET
Rim. Elev.=752.15 Inv. 747.50, 12" HDPE~W.
Inv. 747.50, 12" HDPE~S. STM. STR.#1
MANHOLE
Rim. Elev.=752.62 Inv. 747.37, 12" HDPE~N.
Inv. 748.87, 12" HDPE~S.
Inv. 745.17, 24" RCP~W.
Inv. 745.17, 24" RCP~E.
STM. STR.#8
MANHOLE
Rim. Elev.=760.62 Inv. 755.37, 15" RCP~W.
Inv. 756.22, 12" RCP~N.
Inv. 756.32, 12" RCP~S.
Inv. 755.77, 15" RCP~E.
STM. STR.#6
MANHOLE
Rim. Elev.=754.29 Inv. 748.49, 15" RCP~E.
Inv. 748.19, 24" RCP~W.
Inv. 749.59, 12" RCP~S.
Inv. 749.64, 12" RCP~N.
STM. STR.#7
CURB CAST INLET
Rim. Elev.=753.91 Inv. 750.11, 12" RCP~S.
STM. STR.#9
CURB CAST INLET
Rim. Elev.=760.18 Inv. 756.68, 12" RCP~S.
STM. STR.#10
ROUND INLET
Rim. Elev.=770.64 Inv. 765.99, 10" D.I.~E.
Inv. 766.24, 4" PVC~NW.
STM. STR.#11
MANHOLE
Rim. Elev.=771.58 Inv. 764.53, 12" RCP~S.
Inv. 764.68, 10" D.I.~W.
STM. STR.#17
MANHOLE
Rim. Elev.=771.37 Inv. 764.47, 12" RCP~N.
Inv. 763.72, 8" PVC~NE.
Inv. 761.32, 12" D.I.~N.
Inv. 747.57, 24" RCP~E.
Inv. 762.27, 8" PVC~S.
Inv. 747.27, 24" RCP~W.
STM. STR.#12
ROUND INLET
Rim. Elev.=768.43 Inv. 764.53, 8" PVC~E.
STM. STR.#13
ROUND INLET
Rim. Elev.=768.56 Inv. 763.26, 8" PVC~W.
Inv. 763.26, 10" PVC~SE.
STM. STR.#14
CURB CAST INLET
Rim. Elev.=769.17 Inv. 765.22, 12" RCP~E.
STM. STR.#15
CURB CAST INLET
Rim. Elev.=769.30 Inv. 765.10, 12" RCP~W.
Inv. 764.90, 12" RCP~S.
STM. STR.#16
ROUND INLET
Rim. Elev.=768.95 Inv. 764.95, 8" PVC~SW.
STM. STR.#18
MANHOLE
Rim. Elev.=770.73 Inv. 748.08, 24" RCP~E.
Inv. 762.63, 12" RCP~W.
Inv. 748.08, 24" RCP~SW.
Inv. 761.68, 10" VCP~S.
Inv. 764.38, 12" RCP~SE.
STM. STR.#22
MANHOLE
(NE. 24"RCP HAS
FLOW CONTROL GATE)
Rim. Elev.=767.38 Inv. 747.33, 24" RCP~NE.
Inv. 756.38, 15" RCP~NW.
Inv. 747.33, 24" RCP~SW.
Inv. 763.63, 12" RCP~SE.
Inv. 751.38, 12" RCP~SE.
Inv. 760.08, 10" D.I.~E.
STM. STR.#26
MANHOLE
Rim. Elev.=763.42
SW. PIPE CAPPED
W/CONCRETE
Inv. 746.57, 24" RCP~NE.
Inv. 746.42, 24" RCP~S.
Inv. 757.42, 10" VCP~E.
STM. STR.#27
MANHOLE
Rim. Elev.=765.11 Inv. 746.36, 24" RCP~N.
Inv. 746.16, 24" RCP~S.
Inv. 750.76, 10" PIPE~E.
STM. STR.#28
MANHOLE
Rim. Elev.=753.21 Inv. 745.51, 24" RCP~N.
Inv. 745.51, 24" RCP~SW.STM. STR.#29
MANHOLE
Rim. Elev.=753.39
Inv. 745.49, 24" RCP~NE.
Inv. 745.39, 24" RCP~SW.
STM. STR.#19
MANHOLE
Rim. Elev.=771.60 Inv. 765.15, 12" RCP~NW.
Inv. 765.30, 12" D.I.~S.
STM. STR.#20
CURB CAST INLET
Rim. Elev.=767.91 Inv. 764.61, 12" RCP~SE.
STM. STR.#21
CURB CAST INLET
Rim. Elev.=769.60 Inv. 764.30, 12" RCP~NW.
Inv. 764.05, 12" RCP~E.
STM. STR.#23
CURB CAST INLET
Rim. Elev.=761.53 Inv. 757.08, 15" RCP~SE.
STM. STR.#24
CURB CAST INLET
Rim. Elev.=767.31 Inv. 764.36, 12" RCP~NW.
STM. STR.#25
ROUND INLET
Rim. Elev.=770.18 Inv. 764.28, 10" VCP~W.
(90% BLOCKED BY
SOIL)
STM. STR.#30
MANHOLE
Rim. Elev.=759.20 Inv. 746.20, 24" RCP~W.
Inv. 746.05, 24" RCP~NE.
STM. STR.#31
CURB CAST INLET
Rim. Elev.=758.49 Inv. 756.25, 24" RCP~S.
STM. STR.#32
CURB CAST INLET
Rim. Elev.=761.29
(W. PIPE BENT DOWN
@90°
MEAS. TAKEN AT BOTTOM)
Inv. 757.69, 12" VCP~W.
Inv. 758.19, 8" VCP~N.
STM. STR.#33
CURB CAST INLET
Rim. Elev.=770.33 Inv. 766.03, 8" VCP~E.
Inv. 766.33, 6" VCP~W.
Inv. 766.43, 12" STEEL~S.
STM. STR.#34
CURB CAST INLET
Rim. Elev.=770.28 Inv. 766.08, 8" VCP~W.
Inv. 765.88, 10" VC~E.
STM. STR.#35
ROUND INLET
Rim. Elev.=770.54 Inv. 766.29, 10" VC~W.
Inv. 765.24, 15" RCP~NE.
Inv. 762.14, 12" VCP~NW.
STM. STR.#38
MANHOLE
Rim. Elev.=773.86 Inv. 760.51, 12" VCP~SE.
Inv. 760.51, 12" VCP~W.
STM. STR.#39
ROUND INLET
Rim. Elev.=762.36 Inv. 756.51, 12" VCP~E.
Inv. 758.46, 12" RCP~NE.
Inv. 756.51, 12" VCP~W.
STM. STR.#41
MANHOLE
Rim. Elev.=762.73 Inv. 756.38, 12" VCP~E.
Inv. 755.83, 12" VCP~W.
STM. STR.#36
CURB CAST INLET
Rim. Elev.=771.99 Inv. 768.54, 12" RCP~SW.
STM. STR.#37
CURB CAST INLET
Rim. Elev.=772.09 Inv. 768.24, 12" RCP~NE.
Inv. 768.24, 15" RCP~SW.
STM. STR.#40
CURB CAST INLET
Rim. Elev.=762.26 Inv. 758.71, 12" RCP~SW.
STM. STR.#42
BEEHIVE
Rim. Elev.=762.60 Inv. 761.10, 12" PVC~W.
STM. STR.#43
MANHOLE
Rim. Elev.=763.68 Inv. 760.68, 12" PVC~E.
Inv. 757.38, 12" RCP~NW.
STM. STR.#44
MANHOLE
Rim. Elev.=779.33 Inv. 771.58, 12" RCP~W.
Inv. 771.73, 12" RCP~N.
STM. STR.#45
MANHOLE
Rim. Elev.=778.26 Inv. 770.71, 12" RCP~E.
Inv. 770.61, 12" RCP~W.
Inv. 770.66, 6" PVC~N.
STM. STR.#46
ROUND INLET
Rim. Elev.=777.65 Inv. 773.65, 12" RCP~E.
STM. STR.#47
ROUND INLET
Rim. Elev.=777.20 Inv. 773.25, 12" RCP~W.
Inv. 773.20, 12" PVC~E.
STM. STR.#48
ROUND INLET
Rim. Elev.=777.09 Inv. 772.44, 12" PVC~W.
Inv. 772.44, 15" RCP~E. STM. STR.#49
ROUND INLET
Rim. Elev.=776.93 Inv. 771.13, 15" RCP~W.
Inv. 765.23, 12" RCP~N.
Inv. 765.13, 24" RCP~S.
Inv. 772.63, 10" PVC~NE.
Inv. 772.63, 8" PVC~SE.
STM. STR.#50
MANHOLE
(FULL OF SEDIMENT)
Rim. Elev.=772.47 Inv. 762.17, 8" VCP~S.
STM. STR.#51
ROUND INLET
Rim. Elev.=769.96 Inv. 767.26, 4" PVC~NE.
Inv. 767.26, 4" PVC~NW.
STM. STR.#52
BEEHIVE
Rim. Elev.=772.26 Inv. 769.01, 6" HDPE~S.
Inv. 769.06, 6" HDPE~N.
STM. STR.#53
BEEHIVE
Rim. Elev.=770.08 Inv. 767.63, 6" HDPE~N.
Inv. 767.63, 6" HDPE~E.
Inv. 767.58, 6" HDPE~SE.
STM. STR.#54
ROUND INLET
Rim. Elev.=769.80 Inv. 767.55, 6" HDPE~NW.
Inv. 767.45, 6" PVC~E.
STM. STR.#55
ROUND INLET
Rim. Elev.=769.79 Inv. 766.44, 6" PVC~W.
Inv. 766.29, 6" HDPE Pipe~N.
Inv. 766.39, 6" PVC~S.
Inv. 766.44, 6" PVC~E.
STM. STR.#57
ROUND INLET
Rim. Elev.=770.86 Inv. 768.36, 6" PVC~W.
Inv. 768.41, 6" PVC~S.
Inv. 768.41, 6" HDPE Pipe~N.
STM. STR.#58
BEEHIVE
Rim. Elev.=771.99 Inv. 769.19, 6" HDPE Pipe~S.
Inv. 769.19, 6"…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .