Attachment C Device List.pdf
PDF 919 KB Posted
- Attached to
- H342--Fire Systems Inspections and Maintenance Federal contract opportunity
- Solicitation number
- 36C26323Q0807
About this file
This document contains the results of an inspection of the fire alarm system in Building 5 of the Sioux Falls VA Medical Center.
The inspection reviewed the control panel, annunciators, amplifiers, notification appliance circuits, smoke detectors, heat detectors, duct detectors, manual pull stations, waterflow switches, tamper switches, audible and visual notification devices, door holders, and releasing devices. Key details include the manufacturer and models of the control panel and various components, their locations throughout the building, and the results of testing each component to verify they are in good working condition. The inspection was conducted in accordance with NFPA 72 standards on a semi-annual basis.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C26323Q0807_2.docx | DOCX document | |
| Attachment A- Hospice Cottage Drawing.pdf | ||
| Attachment B- Fire Damper Master List.pdf | ||
| RFQ 36C26323Q0807.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Inspection: Visual Inspection Manufacturer: Notifier
Frequency: Semi-Annual Model Number: IFC2-640 (IFC-3030) Date:
Code REF: NFPA 72 Table 14.3.1 Location: 037-1 W/O#
NODE # 8 Disconnecting Means Location: RM 001B-1 Disconnecting Means: Panel EM, Breaker 15
Line Item #
Loop/ Node#
Equip.
Address
Equipment Model # Description/Location
Location
OK / CA
Condition
OK / CA
1 8 IFC2-640 Fire Alarm Control Panel/Basement Room 037-1
2 JNCA Remote Annunciator/ 1st Floor Corridor 100 By Elevator
3 9 1 DAA2-5070 Amp Panel #1/Basement Room 037 In FACP Enclosure
4 9 2 DAA2-5070 Amp Panel #2/Basement Room 037 In Amp Cabinet #1
5 2 50 ACPS-610PCA NAC Panel/Basement Room 037 Inside FA Cabinet
6 9 3 DAA2-5070 Amp #3/BSMT RM 037 In Amp Cabinet #1
7 n/a n/a E/Clips Transient Suppressors/Basement Room 037
8 1 52 FCPS-24FSPCA 2nd Floor NAC #1 BLD 1 Tower/Room 240
9 1 53 FCPS-24FSPCA 2nd Floor NAC #2 BLD 1 Tower/Room 240
Fire Alarm System Control Panel, Annunciators, & Other (March) Location: SFVAMC Building #1
Address: 2501 W. 22nd St.
City/State/Zip: SF, SD 57105
Contact: Dave Dirks Inspected By: Adam Thompson
Phone: 605-336-3230 ext 6038 CA = Corrective Action Phone: 323-8627
Comments note: JNCA2 Global Display replaced by JCI March 2018
Code REF: NFPA 72 Table 14.3.1 Location: 037-1 W/O#
Disconnecting Means Location: RM 001B-1 Disconnecting Means: Panel EM, Breaker 15
Line Item # Loop #
Device Address Device Type Description/Location
Location
OK / CA
Condition
OK / CA
1 1 2 Smoke(Photo) Hall By RM 31 BLDG 1 BSMT
2 1 3 Smoke(Photo) Hall By RM 29 BLDG 1 BSMT
3 1 4 Smoke(Photo) HALL BY RM 28 BLDG 1 BSMT
4 1 5 Smoke(Photo) HALL BY RM 26 BLDG 1 BSMT
5 1 6 Smoke(Photo) HALL BY RM 037 BLDG 1 BSMT
6 1 7 Smoke(Photo) IN ROOM 37 BLDG 1 BSMT
7 1 11 Smoke(Photo) IN ROOM 1 B BLDG 1 BSMT
8 1 12 Smoke(Photo) IN ROOM 1 C BLDG 1 BSMT
9 1 13 Smoke(Photo) HALL BY RM 20 BLDG 1 BSMT
10 1 14 Smoke(Photo) HALL BY ROOM 2 BLDG 1 BSMT
11 1 15 Smoke(Photo) HALL BY ROOM 4 EAST BLDG 1 BSMT
12 1 20 DuctSmoke(P) North Mech Room BLD 1 1ST FL
13 1 22 HEAT (200) HEAT DETECTORS BLDG 1 ATTIC
14 1 26 Smoke(Photo) IN ROOM 143 BLD 1 1ST FL
15 1 27 Smoke(Photo) HALL BY RM 141 BLD 1 1ST FL
16 1 28 Smoke(Photo) IN ROOM 144 BLD 1 1ST FL
17 1 29 Smoke(Photo) HALL BY ROOM 137 BLD 1 1ST FL
18 1 30 Smoke(Photo) HALL BY ROOM 135 BLD 1 1ST FL
19 1 31 Smoke(Photo) HALL BY ROOM 149 BLD 1 1ST FL
20 1 32 Smoke(Photo) CORR 100 BLD 1 1ST FL
21 1 33 Smoke(Photo) HALL BY ROOM 101 BLD 1 1ST FL
22 1 34 Smoke(Photo) HALL BY ROOM 129 BLD 1 1ST FL
23 1 35 Smoke(Photo) B&C ELEV MACHINE RM BLD 1 3RD FL
24 1 36 HEAT B&C ELEV MACHINE RM BLD 1 3RD FL
25 1 38 Smoke(Photo) ELEVATOR C HOISTWAY BLD 1 3RD FL
26 1 39 Smoke(Photo) 3RD FLR B&C ELEV LOB BLD 1 3RD FL
27 1 40 DuctSmoke(P) CORR BY RM 206 BLD1 2ND FL
28 1 41 DuctSmoke(P) CORR BY RM 201 BLD 1 2ND FL
29 1 42 DuctSmoke(P) RM 223A DUCT BLD 1 2ND FL (Supervisory)
30 1 43 DuctSmoke(P) RM 223A DUCT BLD 1 2ND FL (Supervisory)
31 1 44 DuctSmoke(P) ROOM 307B DUCT BLD 1 3RD FL / RT is by RM 307C
32 1 45 DuctSmoke(P) ROOM 307B DUCT BLD 1 3RD FL / RT is by RM 307C
33 1 46 Smoke(Photo) 2ND FLR B&C ELEV LOB BLD 1 2ND FL
34 1 47 DuctSmoke(P) ATTIC BY RM 308 BLD 1 3RD FL / RT is by RM 308
35 1 48 Smoke(Photo) HALL BY ROOM 202 BLD 1 2ND FL
**can't locate duct smoke but remote test is in this location
**Need to update description because this is no longer elevator lobby 10-2022 device is in access panel in Room 308
Fire Alarm System Smokes & Heats (March) Location: SFVAMC Building #1
Address: 2501 W. 22nd St.
City/State/Zip: SF, SD 57105
Contact: Dave Dirks Inspected By: Adam Thompson
Phone: 605-336-3230 ext 6038 CA = Corrective Action Phone: 323-8627
**Need to update description because this is no longer elevator lobby 10-2022
36 1 49 Smoke(Photo) Hall By RM 206 BLD 1 2ND FL
37 1 50 Smoke(Photo) ELEVATOR B HOISTWAY BLD 1 3RD FL
38 1 51 Smoke(Photo) ED SUITE LINK BLD 1 1st FL
39 1 52 Heat ED SUITE RM 124B BLD 1 1st FL
40 1 53 Smoke(Photo) ED SUITE RM 123A W. BLD 1 1st FL
41 1 54 Smoke(Photo) ED SUITE RM 123A E. BLD 1 1st FL
42 1 55 Smoke(Photo) ED SUITE RM 124A BLD 1 1st FL
43 1 56 Smoke(Photo) ED SUITE RM 124A BLD 1 1st FL
44 1 57 DuctSmoke(P) ED SUITE RM 123A AHU BLD 1 1st FL
45 1 58 DuctSmoke(P) ED SUITE RM 124A AHU BLD 1 1st FL
46 1 59 DuctSmoke(P) ATTIC BY RM 308 BLD 1 3RD FL / RT is by RM 308
47 1 60 DuctSmoke(P) ATTIC BY RM 313 BLD 1 3RD FL /RT by mirror in Elev Lobby
48 1 61 Smoke(Photo) HALL BY ROOM 332 BLD1 3RD FL
49 1 62 Smoke(Photo) WAITING AREA BLD1 3RD FL
50 1 63 Smoke(Photo) HALL BY ROOM 303 BLD1 3RD FL
51 1 64 Smoke(Photo) HALL BY ROOM 307D BLD1 3RD FL
52 1 65 Smoke(Photo) WAITING ROOM 312 BLD1 3RD FL
53 1 66 DuctSmoke(P) BCU 1 RETURN RM 237 BLD1 2ND FL
54 1 67 Smoke(Photo) CORR BY MECH 237 BLD1 2ND FL
55 1 68 Smoke(Photo) MH2 RM 236 BLD1 2ND FL
56 1 69 Smoke(Photo) MH2 WAITING BLD1 2ND FL
57 1 70 Smoke(Photo) MH2 RM 235 BLD1 2ND FL
58 1 71 Smoke(Photo) MH2 BY RM 235 BLD1 2ND FL/Sally Port
59 1 72 Smoke(Photo) MH2 CORR. By RM 214 BLD1 2ND FL
60 1 73 Smoke(Photo) MH2 By DINNING RM 216 BLD1 2ND FL
61 1 74 Smoke(Photo) MH2 RM 231 BLD1 2ND FL
62 1 75 Smoke(Photo) MH2 RM 230 BLD1 2ND FL
63 1 76 Smoke(Photo) MH2 By RM 230 BLD1 2ND FL
64 1 77 Smoke(Photo) MH2 RM 217 BLD1 2ND FL
65 1 78 Smoke(Photo) MH2 RM 229 BLD1 2ND FL
66 1 79 Smoke(Photo) MH2 By RM 229 BLD1 2ND FL
67 1 80 Smoke(Photo) MH2 RM 218 BLD1 2ND FL
68 1 81 Smoke(Photo) MH2 RM 228 BLD1 2ND FL
69 1 82 Smoke(Photo) MH2 RM 219 BLD1 2ND FL
70 1 83 Smoke(Photo) MH2 Hall By RM 227 BLD1 2ND FL
71 1 84 DuctSmoke(P) BCU 2 RETURN RM 224 BLD1 2ND FL
72 1 85 DuctSmoke(P) ATTIC BY RM 335 BLD 1 3RD FL / RT across from RM 315
73 1 86 DuctSmoke(P) ATTIC BY RM 323 BLD 1 3RD FL / RT By RM 326
74 1 87 Smoke(Photo) 1ST FLR B&C ELEV LOB BLD 1 1ST FL
75 1 88 Smoke(Photo) BSMT B&C ELEV BLD 1 BSMT
76 1 91 DuctSmoke(P) AHU-1 ROOM 033 BLD1 BSMT
77 2 15 Smoke(Photo) 3RD FL E STR 352B BLD 1 TOWER
78 2 16 Smoke(Photo) HALL BY ROOM 4 WEST BLDG 1 BSMT
**Need to update description because this is no longer elevator lobby 10-2022
**Need to update description because this is no longer elevator lobby 10-2022 update description as indicated 4-2020 verify location device is in access panel in Room 308 update description as indicated 4-2020 verify location
79 2 17 Smoke(Photo) 1ST FLR TOWER EAST BLD 1 1ST FL
80 2 18 Smoke(Photo) TOWER EAST STAIRWELL BLD 1 1ST FL
81 2 19 Smoke(Photo) 2ND S DAMP RM 247 BLD 1 TOWER
82 2 20 DuctSmoke(P) 2ND N DAMP RM 247 BLDG BLD 1 TOWER
83 2 23 Smoke(Photo) 3RD FL S RM 357 BLD 1 TOWER
84 2 24 DuctSmoke(P) BASE DAMP S RM 051 BLD 1 TOWER
85 2 25 DuctSmoke(P) BASE DAMP N RM 051 BLD 1 TOWER
86 2 95 Smoke(Photo) ELEV A LOBBY 051 BLD1 TOWER
87 2 96 Smoke(Photo) BSMT W STR 009A BLD1 TOWER
88 2 98 Smoke(Photo) BSMT W CORR 47 BLD1 TOWER
89 2 99 Smoke(Photo) BSMT E CORR 047 BLD1 TOWER
90 2 100 Smoke(Photo) BASE RISER RM 012 BLD1 TOWER
91 2 101 Smoke(Photo) BSMT STR STR 007B BLD1 TOWER
92 2 103 Sup L(Duct P) BASE DAMP RM 10 S BLD1 TOWER
93 2 104 Sup L(Duct P) BASE DAMP RM 10 N BLD1 TOWER
94 2 107 Smoke(Photo) 1ST FL E CORR 154A BLD1 TOWER
95 2 108 Smoke(Photo) 1ST FL W CORR 154A BLD1 TOWER
96 2 109 Sup L(Duct P) 1ST FL DAMP RM 117 S BLD1 TOWER
97 2 110 Sup L(Duct P) 1ST FL DAMP RM 117 N BLD1 TOWER
98 2 111 Sup L(Duct P) 1ST FL DAMP RM 157 N BLD1 TOWER
99 2 112 Sup L(Duct P) 1ST FL DAMP RM 157 S BLD1 TOWER
100 2 113 Smoke(Photo) 1ST FL ELEV LOB 157 BLD1 TOWER
101 2 114 Smoke(Photo) 1ST FLR W STR 118A BLD1 TOWER
102 2 117 Smoke(Photo) 2ND FL E STR 239 BLD1 TOWER
103 2 118 Smoke(Photo) 2ND FLR E CORR 241 BLD1 TOWER
104 2 119 Smoke(Photo) 2ND FLR W CORR 241 BLD1 TOWER
105 2 120 Smoke(Photo) 2ND FLR W STR RM244B BLD1 TOWER
106 2 121 Smoke(Photo) 2ND FLR E RM 240 BLD1 TOWER
107 2 122 Smoke(Photo) 2ND FLR CORR 244A BLD1 TOWER
108 2 123 Smoke(Photo) ELEV A 2ND LBY RM 24 BLD1 TOWER
109 2 124 Sup L(Duct P) 2ND FL DAMP RM 248 S BLD1 TOWER
110 2 125 Sup L(Duct P) 2ND FL DAMP RM 248 N BLD1 TOWER
111 2 126 Sup L(Duct P) 2ND FL DAMP RM 244 S BLD1 TOWER
112 2 127 Sup L(Duct P) 2ND FL DAMP RM 244 N BLD1 TOWER
113 2 128 Smoke(Photo) 3RD FL W STR RM358B BLD1 TOWER
114 2 130 Smoke(Photo) 3RD FL W CRRR 358 BLD1 TOWER
115 2 131 Smoke(Photo) ELEV A 3RD RM 361 BLD1 TOWER
116 2 132 Sup L(Duct P) 3RD FL DAMP RM 361 S BLD1 TOWER
117 2 133 Sup L(Duct P) 3RD FL DAMP RM 361 N BLD1 TOWER
118 2 134 Sup L(Duct P) 3RD FL DAMP RM 355 S BLD1 TOWER
119 2 135 Sup L(Duct P) 3RD FL DAMP RM 355 N BLD1 TOWER
120 2 136 Smoke(Photo) 3RD FL N RM 356 BLD 1 TOWER
121 2 137 Smoke(Photo) 3RD FL N RM 355 BLD 1 TOWER
122 2 139 Sup L(Duct P) 3RD FL DAMP RM 360 S BLD1 TOWER
123 2 140 Sup L(Duct P) 3RD FL DAMP RM 360 N BLD1 TOWER
124 2 141 Smoke(Photo) 4TH FL E STR RM 401 BLD1 TOWER
125 2 142 Sup L(Duct P) 4TH FL DMPR RM 410 S BLD1 TOWER
126 2 143 Sup L(Duct P) 4TH FL DMPR RM 410 N BLD1 TOWER
127 2 144 Smoke(Photo) 4TH FL RM 406 BLD1 TOWER
128 2 145 Smoke(Photo) 4TH FL W STR RM 407B BLD1 TOWER
129 2 146 Smoke(Photo) 4TH FLR WEST LANDING BLD1 TOWER
130 2 147 Smoke(Photo) ELEV A SHAFT RM 411A BLD 1 TOWER
131 2 148 Sup L(Duct P) 4TH FL DMPR RM 411 S BLD1 TOWER
132 2 149 Sup L(Duct P) 4TH FL DMPR RM 411 N BLD1 TOWER
133 2 150 Smoke(Photo) 4TH ELEV LOBY RM 411BLD1 TOWER
134 2 151 Smoke(Photo) 4TH ELEV A EQUIP RM BLD1 TOWER
135 2 152 Heat 4TH ELEV A EQUIP RM BLD1 TOWER
136 2 153 Sup L(Duct P) 4TH FL DMPR RM 405 S BLD1 TOWER
137 2 154 Sup L(Duct P) 4TH FL DMPR RM 405 N BLD1 TOWER
138 2 155 Smoke(Photo) 4TH FL RM 405 BLD1 TOWER
139 2 156 Smoke(Photo) 4TH FL RM 404 BLD1 TOWER
Code REF: NFPA 72 Table 14.3.1 Location: 037-1 W/O#
Disconnecting Means Location: RM 001B-1 Disconnecting Means: Panel EM, Breaker 15
Line Item # Loop #
Device Address Device Type Description/Location
Location
OK / CA
Condition
OK / CA
1 1 1 Manual Pull. NORTH STAIRS BLD1 BSMT
2 1 2 Manual Pull. STAIRS BY RM 27 BLD1 BSMT
3 1 3 Manual Pull. STAIR BY RM 2 BLD1 BSMT
4 1 26 Manual Pull. HALL BY ROOM 143 BLD 1 1ST FL
5 1 27 Manual Pull. HALL BY ROOM 135 BLD 1 1ST FL
6 1 41 Manual Pull. HALL BY 105 BLD 1 1st FL
7 1 42 Manual Pull. HALL BY 146 BLDG1 1ST FL N
8 1 43 Manual Pull. HALL BY 141 BLDG1 1ST FL
9 1 44 Manual Pull. STAIR 207A BLD 1 2ND FL / Hall By Room 208
10 1 49 Manual Pull. MENTAL HLTH W STAIRS BLD 1 2ND FL / Hall By RM 206
11 1 61 Manual Pull. HALL BY RM 327 BLD 1 3RD FL
12 1 62 Manual Pull. HALL BY RM 301 BLD 1 3RD FL
13 1 63 Manual Pull. HALL BY RM 308 BLD 1 3RD FL
14 1 79 Manual Pull. BY NORTH STAIRS BLD 1 2ND FL / By RM 223
15 1 80 Manual Pull. BY NURSES STATION BLD 1 2ND FL / MH2 Nurse Station
16 1 81 Manual Pull. BY ED SUITE S EXIT BLD 1 1st FL / Room 123A
17 1 82 Manual Pull. ED SUITE RM 124A W BLD 1 1st FL
18 1 94 Manual Pull. HALL BY 220 BLD 1 2nd FL
19 2 4 Manual Pull. BSMT PULL W STR 009 BLD 1 TOWER
20 2 5 Manual Pull. 1ST FL PULL W CORR 154A BLD 1 TOWER
21 2 17 Manual Pull. 2ND PULL E CORR 241 BLD 1 TOWER
22 2 20 Manual Pull. 3RD FL W CORR 358 BLD 1 TOWER
23 2 27 Manual Pull. 2ND FL PULL W 244 BLD 1 TOWER
24 2 29 Manual Pull. 4TH PULL W CORR 407 BLD 1 TOWER
25 2 30 Manual Pull. 4TH PULL E CORR 403 BLD 1 TOWER
26 2 32 Manual Pull. 1ST FL EAST BLD 1 TOWER
27 2 33 Manual Pull. 3RD FL EAST BLD 1 TOWER
28 2 55 Manual Pull. 1ST FL STR 115B BLD 1 TOWER
29 2 102 Manual Pull. BSMT EAST BLD 1 TOWER
Fire Alarm System Manual Pull-Stations & Other (March) Location: SFVAMC Building #1
Address: 2501 W. 22nd St.
City/State/Zip: SF, SD 57105
Contact: Dave Dirks Inspected By: Adam Thompson
Phone: 605-336-3230 ext 6038 CA = Corrective Action Phone: 323-8627
FIX DESCRIPTION SHOULD BE CORR 115A
Code REF: NFPA 72 Table 14.3.1 Location: 037-1 W/O#
Disconnecting Means Location: RM 001B-1 Disconnecting Means: Panel EM, Breaker 15
Line Item # Device Type Description/Location
Location
OK / CA
Condition
OK / CA
1 Speaker Basement West By Room 004 West
2 Speaker Basement West By Room 004 East
3 Speaker Basement West Room 004
4 Speaker Basement West By Room 017
5 Speaker Basement West By Room 023
6 Speaker/Strobe Basement Center Elevator Lobby
7 Strobe Basement West Rest Room 021
8 Speaker Basement North By Room 034B
9 Strobe Basement North Restroom 026
10 Speaker Basement North Fitness Room 034 South
11 Speaker Basement North By Room 029
12 Speaker Basement North Room 029
13 Speaker Basement North By Room 032
14 Speaker Basement North Room 032
15 Speaker 1st North Room 143
16 Speaker 1st North By Room 144
17 Strobe 1st North Restroom 141
18 Speaker 1st North By Room 138
19 Speaker 1st North By Room 134
20 Strobe 1st Center South of Elevator Above Fire Alarm Annunciator
21 Speaker 1st West By North East Entry
22 Speaker/Strobe 1st West Elevator Lobby
23 Strobe 1st West Restroom 131
24 Speaker 1st West By Room 103
25 Speaker 1st West By Room 129
26 Strobe 1st West Education Foyer 123A West Wall
27 Speaker/Strobe 1st West Education Foyer 123A East Wall
28 Strobe 1st West Education Classroom 124 S.W. Wall
29 Strobe 1st West Education Classroom 124 S.E. Wall
30 Speaker/Strobe 2nd West By Room 206
31 Speaker/Strobe 2nd West By Room 209
32 Strobe 2nd West Restroom 211
33 Strobe 2nd Center Restroom 211A
34 Speaker/Strobe 2nd Center By Restroom 211A
35 Strobe 2nd Center MH2 Waiting Area
1AV6a
1AV20a
1A12
1AV41
1V42
1V30
1V31
1AV37
1AV38
1V39
1V40
1A20
1V21
1A22
1A23
1V28
1AV29
1A14
1A15
1V16
1A17
1A18
1V19
1A8
1V9
1A10
1A11
1A11A
1A13
Equipment ID 1A2
1A3
1A4
1A5
1A6
1V7 temporarily removed for construction 5-2022
Phone: 605-336-3230 ext 6038 CA = Corrective Action Phone: 323-8627
Comments
Fire Alarm System Audibles & Visuals (March) Location: SFVAMC Building #1
Address: 2501 W. 22nd St.
City/State/Zip: SF, SD 57105
Contact: Dave Dirks Inspected By: Adam Thompson
36 Speaker 2nd Center MH2 Waiting Area
37 Speaker/Strobe 2nd Center Elevator Lobby
38 Strobe 2nd Center Sally Port 213
39 Strobe 2nd Center Room 236
40 Speaker 2nd Center Room 234
41 Speaker/Strobe 2nd North By Day Room 216
42 Speaker/Strobe 2nd North By Room 230
43 Speaker/Strobe 2nd North By Room 250A
44 Speaker/Strobe 2nd North By Room 227
45 Speaker 2nd North By Room 220
46 Strobe 2nd North By Room 220
47 Speaker 2nd North Room 225
48 Strobe 2nd North Room 225
49 Speaker 3rd North By Room 326
50 Speaker 3rd North By Room 329
51 Speaker 3rd North By Room 333
52 Strobe 3rd North Restroom 316
53 Speaker 3rd Center By Room 337
54 Speaker/Strobe 3rd Center Elevator Lobby
55 Strobe 3rd West Restroom 310
56 Speaker 3rd West By Room 309
57 Speaker 3rd West By Room 307
58 Speaker/Strobe BSMT Tower By Room 012
59 Speaker/Strobe BSMT Tower By Room 011
60 Speaker/Strobe BSMT Tower By Room 010
61 Speaker/Strobe BSMT Tower Room 008 West
62 Speaker/Strobe BSMT Tower Room 008 East
63 Speaker/Strobe BSMT Tower Room 010
64 Speaker/Strobe BSMT Tower Room 009 By Exit
65 Speaker/Strobe BSMT Tower Room 009A By Elevator
66 Strobe BSMT Tower Room 009A South of Elevator
67 Speaker/Strobe 1st Floor Tower East Stairwell Room 115
68 Speaker/Strobe 1st Floor Tower East
69 Speaker/Strobe 1st Floor Tower By Room 117
70 Speaker/Strobe 1st Floor Tower By Room 117
71 Speaker/Strobe 1st Floor Tower Room 116 West
72 Speaker/Strobe 1st Floor Tower Room 116 East
73 Speaker/Strobe 1st Floor Tower Room 117 East
74 Speaker/Strobe 1st Floor Tower Room 117 West
75 Speaker/Strobe 1st Floor Tower Room 118A Stairwell
76 Speaker/Strobe 1st Floor Tower Room 118 By Elevator
77 Strobe 1st Floor Tower Room 118 Restroom By Elevator
78 Speaker/Strobe 2nd Floor Tower Room 239 East Stairs
1AV56a
1AV77
1V78
1AV79
1AV71
1AV72
1AV73
1AV74
1AV75
1AV76
1AV65
1AV66
1AV67
1V68
1AV69
1AV70
1V57
1A58
1A59
1AV62
1AV63
1AV64
1AV60
1AV61
1AV69A
1A51a
1V51b
1A52
1A54
1V55
1A56
1AV46
1AV47
1AV48
1AV49
1A50
1V51
1A53
1A43
1V44
1V45
1A45a
1AV43a
79 Speaker/Strobe 2nd Floor Tower By Room 242
80 Speaker/Strobe 2nd Floor Tower By Room 244
81 Speaker/Strobe 2nd Floor Tower West Stairwell 244B
82 Speaker/Strobe 2nd Floor Tower Room North of Stairwell
83 Speaker/Strobe 2nd Floor Tower Room 244A By Elevator
84 Strobe 2nd Floor Tower Room 244A South of Elevator
85 Speaker/Strobe 3rd Floor Tower Room 352 By East Stairwell
86 Speaker/Strobe 3rd Floor Tower By Room 359
87 Speaker/Strobe 3rd Floor Tower Room 355 South West
88 Speaker/Strobe 3rd Floor Tower Room 355 North West
89 Speaker/Strobe 3rd Floor Tower Room 355 North East
90 Speaker/Strobe 3rd Floor Tower West Stairwell Room 358B
91 Speaker/Strobe 3rd Floor Tower Room 358 North of West Stairwell
92 Speaker/Strobe 3rd Floor Tower Room 358A By Elevator
93 Strobe 3rd Floor Tower Room 358A South of Elevator
94 Speaker/Strobe 4th Floor Tower Room 401 By East Stairwell
95 Speaker/Strobe 4th Floor Tower By Room 409
96 Speaker/Strobe 4th Floor Tower Room 404 South West
97 Speaker/Strobe 4th Floor Tower Room 404 North West
98 Speaker/Strobe 4th Floor Tower Room 404 North East
99 Speaker/Strobe 4th Floor Tower East Stairwell Room 407B
100 Speaker/Strobe 4th Floor Tower Room 407 North of East Stairwell
101 Speaker/Strobe 4th Floor Tower Room 407A By Elevator
102 Strobe 4th Floor Tower Room 407A South of Elevator
1AV95
1AV96
1AV97
1AV98
1AV99
1AV100
1AV89
1AV90
1AV91
1AV92
1AV93
1V94
1AV83
1AV84
1V85
1AV101
1AV102
1V103
1AV86
1AV87
1AV88
1AV80
1AV81
1AV82
Code REF: NFPA 72 Table 14.3.1 Location: 037-1 W/O#
Disconnecting Means Location: RM 001B-1 Disconnecting Means: Panel EM, Breaker 15
Line Item # Device Type Description/Location
Location
OK / CA
Condition
OK / CA
1 Door Holder Basement By Room 012 West Door N/A N/A
2 Door Holder Basement By Room 012 East Door N/A N/A
3 Door Holder Basement West of Room 017
4 Door Holder Basement East of Room 017
5 Door Holder Basement West of Room 020
6 Door Holder Basement Center Door to Elevator Lobby
7 Door Holder Basement South of Room 027
8 Door Holder Basement North of Room 027
9 Door Holder Basement Corridor 041B South Door
10 Door Holder Basement Corridor 041B North Door
11 Door Holder 1st Stair C Top of Stairs By Emergency Exit
12 Door Holder 1st By Room 129
13 Door Holder 1st By Room 101
14 Door Holder 1st Door to Elevator Lobby
15 Door Holder 1st By Room 133
16 Door Holder 1st By Room 135
17 Door Holder 1st Stair D Top of Stairs By Emergency Exit
18 Door Holder 1st By Room 137
19 Door Holder 1st By Room 141
20 Door Holder 1st Door to Room 143
21 Door Holder 1st Door to Room 144 (door inside 143 that leads to 144)
22 Door Holder 2nd By Room 206
23 Door Holder 2nd By Room 208
24 Door Holder 2nd By Room 238 North Door
25 Door Holder 2nd By Room 238 South Door
26 Door Holder 2nd Door to Elevator Lobby
27 Door Holder 3rd By Room 307E
28 Door Holder 3rd By Room 310
29 Door Holder 3rd Door to Elevator Lobby
30 Door Holder 3rd By Room 333
31 Door Holder BSMT West Stairs by Elevator in Tower
32 Door Holder 1st West Stairs by Elevator in Tower
33 Door Holder 2nd West Stairs by Elevator in Tower
34 Door Holder 3rd West Stairs by Elevator in Tower
35 Door Holder 4th West Stairs by Elevator in Tower1DH31
1DH28
1DH29
1DH30
1DC25
1DC26
1DH27
1DH25a
1DH21
1DC23
1DC24
1DC18
1DC19a
1DH20
1DC22
1DC19
1DH23a
1DC16
1DC16a
1DC17
1DC12a
1DC13
1DC14
1DC15
1DC14a
1DC8
1DC9
1DC10
1DC5
1DC6
1DC7
1DH6a
1DC3 Not used & needs REMOVED 4-2022
1DC4
Phone: 605-336-3230 ext 6038 CA = Corrective Action Phone: 323-8627
Equipment ID Comments
Fire Alarm System Releasing Devices (March) Location: SFVAMC Building #1
Address: 2501 W. 22nd St.
City/State/Zip: SF, SD 57105
1DC2 REMOVED FOR CONSTRUCTION 4-2022
Inspection: Testing Manufacturer: Notifier
Frequency: Semi-Annual Date:
Code REF: NFPA 72 Table 14.4.3.2 Location: 037-1 W/O#
Disconnecting Means Location: RM 001B-1 Disconnecting Means: Panel EM, Breaker 15
Line Item #
Batt.
Type
Rated Ah
Rated Voltage Description/Location
Load Tst Volts
Tested Ah
Visual Check
Battery Dated
1 SLA 26ah 12V Basement FACP/Room 037(Right)(also for AMP1 & NAC Pan.) 3-22
2 SLA 26ah 12V Basement FACP/Room 037(Left)(also for AMP1 & NAC Panel) 3-22
3 SLA 12ah 12V Basement Amp #2/Room 037 (Bottom) (AMP Cab #1) 3-22
4 SLA 12ah 12V Basement Amp #2/Room 037 (Top) (AMP Cab #1) 3-22
5 SLA 12ah 12V Basement Amp #3/Room 037 (Bottom) (AMP Cab #1) 3-22
6 SLA 12ah 12V Basement Amp #3/Room 037 (Top) (AMP Cab #1) 3-22
7 SLA 8ah 12V 2nd Floor NAC #1 BLD 1 Tower/Room 240 (Left) 10-21
8 SLA 8ah 12V 2nd Floor NAC #1 BLD 1 Tower/Room 240 (Right) 10-21
9 SLA 8ah 12V 2nd Floor NAC #2 BLD 1 Tower/Room 240 (Left) 10-21
10 SLA 8ah 12V 2nd Floor NAC #2 BLD 1 Tower/Room 240 (Right) 10-21
Comments/Test Results
Contact: Dave Dirks Inspected By: Adam Thompson
Phone: 605-336-3230 ext 6038 SLA = Sealed Lead Acid Phone: 323-8627
Fire Alarm System Battery Load Voltage Testing (March) Location: SFVAMC Building #1
Address: 2501 W. 22nd St.
City/State/Zip: SF, SD 57105
Model Number: IFC2-640 (IFC-3030), ACPS610(Signal Exp.)
Inspection: Testing Manufacturer: Notifier
Code REF: NFPA 72 Table 14.4.3.2 Location: 037-1 W/O#
Disconnecting Means Location: RM 001B-1 Disconnecting Means: Panel EM, Breaker 15
Line Item # Loop #
Device Address Device Type Description/Location
Location
OK / CA
Test
OK / CA
1 1 11 Waterflow Waterflow In RM 27 BLD1 BSMT/RM 27 in Basement
2 1 12 Tamper RM 27 Sprnkler Mon BLD1 BSMT/RM 27 in Basement
3 1 13 Tamper RM 27 Sprnkler Mon BLD1 BSMT/RM 27 in Basement
4 1 14 Tamper RM 27 Sprnkler Mon BLD1 BSMT/RM 27 in Basement
5 1 15 Waterflow Waterflow Attic BLD 1 Attic/BSMT RM 27
6 1 18 Waterflow Waterflow Stor RM 23 BLD1 BSMT/Ctr Basement Stor RM 23
7 1 19 Tamper Stor RM 23 BLD1 BSMT/Basement Store RM 23
8 1 24 Tamper PIV E SIDE OF BLD BLD 1 BSMT/E. Side of Bldg By RM 034
9 1 32 Waterflow Room 133B BLD 1 1st FL North/RM 133B
10 1 33 Tamper Room 133B BLD 1 1st FL North/RM 133B
11 1 37 Waterflow RM 131A Waterflow BLD 1 1st FL BLD 1 1st West/1st RM 131A
12 1 38 Tamper RM 131A JAN Closet BLD 1 1st FL/1st Floor RM131A Jan RM
13 1 39 Waterflow RM 156 Waterflow BLD 1 1st FL/1st Floor RM 156
14 1 40 Tamper Mech RM 156 BLD 1 1st FL/1st Floor Mech RM 156
15 1 47 Waterflow MH2 RM 214A Flow BLD 1 2nd FL/MH2 2nd Flr RM 214A
16 1 48 Tamper MH2 RM 214A BLD 1 2nd FL/MH2 2nd Floor RM 214A
17 1 50 Waterflow RM 210 Waterflow BLD 1 2nd FL BLD 1 2nd W./2nd Flr RM 210
18 1 51 Tamper Jan Closet RM 210 BLD 1 2nd FL/2nd Floor Jan RM 210
19 1 66 Waterflow RM 311 Waterflow BLD 1 3rd FL/3rd Floor Store RM 311
20 1 67 Tamper Stor RM 311 3rd FL BLD 1 3rd FL/3rd Floor Store RM 311
21 1 68 Waterflow RM 315 Waterflow BLD 1 3rd FL/3rd Floor Store RM 315
22 1 69 Tamper Stor RM 315 3rd FL BLD 1 3rd FL/3rd Floor Store RM 315
23 2 60 Waterflow 4TH FL FLOW BLD 1 TOWER
24 2 113 Waterflow BSMT FLOW BLD 1 TOWER
25 2 114 Tamper BSMT TAMPER BLD 1 TOWER
26 2 115 Waterflow 2ND FL FLOW BLD 1 TOWER
27 2 116 Tamper 2ND FL TAMPER BLD 1 TOWER
28 2 117 Waterflow 3RD FL FLOW BLD 1 TOWER
29 2 118 Tamper 3RD FL TAMPER BLD 1 TOWER
30 2 120 Tamper 4TH FL TAMPER BLD 1 TOWER
31 2 131 Waterflow 1ST FL WATERFLOW BLD 1 TOWER/IN ROOM 122 ABV CEILING
32 2 132 Tamper 1ST FL TAMPER BLD 1 TOWER/IN ROOM 122 ABV CEILING
**NEED WATERFLOW IN DESCRIPTION 10-11-2022
note: cover is off due to too close to ceiling
Fire Alarm System Sprinkler Flow & Control Valve (March) Location: SFVAMC Building #1
Address: 2501 W. 22nd St.
City/State/Zip: SF, SD 57105
Contact: Dave Dirks Inspected By: Adam Thompson
Phone: 605-336-3230 ext 6038 CA = Corrective Action Phone: 323-8627
Frequency: Semi-Annual Model Number: IFC-3030 Date:
Code REF: NFPA 72 Table 14.3.1 Location: E23-5 W/O#
Disconnecting Means Location: RM E23-5 Disconnecting Means: Panel LCE6, Breaker 10
Line Item #
Node/ Loop #
Equip.
Address
Equipment Model # Description/Location
Location
OK / CA
Condition
OK / CA
1 2 IFC2-3030 Fire Alarm Control Panel/Ground Floor Room E23
2 1 JNCA-2 Global Fire Alarm Annunciator/Ground Floor Room E23
3 Fire Alarm Annunciator/Ground Floor Room A02
4 N/A N/A D9412GV4 Bosch Dialer/Ground Floor Room E23 (DC#1)
5 N/A N/A D9412GV4 Bosch Dialer Expansion/Ground Flr Rm E23 (DC#2)
6 1 47 FCPS-24S8 B96 NAC Control FCPS/Ground Floor Room B96 (#1)
7 3 1 DAA2-5070 Amp Panel #1/Ground Floor Room E23 (Cabinet #1)
8 3 2 DAA2-5070 Amp Panel #2/Ground Floor Room E23 (Cabinet #1)
9 3 3 DAA2-5070 Amp Panel #3/Ground Floor Room E23 (Cabinet #1)
10 3 4 DAA2-5070 Amp Panel #4/Ground Floor Room E23 (Cabinet #1)
11 3 5 DAA2-5070 Amp Panel #5/Ground Floor Room E23 (Cabinet #2)
12 3 6 DAA2-5070 Amp Panel #6/Ground Floor Room E23 (Cabinet #2)
13 3 7 DAA2-5070 Amp Panel #7/Ground Floor Room E23 (Cabinet #2)
14 3 8 DAA2-5070 Amp Panel #8/Ground Floor Room E23 (Cabinet #3)
15 3 9 DAA2-5070 Amp Panel #9/Ground Floor Room E23 (Cabinet #3)
16 3 10 DAA2-5070 Amp Panel #10/Ground Floor Room E23 (Cabinet #3)
17 3 11 DAA2-5070 Amp Panel #11/Ground Floor Room E23 (Cabinet #4)
18 3 12 DAA2-5070 Amp Panel #12/Ground Floor Room E23 (Cabinet #4)
19 3 13 DAA2-5070 Amp Panel #13/Ground Floor Room E23 (Cabinet #4)
20 3 15 DAA2-5070 Amp Panel #15/Ground Floor Room E23 (Cabinet #4)
21 4 120 ACPS-610 NAC Panel ACPS-610 # 1/ Grnd Flr E23 NAC Cabinet #1
22 4 130 ACPS-610 NAC Panel ACPS-610 # 2/ Grnd Flr E23 NAC Cabinet #1
23 4 145 ACPS-610PCB NAC Panel ACPS-610PCB # 3/ Grnd Flr E23 NAC Cabinet #1
24 4 135 ACPS-610 NAC Panel ACPS-610 # 4/ Grnd Flr E23 NAC Cabinet #1
25 5 21 FCPS-24S8 Primary Care NAC Panel RM 1003/1st Floor Room 1003 (#2)
26 9 70 FCPS-24S8 Acute Care NAC Panel RM 228B/2nd Floor (Left Panel) (#3)
27 9 70 FCPS-24S8 Acute Care NAC Panel RM 228B/2nd Floor (Right Panel) (#4)
28 2 82 FCPS-24S8 INT HEALTH BLD RM 118 NAC PANEL (#5)
29 2 83 FCPS-24S8 Womens Center NAC PNL 126/1st Floor Room 126 (#6)
30 2 76 FCPS-24S8 RM 195B FCPS CTRL NAC/1st Floor Room 195B (#7)
31 7 56 FCPS-24S8 O.R RM G03 NAC Panel (#8)
32 8 6 FCPS-24S8 NAC PNL RM A87 (#9)
33 8 46 FCPS-24S8 ONCOLOGY NAC PANEL RM 1021 (#10)
34 5 90 FCPS-24S8 SPEC MED INTERSTITIAL RM 1013 (#11)
35 6 66 FCPS-24S8 3rd Floor Chapel NAC RM 348C/Chapel Area Room 348C (#12)
Phone: 605-336-3230 ext 6038 CA = Corrective Action Phone: 323-8627
Comments
Fire Alarm System Control Panel, Annunciators, & Other (March) Location: SFVAMC Building #5
Address: 2501 W. 22nd St.
City/State/Zip: SF, SD 57105 update description as indicated 4-2022
36 1 8 FCPS-24S8 ED NAC PNL ACTIVATE RM B23/Ground RM B23 (#13)
37 3 16 DAA2-5070 Amp #16/Room 1021 (Top)(Cabinet?)
38 3 93 FCPS-24S8 5th FLR NAC Panel Elec RM 527 (#14)
39 8 104 FCPS-24S8 LAB NAC PANEL/1ST FLR LAB MECH RM 1016 BY 1018 (#15)
40 n/a n/a E/Clips Transient Suppressors/Ground Floor Room E23 Right of FACP
41 n/a n/a DTR-120SR Transient Suppressors/Ground Flr RM E23 In Amp Cabinet 4
Code REF: NFPA 72 Table 14.3.1 Location: E23-5 W/O#
Disconnecting Means Location: RM E23-5 Disconnecting Means: Panel LCE6, Breaker 10
Line Item # Loop #
Device Address Device Type Description/Location
Location
OK / CA
Condition
OK / CA
1 1 7 DuctSmoke(P) ED RM B34 STAFF RR
2 1 8 DuctSmoke(P) ED RM B35 FAM CON RET
3 1 9 DuctSmoke(P) ED RM B35 FAM CON SUP
4 1 10 DuctSmoke(P) ED RM B38B TLT SHOWER
5 1 11 DuctSmoke(P) ED RM B38 HALL
6 1 12 DuctSmoke(P) ED RM B38A ON-CALL
7 1 13 Smoke(Photo) ED BY RM 74A
8 1 14 Smoke(Photo) ED BY RM 77A
9 1 15 Smoke(Photo) ED BY RM 78
10 1 16 Smoke(Photo) ED BY RM 69C
11 1 17 Smoke(Photo) ED BY B68B HALL
12 1 18 Smoke(Photo) ED ABOVE NAC PNL RM B23
13 1 19 Smoke(Photo) ED BT B70 HALL
14 1 20 Smoke(Photo) BY B96 CORR C20 BUILDING 5
15 1 21 Smoke(Photo) CORR. WEST of B97 BUILDING 5
16 1 22 Smoke(Photo) HALL BY RM 21 BUILDING 5
17 1 23 Smoke(Photo) Room D39 Lab Area
18 1 30 Smoke(Photo) HALL BY ROOM D13 BUILDING 5
19 1 40 Heat (Fixed) INFU PENT W DET BUILDING 5
20 1 41 Heat (Fixed) INFU PENT E DET BUILDING 5
21 1 42 Smoke(Photo) RM B96 BUILDING 5
22 1 88 DuctSmoke(P) AHU-8 IN RM D28 RELAY 1M46
23 2 1 Smoke(Photo) BY STAIR 1 1ST FLOOR BUILDING 5
24 2 2 Smoke(Photo) HALL BY ROOM 150 BUILDING 5
25 2 3 Smoke(Photo) Hall By Room 101A BUILDING 5
26 2 4 Smoke(Photo) PATRIOT BREW ROOM 101A BUILDING 5
27 2 5 Smoke(Photo) ROOM 101B DENTAL WAIT BUILDING 5
28 2 6 Smoke(Photo) BY ROOM 138 BUILDING 5
29 2 8 Smoke(Photo) ELEVATOR LOBBY 1ST FLR BUILDING 5
30 2 9 Smoke(Photo) ELEVATOR LOBBY 1ST FLR BUILDING 5
31 2 10 Smoke(Photo) ELEVATOR LOBBY BY RM 141 BLDG 5
32 2 11 Smoke(Photo) HALL N. OF RM 190 BUILDING 5
33 2 12 Smoke(Photo) BY SERVICE ELEVATOR 1ST BUILDING 5
34 2 13 DuctSmoke(P) AHU-30 1ST FL N RM147 RELAY 2M37/N. Side of Unit
35 2 15 Smoke(Photo) COMPUTER RM 178 BUILDING 5
Fire Alarm System Smokes & Heats (March) Location: SFVAMC Building #5
Address: 2501 W. 22nd St.
City/State/Zip: SF, SD 57105
Contact: Dave Dirks Inspected By: Adam Thompson
Phone: 605-336-3230 ext 6038 CA = Corrective Action Phone: 323-8627
Comments removed for construction 3-2022 removed for construction 3-2022
36 2 16 Smoke(Photo) COMPUTER RM 178 BUILDING 5
37 2 17 Smoke(Photo) COMPUTER RM 178 BUILDING 5
38 2 18 Smoke(Photo) COMPUTER RM 178 BUILDING 5
39 2 19 Smoke(Photo) COMPUTER RM 178 BUILDING 5
40 2 20 Smoke(Photo) COMPUTER RM 178 BUILDING 5
41 2 21 Smoke(Photo) COMPUTER RM 178 BUILDING 5
42 2 22 Smoke(Photo) COMPUTER RM 178 BUILDING 5
43 2 23 Smoke(Photo) COMPUTER RM 178 BUILDING 5
44 2 24 Smoke(Photo) COMPUTER RM 178 BUILDING 5
45 2 25 Heat COMPUTER RM 178 BUILDING 5
46 2 26 Heat COMPUTER RM 178 BUILDING 5
47 2 27 Heat COMPUTER RM 178 BUILDING 5
48 2 31 DuctSmoke(P) AHU-12 ROOM 133 RELAY 2M39
49 2 32 DuctSmoke(P) AHU-10 RM 122 Womens Ctr BLD 5
50 2 33 DuctSmoke(P) AHU-9 RM 126A RELAY 2M41
51 2 34 DuctSmoke(P) AHU-13 RM 185 RELAY 2M42
52 2 36 DuctSmoke(P) AHU-21 ROOM 193A RELAY 2M44
53 2 37 DuctSmoke(P) AHU-21 ROOM 193A RELAY 2M44
54 2 38 Smoke(Photo) COMPACTOR CORR E BUILDING 5
55 2 39 Smoke(Photo) COMPACTOR CORR E BUILDING 5
56 2 40 Heat (Fixed) COMPACTOR CORR BUILDING 5
57 2 41 Heat COMPACTOR CORR BUILDING 5
58 2 42 Heat COMPACTOR CORR W BUILDING 5
59 2 43 Heat COMPACTOR RM 199 N BUILDING 5
60 2 44 Heat COMPACTOR RM 199 S BUILDING 5
61 2 46 DuctSmoke(P) AHU-25 RM 245F RELAY 2M46
62 2 47 DuctSmoke(P) EF-25 RM 245F RELAY 2M45
63 2 48 Smoke(Photo) W DINNING RM 256 BUILDING 5
64 2 49 Smoke(Photo) E DINNING RM 256 BUILDING 5
65 2 50 Smoke(Photo) HALL BY ROOM 252 BUILDING 5
66 2 51 Smoke(Photo) HALL BY ROOM 272 BUILDING 5
67 2 52 Smoke(Photo) HALL BY RM 247 BUILDING 5
68 2 55 Smoke(Photo) ELEVATOR LOBBY 2ND FLR BUILDING 5
69 2 56 Smoke(Photo) ELEVATOR LOBBY 2ND FLR BUILDING 5
70 2 57 Smoke(Photo) DINING ROOM 244 BUILDING 5
71 2 58 Smoke(Photo) BY RM 245A BUILDING 5
72 2 59 Smoke(Photo) SERVICE ELEVATOR 2ND FLR BUILDING 5
73 2 62 DuctSmoke(P) AHU#28 KIT RM 245A RELAY 2M12/West Side of Unit
74 2 63 DuctSmoke(P) AHU-27 KIT RM 245A RELAY 2M13
75 2 64 DuctSmoke(P) AHU-29 RM 245A RELAY 2M36/ East Side of Unit
76 2 65 Smoke(Photo) HALL BY RM 196B BUILDING 5
77 2 66 Smoke(Photo) HALL BY RM 195A RELAY 2M75
78 2 67 DuctSmoke(P) RTU RM 180 RELAY 2M75/Abv Ceiling By East Entry
79 2 68 Smoke(Photo) ROOM 195B BUILDING 5
80 2 74 Heat STAFF RR 115 BLD 52
81 2 75 Smoke(Photo) CORRIDOR BY RM 129 WOMENS CENT
82 2 76 Smoke(Photo) CORRIDOR BY RM 129 WOMENS CNTR
83 2 77 Smoke(Photo) CORR BY RM 114 WOMENS CNTR
84 2 78 Smoke(Photo) CORR BY RM 126 WOMENS CNTR
85 2 79 Smoke(Photo) ELECTRICAL ROOM 126 WOMENS CNTR
86 2 80 Smoke(Photo) CORR BY RM 123 WOMENS CNTR
87 2 81 Smoke(Photo) CORR BY RM 120 WOMENS CNTR
88 2 82 Smoke(Photo) ROOM 104 BLD 52
89 2 83 Smoke(Photo) ROOM 105 BLD 52
90 2 84 Smoke(Photo) ROOM 103 BLD 52
91 2 85 Smoke(Photo) NORTH HALL BLD 52
92 2 86 Smoke(Photo) RECEPTION DESK BLD 52
93 2 87 Smoke(Photo) ELECTRICAL CLOSET BLD 52
94 2 88 Smoke(Photo) RM 102 BLD 52
95 2 89 Smoke(Photo) HALL BY 107 BLD 52
96 2 90 Smoke(Photo) ROOM 107 N DET BLD 52
97 2 91 Smoke(Photo) ROOM 107 S DET BLD 52
98 2 92 Smoke(Photo) HALL BY S ENT BLD 52
99 2 93 Smoke(Photo) HALL BY 109 BLD 52
100 2 94 Heat MENS RESTROOM BLD 52
101 2 95 Smoke(Photo) NORTH VESTIBULE BLD 52
102 2 96 Smoke(Photo) ROOM 112 BLD 52
103 2 97 Heat WOMENS RESTROOM BLD 52
104 2 98 Smoke(Photo) RM 106 NETWORK CLST BLD 52
105 2 99 Smoke(Photo) ROOM 111 BLD 52
106 3 1 DuctSmoke(P) AHU-35 RM 549 SOUTH 3M2, 6M20
107 3 3 DuctSmoke(P) AHU-32 5TH FLR MECH RM 515/Top of Unit West Side
108 3 4 Heat ELEV EQUIPMENT RM 6TH FL
109 3 5 Heat ELEV EQUIPMENT RM 6TH FL
110 3 6 Heat ELEV EQUIPMENT RM 6TH FL
111 3 7 Heat ELEV EQUIPMENT RM 6TH FL
112 3 10 Smoke(Photo) HALL BY RM 443C
113 3 11 DuctSmoke(P) AHU-15 Room 443F W /W. side of RM 443F Abv Ceil
114 3 24 DuctSmoke(P) AHU-19 RM 549 NORTH RELAY 3M37
115 3 25 DuctSmoke(P) AHU-19 RM 549 SOUTH RELAY 3M37
116 3 29 DuctSmoke(P) AHU-16 RM 551 RELAY 3M34/S.E. Side High
117 3 30 DuctSmoke(P) AHU-16 RM 551 RELAY 3M34/ N. Side
118 3 41 Smoke(Photo) IN ROOM 600 SOUTHWEST
119 3 42 Smoke(Photo) ELEV EQUIPMENT RM 6TH FL
120 3 43 Smoke(Photo) ELEV EQUIPMENT RM 6TH FL
121 3 44 Heat ELEV EQUIPMENT RM 6TH FL
**smoke detector too close to vent 4-2022
122 3 45 Heat ELEV EQUIPMENT RM 6TH FL
123 3 46 Heat ELEV EQUIPMENT RM 6TH FL
124 3 47 Heat ELEV EQUIPMENT RM 6TH FL
125 3 48 DuctSmoke(P) AHU-17 RM 600 RELAY 3M51/N.W. Side of Unit
126 3 49 Smoke(Photo) 5TH FL MECH RM 515 SOUTH
127 3 50 Smoke(Photo) 5TH FL MECH RM 515 NORTH
128 3 53 Smoke(Photo) TOP OF ELEV SHAFT ELEV P2
129 3 54 Smoke(Photo) TOP OF ELEVATR SHAFT W ELEV S6
130 3 56 Smoke(Photo) TOP OF ELEVATR SHAFT E Elev P3
131 3 57 Smoke(Photo) TOP OF ELEV SHAFT W Mid Elev
132 3 58 Smoke(Photo) 5TH FLR BY RM 528 BLDG 5
133 3 59 Smoke(Photo) 5TH FLR BY RM 530 BLDG 5
134 3 60 Smoke(Photo) 5TH FLR BY RM 526 BLDG 5
135 3 61 Smoke(Photo) 5TH FLR BY RM 525 BLDG 5
136 3 62 Smoke(Photo) 5TH FLR BY RM 524 BLDG 5
137 3 63 Smoke(Photo) 5TH FLR BY RM ??? BLDG 5
138 3 65 Smoke(Photo) 5TH FLR BY RM 519
139 3 66 Smoke(Photo) 5TH FLR BY RM 519
140 3 67 Smoke(Photo) 5TH FLR HALL BY ROOM 515
141 3 68 Smoke(Photo) 5TH FLR HALL BY ROOM 509
142 3 69 Smoke(Photo) 5TH FLR LOBBY EAST WAITING ROOM
143 3 70 Smoke(Photo) 5TH FLR LOBBY NORTH WAITING ROOM
144 3 71 Smoke(Photo) 5TH FLR LOBBY SOUTH WAITING ROOM
145 3 72 Smoke(Photo) 5TH FLR EAST BY RECEPT AREA
146 3 73 Smoke(Photo) 5TH FLR WEST BY RECEPT AREA
147 3 74 Smoke(Photo) 5TH FLR WEST BY ROOM 501A
148 3 75 Smoke(Photo) 5TH FLR CENTRAL BY RECEPT AREA
149 3 76 Smoke(Photo) 5TH FLR SOUTH BY ROOM 516
150 3 77 Smoke(Photo) 5TH FLR SOUTH BY ROOM 517
151 3 78 Smoke(Photo) 5TH FLR MED ROOM ROOM 514
152 3 79 Smoke(Photo) 5TH FLR SOILED RM ROOM 513
153 3 80 DuctSmoke(P) 5TH FLR SOUTH BY RM 512 (Supervisory)
154 3 81 DuctSmoke(P) 5TH FLR SOUTH RM 512 (Supervisory)
155 3 82 DuctSmoke(P) 5TH FLR SOUTH BY RM 518 (Supervisory)
156 3 83 DuctSmoke(P) 5TH FLR SOUTH BY RM 511 (Supervisory)
157 3 84 DuctSmoke(P) 5TH FLR SOUTH BY RM 519 (Supervisory)
158 3 85 DuctSmoke(P) 5TH FLR MINOR SURG IN RM 511 (Supervisory)
159 3 86 DuctSmoke(P) 5TH FLR SOUTH BY RM 519 (Supervisory)
160 3 87 DuctSmoke(P) 5TH FLR NORTH BY RM 535(Supervisory)
161 3 88 DuctSmoke(P) 5TH FLR BY RR BY RM 511 (Supervisory)
162 3 89 DuctSmoke(P) 5TH FLR CENTRAL DATA ROOM 546 (Supervisory)
163 3 90 DuctSmoke(P) 5TH FLR SMOKE DAMPER BY RM 510 (Supervisory)
164 3 91 DuctSmoke(P) 5TH FLR SMOKE DAMPER BY RM 522 (Supervisory)
**Verify & HAVE JCI UPDATE descripion 4-22**
**Verify descripion & HAVE JCI UPDATE 4-22**
165 3 92 DuctSmoke(P) 5TH FLR WEST PATIENT BY RM 509 N (Supervisory)
166 3 93 DuctSmoke(P) 5TH FLR WEST WING BY RM 509(Supervisory)
167 3 94 DuctSmoke(P) 5TH FLR WAITING AREA EAST (Supervisory)
168 3 95 DuctSmoke(P) 5TH FLR WAITING AREA WEST (Supervisory)
169 3 96 DuctSmoke(P) 5TH FLR WEST WING BY RM 508(Supervisory)
170 3 97 DuctSmoke(P) 5TH FLR WEST WING BY RM 503(Supervisory)
171 3 98 DuctSmoke(P) 5TH FLR WEST WING BY RM 507 (Supervisory)
172 3 99 DuctSmoke(P) 5TH FLR WEST WING BY RM 506 (Supervisory)
173 3 100 DuctSmoke(P) 5TH FLR SMOKE DAMPER BY RM 518 (Supervisory)
174 3 101 DuctSmoke(P) 5TH FLR SOUTH EXAM BY RM 519 (Supervisory)
175 3 102 DuctSmoke(P) 5TH FLR SMOKE DAMPER BY RM 517 (Supervisory)
176 3 103 Smoke(Photo) 5TH FLR ABOVE HEP ELEC RM 527
177 5 1 DuctSmoke(P) AHU #5 RET DUCT PC FAN ROOM
178 5 2 DuctSmoke(P) AHU #5 SUPPLY DUCT PC FAN ROOM
179 5 3 DuctSmoke(P) AHU #6 RETURN DUCT PC FAN ROOM
180 5 4 DuctSmoke(P) AHU #6 SUPPLY DUCT PC FAN ROOM
181 5 5 DuctSmoke(P) AHU #1 SUPPLY DUCT PC FAN ROOM (supervisory)
182 5 6 DuctSmoke(P) AHU #1 RETURN DUCT PC FAN ROOM
183 5 7 Heat PC INTERSTITIAL RM 1004 S.W.
184 5 8 DuctSmoke(P) AHU #7 SUPPLY DUCT PC FAN ROOM
185 5 9 DuctSmoke(P) AHU #7 RETURN DUCT PC FAN ROOM
186 5 10 Heat PC INTERSTITIAL RM 1004 E.
187 5 11 Heat PC INTERSTITIAL RM 1004 N.W.
188 5 16 Heat PC ELEV EQUIP RM F08 ELEV MECH RM
189 5 17 Smoke(Photo) PC ELEV EQUIP RM F08 ELEV MECH RM
190 5 18 Heat PC ELEV ELEV PIT GRND FL
191 5 19 Smoke(Photo) PC ELEV TOP OF SHAFT 2ND FL
192 5 25 Smoke(Photo) MAIN LOBBY W. of INFO GRND FL
193 5 26 Smoke(Photo) MAIN LOBBY NORTH GRND FL
194 5 27 Smoke(Photo) MAIN LOBBY SOUTH GRND FL
195 5 29 Smoke(Photo) MAIN LOBBY SOUTH GRND FL
196 5 30 Smoke(Photo) CORR BY ROOM F12
197 5 31 Heat PC RM 1005 EAST
198 5 32 DuctSmoke(P) AHU-33 RM 1005 RELAY 5M2/N.W. Side
199 5 33 Heat PC ROOM 1005 E. CENTER
200 5 34 Heat PC ROOM 1005 W. CENTER
201 5 35 Heat PC ROOM 1005 WEST
202 5 37 Smoke(Photo) MAIN LOBBY NORTH GRND FL
203 5 38 Smoke(Photo) PC ROOM 1001 S.E. 1st FL
204 5 39 Smoke(Photo) PC ROOM 1001 S.E. MID DET
205 5 40 Smoke(Photo) PC ROOM 1001 EAST MID DET
206 5 41 Smoke(Photo) PC ROOM 1001 N.E. MID DET
207 5 42 Smoke(Photo) PC ROOM 1001 ELEV LOBBY
208 5 44 Smoke(Photo) PC ELEV LOBBY GRND FLR
209 5 45 Smoke(Photo) HALL BY RM F07
210 5 46 Smoke(Photo) PC TOP OF STAIR #8 2nd Floor
211 5 47 Smoke(Photo) PC RM 1001 N.W. DET
212 5 48 Smoke(Photo) PC RM 1001 N.W. MID DET
213 5 49 DuctSmoke(P) PC AHU #40 RM 1001 RETURN DUCT
214 5 50 DuctSmoke(P) PC AHU #40 RM 1001 SUPPLY DUCT
215 5 51 Smoke(Photo) PC RM 1001 WEST MID DET
216 5 52 DuctSmoke(P) PC Room 1001 AHU 40 Return Duct
217 5 53 DuctSmoke(P) PC Room 1001 AHU 40 Return Duct
218 5 54 Smoke(Photo) PC RM 1001 S.W. DET
219 5 56 Smoke(Photo) PC RM 1003 EC RM
220 5 57 Smoke(Photo) PC RM 1002 COMM CLOSET
221 5 58 Smoke(Photo) PC INTER CORR 1006 PC INTER
222 5 60 Smoke(Photo) PC W. HALL BY RM 2011
223 5 61 Smoke(Photo) PC W. HALL BY RM 2012 North
224 5 62 Smoke(Photo) PC W. HALL BY RM 2014
225 5 63 Smoke(Photo) PC W. HALL BY RM 2016
226 5 64 Smoke(Photo) PC 2ND FLR N. WAITING
227 5 66 Smoke(Photo) PC 2ND FLR ELEV LOBBY
228 5 67 Smoke(Photo) PC 2ND FLR E HALL N
229 5 68 Smoke(Photo) PC E. HALL BY RM 2003
230 5 69 Smoke(Photo) PC E. HALL BY RM 2005
231 5 70 Smoke(Photo) PC E. HALL BY ROOM 2008
232 5 71 Smoke(Photo) PC 2ND FLR E. HALL South DET
233 5 73 Smoke(Photo) PC 2ND FLR TOP STAIR 9
234 5 75 Smoke(Photo) PC HALL BY RM 2009
235 5 80 Heat SPEC MED ELEVATOR Heat IN PIT
236 5 81 Smoke(Photo) SPEC MED ELEV TOP OF SHAFT
237 5 82 Smoke(Photo) SPEC MED ELEVATOR EQUIPMENT RM
238 5 83 HEAT SPEC MED ELEVATOR EQUIPMENT RM
239 5 84 Smoke(Photo) SPEC MED INTERSTITIAL RM 1013
240 5 85 Smoke(Photo) SPEC MED INTERSTITIAL RM 1014
241 5 86 Smoke(Photo) SPEC MED INTERSTITIAL SOUTH WEST
242 5 87 Smoke(Photo) SPEC MED INTERSTITIAL BY 1014
243 5 89 Smoke(Photo) SPEC MED INTERSTITIAL S.E. CTR
244 5 91 DuctSmoke(P) SPEC MED INTERSTITIAL AHU 42 (Supervisory)
245 5 92 Smoke(Photo) SPEC MED INTERSTITIAL SW CENTER
246 5 93 Smoke(Photo) SPEC MED INTERSTITIAL CTR WEST
247 5 94 Smoke(Photo) SPEC MED INTERSTITIAL CENTER OF RM
248 5 95 Smoke(Photo) SPEC MED INTERSTITIAL CENTER EAST
249 5 96 DuctSmoke(P) SPEC MED INTERSTITIAL AHU42 (Supervisory)
250 5 97 Smoke(Photo) SPEC MED INTERSTITIAL N.W.
251 5 100 Smoke(Photo) SPEC MED INTERSTITIAL NORTH WEST
252 5 101 Smoke(Photo) SPEC MED INTERSTITIAL N. CTR.
253 5 102 DuctSmoke(P) SPEC MED INTERSTITIAL RF42 RETURN (Supervisory)
254 5 103 DuctSmoke(P) SPEC MED INTERSTITIAL RF42 SOUTH (Supervisory)
255 5 104 DuctSmoke(P) SPEC MED INTERSTITIAL RF42 CENTER (Supervisory)
256 5 105 DuctSmoke(P) SPEC MED INTERSTITIAL RF42 NORTH (Supervisory)
257 5 107 Smoke(Photo) SPEC MED INTERSTITIAL NORTH CENTER
258 5 108 Smoke(Photo) SPEC MED INTERSTITIAL NORTH EAST
259 5 109 Smoke(Photo) SPEC MED INTERSTITIAL NORTH EAST
260 5 111 Smoke(Photo) SPEC MED GND FLOOR ELEVATOR LOB
261 5 113 Smoke(Photo) SPEC MED EAST WAITING HALL
262 5 114 Smoke(Photo) SPEC MED EAST WAITING
263 5 115 Smoke(Photo) SPEC MED WEST WAITING
264 5 116 Smoke(Photo) SPEC MED WOMENS RR
265 5 117 Smoke(Photo) SPEC MED MENS RR
266 5 118 Smoke(Photo) SPEC MED NORTH WAITING
267 5 119 Smoke(Photo) SPEC MED RECEPTION
268 5 120 Smoke(Photo) SPEC MED BY 2025 ROOM 2025
269 5 121 DuctSmoke(P) SPEC MED HALL BY 2025 (Supervisory)
270 5 122 DuctSmoke(P) SPEC MED OFFICE 2025 (Supervisory)
271 5 123 Smoke(Photo) SPEC MED EAST HALL SOUTH
272 5 124 Smoke(Photo) SPEC MED EAST HALL E HALL CTR
273 5 125 Smoke(Photo) SPEC MED EAST HALL E HALL CTR
274 5 126 DuctSmoke(P) SPEC MED EAST HALL ABOVE FIREDR (Supervisory)
275 5 127 Smoke(Photo) SPEC MED EAST HALL HALL NORTH
276 5 128 Smoke(Photo) SPEC MED EAST HALL HALL NORTH
277 5 129 Smoke(Photo) SPEC MED STAIR STAIR 11
278 5 130 Smoke(Photo) SPEC MED OUTSIDE 2048
279 5 131 Smoke(Photo) SPEC MED OUTSIDE 2046
280 5 132 Smoke(Photo) SPEC MED OUTSIDE 2043
281 5 133 Smoke(Photo) SPEC MED ROOM 2031 N.
282 5 134 Smoke(Photo) SPEC MED OUTSIDE 2031
283 5 135 Smoke(Photo) SPEC MED OUTSIDE 2033
284 5 136 Smoke(Photo) SPEC MED ROOM 2031 S.
285 5 137 Smoke(Photo) SPEC MED OUTSIDE 2040
286 5 138 Smoke(Photo) SPEC MED OUTSIDE 2037
287 5 139 Smoke(Photo) SPEC MED OUTSIDE 2030
288 6 2 Smoke(Photo) ROOM 445 WAITING RM
289 6 3 Smoke(Photo) HALL BY RM 451
290 6 4 Smoke(Photo) HALL BY RM 445
291 6 5 Smoke(Photo) HALL BY RM 402
292 6 6 Smoke(Photo) HALL BY ROOM 433
293 6 7 Smoke(Photo) ELEVATOR LOBBY 4TH FLOOR
294 6 8 Smoke(Photo) ELEVATOR LOBBY 4TH FLOOR
295 6 9 Smoke(Photo) HALL BY ROOM 443A
296 6 10 DuctSmoke(P) AHU-31 RM 445A 6M17/18 /South Side
297 6 12 Smoke(Photo) WAITING RM 473
298 6 15 Smoke(Photo) WAITING RM 408
299 6 16 Smoke(Photo) EYE CLINIC RM 402
300 6 17 Smoke(Photo) IN ROOM 471
301 6 20 Smoke(Photo) IN ROOM 464B NORTH
302 6 28 Smoke(Photo) ROOM 301 BUILDING 5
303 6 29 Smoke(Photo) ENDO HALL BY RM 411 BUILDING 5
304 6 30 Smoke(Photo) ENDO HALL BY RM 429 BUILDING 5
305 6 31 Smoke(Photo) ENDO HALL BY RM 423 BUILDING 5
306 6 65 Smoke(Photo) EYE CLINIC WAIT RM 403
307 6 66 DuctSmoke(P) AHU-26-SF26 RM 352A 6M92/93
308 6 67 DuctSmoke(P) AHU-26-EF26 RM 352A 6M92/93
309 6 68 Smoke(Photo) CLC3 DINNING RM 361 WEST
310 6 69 Smoke(Photo) CLC3 DINNING RM 361 EAST
311 6 70 Smoke(Photo) CLC3 HALL BY ROOM 357
312 6 71 Smoke(Photo) CLC3 HALL BY ROOM 374
313 6 72 Smoke(Photo) CLC3 HALL BY ROOM 352
314 6 73 Smoke(Photo) CLC3 DINING STOR RM 360
315 6 75 Smoke(Photo) ELEVATOR LOBBY 3RD FLR
316 6 76 Smoke(Photo) ELEVATOR LOBBY 3RD FLR
317 6 77 Smoke(Photo) ELEVATOR LOBBY 3RD FLR
318 6 78 Smoke(Photo) RM 328 ICU WAITING
319 6 79 Smoke(Photo) IN ROOM 350
320 6 80 Heat IN ROOM 350
321 6 81 Heat IN ROOM 350
322 6 83 Smoke(Photo) NAC RM 348C CHAPEL
323 6 85 DuctSmoke(P) RM 349G AHU14 Chapel (Supervisory)
324 7 1 Smoke(Photo) NUC MED BY RM A11
325 7 2 Smoke(Photo) NUC MED BY RM A09A GRND FLR
326 7 3 Smoke(Photo) NUC MED RM A08 GRND FLR
327 7 4 Smoke(Photo) NUC MED BY RM A05 GRND FL
328 7 5 Smoke(Photo) NUC MED BY RM A04B
329 7 6 Smoke(Photo) NUC MED BY RM A03A
330 7 7 Smoke(Photo) NUC MED RM A03 S. DET GRND FL
331 7 8 Smoke(Photo) NUC MED RM A03 N. DET GRND FL
332 7 9 Smoke(Photo) MRI DRESSING RM BY RM A17A
333 7 15 Smoke(Photo) O.R. ELEV LOB GRND FLR
334 7 16 Smoke(Photo) O.R. ELEV DR E. GRND FLOOR
335 7 17 Smoke(Photo) O.R. ELEV DR W GRND FLOOR
336 7 18 Smoke(Photo) O.R. ELEV LOB 1ST FLR
Needs moved 3' from vent April 2022
Needs moved 3' from vent April 2022
**UPDATE DESCRIPTION AS INDICATED 4-2022**
337 7 19 Smoke(Photo) O.R. ELEV DR E 1ST FLR
338 7 20 Smoke(Photo) O.R. ELEV LOB 2ND FLR
339 7 21 Smoke(Photo) O.R. ELEV DR E 2ND FLR
340 7 22 Smoke(Photo) O.R. ELEV DR W 2ND FLR
341 7 23 Smoke(Photo) O.R. ELEV LOBBY 3RD FLR
342 7 24 Smoke(Photo) O.R. ELEV DR E 3RD FLR
343 7 25 Smoke(Photo) O.R. ELEV DR W 3RD FLR
344 7 26 Smoke(Photo) O.R. ELEV LOB 4TH FLR
345 7 27 Smoke(Photo) O.R. ELEV DR E 4TH FLR
346 7 28 Smoke(Photo) O.R. ELEV DR W 4TH FLR
347 7 30 Smoke(Photo) O.R. ELEV TOP OF SHAFT
348 7 32 Smoke(Photo) O.R. ELEV TOP OF SHAFT
349 7 33 Smoke(Photo) O.R. GRND FLR DATA RM G03
350 7 34 Heat O.R. GRND FLR ELEV MECH RM G05
351 7 35 Smoke(Photo) O.R. GRND FLR MECH RM G05
352 7 36 Smoke(Photo) O.R. GRND FLR NURSE ST NE
353 7 38 Smoke(Photo) O.R. GRND FLR NURSE ST S
354 7 39 Smoke(Photo) O.R. GRND FLR CORR BY G35
355 7 40 Smoke(Photo) O.R. GRND FLR RM G32
356 7 41 Smoke(Photo) O.R. GRND FLR N CORR C44
357 7 42 Smoke(Photo) O.R. GRND FLR NURSE ST W
358 7 43 Smoke(Photo) O.R. GRND FLR NURSE ST W
359 7 44 Smoke(Photo) O.R. GRND FLR RM G29
360 7 45 Smoke(Photo) O.R. GRND FLR HALL BY G28
361 7 46 Smoke(Photo) O.R. GRND FLR W HALL BY G26
362 7 47 Smoke(Photo) O.R. GRND FLR RM G26 W
363 7 48 Smoke(Photo) O.R. GRND FLR RM G26 MIDD
364 7 49 Smoke(Photo) O.R. GRND FLR CORR C43 S
365 7 50 Smoke(Photo) O.R. GRND FLR CORR C42 MID
366 7 51 Smoke(Photo) O.R. GRND FLR CORR C42 EXI
367 7 52 Smoke(Photo) O.R. GRND FLR RM G26 E
368 7 53 Smoke(Photo) O.R. GRND FLR RM G22
369 7 54 Smoke(Photo) O.R. GRND FLR BY RM G22
370 7 55 Smoke(Photo) O.R. GRND FLR BY RM G20A
371 7 56 Smoke(Photo) O.R. GRND FLR BY RM G20
372 7 57 Smoke(Photo) O.R. GRND FLR CORR C40 E
373 7 58 Smoke(Photo) O.R. GRND FLR PACU BY G13
374 7 59 Smoke(Photo) O.R. GRND FLR PACU RM G13
375 7 60 Smoke(Photo) O.R. GRND FLR PACU RM G14
376 7 61 Heat O.R. GRND FLR PACU RM G16A
377 7 62 DuctSmoke(P) O.R. 1ST FLR MECH RM 1030
378 7 63 DuctSmoke(P) O.R. 1ST FLR MECH RM 1030
379 7 64 DuctSmoke(P) O.R. 1ST FLR MECH RM 1030
380 7 65 Smoke O.R. GRND FLR RM G30
381 7 66 Heat O.R. GRND FLR MECH RM G05
382 8 1 Smoke(Photo) HALL BY RM A07A Building 5
383 8 4 Smoke(Photo) BY RM B98 Building 5
384 8 5 Smoke(Photo) BY RM B89E BUILDING 5
385 8 6 Smoke(Photo) PHARM PICKUP B89B BLD 5
386 8 7 Smoke(Photo) W SKYLIGHT BY B80 BUILDING 5
387 8 8 Smoke(Photo) SW SKYLIGHT BY B80 BUILDING 5
388 8 9 Smoke(Photo) SE SKYLIGHT BY B80 BUILDING 5
389 8 10 Smoke(Photo) E SKYLIGHT BY B80 BUILDING 5
390 8 11 Smoke(Photo) NE SKYLIGHT BY B80 BUILDING 5
391 8 12 Smoke(Photo) HALL BY B45 BUILDING 5
392 8 13 Heat IN ROOM B66A BUILDING 5
393 8 14 Heat IN ROOM B66A BUILDING 5
394 8 15 Smoke(Photo) IN ROOM B66 BUILDING 5
395 8 18 Smoke(Photo) HALL BY ROOM B83 BUILDING 5
396 8 20 Smoke(Photo) ROOM A54 BUILDING 5
397 8 21 Smoke(Photo) ROOM A55 BUILDING 5
398 8 23 Smoke(Photo) ROOM B40 BUILDING 5
399 8 25 Smoke(Photo) IN ROOM A31 BUILDING 5
400 8 26 Smoke(Photo) IN ROOM A31D BUILDING 5
401 8 27 Smoke(Photo) IN ROOM A86 BUILDING 5
402 8 28 Smoke(Photo) ELEVATOR LOBBY GRND FL BLD 5
403 8 29 Smoke(Photo) ELEVATOR LOBBY GRND FL BLD 5
404 8 32 Smoke(Photo) In ROOM E01 BUILDING 5
405 8 33 Smoke(Photo) In ROOM E01 BUILDING 5
406 8 34 Smoke(Photo) HALL BY RM E09 BUILDING 5
407 8 35 Smoke(Photo) BY SERVICE ELEV BLD 5 GRND
408 8 36 Heat In ROOM E03A BUILDING 5
409 8 37 Smoke(Photo) In ROOM E23 BUILDING 5
410 8 38 Smoke(Photo) HALL BY RM A26 BLD 5
411 8 40 Smoke(Photo) In ROOM A31C BUILDING 5
412 8 41 Smoke(Photo) ROOM A31E BUILDING 5
413 8 44 DuctSmoke(P) ONCOLOGY DUCT DOUBLE DOOR (Supervisory)
414 8 45 Smoke(Photo) ONC DBL DR CORR SIDE SMOKE
415 8 46 Smoke(Photo) ONC DBL DR ONC SIDE SMOKE
416 8 50 Smoke(Photo) PT MAIN GYM SW DET ROOM A70
417 8 51 Smoke(Photo) PT MAIN GYM NW DET ROOM A70
418 8 52 Smoke(Photo) PT MAIN GYM SE DET ROOM A70
419 8 53 Smoke(Photo) PT MAIN GYM NE DET ROOM A70
420 8 54 Smoke(Photo) HALL BY A54 BUILDING 5
421 8 55 Smoke(Photo) HALL BY A56 BUILDING 5
422 8 56 Smoke(Photo) HALL BY A57 BUILDING 5 note: smoke det. is in fuction to release smoke window RM B40
423 8 57 Smoke(Photo) HALL BY A58 BUILDING 5
424 8 58 Smoke(Photo) HALL BY A 59 BUILDING 5
425 8 59 Smoke(Photo) HALL BY A87 BUILDING 5
426 8 60 Smoke(Photo) HALL BY A60 BUILDING 5
427 8 61 Smoke(Photo) HALL BY A62 BUILDING 5
428 8 64 Smoke(Photo) RM A87 BUILDING 5
429 8 68 DuctSmoke(P) ONCOLOGY DUCT RETURN RM F71C (Supervisory)
430 8 69 DuctSmoke(P) ONCOLOGY DUCT SUPPLY RM F63A (Supervisory)
431 8 75 DuctSmoke(P) AHU 20 IN RM A84A RELAY 2M43
432 8 76 Smoke(Photo) ROOM E125 BUILDING 5
433 8 77 DuctSmoke(P) AHU-1 ROOM E124 RELAY 8M39/South East Side
434 8 79 DuctSmoke(P) AHU-2 ROOM E124 RELAY 8M40/East Side & South
435 8 80 DuctSmoke(P) AHU-2 ROOM E124 RELAY 8M40/North & East of Entry
436 8 81 DuctSmoke(P) AHU-3 IN RM A12 8M41, 7M2/W. Side
437 8 82 DuctSmoke(P) AHU-3 IN RM A12 8M41, 7M2/E. Side
438 8 83 DuctSmoke(P) AHU-4 IN RM A12 RELAY 8M42/S.E. Side
439 8 84 DuctSmoke(P) AHU-4 IN RM A12 RELAY 8M42/N.E. Side
440 8 91 Smoke(Photo) IN ROOM W5 BUILDING 5
441 8 92 Smoke(Photo) CORR BY ROOM A53 BUILDING 5
442 8 94 Heat SOUTH OH DOOR RM W01
443 8 95 Heat NW INSIDE OH DOOR W01
444 8 96 Heat NW OUTER OH DOOR W01
445 8 97 Smoke(Photo) 1ST FLR LAB MECH SPC E ROOM 1016
446 8 98 Smoke(Photo) 1ST FLR LAB MECH SPC E ROOM 1016
447 8 99 Smoke(Photo) 1ST FLR LAB MECH SPC E ROOM 1016
448 8 100 Smoke(Photo) 1ST FLR LAB MECH SPC SE ROOM 1016
449 8 101 Smoke(Photo) 1ST FLR LAB MECH SPC SE ROOM 1016
450 8 102 Smoke(Photo) 1ST FLR LAB MECH SPC S ROOM 1016
451 8 103 Smoke(Photo) 1ST FLR LAB MECH SPC S ROOM 1016
452 8 104 Smoke(Photo) 1ST FLR LAB MECH SPC CTR RM 1016
453 8 105 Smoke(Photo) 1ST FLR LAB MECH SPC CTR RM 1016
454 8 106 Smoke(Photo) 1ST FLR LAB MECH SPC CTR RM 1016
455 8 107 Smoke(Photo) 1ST FLR LAB MECH SPC N RM 1016
456 8 108 Smoke(Photo) 1ST FLR LAB MECH SPC N RM 1016
457 8 109 Smoke(Photo) 1ST FLR LAB MECH SPC N RM 1016
458 8 110 Smoke(Photo) 1ST FLR LAB MECH SPC N RM 1016
459 8 111 Smoke(Photo) 1ST FLR LAB MECH SPC N RM 1016
460 8 112 Smoke(Photo) 1ST FLR LAB MECH SPC N RM 1016
461 8 113 Smoke(Photo) 1ST FLR LAB MECH SPC CTR RM 1016
462 8 114 Smoke(Photo) 1ST FLR LAB MECH SPC CTR RM 1016
463 8 115 Smoke(Photo) 1ST FLR LAB MECH SPC CTR RM 1016
464 8 116 Smoke(Photo) 1ST FLR LAB MECH SPC SW RM 1016
465 8 117 Smoke(Photo) 1ST FLR LAB MECH SPC SW RM 1016
466 8 118 Smoke(Photo) 1ST FLR LAB MECH SPC SW RM 1016
467 8 119 Smoke(Photo) 1ST FLR LAB MECH SPC SW RM 1016
468 8 120 Smoke(Photo) 1ST FLR LAB MECH SPC WEST RM 1016
469 8 121 Smoke(Photo) 1ST FLR LAB MECH SPC WEST RM 1016
470 8 122 Smoke(Photo) 1ST FLR LAB MECH SPC NW RM 1016
471 8 123 Smoke(Photo) 1ST FLR LAB MECH SPC WEST RM 1016
472 8 124 Smoke(Photo) 1ST FLR LAB MECH SPC WEST RM 1016
473 8 125 Smoke(Photo) 1ST FLR LAB MECH SPC WEST RM 1016
474 8 126 Smoke(Photo) 1ST FLR LAB MECH SPC WEST RM 1016
475 8 127 Sup L(Duct P) 1ST FLR LAB MECH SPC NE ROOM 1016
476 8 129 Sup L(Duct P) 1ST FLR LAB MECH SPC WEST RM 1016
477 8 132 Heat LAB RM 2095 BLD 5 2ND FL
478 8 133 Smoke(Photo) LAB STGE S 2085 BLD 5 2ND FL
479 8 134 Smoke(Photo) LAB STGE N 2085 BLD 5 2ND FL
480 8 135 Smoke(Photo) LAB STGE 2088 B BLD 5 2ND FL
481 8 136 Smoke(Photo) LAB HALL 2060 BLD 5 2ND FL
482 8 137 Smoke(Photo) LAB LOBBY 2001 BLD 5 2ND FL
483 8 138 Smoke(Photo) LAB LOBBY 2001 BLD 5 2NF FL
484 8 139 Smoke(Photo) LAB LOBBY 2001 BLD 5 2ND FL
485 8 140 Smoke(Duct P) LAB LOBBY 2001 BLD 5 2N FL
486 8 141 Sup L(Duct P) LAB LOBBY 2001 BLD 5 2ND FL
487 8 142 Heat LAB HSK 2079 BLD 5 2ND FL
488 8 146 Sup L(Duct P) LAB LOBBY 2001 BLD 5 2ND FL
489 8 147 Sup L(Duct P) LAB HALL N 2000 BLD 5 2ND FL
490 8 148 Sup L(Duct P) LAB HALL 2000 BLD 5 2ND FL
491 8 149 Sup L(Duct P) LAB HALL W 2000 BLD 5 2ND FL
492 8 150 Smoke(Photo) NAC PNL MECH SPAC BLD 5 1ST FL
493 9 1 DuctSmoke(P) AHU-36…
This is the start of the file's text. The full file is on GovTribe.