Attachment C Device List.pdf

PDF 919 KB Posted

Attached to
H342--Fire Systems Inspections and Maintenance Federal contract opportunity
Solicitation number
36C26323Q0807
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 23

About this file

This document contains the results of an inspection of the fire alarm system in Building 5 of the Sioux Falls VA Medical Center.

The inspection reviewed the control panel, annunciators, amplifiers, notification appliance circuits, smoke detectors, heat detectors, duct detectors, manual pull stations, waterflow switches, tamper switches, audible and visual notification devices, door holders, and releasing devices. Key details include the manufacturer and models of the control panel and various components, their locations throughout the building, and the results of testing each component to verify they are in good working condition. The inspection was conducted in accordance with NFPA 72 standards on a semi-annual basis.

View the file

Other files for this federal contract opportunity

Other files attached to H342--Fire Systems Inspections and Maintenance, newest first.
File Type Posted
36C26323Q0807_2.docx DOCX document
Attachment A- Hospice Cottage Drawing.pdf PDF
Attachment B- Fire Damper Master List.pdf PDF
RFQ 36C26323Q0807.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Inspection: Visual Inspection Manufacturer: Notifier

Frequency: Semi-Annual Model Number: IFC2-640 (IFC-3030) Date:

Code REF: NFPA 72 Table 14.3.1 Location: 037-1 W/O#

NODE # 8 Disconnecting Means Location: RM 001B-1 Disconnecting Means: Panel EM, Breaker 15

Line Item #

Loop/ Node#

Equip.

Address

Equipment Model # Description/Location

Location

OK / CA

Condition

OK / CA

1 8 IFC2-640 Fire Alarm Control Panel/Basement Room 037-1

2 JNCA Remote Annunciator/ 1st Floor Corridor 100 By Elevator

3 9 1 DAA2-5070 Amp Panel #1/Basement Room 037 In FACP Enclosure

4 9 2 DAA2-5070 Amp Panel #2/Basement Room 037 In Amp Cabinet #1

5 2 50 ACPS-610PCA NAC Panel/Basement Room 037 Inside FA Cabinet

6 9 3 DAA2-5070 Amp #3/BSMT RM 037 In Amp Cabinet #1

7 n/a n/a E/Clips Transient Suppressors/Basement Room 037

8 1 52 FCPS-24FSPCA 2nd Floor NAC #1 BLD 1 Tower/Room 240

9 1 53 FCPS-24FSPCA 2nd Floor NAC #2 BLD 1 Tower/Room 240

Fire Alarm System Control Panel, Annunciators, & Other (March) Location: SFVAMC Building #1

Address: 2501 W. 22nd St.

City/State/Zip: SF, SD 57105

Contact: Dave Dirks Inspected By: Adam Thompson

Phone: 605-336-3230 ext 6038 CA = Corrective Action Phone: 323-8627

Comments note: JNCA2 Global Display replaced by JCI March 2018

Code REF: NFPA 72 Table 14.3.1 Location: 037-1 W/O#

Disconnecting Means Location: RM 001B-1 Disconnecting Means: Panel EM, Breaker 15

Line Item # Loop #

Device Address Device Type Description/Location

Location

OK / CA

Condition

OK / CA

1 1 2 Smoke(Photo) Hall By RM 31 BLDG 1 BSMT

2 1 3 Smoke(Photo) Hall By RM 29 BLDG 1 BSMT

3 1 4 Smoke(Photo) HALL BY RM 28 BLDG 1 BSMT

4 1 5 Smoke(Photo) HALL BY RM 26 BLDG 1 BSMT

5 1 6 Smoke(Photo) HALL BY RM 037 BLDG 1 BSMT

6 1 7 Smoke(Photo) IN ROOM 37 BLDG 1 BSMT

7 1 11 Smoke(Photo) IN ROOM 1 B BLDG 1 BSMT

8 1 12 Smoke(Photo) IN ROOM 1 C BLDG 1 BSMT

9 1 13 Smoke(Photo) HALL BY RM 20 BLDG 1 BSMT

10 1 14 Smoke(Photo) HALL BY ROOM 2 BLDG 1 BSMT

11 1 15 Smoke(Photo) HALL BY ROOM 4 EAST BLDG 1 BSMT

12 1 20 DuctSmoke(P) North Mech Room BLD 1 1ST FL

13 1 22 HEAT (200) HEAT DETECTORS BLDG 1 ATTIC

14 1 26 Smoke(Photo) IN ROOM 143 BLD 1 1ST FL

15 1 27 Smoke(Photo) HALL BY RM 141 BLD 1 1ST FL

16 1 28 Smoke(Photo) IN ROOM 144 BLD 1 1ST FL

17 1 29 Smoke(Photo) HALL BY ROOM 137 BLD 1 1ST FL

18 1 30 Smoke(Photo) HALL BY ROOM 135 BLD 1 1ST FL

19 1 31 Smoke(Photo) HALL BY ROOM 149 BLD 1 1ST FL

20 1 32 Smoke(Photo) CORR 100 BLD 1 1ST FL

21 1 33 Smoke(Photo) HALL BY ROOM 101 BLD 1 1ST FL

22 1 34 Smoke(Photo) HALL BY ROOM 129 BLD 1 1ST FL

23 1 35 Smoke(Photo) B&C ELEV MACHINE RM BLD 1 3RD FL

24 1 36 HEAT B&C ELEV MACHINE RM BLD 1 3RD FL

25 1 38 Smoke(Photo) ELEVATOR C HOISTWAY BLD 1 3RD FL

26 1 39 Smoke(Photo) 3RD FLR B&C ELEV LOB BLD 1 3RD FL

27 1 40 DuctSmoke(P) CORR BY RM 206 BLD1 2ND FL

28 1 41 DuctSmoke(P) CORR BY RM 201 BLD 1 2ND FL

29 1 42 DuctSmoke(P) RM 223A DUCT BLD 1 2ND FL (Supervisory)

30 1 43 DuctSmoke(P) RM 223A DUCT BLD 1 2ND FL (Supervisory)

31 1 44 DuctSmoke(P) ROOM 307B DUCT BLD 1 3RD FL / RT is by RM 307C

32 1 45 DuctSmoke(P) ROOM 307B DUCT BLD 1 3RD FL / RT is by RM 307C

33 1 46 Smoke(Photo) 2ND FLR B&C ELEV LOB BLD 1 2ND FL

34 1 47 DuctSmoke(P) ATTIC BY RM 308 BLD 1 3RD FL / RT is by RM 308

35 1 48 Smoke(Photo) HALL BY ROOM 202 BLD 1 2ND FL

**can't locate duct smoke but remote test is in this location

**Need to update description because this is no longer elevator lobby 10-2022 device is in access panel in Room 308

Fire Alarm System Smokes & Heats (March) Location: SFVAMC Building #1

Address: 2501 W. 22nd St.

City/State/Zip: SF, SD 57105

Contact: Dave Dirks Inspected By: Adam Thompson

Phone: 605-336-3230 ext 6038 CA = Corrective Action Phone: 323-8627

**Need to update description because this is no longer elevator lobby 10-2022

36 1 49 Smoke(Photo) Hall By RM 206 BLD 1 2ND FL

37 1 50 Smoke(Photo) ELEVATOR B HOISTWAY BLD 1 3RD FL

38 1 51 Smoke(Photo) ED SUITE LINK BLD 1 1st FL

39 1 52 Heat ED SUITE RM 124B BLD 1 1st FL

40 1 53 Smoke(Photo) ED SUITE RM 123A W. BLD 1 1st FL

41 1 54 Smoke(Photo) ED SUITE RM 123A E. BLD 1 1st FL

42 1 55 Smoke(Photo) ED SUITE RM 124A BLD 1 1st FL

43 1 56 Smoke(Photo) ED SUITE RM 124A BLD 1 1st FL

44 1 57 DuctSmoke(P) ED SUITE RM 123A AHU BLD 1 1st FL

45 1 58 DuctSmoke(P) ED SUITE RM 124A AHU BLD 1 1st FL

46 1 59 DuctSmoke(P) ATTIC BY RM 308 BLD 1 3RD FL / RT is by RM 308

47 1 60 DuctSmoke(P) ATTIC BY RM 313 BLD 1 3RD FL /RT by mirror in Elev Lobby

48 1 61 Smoke(Photo) HALL BY ROOM 332 BLD1 3RD FL

49 1 62 Smoke(Photo) WAITING AREA BLD1 3RD FL

50 1 63 Smoke(Photo) HALL BY ROOM 303 BLD1 3RD FL

51 1 64 Smoke(Photo) HALL BY ROOM 307D BLD1 3RD FL

52 1 65 Smoke(Photo) WAITING ROOM 312 BLD1 3RD FL

53 1 66 DuctSmoke(P) BCU 1 RETURN RM 237 BLD1 2ND FL

54 1 67 Smoke(Photo) CORR BY MECH 237 BLD1 2ND FL

55 1 68 Smoke(Photo) MH2 RM 236 BLD1 2ND FL

56 1 69 Smoke(Photo) MH2 WAITING BLD1 2ND FL

57 1 70 Smoke(Photo) MH2 RM 235 BLD1 2ND FL

58 1 71 Smoke(Photo) MH2 BY RM 235 BLD1 2ND FL/Sally Port

59 1 72 Smoke(Photo) MH2 CORR. By RM 214 BLD1 2ND FL

60 1 73 Smoke(Photo) MH2 By DINNING RM 216 BLD1 2ND FL

61 1 74 Smoke(Photo) MH2 RM 231 BLD1 2ND FL

62 1 75 Smoke(Photo) MH2 RM 230 BLD1 2ND FL

63 1 76 Smoke(Photo) MH2 By RM 230 BLD1 2ND FL

64 1 77 Smoke(Photo) MH2 RM 217 BLD1 2ND FL

65 1 78 Smoke(Photo) MH2 RM 229 BLD1 2ND FL

66 1 79 Smoke(Photo) MH2 By RM 229 BLD1 2ND FL

67 1 80 Smoke(Photo) MH2 RM 218 BLD1 2ND FL

68 1 81 Smoke(Photo) MH2 RM 228 BLD1 2ND FL

69 1 82 Smoke(Photo) MH2 RM 219 BLD1 2ND FL

70 1 83 Smoke(Photo) MH2 Hall By RM 227 BLD1 2ND FL

71 1 84 DuctSmoke(P) BCU 2 RETURN RM 224 BLD1 2ND FL

72 1 85 DuctSmoke(P) ATTIC BY RM 335 BLD 1 3RD FL / RT across from RM 315

73 1 86 DuctSmoke(P) ATTIC BY RM 323 BLD 1 3RD FL / RT By RM 326

74 1 87 Smoke(Photo) 1ST FLR B&C ELEV LOB BLD 1 1ST FL

75 1 88 Smoke(Photo) BSMT B&C ELEV BLD 1 BSMT

76 1 91 DuctSmoke(P) AHU-1 ROOM 033 BLD1 BSMT

77 2 15 Smoke(Photo) 3RD FL E STR 352B BLD 1 TOWER

78 2 16 Smoke(Photo) HALL BY ROOM 4 WEST BLDG 1 BSMT

**Need to update description because this is no longer elevator lobby 10-2022

**Need to update description because this is no longer elevator lobby 10-2022 update description as indicated 4-2020 verify location device is in access panel in Room 308 update description as indicated 4-2020 verify location

79 2 17 Smoke(Photo) 1ST FLR TOWER EAST BLD 1 1ST FL

80 2 18 Smoke(Photo) TOWER EAST STAIRWELL BLD 1 1ST FL

81 2 19 Smoke(Photo) 2ND S DAMP RM 247 BLD 1 TOWER

82 2 20 DuctSmoke(P) 2ND N DAMP RM 247 BLDG BLD 1 TOWER

83 2 23 Smoke(Photo) 3RD FL S RM 357 BLD 1 TOWER

84 2 24 DuctSmoke(P) BASE DAMP S RM 051 BLD 1 TOWER

85 2 25 DuctSmoke(P) BASE DAMP N RM 051 BLD 1 TOWER

86 2 95 Smoke(Photo) ELEV A LOBBY 051 BLD1 TOWER

87 2 96 Smoke(Photo) BSMT W STR 009A BLD1 TOWER

88 2 98 Smoke(Photo) BSMT W CORR 47 BLD1 TOWER

89 2 99 Smoke(Photo) BSMT E CORR 047 BLD1 TOWER

90 2 100 Smoke(Photo) BASE RISER RM 012 BLD1 TOWER

91 2 101 Smoke(Photo) BSMT STR STR 007B BLD1 TOWER

92 2 103 Sup L(Duct P) BASE DAMP RM 10 S BLD1 TOWER

93 2 104 Sup L(Duct P) BASE DAMP RM 10 N BLD1 TOWER

94 2 107 Smoke(Photo) 1ST FL E CORR 154A BLD1 TOWER

95 2 108 Smoke(Photo) 1ST FL W CORR 154A BLD1 TOWER

96 2 109 Sup L(Duct P) 1ST FL DAMP RM 117 S BLD1 TOWER

97 2 110 Sup L(Duct P) 1ST FL DAMP RM 117 N BLD1 TOWER

98 2 111 Sup L(Duct P) 1ST FL DAMP RM 157 N BLD1 TOWER

99 2 112 Sup L(Duct P) 1ST FL DAMP RM 157 S BLD1 TOWER

100 2 113 Smoke(Photo) 1ST FL ELEV LOB 157 BLD1 TOWER

101 2 114 Smoke(Photo) 1ST FLR W STR 118A BLD1 TOWER

102 2 117 Smoke(Photo) 2ND FL E STR 239 BLD1 TOWER

103 2 118 Smoke(Photo) 2ND FLR E CORR 241 BLD1 TOWER

104 2 119 Smoke(Photo) 2ND FLR W CORR 241 BLD1 TOWER

105 2 120 Smoke(Photo) 2ND FLR W STR RM244B BLD1 TOWER

106 2 121 Smoke(Photo) 2ND FLR E RM 240 BLD1 TOWER

107 2 122 Smoke(Photo) 2ND FLR CORR 244A BLD1 TOWER

108 2 123 Smoke(Photo) ELEV A 2ND LBY RM 24 BLD1 TOWER

109 2 124 Sup L(Duct P) 2ND FL DAMP RM 248 S BLD1 TOWER

110 2 125 Sup L(Duct P) 2ND FL DAMP RM 248 N BLD1 TOWER

111 2 126 Sup L(Duct P) 2ND FL DAMP RM 244 S BLD1 TOWER

112 2 127 Sup L(Duct P) 2ND FL DAMP RM 244 N BLD1 TOWER

113 2 128 Smoke(Photo) 3RD FL W STR RM358B BLD1 TOWER

114 2 130 Smoke(Photo) 3RD FL W CRRR 358 BLD1 TOWER

115 2 131 Smoke(Photo) ELEV A 3RD RM 361 BLD1 TOWER

116 2 132 Sup L(Duct P) 3RD FL DAMP RM 361 S BLD1 TOWER

117 2 133 Sup L(Duct P) 3RD FL DAMP RM 361 N BLD1 TOWER

118 2 134 Sup L(Duct P) 3RD FL DAMP RM 355 S BLD1 TOWER

119 2 135 Sup L(Duct P) 3RD FL DAMP RM 355 N BLD1 TOWER

120 2 136 Smoke(Photo) 3RD FL N RM 356 BLD 1 TOWER

121 2 137 Smoke(Photo) 3RD FL N RM 355 BLD 1 TOWER

122 2 139 Sup L(Duct P) 3RD FL DAMP RM 360 S BLD1 TOWER

123 2 140 Sup L(Duct P) 3RD FL DAMP RM 360 N BLD1 TOWER

124 2 141 Smoke(Photo) 4TH FL E STR RM 401 BLD1 TOWER

125 2 142 Sup L(Duct P) 4TH FL DMPR RM 410 S BLD1 TOWER

126 2 143 Sup L(Duct P) 4TH FL DMPR RM 410 N BLD1 TOWER

127 2 144 Smoke(Photo) 4TH FL RM 406 BLD1 TOWER

128 2 145 Smoke(Photo) 4TH FL W STR RM 407B BLD1 TOWER

129 2 146 Smoke(Photo) 4TH FLR WEST LANDING BLD1 TOWER

130 2 147 Smoke(Photo) ELEV A SHAFT RM 411A BLD 1 TOWER

131 2 148 Sup L(Duct P) 4TH FL DMPR RM 411 S BLD1 TOWER

132 2 149 Sup L(Duct P) 4TH FL DMPR RM 411 N BLD1 TOWER

133 2 150 Smoke(Photo) 4TH ELEV LOBY RM 411BLD1 TOWER

134 2 151 Smoke(Photo) 4TH ELEV A EQUIP RM BLD1 TOWER

135 2 152 Heat 4TH ELEV A EQUIP RM BLD1 TOWER

136 2 153 Sup L(Duct P) 4TH FL DMPR RM 405 S BLD1 TOWER

137 2 154 Sup L(Duct P) 4TH FL DMPR RM 405 N BLD1 TOWER

138 2 155 Smoke(Photo) 4TH FL RM 405 BLD1 TOWER

139 2 156 Smoke(Photo) 4TH FL RM 404 BLD1 TOWER

Code REF: NFPA 72 Table 14.3.1 Location: 037-1 W/O#

Disconnecting Means Location: RM 001B-1 Disconnecting Means: Panel EM, Breaker 15

Line Item # Loop #

Device Address Device Type Description/Location

Location

OK / CA

Condition

OK / CA

1 1 1 Manual Pull. NORTH STAIRS BLD1 BSMT

2 1 2 Manual Pull. STAIRS BY RM 27 BLD1 BSMT

3 1 3 Manual Pull. STAIR BY RM 2 BLD1 BSMT

4 1 26 Manual Pull. HALL BY ROOM 143 BLD 1 1ST FL

5 1 27 Manual Pull. HALL BY ROOM 135 BLD 1 1ST FL

6 1 41 Manual Pull. HALL BY 105 BLD 1 1st FL

7 1 42 Manual Pull. HALL BY 146 BLDG1 1ST FL N

8 1 43 Manual Pull. HALL BY 141 BLDG1 1ST FL

9 1 44 Manual Pull. STAIR 207A BLD 1 2ND FL / Hall By Room 208

10 1 49 Manual Pull. MENTAL HLTH W STAIRS BLD 1 2ND FL / Hall By RM 206

11 1 61 Manual Pull. HALL BY RM 327 BLD 1 3RD FL

12 1 62 Manual Pull. HALL BY RM 301 BLD 1 3RD FL

13 1 63 Manual Pull. HALL BY RM 308 BLD 1 3RD FL

14 1 79 Manual Pull. BY NORTH STAIRS BLD 1 2ND FL / By RM 223

15 1 80 Manual Pull. BY NURSES STATION BLD 1 2ND FL / MH2 Nurse Station

16 1 81 Manual Pull. BY ED SUITE S EXIT BLD 1 1st FL / Room 123A

17 1 82 Manual Pull. ED SUITE RM 124A W BLD 1 1st FL

18 1 94 Manual Pull. HALL BY 220 BLD 1 2nd FL

19 2 4 Manual Pull. BSMT PULL W STR 009 BLD 1 TOWER

20 2 5 Manual Pull. 1ST FL PULL W CORR 154A BLD 1 TOWER

21 2 17 Manual Pull. 2ND PULL E CORR 241 BLD 1 TOWER

22 2 20 Manual Pull. 3RD FL W CORR 358 BLD 1 TOWER

23 2 27 Manual Pull. 2ND FL PULL W 244 BLD 1 TOWER

24 2 29 Manual Pull. 4TH PULL W CORR 407 BLD 1 TOWER

25 2 30 Manual Pull. 4TH PULL E CORR 403 BLD 1 TOWER

26 2 32 Manual Pull. 1ST FL EAST BLD 1 TOWER

27 2 33 Manual Pull. 3RD FL EAST BLD 1 TOWER

28 2 55 Manual Pull. 1ST FL STR 115B BLD 1 TOWER

29 2 102 Manual Pull. BSMT EAST BLD 1 TOWER

Fire Alarm System Manual Pull-Stations & Other (March) Location: SFVAMC Building #1

Address: 2501 W. 22nd St.

City/State/Zip: SF, SD 57105

Contact: Dave Dirks Inspected By: Adam Thompson

Phone: 605-336-3230 ext 6038 CA = Corrective Action Phone: 323-8627

FIX DESCRIPTION SHOULD BE CORR 115A

Code REF: NFPA 72 Table 14.3.1 Location: 037-1 W/O#

Disconnecting Means Location: RM 001B-1 Disconnecting Means: Panel EM, Breaker 15

Line Item # Device Type Description/Location

Location

OK / CA

Condition

OK / CA

1 Speaker Basement West By Room 004 West

2 Speaker Basement West By Room 004 East

3 Speaker Basement West Room 004

4 Speaker Basement West By Room 017

5 Speaker Basement West By Room 023

6 Speaker/Strobe Basement Center Elevator Lobby

7 Strobe Basement West Rest Room 021

8 Speaker Basement North By Room 034B

9 Strobe Basement North Restroom 026

10 Speaker Basement North Fitness Room 034 South

11 Speaker Basement North By Room 029

12 Speaker Basement North Room 029

13 Speaker Basement North By Room 032

14 Speaker Basement North Room 032

15 Speaker 1st North Room 143

16 Speaker 1st North By Room 144

17 Strobe 1st North Restroom 141

18 Speaker 1st North By Room 138

19 Speaker 1st North By Room 134

20 Strobe 1st Center South of Elevator Above Fire Alarm Annunciator

21 Speaker 1st West By North East Entry

22 Speaker/Strobe 1st West Elevator Lobby

23 Strobe 1st West Restroom 131

24 Speaker 1st West By Room 103

25 Speaker 1st West By Room 129

26 Strobe 1st West Education Foyer 123A West Wall

27 Speaker/Strobe 1st West Education Foyer 123A East Wall

28 Strobe 1st West Education Classroom 124 S.W. Wall

29 Strobe 1st West Education Classroom 124 S.E. Wall

30 Speaker/Strobe 2nd West By Room 206

31 Speaker/Strobe 2nd West By Room 209

32 Strobe 2nd West Restroom 211

33 Strobe 2nd Center Restroom 211A

34 Speaker/Strobe 2nd Center By Restroom 211A

35 Strobe 2nd Center MH2 Waiting Area

1AV6a

1AV20a

1A12

1AV41

1V42

1V30

1V31

1AV37

1AV38

1V39

1V40

1A20

1V21

1A22

1A23

1V28

1AV29

1A14

1A15

1V16

1A17

1A18

1V19

1A8

1V9

1A10

1A11

1A11A

1A13

Equipment ID 1A2

1A3

1A4

1A5

1A6

1V7 temporarily removed for construction 5-2022

Phone: 605-336-3230 ext 6038 CA = Corrective Action Phone: 323-8627

Comments

Fire Alarm System Audibles & Visuals (March) Location: SFVAMC Building #1

Address: 2501 W. 22nd St.

City/State/Zip: SF, SD 57105

Contact: Dave Dirks Inspected By: Adam Thompson

36 Speaker 2nd Center MH2 Waiting Area

37 Speaker/Strobe 2nd Center Elevator Lobby

38 Strobe 2nd Center Sally Port 213

39 Strobe 2nd Center Room 236

40 Speaker 2nd Center Room 234

41 Speaker/Strobe 2nd North By Day Room 216

42 Speaker/Strobe 2nd North By Room 230

43 Speaker/Strobe 2nd North By Room 250A

44 Speaker/Strobe 2nd North By Room 227

45 Speaker 2nd North By Room 220

46 Strobe 2nd North By Room 220

47 Speaker 2nd North Room 225

48 Strobe 2nd North Room 225

49 Speaker 3rd North By Room 326

50 Speaker 3rd North By Room 329

51 Speaker 3rd North By Room 333

52 Strobe 3rd North Restroom 316

53 Speaker 3rd Center By Room 337

54 Speaker/Strobe 3rd Center Elevator Lobby

55 Strobe 3rd West Restroom 310

56 Speaker 3rd West By Room 309

57 Speaker 3rd West By Room 307

58 Speaker/Strobe BSMT Tower By Room 012

59 Speaker/Strobe BSMT Tower By Room 011

60 Speaker/Strobe BSMT Tower By Room 010

61 Speaker/Strobe BSMT Tower Room 008 West

62 Speaker/Strobe BSMT Tower Room 008 East

63 Speaker/Strobe BSMT Tower Room 010

64 Speaker/Strobe BSMT Tower Room 009 By Exit

65 Speaker/Strobe BSMT Tower Room 009A By Elevator

66 Strobe BSMT Tower Room 009A South of Elevator

67 Speaker/Strobe 1st Floor Tower East Stairwell Room 115

68 Speaker/Strobe 1st Floor Tower East

69 Speaker/Strobe 1st Floor Tower By Room 117

70 Speaker/Strobe 1st Floor Tower By Room 117

71 Speaker/Strobe 1st Floor Tower Room 116 West

72 Speaker/Strobe 1st Floor Tower Room 116 East

73 Speaker/Strobe 1st Floor Tower Room 117 East

74 Speaker/Strobe 1st Floor Tower Room 117 West

75 Speaker/Strobe 1st Floor Tower Room 118A Stairwell

76 Speaker/Strobe 1st Floor Tower Room 118 By Elevator

77 Strobe 1st Floor Tower Room 118 Restroom By Elevator

78 Speaker/Strobe 2nd Floor Tower Room 239 East Stairs

1AV56a

1AV77

1V78

1AV79

1AV71

1AV72

1AV73

1AV74

1AV75

1AV76

1AV65

1AV66

1AV67

1V68

1AV69

1AV70

1V57

1A58

1A59

1AV62

1AV63

1AV64

1AV60

1AV61

1AV69A

1A51a

1V51b

1A52

1A54

1V55

1A56

1AV46

1AV47

1AV48

1AV49

1A50

1V51

1A53

1A43

1V44

1V45

1A45a

1AV43a

79 Speaker/Strobe 2nd Floor Tower By Room 242

80 Speaker/Strobe 2nd Floor Tower By Room 244

81 Speaker/Strobe 2nd Floor Tower West Stairwell 244B

82 Speaker/Strobe 2nd Floor Tower Room North of Stairwell

83 Speaker/Strobe 2nd Floor Tower Room 244A By Elevator

84 Strobe 2nd Floor Tower Room 244A South of Elevator

85 Speaker/Strobe 3rd Floor Tower Room 352 By East Stairwell

86 Speaker/Strobe 3rd Floor Tower By Room 359

87 Speaker/Strobe 3rd Floor Tower Room 355 South West

88 Speaker/Strobe 3rd Floor Tower Room 355 North West

89 Speaker/Strobe 3rd Floor Tower Room 355 North East

90 Speaker/Strobe 3rd Floor Tower West Stairwell Room 358B

91 Speaker/Strobe 3rd Floor Tower Room 358 North of West Stairwell

92 Speaker/Strobe 3rd Floor Tower Room 358A By Elevator

93 Strobe 3rd Floor Tower Room 358A South of Elevator

94 Speaker/Strobe 4th Floor Tower Room 401 By East Stairwell

95 Speaker/Strobe 4th Floor Tower By Room 409

96 Speaker/Strobe 4th Floor Tower Room 404 South West

97 Speaker/Strobe 4th Floor Tower Room 404 North West

98 Speaker/Strobe 4th Floor Tower Room 404 North East

99 Speaker/Strobe 4th Floor Tower East Stairwell Room 407B

100 Speaker/Strobe 4th Floor Tower Room 407 North of East Stairwell

101 Speaker/Strobe 4th Floor Tower Room 407A By Elevator

102 Strobe 4th Floor Tower Room 407A South of Elevator

1AV95

1AV96

1AV97

1AV98

1AV99

1AV100

1AV89

1AV90

1AV91

1AV92

1AV93

1V94

1AV83

1AV84

1V85

1AV101

1AV102

1V103

1AV86

1AV87

1AV88

1AV80

1AV81

1AV82

Code REF: NFPA 72 Table 14.3.1 Location: 037-1 W/O#

Disconnecting Means Location: RM 001B-1 Disconnecting Means: Panel EM, Breaker 15

Line Item # Device Type Description/Location

Location

OK / CA

Condition

OK / CA

1 Door Holder Basement By Room 012 West Door N/A N/A

2 Door Holder Basement By Room 012 East Door N/A N/A

3 Door Holder Basement West of Room 017

4 Door Holder Basement East of Room 017

5 Door Holder Basement West of Room 020

6 Door Holder Basement Center Door to Elevator Lobby

7 Door Holder Basement South of Room 027

8 Door Holder Basement North of Room 027

9 Door Holder Basement Corridor 041B South Door

10 Door Holder Basement Corridor 041B North Door

11 Door Holder 1st Stair C Top of Stairs By Emergency Exit

12 Door Holder 1st By Room 129

13 Door Holder 1st By Room 101

14 Door Holder 1st Door to Elevator Lobby

15 Door Holder 1st By Room 133

16 Door Holder 1st By Room 135

17 Door Holder 1st Stair D Top of Stairs By Emergency Exit

18 Door Holder 1st By Room 137

19 Door Holder 1st By Room 141

20 Door Holder 1st Door to Room 143

21 Door Holder 1st Door to Room 144 (door inside 143 that leads to 144)

22 Door Holder 2nd By Room 206

23 Door Holder 2nd By Room 208

24 Door Holder 2nd By Room 238 North Door

25 Door Holder 2nd By Room 238 South Door

26 Door Holder 2nd Door to Elevator Lobby

27 Door Holder 3rd By Room 307E

28 Door Holder 3rd By Room 310

29 Door Holder 3rd Door to Elevator Lobby

30 Door Holder 3rd By Room 333

31 Door Holder BSMT West Stairs by Elevator in Tower

32 Door Holder 1st West Stairs by Elevator in Tower

33 Door Holder 2nd West Stairs by Elevator in Tower

34 Door Holder 3rd West Stairs by Elevator in Tower

35 Door Holder 4th West Stairs by Elevator in Tower1DH31

1DH28

1DH29

1DH30

1DC25

1DC26

1DH27

1DH25a

1DH21

1DC23

1DC24

1DC18

1DC19a

1DH20

1DC22

1DC19

1DH23a

1DC16

1DC16a

1DC17

1DC12a

1DC13

1DC14

1DC15

1DC14a

1DC8

1DC9

1DC10

1DC5

1DC6

1DC7

1DH6a

1DC3 Not used & needs REMOVED 4-2022

1DC4

Phone: 605-336-3230 ext 6038 CA = Corrective Action Phone: 323-8627

Equipment ID Comments

Fire Alarm System Releasing Devices (March) Location: SFVAMC Building #1

Address: 2501 W. 22nd St.

City/State/Zip: SF, SD 57105

1DC2 REMOVED FOR CONSTRUCTION 4-2022

Inspection: Testing Manufacturer: Notifier

Frequency: Semi-Annual Date:

Code REF: NFPA 72 Table 14.4.3.2 Location: 037-1 W/O#

Disconnecting Means Location: RM 001B-1 Disconnecting Means: Panel EM, Breaker 15

Line Item #

Batt.

Type

Rated Ah

Rated Voltage Description/Location

Load Tst Volts

Tested Ah

Visual Check

Battery Dated

1 SLA 26ah 12V Basement FACP/Room 037(Right)(also for AMP1 & NAC Pan.) 3-22

2 SLA 26ah 12V Basement FACP/Room 037(Left)(also for AMP1 & NAC Panel) 3-22

3 SLA 12ah 12V Basement Amp #2/Room 037 (Bottom) (AMP Cab #1) 3-22

4 SLA 12ah 12V Basement Amp #2/Room 037 (Top) (AMP Cab #1) 3-22

5 SLA 12ah 12V Basement Amp #3/Room 037 (Bottom) (AMP Cab #1) 3-22

6 SLA 12ah 12V Basement Amp #3/Room 037 (Top) (AMP Cab #1) 3-22

7 SLA 8ah 12V 2nd Floor NAC #1 BLD 1 Tower/Room 240 (Left) 10-21

8 SLA 8ah 12V 2nd Floor NAC #1 BLD 1 Tower/Room 240 (Right) 10-21

9 SLA 8ah 12V 2nd Floor NAC #2 BLD 1 Tower/Room 240 (Left) 10-21

10 SLA 8ah 12V 2nd Floor NAC #2 BLD 1 Tower/Room 240 (Right) 10-21

Comments/Test Results

Contact: Dave Dirks Inspected By: Adam Thompson

Phone: 605-336-3230 ext 6038 SLA = Sealed Lead Acid Phone: 323-8627

Fire Alarm System Battery Load Voltage Testing (March) Location: SFVAMC Building #1

Address: 2501 W. 22nd St.

City/State/Zip: SF, SD 57105

Model Number: IFC2-640 (IFC-3030), ACPS610(Signal Exp.)

Inspection: Testing Manufacturer: Notifier

Code REF: NFPA 72 Table 14.4.3.2 Location: 037-1 W/O#

Disconnecting Means Location: RM 001B-1 Disconnecting Means: Panel EM, Breaker 15

Line Item # Loop #

Device Address Device Type Description/Location

Location

OK / CA

Test

OK / CA

1 1 11 Waterflow Waterflow In RM 27 BLD1 BSMT/RM 27 in Basement

2 1 12 Tamper RM 27 Sprnkler Mon BLD1 BSMT/RM 27 in Basement

3 1 13 Tamper RM 27 Sprnkler Mon BLD1 BSMT/RM 27 in Basement

4 1 14 Tamper RM 27 Sprnkler Mon BLD1 BSMT/RM 27 in Basement

5 1 15 Waterflow Waterflow Attic BLD 1 Attic/BSMT RM 27

6 1 18 Waterflow Waterflow Stor RM 23 BLD1 BSMT/Ctr Basement Stor RM 23

7 1 19 Tamper Stor RM 23 BLD1 BSMT/Basement Store RM 23

8 1 24 Tamper PIV E SIDE OF BLD BLD 1 BSMT/E. Side of Bldg By RM 034

9 1 32 Waterflow Room 133B BLD 1 1st FL North/RM 133B

10 1 33 Tamper Room 133B BLD 1 1st FL North/RM 133B

11 1 37 Waterflow RM 131A Waterflow BLD 1 1st FL BLD 1 1st West/1st RM 131A

12 1 38 Tamper RM 131A JAN Closet BLD 1 1st FL/1st Floor RM131A Jan RM

13 1 39 Waterflow RM 156 Waterflow BLD 1 1st FL/1st Floor RM 156

14 1 40 Tamper Mech RM 156 BLD 1 1st FL/1st Floor Mech RM 156

15 1 47 Waterflow MH2 RM 214A Flow BLD 1 2nd FL/MH2 2nd Flr RM 214A

16 1 48 Tamper MH2 RM 214A BLD 1 2nd FL/MH2 2nd Floor RM 214A

17 1 50 Waterflow RM 210 Waterflow BLD 1 2nd FL BLD 1 2nd W./2nd Flr RM 210

18 1 51 Tamper Jan Closet RM 210 BLD 1 2nd FL/2nd Floor Jan RM 210

19 1 66 Waterflow RM 311 Waterflow BLD 1 3rd FL/3rd Floor Store RM 311

20 1 67 Tamper Stor RM 311 3rd FL BLD 1 3rd FL/3rd Floor Store RM 311

21 1 68 Waterflow RM 315 Waterflow BLD 1 3rd FL/3rd Floor Store RM 315

22 1 69 Tamper Stor RM 315 3rd FL BLD 1 3rd FL/3rd Floor Store RM 315

23 2 60 Waterflow 4TH FL FLOW BLD 1 TOWER

24 2 113 Waterflow BSMT FLOW BLD 1 TOWER

25 2 114 Tamper BSMT TAMPER BLD 1 TOWER

26 2 115 Waterflow 2ND FL FLOW BLD 1 TOWER

27 2 116 Tamper 2ND FL TAMPER BLD 1 TOWER

28 2 117 Waterflow 3RD FL FLOW BLD 1 TOWER

29 2 118 Tamper 3RD FL TAMPER BLD 1 TOWER

30 2 120 Tamper 4TH FL TAMPER BLD 1 TOWER

31 2 131 Waterflow 1ST FL WATERFLOW BLD 1 TOWER/IN ROOM 122 ABV CEILING

32 2 132 Tamper 1ST FL TAMPER BLD 1 TOWER/IN ROOM 122 ABV CEILING

**NEED WATERFLOW IN DESCRIPTION 10-11-2022

note: cover is off due to too close to ceiling

Fire Alarm System Sprinkler Flow & Control Valve (March) Location: SFVAMC Building #1

Address: 2501 W. 22nd St.

City/State/Zip: SF, SD 57105

Contact: Dave Dirks Inspected By: Adam Thompson

Phone: 605-336-3230 ext 6038 CA = Corrective Action Phone: 323-8627

Frequency: Semi-Annual Model Number: IFC-3030 Date:

Code REF: NFPA 72 Table 14.3.1 Location: E23-5 W/O#

Disconnecting Means Location: RM E23-5 Disconnecting Means: Panel LCE6, Breaker 10

Line Item #

Node/ Loop #

Equip.

Address

Equipment Model # Description/Location

Location

OK / CA

Condition

OK / CA

1 2 IFC2-3030 Fire Alarm Control Panel/Ground Floor Room E23

2 1 JNCA-2 Global Fire Alarm Annunciator/Ground Floor Room E23

3 Fire Alarm Annunciator/Ground Floor Room A02

4 N/A N/A D9412GV4 Bosch Dialer/Ground Floor Room E23 (DC#1)

5 N/A N/A D9412GV4 Bosch Dialer Expansion/Ground Flr Rm E23 (DC#2)

6 1 47 FCPS-24S8 B96 NAC Control FCPS/Ground Floor Room B96 (#1)

7 3 1 DAA2-5070 Amp Panel #1/Ground Floor Room E23 (Cabinet #1)

8 3 2 DAA2-5070 Amp Panel #2/Ground Floor Room E23 (Cabinet #1)

9 3 3 DAA2-5070 Amp Panel #3/Ground Floor Room E23 (Cabinet #1)

10 3 4 DAA2-5070 Amp Panel #4/Ground Floor Room E23 (Cabinet #1)

11 3 5 DAA2-5070 Amp Panel #5/Ground Floor Room E23 (Cabinet #2)

12 3 6 DAA2-5070 Amp Panel #6/Ground Floor Room E23 (Cabinet #2)

13 3 7 DAA2-5070 Amp Panel #7/Ground Floor Room E23 (Cabinet #2)

14 3 8 DAA2-5070 Amp Panel #8/Ground Floor Room E23 (Cabinet #3)

15 3 9 DAA2-5070 Amp Panel #9/Ground Floor Room E23 (Cabinet #3)

16 3 10 DAA2-5070 Amp Panel #10/Ground Floor Room E23 (Cabinet #3)

17 3 11 DAA2-5070 Amp Panel #11/Ground Floor Room E23 (Cabinet #4)

18 3 12 DAA2-5070 Amp Panel #12/Ground Floor Room E23 (Cabinet #4)

19 3 13 DAA2-5070 Amp Panel #13/Ground Floor Room E23 (Cabinet #4)

20 3 15 DAA2-5070 Amp Panel #15/Ground Floor Room E23 (Cabinet #4)

21 4 120 ACPS-610 NAC Panel ACPS-610 # 1/ Grnd Flr E23 NAC Cabinet #1

22 4 130 ACPS-610 NAC Panel ACPS-610 # 2/ Grnd Flr E23 NAC Cabinet #1

23 4 145 ACPS-610PCB NAC Panel ACPS-610PCB # 3/ Grnd Flr E23 NAC Cabinet #1

24 4 135 ACPS-610 NAC Panel ACPS-610 # 4/ Grnd Flr E23 NAC Cabinet #1

25 5 21 FCPS-24S8 Primary Care NAC Panel RM 1003/1st Floor Room 1003 (#2)

26 9 70 FCPS-24S8 Acute Care NAC Panel RM 228B/2nd Floor (Left Panel) (#3)

27 9 70 FCPS-24S8 Acute Care NAC Panel RM 228B/2nd Floor (Right Panel) (#4)

28 2 82 FCPS-24S8 INT HEALTH BLD RM 118 NAC PANEL (#5)

29 2 83 FCPS-24S8 Womens Center NAC PNL 126/1st Floor Room 126 (#6)

30 2 76 FCPS-24S8 RM 195B FCPS CTRL NAC/1st Floor Room 195B (#7)

31 7 56 FCPS-24S8 O.R RM G03 NAC Panel (#8)

32 8 6 FCPS-24S8 NAC PNL RM A87 (#9)

33 8 46 FCPS-24S8 ONCOLOGY NAC PANEL RM 1021 (#10)

34 5 90 FCPS-24S8 SPEC MED INTERSTITIAL RM 1013 (#11)

35 6 66 FCPS-24S8 3rd Floor Chapel NAC RM 348C/Chapel Area Room 348C (#12)

Phone: 605-336-3230 ext 6038 CA = Corrective Action Phone: 323-8627

Comments

Fire Alarm System Control Panel, Annunciators, & Other (March) Location: SFVAMC Building #5

Address: 2501 W. 22nd St.

City/State/Zip: SF, SD 57105 update description as indicated 4-2022

36 1 8 FCPS-24S8 ED NAC PNL ACTIVATE RM B23/Ground RM B23 (#13)

37 3 16 DAA2-5070 Amp #16/Room 1021 (Top)(Cabinet?)

38 3 93 FCPS-24S8 5th FLR NAC Panel Elec RM 527 (#14)

39 8 104 FCPS-24S8 LAB NAC PANEL/1ST FLR LAB MECH RM 1016 BY 1018 (#15)

40 n/a n/a E/Clips Transient Suppressors/Ground Floor Room E23 Right of FACP

41 n/a n/a DTR-120SR Transient Suppressors/Ground Flr RM E23 In Amp Cabinet 4

Code REF: NFPA 72 Table 14.3.1 Location: E23-5 W/O#

Disconnecting Means Location: RM E23-5 Disconnecting Means: Panel LCE6, Breaker 10

Line Item # Loop #

Device Address Device Type Description/Location

Location

OK / CA

Condition

OK / CA

1 1 7 DuctSmoke(P) ED RM B34 STAFF RR

2 1 8 DuctSmoke(P) ED RM B35 FAM CON RET

3 1 9 DuctSmoke(P) ED RM B35 FAM CON SUP

4 1 10 DuctSmoke(P) ED RM B38B TLT SHOWER

5 1 11 DuctSmoke(P) ED RM B38 HALL

6 1 12 DuctSmoke(P) ED RM B38A ON-CALL

7 1 13 Smoke(Photo) ED BY RM 74A

8 1 14 Smoke(Photo) ED BY RM 77A

9 1 15 Smoke(Photo) ED BY RM 78

10 1 16 Smoke(Photo) ED BY RM 69C

11 1 17 Smoke(Photo) ED BY B68B HALL

12 1 18 Smoke(Photo) ED ABOVE NAC PNL RM B23

13 1 19 Smoke(Photo) ED BT B70 HALL

14 1 20 Smoke(Photo) BY B96 CORR C20 BUILDING 5

15 1 21 Smoke(Photo) CORR. WEST of B97 BUILDING 5

16 1 22 Smoke(Photo) HALL BY RM 21 BUILDING 5

17 1 23 Smoke(Photo) Room D39 Lab Area

18 1 30 Smoke(Photo) HALL BY ROOM D13 BUILDING 5

19 1 40 Heat (Fixed) INFU PENT W DET BUILDING 5

20 1 41 Heat (Fixed) INFU PENT E DET BUILDING 5

21 1 42 Smoke(Photo) RM B96 BUILDING 5

22 1 88 DuctSmoke(P) AHU-8 IN RM D28 RELAY 1M46

23 2 1 Smoke(Photo) BY STAIR 1 1ST FLOOR BUILDING 5

24 2 2 Smoke(Photo) HALL BY ROOM 150 BUILDING 5

25 2 3 Smoke(Photo) Hall By Room 101A BUILDING 5

26 2 4 Smoke(Photo) PATRIOT BREW ROOM 101A BUILDING 5

27 2 5 Smoke(Photo) ROOM 101B DENTAL WAIT BUILDING 5

28 2 6 Smoke(Photo) BY ROOM 138 BUILDING 5

29 2 8 Smoke(Photo) ELEVATOR LOBBY 1ST FLR BUILDING 5

30 2 9 Smoke(Photo) ELEVATOR LOBBY 1ST FLR BUILDING 5

31 2 10 Smoke(Photo) ELEVATOR LOBBY BY RM 141 BLDG 5

32 2 11 Smoke(Photo) HALL N. OF RM 190 BUILDING 5

33 2 12 Smoke(Photo) BY SERVICE ELEVATOR 1ST BUILDING 5

34 2 13 DuctSmoke(P) AHU-30 1ST FL N RM147 RELAY 2M37/N. Side of Unit

35 2 15 Smoke(Photo) COMPUTER RM 178 BUILDING 5

Fire Alarm System Smokes & Heats (March) Location: SFVAMC Building #5

Address: 2501 W. 22nd St.

City/State/Zip: SF, SD 57105

Contact: Dave Dirks Inspected By: Adam Thompson

Phone: 605-336-3230 ext 6038 CA = Corrective Action Phone: 323-8627

Comments removed for construction 3-2022 removed for construction 3-2022

36 2 16 Smoke(Photo) COMPUTER RM 178 BUILDING 5

37 2 17 Smoke(Photo) COMPUTER RM 178 BUILDING 5

38 2 18 Smoke(Photo) COMPUTER RM 178 BUILDING 5

39 2 19 Smoke(Photo) COMPUTER RM 178 BUILDING 5

40 2 20 Smoke(Photo) COMPUTER RM 178 BUILDING 5

41 2 21 Smoke(Photo) COMPUTER RM 178 BUILDING 5

42 2 22 Smoke(Photo) COMPUTER RM 178 BUILDING 5

43 2 23 Smoke(Photo) COMPUTER RM 178 BUILDING 5

44 2 24 Smoke(Photo) COMPUTER RM 178 BUILDING 5

45 2 25 Heat COMPUTER RM 178 BUILDING 5

46 2 26 Heat COMPUTER RM 178 BUILDING 5

47 2 27 Heat COMPUTER RM 178 BUILDING 5

48 2 31 DuctSmoke(P) AHU-12 ROOM 133 RELAY 2M39

49 2 32 DuctSmoke(P) AHU-10 RM 122 Womens Ctr BLD 5

50 2 33 DuctSmoke(P) AHU-9 RM 126A RELAY 2M41

51 2 34 DuctSmoke(P) AHU-13 RM 185 RELAY 2M42

52 2 36 DuctSmoke(P) AHU-21 ROOM 193A RELAY 2M44

53 2 37 DuctSmoke(P) AHU-21 ROOM 193A RELAY 2M44

54 2 38 Smoke(Photo) COMPACTOR CORR E BUILDING 5

55 2 39 Smoke(Photo) COMPACTOR CORR E BUILDING 5

56 2 40 Heat (Fixed) COMPACTOR CORR BUILDING 5

57 2 41 Heat COMPACTOR CORR BUILDING 5

58 2 42 Heat COMPACTOR CORR W BUILDING 5

59 2 43 Heat COMPACTOR RM 199 N BUILDING 5

60 2 44 Heat COMPACTOR RM 199 S BUILDING 5

61 2 46 DuctSmoke(P) AHU-25 RM 245F RELAY 2M46

62 2 47 DuctSmoke(P) EF-25 RM 245F RELAY 2M45

63 2 48 Smoke(Photo) W DINNING RM 256 BUILDING 5

64 2 49 Smoke(Photo) E DINNING RM 256 BUILDING 5

65 2 50 Smoke(Photo) HALL BY ROOM 252 BUILDING 5

66 2 51 Smoke(Photo) HALL BY ROOM 272 BUILDING 5

67 2 52 Smoke(Photo) HALL BY RM 247 BUILDING 5

68 2 55 Smoke(Photo) ELEVATOR LOBBY 2ND FLR BUILDING 5

69 2 56 Smoke(Photo) ELEVATOR LOBBY 2ND FLR BUILDING 5

70 2 57 Smoke(Photo) DINING ROOM 244 BUILDING 5

71 2 58 Smoke(Photo) BY RM 245A BUILDING 5

72 2 59 Smoke(Photo) SERVICE ELEVATOR 2ND FLR BUILDING 5

73 2 62 DuctSmoke(P) AHU#28 KIT RM 245A RELAY 2M12/West Side of Unit

74 2 63 DuctSmoke(P) AHU-27 KIT RM 245A RELAY 2M13

75 2 64 DuctSmoke(P) AHU-29 RM 245A RELAY 2M36/ East Side of Unit

76 2 65 Smoke(Photo) HALL BY RM 196B BUILDING 5

77 2 66 Smoke(Photo) HALL BY RM 195A RELAY 2M75

78 2 67 DuctSmoke(P) RTU RM 180 RELAY 2M75/Abv Ceiling By East Entry

79 2 68 Smoke(Photo) ROOM 195B BUILDING 5

80 2 74 Heat STAFF RR 115 BLD 52

81 2 75 Smoke(Photo) CORRIDOR BY RM 129 WOMENS CENT

82 2 76 Smoke(Photo) CORRIDOR BY RM 129 WOMENS CNTR

83 2 77 Smoke(Photo) CORR BY RM 114 WOMENS CNTR

84 2 78 Smoke(Photo) CORR BY RM 126 WOMENS CNTR

85 2 79 Smoke(Photo) ELECTRICAL ROOM 126 WOMENS CNTR

86 2 80 Smoke(Photo) CORR BY RM 123 WOMENS CNTR

87 2 81 Smoke(Photo) CORR BY RM 120 WOMENS CNTR

88 2 82 Smoke(Photo) ROOM 104 BLD 52

89 2 83 Smoke(Photo) ROOM 105 BLD 52

90 2 84 Smoke(Photo) ROOM 103 BLD 52

91 2 85 Smoke(Photo) NORTH HALL BLD 52

92 2 86 Smoke(Photo) RECEPTION DESK BLD 52

93 2 87 Smoke(Photo) ELECTRICAL CLOSET BLD 52

94 2 88 Smoke(Photo) RM 102 BLD 52

95 2 89 Smoke(Photo) HALL BY 107 BLD 52

96 2 90 Smoke(Photo) ROOM 107 N DET BLD 52

97 2 91 Smoke(Photo) ROOM 107 S DET BLD 52

98 2 92 Smoke(Photo) HALL BY S ENT BLD 52

99 2 93 Smoke(Photo) HALL BY 109 BLD 52

100 2 94 Heat MENS RESTROOM BLD 52

101 2 95 Smoke(Photo) NORTH VESTIBULE BLD 52

102 2 96 Smoke(Photo) ROOM 112 BLD 52

103 2 97 Heat WOMENS RESTROOM BLD 52

104 2 98 Smoke(Photo) RM 106 NETWORK CLST BLD 52

105 2 99 Smoke(Photo) ROOM 111 BLD 52

106 3 1 DuctSmoke(P) AHU-35 RM 549 SOUTH 3M2, 6M20

107 3 3 DuctSmoke(P) AHU-32 5TH FLR MECH RM 515/Top of Unit West Side

108 3 4 Heat ELEV EQUIPMENT RM 6TH FL

109 3 5 Heat ELEV EQUIPMENT RM 6TH FL

110 3 6 Heat ELEV EQUIPMENT RM 6TH FL

111 3 7 Heat ELEV EQUIPMENT RM 6TH FL

112 3 10 Smoke(Photo) HALL BY RM 443C

113 3 11 DuctSmoke(P) AHU-15 Room 443F W /W. side of RM 443F Abv Ceil

114 3 24 DuctSmoke(P) AHU-19 RM 549 NORTH RELAY 3M37

115 3 25 DuctSmoke(P) AHU-19 RM 549 SOUTH RELAY 3M37

116 3 29 DuctSmoke(P) AHU-16 RM 551 RELAY 3M34/S.E. Side High

117 3 30 DuctSmoke(P) AHU-16 RM 551 RELAY 3M34/ N. Side

118 3 41 Smoke(Photo) IN ROOM 600 SOUTHWEST

119 3 42 Smoke(Photo) ELEV EQUIPMENT RM 6TH FL

120 3 43 Smoke(Photo) ELEV EQUIPMENT RM 6TH FL

121 3 44 Heat ELEV EQUIPMENT RM 6TH FL

**smoke detector too close to vent 4-2022

122 3 45 Heat ELEV EQUIPMENT RM 6TH FL

123 3 46 Heat ELEV EQUIPMENT RM 6TH FL

124 3 47 Heat ELEV EQUIPMENT RM 6TH FL

125 3 48 DuctSmoke(P) AHU-17 RM 600 RELAY 3M51/N.W. Side of Unit

126 3 49 Smoke(Photo) 5TH FL MECH RM 515 SOUTH

127 3 50 Smoke(Photo) 5TH FL MECH RM 515 NORTH

128 3 53 Smoke(Photo) TOP OF ELEV SHAFT ELEV P2

129 3 54 Smoke(Photo) TOP OF ELEVATR SHAFT W ELEV S6

130 3 56 Smoke(Photo) TOP OF ELEVATR SHAFT E Elev P3

131 3 57 Smoke(Photo) TOP OF ELEV SHAFT W Mid Elev

132 3 58 Smoke(Photo) 5TH FLR BY RM 528 BLDG 5

133 3 59 Smoke(Photo) 5TH FLR BY RM 530 BLDG 5

134 3 60 Smoke(Photo) 5TH FLR BY RM 526 BLDG 5

135 3 61 Smoke(Photo) 5TH FLR BY RM 525 BLDG 5

136 3 62 Smoke(Photo) 5TH FLR BY RM 524 BLDG 5

137 3 63 Smoke(Photo) 5TH FLR BY RM ??? BLDG 5

138 3 65 Smoke(Photo) 5TH FLR BY RM 519

139 3 66 Smoke(Photo) 5TH FLR BY RM 519

140 3 67 Smoke(Photo) 5TH FLR HALL BY ROOM 515

141 3 68 Smoke(Photo) 5TH FLR HALL BY ROOM 509

142 3 69 Smoke(Photo) 5TH FLR LOBBY EAST WAITING ROOM

143 3 70 Smoke(Photo) 5TH FLR LOBBY NORTH WAITING ROOM

144 3 71 Smoke(Photo) 5TH FLR LOBBY SOUTH WAITING ROOM

145 3 72 Smoke(Photo) 5TH FLR EAST BY RECEPT AREA

146 3 73 Smoke(Photo) 5TH FLR WEST BY RECEPT AREA

147 3 74 Smoke(Photo) 5TH FLR WEST BY ROOM 501A

148 3 75 Smoke(Photo) 5TH FLR CENTRAL BY RECEPT AREA

149 3 76 Smoke(Photo) 5TH FLR SOUTH BY ROOM 516

150 3 77 Smoke(Photo) 5TH FLR SOUTH BY ROOM 517

151 3 78 Smoke(Photo) 5TH FLR MED ROOM ROOM 514

152 3 79 Smoke(Photo) 5TH FLR SOILED RM ROOM 513

153 3 80 DuctSmoke(P) 5TH FLR SOUTH BY RM 512 (Supervisory)

154 3 81 DuctSmoke(P) 5TH FLR SOUTH RM 512 (Supervisory)

155 3 82 DuctSmoke(P) 5TH FLR SOUTH BY RM 518 (Supervisory)

156 3 83 DuctSmoke(P) 5TH FLR SOUTH BY RM 511 (Supervisory)

157 3 84 DuctSmoke(P) 5TH FLR SOUTH BY RM 519 (Supervisory)

158 3 85 DuctSmoke(P) 5TH FLR MINOR SURG IN RM 511 (Supervisory)

159 3 86 DuctSmoke(P) 5TH FLR SOUTH BY RM 519 (Supervisory)

160 3 87 DuctSmoke(P) 5TH FLR NORTH BY RM 535(Supervisory)

161 3 88 DuctSmoke(P) 5TH FLR BY RR BY RM 511 (Supervisory)

162 3 89 DuctSmoke(P) 5TH FLR CENTRAL DATA ROOM 546 (Supervisory)

163 3 90 DuctSmoke(P) 5TH FLR SMOKE DAMPER BY RM 510 (Supervisory)

164 3 91 DuctSmoke(P) 5TH FLR SMOKE DAMPER BY RM 522 (Supervisory)

**Verify & HAVE JCI UPDATE descripion 4-22**

**Verify descripion & HAVE JCI UPDATE 4-22**

165 3 92 DuctSmoke(P) 5TH FLR WEST PATIENT BY RM 509 N (Supervisory)

166 3 93 DuctSmoke(P) 5TH FLR WEST WING BY RM 509(Supervisory)

167 3 94 DuctSmoke(P) 5TH FLR WAITING AREA EAST (Supervisory)

168 3 95 DuctSmoke(P) 5TH FLR WAITING AREA WEST (Supervisory)

169 3 96 DuctSmoke(P) 5TH FLR WEST WING BY RM 508(Supervisory)

170 3 97 DuctSmoke(P) 5TH FLR WEST WING BY RM 503(Supervisory)

171 3 98 DuctSmoke(P) 5TH FLR WEST WING BY RM 507 (Supervisory)

172 3 99 DuctSmoke(P) 5TH FLR WEST WING BY RM 506 (Supervisory)

173 3 100 DuctSmoke(P) 5TH FLR SMOKE DAMPER BY RM 518 (Supervisory)

174 3 101 DuctSmoke(P) 5TH FLR SOUTH EXAM BY RM 519 (Supervisory)

175 3 102 DuctSmoke(P) 5TH FLR SMOKE DAMPER BY RM 517 (Supervisory)

176 3 103 Smoke(Photo) 5TH FLR ABOVE HEP ELEC RM 527

177 5 1 DuctSmoke(P) AHU #5 RET DUCT PC FAN ROOM

178 5 2 DuctSmoke(P) AHU #5 SUPPLY DUCT PC FAN ROOM

179 5 3 DuctSmoke(P) AHU #6 RETURN DUCT PC FAN ROOM

180 5 4 DuctSmoke(P) AHU #6 SUPPLY DUCT PC FAN ROOM

181 5 5 DuctSmoke(P) AHU #1 SUPPLY DUCT PC FAN ROOM (supervisory)

182 5 6 DuctSmoke(P) AHU #1 RETURN DUCT PC FAN ROOM

183 5 7 Heat PC INTERSTITIAL RM 1004 S.W.

184 5 8 DuctSmoke(P) AHU #7 SUPPLY DUCT PC FAN ROOM

185 5 9 DuctSmoke(P) AHU #7 RETURN DUCT PC FAN ROOM

186 5 10 Heat PC INTERSTITIAL RM 1004 E.

187 5 11 Heat PC INTERSTITIAL RM 1004 N.W.

188 5 16 Heat PC ELEV EQUIP RM F08 ELEV MECH RM

189 5 17 Smoke(Photo) PC ELEV EQUIP RM F08 ELEV MECH RM

190 5 18 Heat PC ELEV ELEV PIT GRND FL

191 5 19 Smoke(Photo) PC ELEV TOP OF SHAFT 2ND FL

192 5 25 Smoke(Photo) MAIN LOBBY W. of INFO GRND FL

193 5 26 Smoke(Photo) MAIN LOBBY NORTH GRND FL

194 5 27 Smoke(Photo) MAIN LOBBY SOUTH GRND FL

195 5 29 Smoke(Photo) MAIN LOBBY SOUTH GRND FL

196 5 30 Smoke(Photo) CORR BY ROOM F12

197 5 31 Heat PC RM 1005 EAST

198 5 32 DuctSmoke(P) AHU-33 RM 1005 RELAY 5M2/N.W. Side

199 5 33 Heat PC ROOM 1005 E. CENTER

200 5 34 Heat PC ROOM 1005 W. CENTER

201 5 35 Heat PC ROOM 1005 WEST

202 5 37 Smoke(Photo) MAIN LOBBY NORTH GRND FL

203 5 38 Smoke(Photo) PC ROOM 1001 S.E. 1st FL

204 5 39 Smoke(Photo) PC ROOM 1001 S.E. MID DET

205 5 40 Smoke(Photo) PC ROOM 1001 EAST MID DET

206 5 41 Smoke(Photo) PC ROOM 1001 N.E. MID DET

207 5 42 Smoke(Photo) PC ROOM 1001 ELEV LOBBY

208 5 44 Smoke(Photo) PC ELEV LOBBY GRND FLR

209 5 45 Smoke(Photo) HALL BY RM F07

210 5 46 Smoke(Photo) PC TOP OF STAIR #8 2nd Floor

211 5 47 Smoke(Photo) PC RM 1001 N.W. DET

212 5 48 Smoke(Photo) PC RM 1001 N.W. MID DET

213 5 49 DuctSmoke(P) PC AHU #40 RM 1001 RETURN DUCT

214 5 50 DuctSmoke(P) PC AHU #40 RM 1001 SUPPLY DUCT

215 5 51 Smoke(Photo) PC RM 1001 WEST MID DET

216 5 52 DuctSmoke(P) PC Room 1001 AHU 40 Return Duct

217 5 53 DuctSmoke(P) PC Room 1001 AHU 40 Return Duct

218 5 54 Smoke(Photo) PC RM 1001 S.W. DET

219 5 56 Smoke(Photo) PC RM 1003 EC RM

220 5 57 Smoke(Photo) PC RM 1002 COMM CLOSET

221 5 58 Smoke(Photo) PC INTER CORR 1006 PC INTER

222 5 60 Smoke(Photo) PC W. HALL BY RM 2011

223 5 61 Smoke(Photo) PC W. HALL BY RM 2012 North

224 5 62 Smoke(Photo) PC W. HALL BY RM 2014

225 5 63 Smoke(Photo) PC W. HALL BY RM 2016

226 5 64 Smoke(Photo) PC 2ND FLR N. WAITING

227 5 66 Smoke(Photo) PC 2ND FLR ELEV LOBBY

228 5 67 Smoke(Photo) PC 2ND FLR E HALL N

229 5 68 Smoke(Photo) PC E. HALL BY RM 2003

230 5 69 Smoke(Photo) PC E. HALL BY RM 2005

231 5 70 Smoke(Photo) PC E. HALL BY ROOM 2008

232 5 71 Smoke(Photo) PC 2ND FLR E. HALL South DET

233 5 73 Smoke(Photo) PC 2ND FLR TOP STAIR 9

234 5 75 Smoke(Photo) PC HALL BY RM 2009

235 5 80 Heat SPEC MED ELEVATOR Heat IN PIT

236 5 81 Smoke(Photo) SPEC MED ELEV TOP OF SHAFT

237 5 82 Smoke(Photo) SPEC MED ELEVATOR EQUIPMENT RM

238 5 83 HEAT SPEC MED ELEVATOR EQUIPMENT RM

239 5 84 Smoke(Photo) SPEC MED INTERSTITIAL RM 1013

240 5 85 Smoke(Photo) SPEC MED INTERSTITIAL RM 1014

241 5 86 Smoke(Photo) SPEC MED INTERSTITIAL SOUTH WEST

242 5 87 Smoke(Photo) SPEC MED INTERSTITIAL BY 1014

243 5 89 Smoke(Photo) SPEC MED INTERSTITIAL S.E. CTR

244 5 91 DuctSmoke(P) SPEC MED INTERSTITIAL AHU 42 (Supervisory)

245 5 92 Smoke(Photo) SPEC MED INTERSTITIAL SW CENTER

246 5 93 Smoke(Photo) SPEC MED INTERSTITIAL CTR WEST

247 5 94 Smoke(Photo) SPEC MED INTERSTITIAL CENTER OF RM

248 5 95 Smoke(Photo) SPEC MED INTERSTITIAL CENTER EAST

249 5 96 DuctSmoke(P) SPEC MED INTERSTITIAL AHU42 (Supervisory)

250 5 97 Smoke(Photo) SPEC MED INTERSTITIAL N.W.

251 5 100 Smoke(Photo) SPEC MED INTERSTITIAL NORTH WEST

252 5 101 Smoke(Photo) SPEC MED INTERSTITIAL N. CTR.

253 5 102 DuctSmoke(P) SPEC MED INTERSTITIAL RF42 RETURN (Supervisory)

254 5 103 DuctSmoke(P) SPEC MED INTERSTITIAL RF42 SOUTH (Supervisory)

255 5 104 DuctSmoke(P) SPEC MED INTERSTITIAL RF42 CENTER (Supervisory)

256 5 105 DuctSmoke(P) SPEC MED INTERSTITIAL RF42 NORTH (Supervisory)

257 5 107 Smoke(Photo) SPEC MED INTERSTITIAL NORTH CENTER

258 5 108 Smoke(Photo) SPEC MED INTERSTITIAL NORTH EAST

259 5 109 Smoke(Photo) SPEC MED INTERSTITIAL NORTH EAST

260 5 111 Smoke(Photo) SPEC MED GND FLOOR ELEVATOR LOB

261 5 113 Smoke(Photo) SPEC MED EAST WAITING HALL

262 5 114 Smoke(Photo) SPEC MED EAST WAITING

263 5 115 Smoke(Photo) SPEC MED WEST WAITING

264 5 116 Smoke(Photo) SPEC MED WOMENS RR

265 5 117 Smoke(Photo) SPEC MED MENS RR

266 5 118 Smoke(Photo) SPEC MED NORTH WAITING

267 5 119 Smoke(Photo) SPEC MED RECEPTION

268 5 120 Smoke(Photo) SPEC MED BY 2025 ROOM 2025

269 5 121 DuctSmoke(P) SPEC MED HALL BY 2025 (Supervisory)

270 5 122 DuctSmoke(P) SPEC MED OFFICE 2025 (Supervisory)

271 5 123 Smoke(Photo) SPEC MED EAST HALL SOUTH

272 5 124 Smoke(Photo) SPEC MED EAST HALL E HALL CTR

273 5 125 Smoke(Photo) SPEC MED EAST HALL E HALL CTR

274 5 126 DuctSmoke(P) SPEC MED EAST HALL ABOVE FIREDR (Supervisory)

275 5 127 Smoke(Photo) SPEC MED EAST HALL HALL NORTH

276 5 128 Smoke(Photo) SPEC MED EAST HALL HALL NORTH

277 5 129 Smoke(Photo) SPEC MED STAIR STAIR 11

278 5 130 Smoke(Photo) SPEC MED OUTSIDE 2048

279 5 131 Smoke(Photo) SPEC MED OUTSIDE 2046

280 5 132 Smoke(Photo) SPEC MED OUTSIDE 2043

281 5 133 Smoke(Photo) SPEC MED ROOM 2031 N.

282 5 134 Smoke(Photo) SPEC MED OUTSIDE 2031

283 5 135 Smoke(Photo) SPEC MED OUTSIDE 2033

284 5 136 Smoke(Photo) SPEC MED ROOM 2031 S.

285 5 137 Smoke(Photo) SPEC MED OUTSIDE 2040

286 5 138 Smoke(Photo) SPEC MED OUTSIDE 2037

287 5 139 Smoke(Photo) SPEC MED OUTSIDE 2030

288 6 2 Smoke(Photo) ROOM 445 WAITING RM

289 6 3 Smoke(Photo) HALL BY RM 451

290 6 4 Smoke(Photo) HALL BY RM 445

291 6 5 Smoke(Photo) HALL BY RM 402

292 6 6 Smoke(Photo) HALL BY ROOM 433

293 6 7 Smoke(Photo) ELEVATOR LOBBY 4TH FLOOR

294 6 8 Smoke(Photo) ELEVATOR LOBBY 4TH FLOOR

295 6 9 Smoke(Photo) HALL BY ROOM 443A

296 6 10 DuctSmoke(P) AHU-31 RM 445A 6M17/18 /South Side

297 6 12 Smoke(Photo) WAITING RM 473

298 6 15 Smoke(Photo) WAITING RM 408

299 6 16 Smoke(Photo) EYE CLINIC RM 402

300 6 17 Smoke(Photo) IN ROOM 471

301 6 20 Smoke(Photo) IN ROOM 464B NORTH

302 6 28 Smoke(Photo) ROOM 301 BUILDING 5

303 6 29 Smoke(Photo) ENDO HALL BY RM 411 BUILDING 5

304 6 30 Smoke(Photo) ENDO HALL BY RM 429 BUILDING 5

305 6 31 Smoke(Photo) ENDO HALL BY RM 423 BUILDING 5

306 6 65 Smoke(Photo) EYE CLINIC WAIT RM 403

307 6 66 DuctSmoke(P) AHU-26-SF26 RM 352A 6M92/93

308 6 67 DuctSmoke(P) AHU-26-EF26 RM 352A 6M92/93

309 6 68 Smoke(Photo) CLC3 DINNING RM 361 WEST

310 6 69 Smoke(Photo) CLC3 DINNING RM 361 EAST

311 6 70 Smoke(Photo) CLC3 HALL BY ROOM 357

312 6 71 Smoke(Photo) CLC3 HALL BY ROOM 374

313 6 72 Smoke(Photo) CLC3 HALL BY ROOM 352

314 6 73 Smoke(Photo) CLC3 DINING STOR RM 360

315 6 75 Smoke(Photo) ELEVATOR LOBBY 3RD FLR

316 6 76 Smoke(Photo) ELEVATOR LOBBY 3RD FLR

317 6 77 Smoke(Photo) ELEVATOR LOBBY 3RD FLR

318 6 78 Smoke(Photo) RM 328 ICU WAITING

319 6 79 Smoke(Photo) IN ROOM 350

320 6 80 Heat IN ROOM 350

321 6 81 Heat IN ROOM 350

322 6 83 Smoke(Photo) NAC RM 348C CHAPEL

323 6 85 DuctSmoke(P) RM 349G AHU14 Chapel (Supervisory)

324 7 1 Smoke(Photo) NUC MED BY RM A11

325 7 2 Smoke(Photo) NUC MED BY RM A09A GRND FLR

326 7 3 Smoke(Photo) NUC MED RM A08 GRND FLR

327 7 4 Smoke(Photo) NUC MED BY RM A05 GRND FL

328 7 5 Smoke(Photo) NUC MED BY RM A04B

329 7 6 Smoke(Photo) NUC MED BY RM A03A

330 7 7 Smoke(Photo) NUC MED RM A03 S. DET GRND FL

331 7 8 Smoke(Photo) NUC MED RM A03 N. DET GRND FL

332 7 9 Smoke(Photo) MRI DRESSING RM BY RM A17A

333 7 15 Smoke(Photo) O.R. ELEV LOB GRND FLR

334 7 16 Smoke(Photo) O.R. ELEV DR E. GRND FLOOR

335 7 17 Smoke(Photo) O.R. ELEV DR W GRND FLOOR

336 7 18 Smoke(Photo) O.R. ELEV LOB 1ST FLR

Needs moved 3' from vent April 2022

Needs moved 3' from vent April 2022

**UPDATE DESCRIPTION AS INDICATED 4-2022**

337 7 19 Smoke(Photo) O.R. ELEV DR E 1ST FLR

338 7 20 Smoke(Photo) O.R. ELEV LOB 2ND FLR

339 7 21 Smoke(Photo) O.R. ELEV DR E 2ND FLR

340 7 22 Smoke(Photo) O.R. ELEV DR W 2ND FLR

341 7 23 Smoke(Photo) O.R. ELEV LOBBY 3RD FLR

342 7 24 Smoke(Photo) O.R. ELEV DR E 3RD FLR

343 7 25 Smoke(Photo) O.R. ELEV DR W 3RD FLR

344 7 26 Smoke(Photo) O.R. ELEV LOB 4TH FLR

345 7 27 Smoke(Photo) O.R. ELEV DR E 4TH FLR

346 7 28 Smoke(Photo) O.R. ELEV DR W 4TH FLR

347 7 30 Smoke(Photo) O.R. ELEV TOP OF SHAFT

348 7 32 Smoke(Photo) O.R. ELEV TOP OF SHAFT

349 7 33 Smoke(Photo) O.R. GRND FLR DATA RM G03

350 7 34 Heat O.R. GRND FLR ELEV MECH RM G05

351 7 35 Smoke(Photo) O.R. GRND FLR MECH RM G05

352 7 36 Smoke(Photo) O.R. GRND FLR NURSE ST NE

353 7 38 Smoke(Photo) O.R. GRND FLR NURSE ST S

354 7 39 Smoke(Photo) O.R. GRND FLR CORR BY G35

355 7 40 Smoke(Photo) O.R. GRND FLR RM G32

356 7 41 Smoke(Photo) O.R. GRND FLR N CORR C44

357 7 42 Smoke(Photo) O.R. GRND FLR NURSE ST W

358 7 43 Smoke(Photo) O.R. GRND FLR NURSE ST W

359 7 44 Smoke(Photo) O.R. GRND FLR RM G29

360 7 45 Smoke(Photo) O.R. GRND FLR HALL BY G28

361 7 46 Smoke(Photo) O.R. GRND FLR W HALL BY G26

362 7 47 Smoke(Photo) O.R. GRND FLR RM G26 W

363 7 48 Smoke(Photo) O.R. GRND FLR RM G26 MIDD

364 7 49 Smoke(Photo) O.R. GRND FLR CORR C43 S

365 7 50 Smoke(Photo) O.R. GRND FLR CORR C42 MID

366 7 51 Smoke(Photo) O.R. GRND FLR CORR C42 EXI

367 7 52 Smoke(Photo) O.R. GRND FLR RM G26 E

368 7 53 Smoke(Photo) O.R. GRND FLR RM G22

369 7 54 Smoke(Photo) O.R. GRND FLR BY RM G22

370 7 55 Smoke(Photo) O.R. GRND FLR BY RM G20A

371 7 56 Smoke(Photo) O.R. GRND FLR BY RM G20

372 7 57 Smoke(Photo) O.R. GRND FLR CORR C40 E

373 7 58 Smoke(Photo) O.R. GRND FLR PACU BY G13

374 7 59 Smoke(Photo) O.R. GRND FLR PACU RM G13

375 7 60 Smoke(Photo) O.R. GRND FLR PACU RM G14

376 7 61 Heat O.R. GRND FLR PACU RM G16A

377 7 62 DuctSmoke(P) O.R. 1ST FLR MECH RM 1030

378 7 63 DuctSmoke(P) O.R. 1ST FLR MECH RM 1030

379 7 64 DuctSmoke(P) O.R. 1ST FLR MECH RM 1030

380 7 65 Smoke O.R. GRND FLR RM G30

381 7 66 Heat O.R. GRND FLR MECH RM G05

382 8 1 Smoke(Photo) HALL BY RM A07A Building 5

383 8 4 Smoke(Photo) BY RM B98 Building 5

384 8 5 Smoke(Photo) BY RM B89E BUILDING 5

385 8 6 Smoke(Photo) PHARM PICKUP B89B BLD 5

386 8 7 Smoke(Photo) W SKYLIGHT BY B80 BUILDING 5

387 8 8 Smoke(Photo) SW SKYLIGHT BY B80 BUILDING 5

388 8 9 Smoke(Photo) SE SKYLIGHT BY B80 BUILDING 5

389 8 10 Smoke(Photo) E SKYLIGHT BY B80 BUILDING 5

390 8 11 Smoke(Photo) NE SKYLIGHT BY B80 BUILDING 5

391 8 12 Smoke(Photo) HALL BY B45 BUILDING 5

392 8 13 Heat IN ROOM B66A BUILDING 5

393 8 14 Heat IN ROOM B66A BUILDING 5

394 8 15 Smoke(Photo) IN ROOM B66 BUILDING 5

395 8 18 Smoke(Photo) HALL BY ROOM B83 BUILDING 5

396 8 20 Smoke(Photo) ROOM A54 BUILDING 5

397 8 21 Smoke(Photo) ROOM A55 BUILDING 5

398 8 23 Smoke(Photo) ROOM B40 BUILDING 5

399 8 25 Smoke(Photo) IN ROOM A31 BUILDING 5

400 8 26 Smoke(Photo) IN ROOM A31D BUILDING 5

401 8 27 Smoke(Photo) IN ROOM A86 BUILDING 5

402 8 28 Smoke(Photo) ELEVATOR LOBBY GRND FL BLD 5

403 8 29 Smoke(Photo) ELEVATOR LOBBY GRND FL BLD 5

404 8 32 Smoke(Photo) In ROOM E01 BUILDING 5

405 8 33 Smoke(Photo) In ROOM E01 BUILDING 5

406 8 34 Smoke(Photo) HALL BY RM E09 BUILDING 5

407 8 35 Smoke(Photo) BY SERVICE ELEV BLD 5 GRND

408 8 36 Heat In ROOM E03A BUILDING 5

409 8 37 Smoke(Photo) In ROOM E23 BUILDING 5

410 8 38 Smoke(Photo) HALL BY RM A26 BLD 5

411 8 40 Smoke(Photo) In ROOM A31C BUILDING 5

412 8 41 Smoke(Photo) ROOM A31E BUILDING 5

413 8 44 DuctSmoke(P) ONCOLOGY DUCT DOUBLE DOOR (Supervisory)

414 8 45 Smoke(Photo) ONC DBL DR CORR SIDE SMOKE

415 8 46 Smoke(Photo) ONC DBL DR ONC SIDE SMOKE

416 8 50 Smoke(Photo) PT MAIN GYM SW DET ROOM A70

417 8 51 Smoke(Photo) PT MAIN GYM NW DET ROOM A70

418 8 52 Smoke(Photo) PT MAIN GYM SE DET ROOM A70

419 8 53 Smoke(Photo) PT MAIN GYM NE DET ROOM A70

420 8 54 Smoke(Photo) HALL BY A54 BUILDING 5

421 8 55 Smoke(Photo) HALL BY A56 BUILDING 5

422 8 56 Smoke(Photo) HALL BY A57 BUILDING 5 note: smoke det. is in fuction to release smoke window RM B40

423 8 57 Smoke(Photo) HALL BY A58 BUILDING 5

424 8 58 Smoke(Photo) HALL BY A 59 BUILDING 5

425 8 59 Smoke(Photo) HALL BY A87 BUILDING 5

426 8 60 Smoke(Photo) HALL BY A60 BUILDING 5

427 8 61 Smoke(Photo) HALL BY A62 BUILDING 5

428 8 64 Smoke(Photo) RM A87 BUILDING 5

429 8 68 DuctSmoke(P) ONCOLOGY DUCT RETURN RM F71C (Supervisory)

430 8 69 DuctSmoke(P) ONCOLOGY DUCT SUPPLY RM F63A (Supervisory)

431 8 75 DuctSmoke(P) AHU 20 IN RM A84A RELAY 2M43

432 8 76 Smoke(Photo) ROOM E125 BUILDING 5

433 8 77 DuctSmoke(P) AHU-1 ROOM E124 RELAY 8M39/South East Side

434 8 79 DuctSmoke(P) AHU-2 ROOM E124 RELAY 8M40/East Side & South

435 8 80 DuctSmoke(P) AHU-2 ROOM E124 RELAY 8M40/North & East of Entry

436 8 81 DuctSmoke(P) AHU-3 IN RM A12 8M41, 7M2/W. Side

437 8 82 DuctSmoke(P) AHU-3 IN RM A12 8M41, 7M2/E. Side

438 8 83 DuctSmoke(P) AHU-4 IN RM A12 RELAY 8M42/S.E. Side

439 8 84 DuctSmoke(P) AHU-4 IN RM A12 RELAY 8M42/N.E. Side

440 8 91 Smoke(Photo) IN ROOM W5 BUILDING 5

441 8 92 Smoke(Photo) CORR BY ROOM A53 BUILDING 5

442 8 94 Heat SOUTH OH DOOR RM W01

443 8 95 Heat NW INSIDE OH DOOR W01

444 8 96 Heat NW OUTER OH DOOR W01

445 8 97 Smoke(Photo) 1ST FLR LAB MECH SPC E ROOM 1016

446 8 98 Smoke(Photo) 1ST FLR LAB MECH SPC E ROOM 1016

447 8 99 Smoke(Photo) 1ST FLR LAB MECH SPC E ROOM 1016

448 8 100 Smoke(Photo) 1ST FLR LAB MECH SPC SE ROOM 1016

449 8 101 Smoke(Photo) 1ST FLR LAB MECH SPC SE ROOM 1016

450 8 102 Smoke(Photo) 1ST FLR LAB MECH SPC S ROOM 1016

451 8 103 Smoke(Photo) 1ST FLR LAB MECH SPC S ROOM 1016

452 8 104 Smoke(Photo) 1ST FLR LAB MECH SPC CTR RM 1016

453 8 105 Smoke(Photo) 1ST FLR LAB MECH SPC CTR RM 1016

454 8 106 Smoke(Photo) 1ST FLR LAB MECH SPC CTR RM 1016

455 8 107 Smoke(Photo) 1ST FLR LAB MECH SPC N RM 1016

456 8 108 Smoke(Photo) 1ST FLR LAB MECH SPC N RM 1016

457 8 109 Smoke(Photo) 1ST FLR LAB MECH SPC N RM 1016

458 8 110 Smoke(Photo) 1ST FLR LAB MECH SPC N RM 1016

459 8 111 Smoke(Photo) 1ST FLR LAB MECH SPC N RM 1016

460 8 112 Smoke(Photo) 1ST FLR LAB MECH SPC N RM 1016

461 8 113 Smoke(Photo) 1ST FLR LAB MECH SPC CTR RM 1016

462 8 114 Smoke(Photo) 1ST FLR LAB MECH SPC CTR RM 1016

463 8 115 Smoke(Photo) 1ST FLR LAB MECH SPC CTR RM 1016

464 8 116 Smoke(Photo) 1ST FLR LAB MECH SPC SW RM 1016

465 8 117 Smoke(Photo) 1ST FLR LAB MECH SPC SW RM 1016

466 8 118 Smoke(Photo) 1ST FLR LAB MECH SPC SW RM 1016

467 8 119 Smoke(Photo) 1ST FLR LAB MECH SPC SW RM 1016

468 8 120 Smoke(Photo) 1ST FLR LAB MECH SPC WEST RM 1016

469 8 121 Smoke(Photo) 1ST FLR LAB MECH SPC WEST RM 1016

470 8 122 Smoke(Photo) 1ST FLR LAB MECH SPC NW RM 1016

471 8 123 Smoke(Photo) 1ST FLR LAB MECH SPC WEST RM 1016

472 8 124 Smoke(Photo) 1ST FLR LAB MECH SPC WEST RM 1016

473 8 125 Smoke(Photo) 1ST FLR LAB MECH SPC WEST RM 1016

474 8 126 Smoke(Photo) 1ST FLR LAB MECH SPC WEST RM 1016

475 8 127 Sup L(Duct P) 1ST FLR LAB MECH SPC NE ROOM 1016

476 8 129 Sup L(Duct P) 1ST FLR LAB MECH SPC WEST RM 1016

477 8 132 Heat LAB RM 2095 BLD 5 2ND FL

478 8 133 Smoke(Photo) LAB STGE S 2085 BLD 5 2ND FL

479 8 134 Smoke(Photo) LAB STGE N 2085 BLD 5 2ND FL

480 8 135 Smoke(Photo) LAB STGE 2088 B BLD 5 2ND FL

481 8 136 Smoke(Photo) LAB HALL 2060 BLD 5 2ND FL

482 8 137 Smoke(Photo) LAB LOBBY 2001 BLD 5 2ND FL

483 8 138 Smoke(Photo) LAB LOBBY 2001 BLD 5 2NF FL

484 8 139 Smoke(Photo) LAB LOBBY 2001 BLD 5 2ND FL

485 8 140 Smoke(Duct P) LAB LOBBY 2001 BLD 5 2N FL

486 8 141 Sup L(Duct P) LAB LOBBY 2001 BLD 5 2ND FL

487 8 142 Heat LAB HSK 2079 BLD 5 2ND FL

488 8 146 Sup L(Duct P) LAB LOBBY 2001 BLD 5 2ND FL

489 8 147 Sup L(Duct P) LAB HALL N 2000 BLD 5 2ND FL

490 8 148 Sup L(Duct P) LAB HALL 2000 BLD 5 2ND FL

491 8 149 Sup L(Duct P) LAB HALL W 2000 BLD 5 2ND FL

492 8 150 Smoke(Photo) NAC PNL MECH SPAC BLD 5 1ST FL

493 9 1 DuctSmoke(P) AHU-36…