Attachment 2 - Statement of Work.pdf

PDF 303 KB Posted

Attached to
Generator Rebuild Federal contract opportunity
Solicitation number
N0018922QGENE
Issued by
Department of the Navy Naval Supply Systems Command

View the file

Other files for this federal contract opportunity

Other files attached to Generator Rebuild, newest first.
File Type Posted
3.1 NAVSEA STANDARD ITEMS.pdf PDF
3.5 DELCO Appendix DP 1567 10-64, DELCO Alternating Current.pdf PDF
3.2b 107788_A_SH12-27.pdf PDF
Attachment 1 - Clauses and Provisions.pdf PDF
3.2a 5107788_A_SH01-11 SWBD fabrication.pdf PDF
3.4 DELCO Appendix DP 1878 965, DELCO Alternating Current Generators.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Performance Work Statement

Assault Craft Unit 2 Generator Rebuild

SECTION 1.0 INTRODUCTION:

Assault Craft Unit TWO (ACU- 2) requires (4) DELCO Model E5257WV, Serial Nos. 86-D-69, 70-B-69, 79-D-

69, and 106-11-69, 40KW, 225/450 VAC, 60 cycle, 1800 RPM generators remanufactured for the 135’ Landing

Craft Utility (LCU) 1663

SECTION 2.0 OBJECTIVES:

ACU-2 requires remanufactured generators for their craft at Joint Expeditionary Base Little Creek (JEBLC)

SECTION 3.0 REFERENCES:

3.1 - NAVSEA Standard Items

3.2 a - NAVSEA Drawing 300-5107788, 1627/1646 Class Electrical Plant Control Panel (EPCP) fabrication B/A

297A

3.2 b - 107788_A_SH12-27

3.3 - NAVSEA 0961-LP-009-8010, Service Manual Model 3151 Diesel Generator Set, 40 KW, 225/450 VAC

3.4 - DELCO Appendix DP 1878 9/65, DELCO Alternating Current

Generators.

3.5 - DELCO Appendix DP 1567 10/64, DELCO Alternating

Current Generators

3.6 - 29 CR 1915, Occupational Safety and Health Standards for

Shipyard Employment

SECTION 4.0 SCOPE OF WORK:

4.1 Services for LCU 1663

Navy will deliver the generators (without engine), to the contractors facility in sets of 2. The first 2 generators will be delivered After Date of Contract (ADC), and the final 2 generators will be delivered once the first 2 generators have been returned to the Navy.

Contractor shall accomplish the requirements of 009-33 ref. 3.1 NAVSEA Standard Items for the generators to rewind the stator, rotor, and exciter fields.

Procure and install a new rectifier/exciter diode rings. For specification reference NAVSEA Drawing

300-5107788, 1627/1646 Class Electrical Plant Control Panel (EPCP) fabrication B/A 297A, NAVSEA 0961-LP-009-8010, Service Manual Model 3151 Diesel Generator Set, 40 KW, 225/450

VAC, DELCO Appendix DP 1878 9/65, DELCO Alternating Current Generators, and DELCO

Appendix DP 1567 10/64, DELCO Alternating Current Generators. If a new assembly is not available, refurbishing the existing one with new wiring, diodes and resistors is satisfactory.

Compensation and main field wiring is spliced. Replace the pigtail from the windings to the connection box on the generator. See ref. NAVSEA Drawing 300-5107788, 1627/1646 Class

Electrical Plant Control Panel (EPCP) fabrication B/A 297A, NAVSEA 0961-LP-009-8010, Service

Manual Model 3151 Diesel Generator Set, 40 KW, 225/450 VAC, DELCO Appendix DP 1878

9/65, DELCO Alternating Current Generators, and DELCO Appendix DP 1567 10/64, DELCO

Alternating Current Generators for specifications.

Bore and bush opposite drive end bell bearing housings to proper clearance as required.

The contractor shall install aluminum tags on each conductor that has to be reconnected on the craft and provide a connection diagram using NAVSEA Drawing 300-5107788, 1627/1646 Class

Electrical Plant Control Panel (EPCP) fabrication B/A 297A, NAVSEA 0961-LP-009-8010, Service

Manual Model 3151 Diesel Generator Set, 40 KW, 225/450 VAC, DELCO Appendix DP 1878

9/65, DELCO Alternating Current Generators, and DELCO Appendix DP 1567 10/64, DELCO

Alternating Current Generators for guidance. The nomenclature is covered in 3.2 through 3.5 and fabrication/installation is covered in 009-33 of NAVSEA Standard Items and its references

Contractor shall clean and preserve the remanufactured generators in accordance with 009-32 of

NAVSEA Standard Items. Final coat shall be machinery gray.

Navy will pick up the remanufactured generators at the contractor facility.

The technical manual will be provided separately to the awardee.

This is not an open and inspect, but a complete overhaul and bid accordingly.

SECTION 6.0 PLACE OF PERFORMANCE:

Contractor’s facility

Joint Expeditionary Base Little Creek

BLDG 1522

Assault Craft Unit TWO (ACU- 2)

2901 Amphibious Drive

Virginia Beach, VA 23459

SECTION 7.0 CONFERENCES AND MEETINGS

Contractor personnel shall be available for meetings at the Government and Contractor’s facilities, as required, throughout the performance of this task. The Technical Point of Contact (TPOC) shall give notice before meetings.