Attachment 1 - Salient Characteristics.pdf

PDF 15 KB Posted

Attached to
Trane Chillers Federal contract opportunity
Solicitation number
FA461323Q0023
Issued by
Department of the Air Force Global Strike Command

About this file

This document contains details for two air-cooled packaged chiller clinical line items (CLINs) to be provided under federal contract number FA461323Q0023 with the Department of the Air Force Global Strike Command. CLIN 0001 is for a 40 ton air-cooled chiller with R-454B refrigerant and factory installed freeze protection. CLIN 0002 is for an 80 ton air-cooled chiller also with R-454B refrigerant and factory installed freeze protection. Both units will be delivered FOB destination to Francis E. Warren Air Force Base and require startup by Trane certified service personnel.

View the file

Other files for this federal contract opportunity

Other files attached to Trane Chillers, newest first.
File Type Posted
Combined Synopsis - Trane Chillers.pdf PDF
Attachment 2 - Brand Name JnA.pdf PDF
Attachment 3 - Provisions and Clauses.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment 1: Salient Characteristics

CLIN 0001

Air-Cooled Scroll Packaged Chiller

40 nominal tons

60 hertz

230 volt 3 phases

Extra efficiency/performance

Refrigerant Charge R-454B

With factory installed freeze protection

Refrigerant isolation valves (discharge valve)

UL listed to US and Canadian safety standard

ASHRAE 90.1/CSA C743 - No Compliance

AHRI certified

Factory installed flow switch - set point 15 cm/sec

Phase Reversal Protection

Standard Cooling

Grooved pipe connection

Factory insulation 0.75"

Performance based on propylene glycol

Wide Ambient

Lanced aluminum fins

Across the line starter/direct on line

Single point connection main line unit power-ancillary items require other power

Terminal block conn for incoming lines

Enclosure Type UL 60335 Rated for Outdoor Applications

No Wireless Options

Default A short circuit rating

Elastomeric isolators

With water strainer factory installed

Super quiet

Architectural louvered panels

1st year refrigerant warranty

CLIN 0002

Air-Cooled Scroll Packaged Chiller

80 nominal tons

Factory Assigned

60 hertz

460 volt 3 phases

High efficiency/performance

Refrigerant Charge R-454B

With factory installed freeze protection

Refrigerant isolation valves (discharge valve)

UL Listed to U.S. and Canadian safety std via ETL - 2019

ASHRAE 90.1/CSA C743 - No Compliance

AHRI certified

Factory installed flow switch - set point 60 cm/sec

Standard Cooling

Grooved pipe connection

Factory insulation 0.75"

Performance based on water

Extreme Low Ambient

Lanced aluminum fins

Across the line starter/direct on line

Single point connection main line unit power-ancillary items require other power

Circuit breaker

Enclosure Type UL 60335 Rated for Outdoor Applications

External chilled/hot water and demand limit setpoint - 4-20mA

With % capacity

Programmable relays

Default A short circuit rating

Elastomeric isolators

With water strainer factory installed

Super quiet

Louvers

1st year refrigerant warranty

CLIN 0003

Startup must be provided by TRANE U.S Inc. certified service personnel.

Delivery Information:

FOB Destination

Address:

ATTN: Herman Dawkins

6001 Fuel Road, Bldg 665

Francis E. Warren AFB, WY, 82005