Attachment 1 - Salient Characteristics.pdf

PDF 124 KB Posted

Attached to
Chiller Building 698 Federal contract opportunity
Solicitation number
FA252122QA011
Issued by
Department of the Air Force Space Command

View the file

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ATTACHMENT 1 – SALIENT

CHARACTERISTICS

NEED/ REQUEST FOR BUILDING 698.

This is a commodity purchase. No installation is required for the requirement.

The request for one air cooled chiller is required to maintain the 920th Rescue Wing at facility 698. The chiller provides necessary equipment cooling to environmental sensitive server and comfort cooling. All equipment in the facility must have and maintain a 65°F-70°F +/- 2°F degree condition space as well as a 20-30% relative humidity.

COMMODITY REPLACEMENT

An air cooled chiller is a machine that that removes heat via the refrigeration cycle. Providing a range of cooling to a condition space.

SALIENT CHARACTRERISTIC

Brand name Trane Startup Included - Trane Service must start equipment for warranty to be honored 35 nominal tons 460 volt 3 phases High efficiency/performance Full factory refrigerant charge (HFC-410A) With factory installed freeze protection Refrigerant isolation valves (discharge valve) Factory installed flow switch - set point 60 cm/sec Grooved pipe connection

Factory insulation 1.25" - high humidity/low evaporator temperature Wide ambient (0 to 125F/-18 to 52C) Lanced aluminum fins Across the line starter/direct on line Single point connection main line unit power-ancillary items require other power Circuit breaker Enclosure type UL 1995 rated for outdoor applications LonTalk/Tracer Summit interface Dual high head pump Pump flow ctrl by var speed drive With buffer storage tank Default A short circuit rating

With water strainer factory installed Architectural louvered panels 10 year parts/labor/refrigerant warranty Corrosion coating for condenser coil and cabinet

ATTACHMENT 1 – SALIENT CHARACTERISTICS
COMMODITY REPLACEMENT
SALIENT CHARACTRERISTIC

File details come from the government source that posted it. Updated .