Attachment_1_-_Revised_Flowmeter_Salient_Characteristics_-_21_March_2024.pdf

PDF 154 KB Posted

Attached to
EC - FI Flowmeter Federal contract opportunity
Solicitation number
140R6024Q0041
Issued by
Department of the Interior Bureau of Reclamation

About this file

This document is an attachment titled "Attachment_1_-Revised_Flowmeter_Salient_Characteristics-_21_March_2024.pdf" related to a federal contract opportunity for the Bureau of Reclamation to procure three AccuSonic 8510+ flow meters or equivalent. The attachment outlines the detailed technical specifications for the required flowmeter console, including size, power, connectivity, data logging, and display requirements. It also provides the salient characteristics of the FlatIron Power Plant flow meter location, including pipe size, fluid type and conditions, and expected flow rates and pressure. The delivery location, schedule, and one-year warranty terms are also specified. The related federal contract opportunity is solicitation number 140R6024Q0041 for the "EC - FI Flowmeter" requirement, which is a total small business set-aside under NAICS code 334513.

View the file

Other files for this federal contract opportunity

Other files attached to EC - FI Flowmeter, newest first.
File Type Posted
Combined_Synopsis_Solicitation_Flowmeter_-_21_March_2024.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Bureau of Reclamation, Eastern Colorado Area Office EC-FI Flowmeter

1. Flowmeter Characteristics

a. Standard Equipment

i. Three (3) AccuSonic 8510+ Flow Meters or equivalent

2. Required Specifications for Flowmeter Portable Console

a. Capably to measure discrete acoustic travel times to arrive at an average velocity for each of the acoustic paths. These velocity data points shall be integrated over the cross-sectional area of flow to determine the average flowrate through the pipe. The method of measuring and computing water velocity shall be independent of the speed of sound in water.

b. Console housed in NEMA 4X wall-mount weatherproof enclosure.

i. Must not exceed 18” H x 16” W x 10” D

c. 90-250 VAC, 47-63 Hz or 100-300 VDC External Power

d. Fully compatible with Accusonic internal mount and feedthrough transducers

e. Six (6) Contact Relay Outputs for Alarming

f. Evaluate each acoustic signal received and shall reject those which are distorted by reflections or reverberations or whose amplitude is below a minimum value. Velocity and rate-of-change-of-velocity limits shall be user-selectable and adjustable on- site.

g. The flowmeter console shall include a Modbus interface via RS-232, RS-485, or TCP/IP, capable of providing flowrate, total flow, and flowmeter alarming.

h. The flowmeter console shall have at a minimum auxiliary relays with contacts rated for 125 Vdc, to annunciate a flowmeter watchdog alarm, a flowmeter under voltage alarm, and a general flowmeter system alarm.

i. Minimum 2 Gigabyte internal data logging storage

j. LCD Touchscreen Display for user interface, with a minimum of 4 lines of vertical output display. The touchscreen display shall be mounted inside the door of the enclosure.

k. Capable of communication via a PC through a Microsoft Windows 10 user interface.

l. Display pipe flowrate and totalized flow.

m. Minimum of two (2) isolated analog 4-20 mA outputs of flowrate in two different pipe sections.

n. Designed to return to full operation following a short-term power interruption, with all stored values retained.

3. FlatIron Power Plant Flow Meter Salient Characteristics

a. Penstock (at location of flow meter): 72” welded steel pipe, epoxy coated.

b. Fluid: Untreated fresh water.

c. Fluid Temp: Operation temps between 34°F and 60°F.

d. Fluid Velocity: Min. Flow 0.1 ft/sec; Max. expected flow 20.2 ft/sec.

e. Expected pressure: 1,100 ft of h2O.

f. Fluid viscosity and density: Fresh Water.

g. Outside Temperature: -20°F to 100°F.

4. Delivery Location and Time

a. The delivery location is: 11056 W CR 18 E - Loveland, CO 80537

i. The point of contact will be Anthony Nguyen (anguyen@usbr.gov) or Tyler

Myers (tmyers@usbr.gov).

b. Delivery will be conducted during business hours Monday through Thursday 8:00 AM to

4:00 PM. Contact Anthony Nguyen or Tyler Myers with the time of the delivery at minimum three days before arrival. No deliveries on federal holidays.

5. Warranty mailto:anguyen@usbr.gov

Bureau of Reclamation, Eastern Colorado Area Office EC-FI Flowmeter

a. The flowmeter manufacturer shall provide a factory warranty for a period of one (1) year following shipment of the flowmeter system. During the one (1) year warranty period, the manufacturer shall, at the manufacturer's option, repair or replace any part which fails due to defects in materials.

File details come from the government source that posted it. Updated .