This document includes technical specifications for electrical utility service requirements at multiple locations for the Bureau of Reclamation. The utility service is needed at nine pumping plant locations in the Klamath Falls, Oregon area, as well as structures along the A Canal, to include underground 3-phase power at 240/480 volts or single-phase power at 120/240 volts. Specific requirements are outlined for each location, with voltage and phase requirements varying based on equipment needs. Maps showing site locations are included as attachments. The related federal contract opportunity is to provide the electrical utility service under solicitation number 140R2020Q0051.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attach 1 Site Map B.pdf | ||
| Attach 1 Site Map A.pdf | ||
| Sol_140R2020Q0051.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
KBAO Pacific Power Utility Service – 19KBAO0088 Updated 7/11/19
Line Item
Description Account # Address Map Number
The type of electric service required by the Government is:
The normal delivery voltage shall be:
00010 Pumping Power to No.
1,2 and 3- Drainage Pumps, Sump
40470641-005-1, No. 2 Pump, 1.4 Mile S. Township Road, Worden, CA (AREA K)
12-201-5283 Attach 1 Site Map A
[] overhead [X] underground, 60 cycle/hertz, [] single-phase [] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]
[] 120/240 [] 120/208 [X] 240/480 [] 277/480 [] _______ [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of _____ percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]
40470641-006-9, No. 3 Pump, 1.4 Mile S. Township Road, Warden, CA (AREA K)
12-201-5283 Attach 1 Site Map A
[] overhead [X] underground, 60 cycle/hertz, [] single-phase [] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]
[] 120/240 [] 120/208 [X] 240/480 [] 277/480 [] _______ [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of _____ percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]
40470641-007-7, No. 1 Pump, 1 Mile S.
Township Road, Worden, CA (AREA K)
12-201-5283 Attach 1 Site Map A
[] overhead [X] underground, 60 cycle/hertz, [] single-phase [] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]
[] 120/240 [] 120/208 [X] 240/480 [] 277/480 [] _______ [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of _____ percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]
40470641-015-0 Sump 3, Lot 8327 Washrack # 3, County Road 103, Tulelake, CA
12-201-5386 Attach2 Site Map B
[X] overhead [] underground, 60 cycle/hertz, [] single-phase [] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]
[] 120/240 [] 120/208 [X] 240/480 [] 277/480 [] _______ [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of _____ percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]
00020 Power to Lower Lake Rd Merrill
40470641-002-8 No. 4 Pump & C-1-1 pump, AREA K, OR
12-201-5283 Attach 1 Site Map A
[] overhead [X] underground, 60 cycle/hertz, [] single-phase [X] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]
[] 120/240 [] 120/208 [X] 240/480 [] 277/480 [] _______ [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of _____ percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]
00030 Power to
KBAO &
Boat Barn/O&M Office
40470641-011-9, 6600 Washburn Way, Klamath Falls OR, 97603
[X- historical meter # 237657730] overhead [X-historical meter # 16488548] underground, 60 cycle/hertz, [X] single-phase [] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]
[X] 120/240 [] 120/208 [] 240/480 [] 277/480 [] _______ [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of _____ percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]
40470641-001-0 6600 Washburn Way, Klamath Falls OR, 97603
[] overhead [X] underground, 60 cycle/hertz, [X] single-phase [] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]
[X] 120/240 [] 120/208 [] 240/480 [] 277/480 [] _______ [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of _____ percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]
00040 Power to Station 48, Wilson Dam
40470641-012-7, Station 48 at Henley Road, Lost River
[] overhead [X] underground, 60 cycle/hertz, [X] single-phase [] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]
[] 120/240 [] 120/208 [X] 240/480 [] 277/480 [] _______ [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of _____ percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]
40470641-013-5 Wilson Dam at Hill Road, Lost River
[] overhead [X] underground, 60 cycle/hertz, [X] single-phase [] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]
[X] 120/240 [] 120/208 [] 240/480 [] 277/480 [] _______ [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of _____ percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]
00050 Power to Plant E & EE
40470641-004-4, Pumping Plant E, Klamath Falls, OR
[] overhead [X] underground, 60 cycle/hertz, [] single-phase [X] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]
[] 120/240 [] 120/208 [] 240/480 [] 277/480 [X] 2400 [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of _____ percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]
40470641-008-5 Pumping Plant EE, Hwy 97, Klamath Falls, OR
[] overhead [X] underground, 60 cycle/hertz, [] single-phase [X] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]
[] 120/240 [] 120/208 [] 240/480 [] 277/480 [X] 2400 [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of _____ percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]
00060 Power to Plant F & FF
40470641-009-3, Pumping Plant FF, Ashland Star Rt
[] overhead [X] underground, 60 cycle/hertz, [] single-phase [X] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]
[] 120/240 [] 120/208 [] 240/480 [] 277/480 [X] 2400 [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of _____ percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]
40470641-010-1 Pumping Plant F, Klamath Falls, OR
[] overhead [X] underground, 60 cycle/hertz, [] single-phase [X] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]
[] 120/240 [] 120/208 [] 240/480 [] 277/480 [X] 2400 [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of _____ percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]
00070 A Canal 40470641-004-4 A Canal Structures at 400 Nevada Street, Klamath Falls, OR
[] overhead [X] underground, 60 cycle/hertz, [] single-phase [X] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]
[] 120/240 [] 120/208 [X] 240/480 [] 277/480 [] _______ [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of _____ percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]