Attach-1-SOW.pdf
PDF 9 MB Posted
- Attached to
- VALLE DE ORO-METAL BUILDING Federal contract opportunity
- Solicitation number
- 140F0220R0053
About this file
This solicitation requests proposals for the construction of a metal building at Valle de Oro National Wildlife Refuge. The project involves erecting a pre-engineered metal building to serve as a maintenance shop. Proposals are due by February 20, 2023, with award anticipated by April 2023. The period of performance is 120 days after award. The solicitation is set aside for small businesses and issued by the Department of the Interior U.S. Fish and Wildlife Service Region 2. Pricing shall be firm-fixed price and include all labor, materials, equipment, shipping, and permits to complete the project.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attach-4-DBA Min. Wage Rates.pdf | ||
| Sol_140F0220R0053.pdf | ||
| Attach-3-Price Sheet.xlsx | XLSX spreadsheet | |
| Attach-2-Past Performance and Clauses.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WW0.01
GENERAL NOTE, DESIGN DATA, LEGEND, AND INDEX OF SHEETS
WW1.01 OVERALL SITE PLAN
WW1.02 COLLECTION PLAN - VISITOR CENTER
WW1.03 COLLECTION PLAN - MAITENANCE SHOP
WW1.04 PRIMARY TREATMENT AND DOSING TANK - VISITOR CENTER
WW1.05 PRIMARY TREATMENT TANK - MAINTENENCE SHOP
WW1.06 DOSING TANK - MAINTENANCE SHOP
WW1.07 COLLECTION DETAILS
WW2.01 LOW PRESSURE PIPE DRAINFIELD - VISITOR CENTER
WW2.02 LOW PRESSURE PIPE DRAINFIELD - MAINTENANCE SHOP
WW2.03 LOW PRESSURE DRAINFIELD DETAILS
WW2.04 LOW PRESSURE DRAINFIELD DETAILS
PROJECT #
SHEET TITLE
PLOT DATE
DATEREV ISSUE
F17PS00661
17 OCT 2019
WW0.01
UNITED STATES
DEPARTMENT OF THE INTERIOR
US FISH & WILDLIFE
SERVICE
100% CONSTRUCTION
DOCUMENTS
DIVISION OF ENGINEERING
VALLE DE ORO
NATIONAL WILDLIFE
REFUGE
BERNALILLO COUNTY NEW MEXICO
HEADQUARTERS &
VISITOR CENTER
ARCHITECTURAL
WEDDLE GILMORE
6916 east fifth avenue scottsdale arizona 85251
480 517 5055
DESIGN ARCHITECT
PADILLA-BRYCON
134 rio rancho boulevard ne rio rancho new mexico 87124
505 916 0695
GENERAL CONTRACTOR
FORMATIVE ARCHITECTURE
209 gold avenue sw albuquerque new mexico 87102
505 510 4600
EXECUTIVE ARCHITECT
SURROUNDINGS
1611 paseo de peralta santa fe new mexico 87501
505 982 3454
LANDSCAPE ARCHITECT
BIOHABITATS INC
3600 cerrillos road #1102 santa fe new mexico 87507
505 988 7453
WETLAND / WASTE WATER
HIGH MESA CONSULTING GROUP
6010-b midway park boulevard ne albuquerque new mexico 87109
505 345 4250
CIVIL ENGINEER
RME ABQ, LLC
2715 broadbent parkway ne, suite D albuquerque new mexico 87107
505 889 3004
STRUCTURAL ENGINEER
BRIDGERS & PAXTON
4600-c montgomery boulevard ne albuquerque new mexico 87109
505 883 4111
MEP ENGINEER
IDEUM
2469 corrales road, building d corrales, new mexico 87048
505-792-1110
EXHIBIT DESIGN
IRRIGATION SERVICES, INC.
44 good drive belen new mexico 87002
505 861 1536
IRRIGATION DESIGN
Rev 1. 5-15-20 Maintenance Shop Septic Update to Invert and Models1 5-15-20
GENERAL NOTES
1. DO NOT PROVIDE PARTIAL SETS OF DRAWINGS TO SUB-CONTRACTORS.
DISTRIBUTE FULL SETS ONLY.
2. SPECIFICATIONS MUST ACCOMPANY DRAWINGS.
3. IMMEDIATELY CONTACT ENGINEER LISTED ON TITLE BLOCK IF ANY
DISCREPANCIES ARE FOUND BETWEEN DRAWINGS AND/OR SPECIFICATIONS.
4. INSULATE PIPES WHERE LESS THAN MINIMUM COVER. SEE SPEC. 220719.
5. IN THE EVENT THAT GROUNDWATER IS PRESENT DURING THE EXCAVATION OF
TANKS, OR IF SOIL CONDITIONS INDICATE THE PRESENCE OF SEASONALLY HIGH
GROUND WATER, THE ENGINEER IS TO BE NOTIFIED IMMEDIATELY.
INSTRUCTIONS FOR THE INSTALLATION USING CONCRETE DEADMEN ARE TO BE
FOLLOWED.
6. THIS SYMBOL ( ) INDICATES A CONTROL ELEVATION. CONTROL ELEVATIONS ARE
CRUCIAL DESIGN POINTS THAT MUST BE SURVEYED, RECORDED AND VERIFIED
BY THE CONTRACTOR DURING AND AFTER INSTALLATION OF EQUIPMENT OR
TREATMENT ELEMENTS. CONTRACTOR TO NOTIFY ENGINEER IN EVENT OF
DISCREPANCY. SEE SPECIFICATIONS FOR ELEVATION TOLERANCE LIMITS
(TYPICALLY +/- 0.01 FT).
7. ALL UNIONS, VALVES, VAULT HANDLES, FLOAT TREE ASSEMBLIES AND OTHER
EQUIPMENT USED DURING ROUTINE OPERATIONS MUST BE WITHIN REACH OF
THE RISER/VAULT OPENING. REFER TO SPECIFIC DETAILS FOR REACH DEPTH
RECOMMENDATION.
8. SIZE ALL WIRE AND CONDUIT PER NEC.
9. MINIMUM COVERS
PRESSURE PIPES: 36"
GRAVITY PIPES: 36"
TOP OF TANK: 12"
10. SPACING AND SETBACKS
CLEANOUTS: END OF LINE CLEANOUT TO BE PLACED AT END OF EVERY
COLLECTION LINE. SINGLE CLEANOUTS TO BE PLACED EVERY 300 FT ALONG
COLLECTION LINE. DOUBLE CLEANOUTS TO BE PLACED OUTSIDE OF BUILDINGS
AS SHOWN ON DRAWINGS.
SEWER NOTES (PRIVATE)
1. ALL SEWER CONSTRUCTION SHALL BE PERFORMED IN ACCORDANCE WITH
LOCAL AND NATIONAL BUILDING CODES.
2. MINIMUM SLOPE FOR GRAVITY SEWER LATERALS SHALL BE 2.00% UNLESS
OTHERWISE NOTED.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY SEWAGE SPILLS
CAUSED DURING CONSTRUCTION. THE CONTRACTOR SHALL NOTIFY
APPROPRIATE AUTHORITIES AND UTILIZE APPROPRIATE SAMPLING AND
ANALYZING PROCEDURES. THE CONTRACTOR SHALL BE RESPONSIBLE FOR
ALL PUBLIC NOTIFICATION AND PRESS RELEASES. THIS WORK SHALL BE
DONE AT THE CONTRACTOR'S EXPENSE.
3. WHEREVER CONNECTIONS OF NEW UTILITIES TO EXISTING UTILITIES ARE
SHOWN ON THE DRAWINGS, THE CONTRACTOR SHALL EXPOSE THE EXISTING
LINES AT THE PROPOSED CONNECTIONS TO VERIFY THEIR LOCATIONS AND
DEPTHS PRIOR TO EXCAVATING FOR THE NEW LINES.
4. INVERTS SHOWN FOR ANY EXISTING SEWER PIPING ARE APPROXIMATE. THE
CONTRACTOR SHALL VERIFY LOCATION AND INVERT OF EXISTING SEWER. IN
THE EVENT THAT ANY CHANGE IN ALIGNMENT OR GRADE FOR THE
PROPOSED SEWERS ARE REQUIRED DUE TO EXISTING SEWER LINE INVERT
OR UNFORESEEN CONFLICT WITH OTHER UTILITIES, THE CONTRACTOR
SHALL ADJUST INVERTS AND ALIGNMENTS FOR NEW PIPING ACCORDINGLY.
MODIFICATIONS SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL
PRIOR TO PROCEEDING WITH RE-ALIGNMENT WORK.
5. THE CONTRACTOR SHALL NOTIFY THE ENGINEER FOURTEEN DAYS IN
ADVANCE TO OBSERVE THE INSTALLATION OF THE WASTEWATER SYSTEM
BEFORE BACKFILLING. IF THE SYSTEM IS BACKFILLED PRIOR TO
OBSERVATION, THE CONTRACTOR SHALL BE REQUIRED TO EXPOSED THE
SYSTEM FOR INSPECTION AT THEIR OWN EXPENSE.
6. THE CONTRACTOR SHALL PHOTOGRAPH ALL STAGES OF INSTALLATION OF
WASTEWATER SYSTEM INCLUDING EXCAVATED AREAS AND TRENCHES
PRIOR TO INSTALLATIONS, WASTEWATER SYSTEM AND PIPING PRIOR TO
BACKFILL, AND WASTEWATER SYSTEM AND PIPING AFTER BACKFILLED AND
PRIOR TO GRASSING. THE CONTRACTOR SHALL SUBMIT PHOTOS TO THE
ENGINEER AFTER COMPLETION OF EACH STAGE NOTED.
CONSTRUCTION NOTES
1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH LOCAL AND NATIONAL CODES.
2. THE CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS AND LICENSES, PAY
ALL CHARGES, FEES AND TAXES, GIVE ALL NOTICES AND COMPLY WITH ALL LAWS,
ORDINANCES, RULES AND REGULATIONS BEARING ON THE CONDUCT OF THE
WORK AS DRAWN AND SPECIFIED.
3. THE CONTRACTOR SHALL PROVIDE ACCESS TO AND FROM DRIVEWAYS AND PUBLIC
STREETS AT ALL TIMES EXCEPT AS NOTED ON THE PLAN.
4. WHEN TRENCH EXCAVATION IS ADJACENT TO OR UNDER EXISTING STRUCTURES
OR FACILITIES, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROPERLY
SHEETING AND BRACING THE EXCAVATION AND STABILIZING THE EXISTING
GROUND TO RENDER IT SAFE AND SECURE FROM POSSIBLE SLIDES, CAVE-INS AND
SETTLEMENT AND FOR PROPERLY SUPPORTING EXISTING STRUCTURES AND
FACILITIES WITH BEAMS, STRUTS OR UNDER-PINNING TO FULLY PROTECT THEM
FROM DAMAGE.
5. VERIFY AND CHECK ALL DIMENSIONS AND DETAILS SHOWN ON THE DRAWINGS
PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCY SHALL BE
IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ENGINEER. COMMENCEMENT
OF CONSTRUCTION SHALL INDICATE CONTRACTOR'S ACCEPTANCE OF EXISTING
SITE CONDITIONS.
6. THE CONTRACTOR SHALL NOTIFY ALL AGENCIES TO VERIFY THE ACTUAL
LOCATIONS OF ALL UTILITIES IN THE PROJECT AREA PRIOR TO EXCAVATING. THE
CONTRACTOR SHALL COORDINATE ALL WORK.
7. THE CONTRACTOR SHALL RESTORE TO THEIR ORIGINAL CONDITION ALL
IMPROVEMENTS DAMAGED AS A RESULT OF THE CONSTRUCTION, INCLUDING
PAVEMENTS, EMBANKMENTS, SIGNS, LANDSCAPING, STRUCTURES, UTILITIES,
WALLS, FENCES, ETC. AT NO ADDITIONAL EXPENSE TO THE OWNER.
8. THE CONTRACTOR SHALL NOT PERFORM ANY CONSTRUCTION OPERATION SO AS
TO CAUSE FALLING ROCKS, SOIL OR DEBRIS IN ANY FORM TO FALL, SLIDE OR FLOW
INTO EXISTING DRAINAGE SYSTEMS, OR ADJOINING PROPERTIES, STREETS OR
NATURAL WATER COURSES. SHOULD SUCH VIOLATIONS OCCUR, THE
CONTRACTOR MAY BE CITED AND THE CONTRACTOR SHALL IMMEDIATELY MAKE
ALL REMEDIAL ACTIONS NECESSARY AT NO COST TO THE OWNER.
9. CONFINED SPACE
FOR ENTRY BY STATE PERSONNEL, INCLUDING INSPECTORS, INTO A PERMIT
REQUIRED CONFINED SPACE, THE CONTRACTOR SHALL BE RESPONSIBLE FOR
PROVIDING:
A. ALL SAFETY EQUIPMENT REQUIRED BY THE CONFINED SPACE
REGULATIONS APPLICABLE TO ALL PARTIES OTHER THAN THE
CONSTRUCTION INDUSTRY, TO INCLUDE, BUT NOT LIMITED TO, THE
FOLLOWING:
1) FULL BODY HARNESSES FOR UP TO TWO PERSONNEL.
2) LIFELINE AND ASSOCIATED CLIPS.
3) INGRESS/EGRESS AND FALL PROTECTION EQUIPMENT.
4) TWO-WAY RADIOS (WALKIE-TALKIES) IF OUT OF LINE-OF-SIGHT.
5) EMERGENCY (ESCAPE) RESPIRATOR (10 MINUTE DURATION).
6) CELLULAR TELEPHONE TO CALL FOR EMERGENCY ASSISTANCE.
7) CONTINUOUS GAS DETECTOR (CALIBRATED) TO MEASURE OXYGEN,
HYDROGEN SULFIDE, CARBON MONOXIDE AND FLAMMABLES
(CAPABLE OF MONITORING AT A DISTANCE AT LEAST 20 FEET
AWAY).
8) PERSONAL MULTI-GAS DETECTOR TO BE CARRIED BY INSPECTOR.
B. CONTINUOUS FORCED AIR VENTILATION ADEQUATE TO PROVIDE SAFE
ENTRY CONDITIONS.
C. ONE ATTENDANT / RESCUE PERSONNEL. TOPSIDE (TWO, IF CONDITIONS
WARRANT IT).
14. BOULDERS, ROCK, OR SIMILAR MATERIAL MAY BE ENCOUNTERED DURING
EXCAVATION. EXCAVATION OF THESE MATERIALS SHALL BE DONE AT NOT
ADDITIONAL COST TO THE OWNER.
15. CONTRACTOR SHALL MAKE ARRANGEMENTS FOR UTILITIES SUCH AS ELECTRICITY,
WATER, TELEPHONE ETC., REQUIRED FOR THEIR OPERATIONS AND ALL COSTS
SHALL BE BORNE BY THE CONTRACTOR.
PW
P
WASTEWATER / STORMWATER LINE
ELECTRICAL LINE
POTABLE WATER LINE
END OF LINE CLEANOUT
DOUBLE CLEANOUT
VALVE
PUMP INSTALLED
WELL LOCATION
INDEX OF SHEETS
LEGEND
GENERAL NOTE, DESIGN DATA,
LEGEND, AND INDEX OF SHEETS
SOIL BORING
W
2 2
TP-03
TP-02
TP-04
TP-05
TP-06
TP-07
TP-08
TP-01
22222222222
22222222222
22222222222
22222222222
22222222222
22222222222
4914.3 x
4914.5 x
4914.5 x
4918.8 x
4918.8 x
4916.1 x
4917.5 x
4918.8 x
PROJECT #
SHEET TITLE
PLOT DATE
DATEREV ISSUE
F17PS00661
17 OCT 2019
WW1.01
UNITED STATES
DEPARTMENT OF THE INTERIOR
US FISH & WILDLIFE
SERVICE
100% CONSTRUCTION
DOCUMENTS
DIVISION OF ENGINEERING
VALLE DE ORO
NATIONAL WILDLIFE
REFUGE
BERNALILLO COUNTY NEW MEXICO
HEADQUARTERS &
VISITOR CENTER
ARCHITECTURAL
WEDDLE GILMORE
6916 east fifth avenue scottsdale arizona 85251
480 517 5055
DESIGN ARCHITECT
PADILLA-BRYCON
134 rio rancho boulevard ne rio rancho new mexico 87124
505 916 0695
GENERAL CONTRACTOR
FORMATIVE ARCHITECTURE
209 gold avenue sw albuquerque new mexico 87102
505 510 4600
EXECUTIVE ARCHITECT
SURROUNDINGS
1611 paseo de peralta santa fe new mexico 87501
505 982 3454
LANDSCAPE ARCHITECT
BIOHABITATS INC
3600 cerrillos road #1102 santa fe new mexico 87507
505 988 7453
WETLAND / WASTE WATER
HIGH MESA CONSULTING GROUP
6010-b midway park boulevard ne albuquerque new mexico 87109
505 345 4250
CIVIL ENGINEER
RME ABQ, LLC
2715 broadbent parkway ne, suite D albuquerque new mexico 87107
505 889 3004
STRUCTURAL ENGINEER
BRIDGERS & PAXTON
4600-c montgomery boulevard ne albuquerque new mexico 87109
505 883 4111
MEP ENGINEER
IDEUM
2469 corrales road, building d corrales, new mexico 87048
505-792-1110
EXHIBIT DESIGN
IRRIGATION SERVICES, INC.
44 good drive belen new mexico 87002
505 861 1536
IRRIGATION DESIGN
Rev 1. 5-15-20 Maintenance Shop Septic Update to Invert and Models1 5-15-20
OVERALL SITE PLAN
SCALE:
0100 100 200
N
1" = 100'
CAP FORCE MAIN PIPE
FOR FUTURE BYPASS
TO SANITARY SEWER
LOW PRESSURE
PIPE DRAINFIELD
MAINTENANCE SHOP
WASTEWATER NOTES
N-1. THE PROPOSED WASTEWATER APPROACH IS TO PROVIDE TWO SEPARATE SYSTEMS FOR THE VISITOR CENTER AND
MAINTENANCE SHOP.
N-2. ALL SOILS WITHIN 25 FT OF THE PRIMARY AND RESERVE AREAS SHALL BE PROTECTED FROM DISTURBANCE AND
COMPACTION. FAILURE TO PROTECT THESE SOILS COULD ELIMINATE THEIR USE FOR ONSITE DISPOSAL.
N-3. THE WASTEWATER SYSTEMS ARE DESIGNED TO BE CONSISTENT WITH BERNALILLO COUNTY CODE 2014-17 SECTIONS
42-491 TROUGH42-523 FOR SYSTEMS THAT ARE UNDER 5,000 GPD.
N-4. THE WASTEWATER SYSTEMS CONSISTS OF THE FOLLOWING ELEMENTS:
- PRIMARY TREATMENT TANK(S) AT EACH POINT OF WASTEWATER GENERATION
- GRAVITY PIPING TO THE DOSING TANK
- DOSING TANK WITH DUPLEX PUMP SYSTEMS
- LOW PRESSURE PIPE DOSED DRAINFIELD CONSTRUCTED AT GRADE.
N-5. WASTEWATER FLOWS
RESERVE AREA
RESERVE AREA
COLLECTION PLAN
- VISITOR CENTER
N-6. SYSTEM SIZING DATA
VISITOR CENTER
DESIGN FLOW Q = 3,829 GPD
SOIL TYPE = LOAM
LOADING RATE = 2 SF/GPD
TYPE = LOW PRESSURE PIPE INSTALLED AT GRADE WITH MOUND
TREATMENT AREA (MINIMUM/DESIGN) = 7,658 SF / 7,700 SF
PRIMARY TREATMENT TANK SIZE = 4,000 GAL.
DOSING TANK = 4,000 GAL.
TOTAL TANK VOLUME INSTALLED = 8,000 GAL.
DRAINFIELD AREA = TWO FIELDS 65' L x 35' W = 4550 SF TOTAL . PLUS EQUAL (100%) RESERVE AREA
MAINTENANCE SHOP
PROPOSED FLOWS = 843 GPD
SOIL TYPE = LOAM
LOADING RATE = 2 SF/GPD
TYPE = LOW PRESSURE PIPE INSTALLED AT GRADE WITH MOUND
TREATMENT AREA (MINIMUM/DESIGN) = 1,686 SF / 1,800 SF
PRIMARY TREATMENT TANK SIZE = 2,000 GAL.
DOSING TANK SIZE = 1,000 GAL
DRAINFIELD AREA = 1,800 SF PLUS EQUAL (100%) RESERVE AREA
N-7. SITE DATA
PROPERTY = 570 AC.
DOMESTIC WATER SUPPLY = OFFSITE CONNECTION TO MUNICIPAL WATER SUPPLY
IRRIGATION WATER SUPPLY = IRRIGATION WELLS
IRRIGATION
WELL
MAINTENANCE
SHOP FACILITIES
FUTURE
CONNECTION
VISITOR CENTER
FACILITIES
DESIGN FLOW AT VISITOR CENTER FACILITIES
DESIGN FLOW AT MAINTENANCE SHOP FACILITIES
CAP FORCE MAIN PIPE
FOR FUTURE BYPASS
TO SANITARY SEWER
INSTALL APPROX. 1988 LF OF 2"
HDPE PRESSURE LINE FROM
VISITOR CENTER PRIMARY
TREATMENT TANK TO FUTURE
LIFT STATION FOR FUTURE
BYPASS TO SANITARY SEWER
WW1.02
WW2.01
COLLECTION PLAN
MAINTENANCE SHOP
WW2.02
WW1.03
SCALE: 1" = 100'
WW1.01
OVERALL SITE PLAN
200' WELL SETBACK
INSTALL AIR
RELEASE
VALVES AT HIGH
POINTS
LOW PRESSURE
PIPE DRAINFIELD
VISITOR CENTER
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
INV15.65
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
INV15.00
AutoCAD SHX Text
INV15.09
AutoCAD SHX Text
INV15.05
AutoCAD SHX Text
INV14.85
AutoCAD SHX Text
INV15.05
AutoCAD SHX Text
INV14.51
AutoCAD SHX Text
INV15.60
AutoCAD SHX Text
INV15.40
AutoCAD SHX Text
INV16.32
AutoCAD SHX Text
INV16.63
AutoCAD SHX Text
INV14.85
AutoCAD SHX Text
INV14.68
AutoCAD SHX Text
INV14.71
AutoCAD SHX Text
INV14.58
AutoCAD SHX Text
INV14.65
AutoCAD SHX Text
INV14.97
AutoCAD SHX Text
INV14.89
AutoCAD SHX Text 22.6
AutoCAD SHX Text 23.1
AutoCAD SHX Text 23.2
AutoCAD SHX Text 22.6
AutoCAD SHX Text 22.5
AutoCAD SHX Text 23.8
AutoCAD SHX Text 24.7
AutoCAD SHX Text 24.9
AutoCAD SHX Text 24.2
AutoCAD SHX Text 22.2
AutoCAD SHX Text 22.0
AutoCAD SHX Text 22.6
AutoCAD SHX Text 24.4
AutoCAD SHX Text 22.2
AutoCAD SHX Text 22.0
AutoCAD SHX Text 24.7
AutoCAD SHX Text 23.9
AutoCAD SHX Text 22.9
AutoCAD SHX Text 22.5
AutoCAD SHX Text 22.1
AutoCAD SHX Text 22.7
AutoCAD SHX Text 22.7
AutoCAD SHX Text 22.8
AutoCAD SHX Text 22.4
AutoCAD SHX Text 23.1
AutoCAD SHX Text 22.7
AutoCAD SHX Text 22.6
AutoCAD SHX Text 22.4
AutoCAD SHX Text 22.3
AutoCAD SHX Text 22.1
AutoCAD SHX Text 22.8
AutoCAD SHX Text
EM
AutoCAD SHX Text 16.97
AutoCAD SHX Text 17.30
AutoCAD SHX Text 20.28
AutoCAD SHX Text
GS
AutoCAD SHX Text
CO18.32
AutoCAD SHX Text
GS
AutoCAD SHX Text 20.47
AutoCAD SHX Text 19.40
AutoCAD SHX Text 19.39
AutoCAD SHX Text 19.17
AutoCAD SHX Text
WF
AutoCAD SHX Text
WMB
AutoCAD SHX Text
EM
AutoCAD SHX Text
WF
AutoCAD SHX Text
WF
AutoCAD SHX Text 19.38
AutoCAD SHX Text 19.33
AutoCAD SHX Text
CO20.15
AutoCAD SHX Text
CO19.85
AutoCAD SHX Text
CO19.47
AutoCAD SHX Text
CO19.43
AutoCAD SHX Text
CO17.51
AutoCAD SHX Text
WF
AutoCAD SHX Text
WF
AutoCAD SHX Text
WF
AutoCAD SHX Text
SAPM
AutoCAD SHX Text
SAPM
AutoCAD SHX Text
SAPM
AutoCAD SHX Text
SAPM
AutoCAD SHX Text
SAPM
AutoCAD SHX Text
SAPM
AutoCAD SHX Text
SAPM
AutoCAD SHX Text
SAPM
AutoCAD SHX Text
SAPM
AutoCAD SHX Text
SAPM
AutoCAD SHX Text
SAPM
AutoCAD SHX Text
WARV
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
INV16.50
AutoCAD SHX Text
INV15.10
AutoCAD SHX Text
INV13.70
AutoCAD SHX Text
INV16.30
AutoCAD SHX Text
INV16.59
AutoCAD SHX Text
INV15.08
AutoCAD SHX Text
INV15.32
AutoCAD SHX Text
INV16.62
AutoCAD SHX Text
INV16.31
AutoCAD SHX Text
INV15.56
AutoCAD SHX Text
INV14.17
AutoCAD SHX Text
INV16.50
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
INV14.31
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
TRACT 3-A
AutoCAD SHX Text
TRACT 1
AutoCAD SHX Text
TRACT 2-A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FG15.00
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 17.10
AutoCAD SHX Text 17.10
AutoCAD SHX Text W
AutoCAD SHX Text 2"
AutoCAD SHX Text W
AutoCAD SHX Text 2"
AutoCAD SHX Text W
AutoCAD SHX Text 2"
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text 8"
AutoCAD SHX Text 8"
AutoCAD SHX Text 8"
AutoCAD SHX Text F
AutoCAD SHX Text 8"
AutoCAD SHX Text W
AutoCAD SHX Text 2"
AutoCAD SHX Text W
AutoCAD SHX Text 2"
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text 2"
AutoCAD SHX Text 2"
AutoCAD SHX Text W
AutoCAD SHX Text 2"
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text 8"
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text 8"
AutoCAD SHX Text 1-1/4"
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text 2"
AutoCAD SHX Text W
AutoCAD SHX Text 2"
AutoCAD SHX Text W
AutoCAD SHX Text 2"
AutoCAD SHX Text W
AutoCAD SHX Text 2"
AutoCAD SHX Text W
AutoCAD SHX Text 2"
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text 3"
AutoCAD SHX Text
IRR
AutoCAD SHX Text 2"
AutoCAD SHX Text
FP
AutoCAD SHX Text 8"
AutoCAD SHX Text 3"
AutoCAD SHX Text
IRR
AutoCAD SHX Text
IRR
AutoCAD SHX Text 2"
AutoCAD SHX Text
FP
AutoCAD SHX Text W
AutoCAD SHX Text 3"
AutoCAD SHX Text 8"
AutoCAD SHX Text 2"
AutoCAD SHX Text
IRR
AutoCAD SHX Text
FP
AutoCAD SHX Text W
AutoCAD SHX Text 8"
AutoCAD SHX Text 3"
AutoCAD SHX Text 2"
AutoCAD SHX Text
IRR
AutoCAD SHX Text
IRR
AutoCAD SHX Text W
AutoCAD SHX Text
FP
AutoCAD SHX Text 8"
AutoCAD SHX Text 3"
AutoCAD SHX Text 2"
AutoCAD SHX Text 2"
AutoCAD SHX Text
FP
AutoCAD SHX Text W
AutoCAD SHX Text 8"
AutoCAD SHX Text 3"
AutoCAD SHX Text 2"
AutoCAD SHX Text
FP
AutoCAD SHX Text W
AutoCAD SHX Text 8"
AutoCAD SHX Text
IRR
AutoCAD SHX Text
IRR
AutoCAD SHX Text 8"
AutoCAD SHX Text 2"
AutoCAD SHX Text
FP
AutoCAD SHX Text W
AutoCAD SHX Text 3"
AutoCAD SHX Text 2"
AutoCAD SHX Text
IRR
AutoCAD SHX Text 8"
AutoCAD SHX Text
FP
AutoCAD SHX Text W
AutoCAD SHX Text 8"
AutoCAD SHX Text 3"
AutoCAD SHX Text
IRR
AutoCAD SHX Text 2"
AutoCAD SHX Text
FP
AutoCAD SHX Text W
AutoCAD SHX Text 3"
AutoCAD SHX Text W
AutoCAD SHX Text 3"
AutoCAD SHX Text 8"
AutoCAD SHX Text
FP
AutoCAD SHX Text
IRR
AutoCAD SHX Text 2"
AutoCAD SHX Text W
AutoCAD SHX Text
FP
AutoCAD SHX Text 8"
AutoCAD SHX Text 2"
AutoCAD SHX Text 3"
AutoCAD SHX Text
IRR
AutoCAD SHX Text 2"
AutoCAD SHX Text
IRR
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text W
AutoCAD SHX Text D
AutoCAD SHX Text 3/4"
AutoCAD SHX Text 3/4"
AutoCAD SHX Text 3/4"
AutoCAD SHX Text 1-1/4"
AutoCAD SHX Text 1-1/4"
AutoCAD SHX Text 1-1/4"
AutoCAD SHX Text 1-1/4"
AutoCAD SHX Text 1-1/4"
AutoCAD SHX Text
TP15.00
AutoCAD SHX Text
TP15.00
AutoCAD SHX Text
TP15.00
AutoCAD SHX Text
TP15.00
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 17.95
AutoCAD SHX Text 17.95
AutoCAD SHX Text 17.30
AutoCAD SHX Text 17.30
AutoCAD SHX Text 18.00
AutoCAD SHX Text 17.75
AutoCAD SHX Text 17.75
AutoCAD SHX Text 17.85
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text 3/4"
AutoCAD SHX Text 3/4"
AutoCAD SHX Text sdominik Highlight
PRIMARY TREATMENT TANK SIZE = 2,000 GAL.
sdominik Highlight
DRAINFIELD AREA = 1,800 SF PLUS EQUAL (100%) RESERVE AREA
sdominik Highlight
COLLECTION PLAN
MAINTENANCE SHOP
WW2.02
WW1.03
4914.5 x
PROJECT #
SHEET TITLE
PLOT DATE
DATEREV ISSUE
F17PS00661
17 OCT 2019
WW1.02
UNITED STATES
DEPARTMENT OF THE INTERIOR
US FISH & WILDLIFE
SERVICE
100% CONSTRUCTION
DOCUMENTS
DIVISION OF ENGINEERING
VALLE DE ORO
NATIONAL WILDLIFE
REFUGE
BERNALILLO COUNTY NEW MEXICO
HEADQUARTERS &
VISITOR CENTER
ARCHITECTURAL
WEDDLE GILMORE
6916 east fifth avenue scottsdale arizona 85251
480 517 5055
DESIGN ARCHITECT
PADILLA-BRYCON
134 rio rancho boulevard ne rio rancho new mexico 87124
505 916 0695
GENERAL CONTRACTOR
FORMATIVE ARCHITECTURE
209 gold avenue sw albuquerque new mexico 87102
505 510 4600
EXECUTIVE ARCHITECT
SURROUNDINGS
1611 paseo de peralta santa fe new mexico 87501
505 982 3454
LANDSCAPE ARCHITECT
BIOHABITATS INC
3600 cerrillos road #1102 santa fe new mexico 87507
505 988 7453
WETLAND / WASTE WATER
HIGH MESA CONSULTING GROUP
6010-b midway park boulevard ne albuquerque new mexico 87109
505 345 4250
CIVIL ENGINEER
RME ABQ, LLC
2715 broadbent parkway ne, suite D albuquerque new mexico 87107
505 889 3004
STRUCTURAL ENGINEER
BRIDGERS & PAXTON
4600-c montgomery boulevard ne albuquerque new mexico 87109
505 883 4111
MEP ENGINEER
IDEUM
2469 corrales road, building d corrales, new mexico 87048
505-792-1110
EXHIBIT DESIGN
IRRIGATION SERVICES, INC.
44 good drive belen new mexico 87002
505 861 1536
IRRIGATION DESIGN
Rev 1. 5-15-20 Maintenance Shop Septic Update to Invert and Models1 5-15-20
COLLECTION PLAN - VISITOR
CENTER
SCALE:
N
10 10 20
1" = 10'
SCALE: 1" = 10'
WW1.02
COLLECTION PLAN - VISITOR CENTER
WW1.04
PRIMARY TREATMENT
AND DOSING TANK
4" PVC SCH 40 FROM
VISITOR CENTER
SEE CIVIL PLANS
FOR CONTINUATION
2" PVC SCH 40 TO
LOW PRESURE PIPE
DRAINFIELD 1
2" PVC SCH 40 TO
LOW PRESURE PIPE
DRAINFIELD 2
CAP FORCE MAIN PIPE
FOR FUTURE BYPASS
TO SANITARY SEWER
WW1.07
CONTROL PANEL
WITH ALARM
2% MIN SLOPE TO
DRAIN BACK TO
DOSING TANK
10' SETBACK
FROM EASEMENT
FUTURE BYPASS TO
SANITARY SEWER
FLOW METER
BOX
WW2.04
PARKING
STRUCTURE
EXISTING UTILITY
EASEMENT
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
IRR
AutoCAD SHX Text 2"
AutoCAD SHX Text 2"
AutoCAD SHX Text
IRR
AutoCAD SHX Text
PROJECT #
SHEET TITLE
PLOT DATE
DATEREV ISSUE
F17PS00661
17 OCT 2019
WW1.03
UNITED STATES
DEPARTMENT OF THE INTERIOR
US FISH & WILDLIFE
SERVICE
100% CONSTRUCTION
DOCUMENTS
DIVISION OF ENGINEERING
VALLE DE ORO
NATIONAL WILDLIFE
REFUGE
BERNALILLO COUNTY NEW MEXICO
HEADQUARTERS &
VISITOR CENTER
ARCHITECTURAL
WEDDLE GILMORE
6916 east fifth avenue scottsdale arizona 85251
480 517 5055
DESIGN ARCHITECT
PADILLA-BRYCON
134 rio rancho boulevard ne rio rancho new mexico 87124
505 916 0695
GENERAL CONTRACTOR
FORMATIVE ARCHITECTURE
209 gold avenue sw albuquerque new mexico 87102
505 510 4600
EXECUTIVE ARCHITECT
SURROUNDINGS
1611 paseo de peralta santa fe new mexico 87501
505 982 3454
LANDSCAPE ARCHITECT
BIOHABITATS INC
3600 cerrillos road #1102 santa fe new mexico 87507
505 988 7453
WETLAND / WASTE WATER
HIGH MESA CONSULTING GROUP
6010-b midway park boulevard ne albuquerque new mexico 87109
505 345 4250
CIVIL ENGINEER
RME ABQ, LLC
2715 broadbent parkway ne, suite D albuquerque new mexico 87107
505 889 3004
STRUCTURAL ENGINEER
BRIDGERS & PAXTON
4600-c montgomery boulevard ne albuquerque new mexico 87109
505 883 4111
MEP ENGINEER
IDEUM
2469 corrales road, building d corrales, new mexico 87048
505-792-1110
EXHIBIT DESIGN
IRRIGATION SERVICES, INC.
44 good drive belen new mexico 87002
505 861 1536
IRRIGATION DESIGN
Rev 1. 5-15-20 Maintenance Shop Septic Update to Invert and Models1 5-15-20
COLLECTION PLAN -
MAITENANCE SHOP
SCALE:
N
5 5 10
1" = 5'
SCALE: 1" = 5'
WW1.03
COLLECTION PLAN - MAINTENANCE SHOP
PRIMARY
TREATMENT TANK
2,000 GALLON
DOSING TANK
1,000 GALLON
WW1.05
WW1.06
4" PVC SCH 40 FROM
MAINTENANCE SHOP
(SEE CIVIL PLANS)
CONTROL PANEL
WITH ALARM
WW1.07
4" PVC SCH 40 FROM
RV PARKING
(SEE CIVIL PLANS)
2" SCH 40 PVC
PRESSURE LINE TO
LOW PRESSURE DRAIN
FIELD (MAINTENANCE)
SEE SHEET NSI2.02
APPROXIMATELY 400 FT
OVERHEAD
ELECTRICAL
EASEMENT
FLOW METER
BOX
WW2.04
4" PVC SCH 40
at 2% min.
INV IN = 4911.12
INV OUT =4910.95
INV IN = 4910.87
POINT OF
CONNECTION
INV IN = 4911.60
FUTURE BUNKHOUSE
7' SETBACK
FROM FUTURE BUILDING
AutoCAD SHX Text
INV13.70
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text W
AutoCAD SHX Text 1-1/4"
AutoCAD SHX Text W
AutoCAD SHX Text 1-1/4"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text sdominik Highlight
2" SCH 40 PVC
PRESSURE LINE TO
LOW PRESSURE DRAIN
FIELD (MAINTENANCE)
SEE SHEET NSI2.02
APPROXIMATELY 400 FT
sdominik Highlight
FLOW METER
BOX
WW2.0
FLOAT TABLE
FLOAT FUNCTION LOCATION
A HIGH LEVEL ALARM 83" ABOVE TANK FLOOR
B OVERRIDE TIMER ENABLE / DISABLE 77" ABOVE TANK FLOOR
C TIMER ENABLE / DISABLE 28" ABOVE TANK FLOOR
D REDUNDANT OFF / LOW LEVEL ALARM 26" ABOVE TANK FLOOR
CONDUIT
TO
CONTROL
PANEL
4" PVC SCH 40 INFLOW WITH
FLEXIBLE COUPLER
MINIMUM
COVER
SLOPE GROUND AWAY
FROM RISER (TYP)
INSULATE PIPE WHERE LESS
THAN MINIMUM COVER
2" PVC SCH 40
OUTFLOW
PART TABLE
1. FIBERGLASS TANK
8,000 GALLON (312 1/2" L x 96" DIA.)
AVAILABLE FROM: XERXES
SEE SPEC. 333600
2. HIGH HEAD EFFLUENT PUMP (TYP 2)
0.5 HP, 208 V, 3.7 A, x 3 PHASE, 38.2 GPM @ 39.0 TDH MIN.
MODEL: PF50053200
AVAILABLE FROM: ORENCO SYSTEMS INC.
SEE SPEC. 221336
3. 24" ACCESS RISER (TYP 2)
WITH SAFETY GRATE
MODEL: RR24-XX
(XX = CONTRACTOR VERIFIED HEIGHT)
AVAILABLE FROM: ORENCO SYSTEMS, INC.
SEE SPEC. 333600
4. 30" ACCESS RISER
WITH SAFETY GRATE
MODEL: RR30-XX+SX+XD+2(20)
(XX = CONTRACTOR VERIFIED HEIGHT)
AVAILABLE FROM: ORENCO SYSTEMS, INC.
SEE SPEC. 333600
5. 24" FIBERGLASS ACCESS LID (TYP 2)
WITH RISER TO LID ADAPTER
MODEL: FLD24GI2
AVAILABLE FROM: ORENCO SYSTEMS, INC.
SEE SPEC. 333600
6. 30" FIBERGLASS ACCESS LID
WITH RISER TO LID ADAPTER
MODEL: FLD30GCFVI2
AVAILABLE FROM: ORENCO SYSTEMS, INC.
SEE SPEC. 333600
7. INTERNAL EXPLOSION PROOF SPLICE BOX
WITH CONDUIT SEAL KIT
MODEL: SBX-D
AVAILABLE FROM: ORENCO SYSTEMS, INC.
SEE SPEC. 333600
8. BIOTUBE PUMP VAULT
MODEL: PVU102-2419
AVAILABLE FROM: ORENCO SYSTEMS INC.
SEE SPEC. 333600
9. CONTROL PANEL
MODEL: MVP-DAX208V3DMHTPRL - CUSTOM
AVAILABLE FROM: ORENCO SYSTEMS, INC.
SEE SPEC. 409000
10. EXTERNAL SPLICE BOX
MODEL: SBEX SERIES
AVAILABLE FROM: ORENCO SYSTEMS INC.
SEE SPEC. 333600
C
B
A
D
18"
2"
BIOTUBE
PUMP
VAULT
HIGH HEAD
EFFLUENT
PUMP
(TYP 2)
FIBERGLASS
TANK
83"
NOTES:
N-1. PROVIDE WIRING BETWEEN CONTROL PANELS, PUMPS, AND ACCESSORIES IN
ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS AND THE NEC.
N-2. INSULATE PIPES WHERE LESS THAN MINIMUM COVER.
N-3. ALL CONNECTIONS INTO AND OUT OF THE TANKS INCLUDING RISERS MUST BE
SEALED WATERTIGHT TO PREVENT GROUNDWATER INFILTRATION.
N-4. CONTROL PANEL PER DETAIL 5 SHEET WW1.07
N-5. ALL UNIONS, BALL VALVES, VAULT HANDLES, FLOAT TREE ASSEMBLIES AND
OTHER EQUIPMENT USED DURING ROUTINE OPERATIONS SHALL BE EASILY
REMOVABLE FOR OPERATION AND MAINTENANCE AND MUST BE WITHIN 18"
REACH OF THE RISER/VAULT OPENING.
N-6. IN THE EVENT THAT GROUNDWATER IS PRESENT DURING THE EXCAVATION OF
TANKS, OR IF SOIL CONDITIONS INDICATE THE PRESENCE OF SEASONALLY HIGH
GROUND WATER, THE ENGINEER IS TO BE NOTIFIED IMMEDIATELY.
INSTRUCTIONS FOR THE INSTALLATION USING CONCRETE DEADMEN ARE TO
BE FOLLOWED.
N-8. LOCATE CHECK VALVES ADEQUATE DISTANCE FROM PUMP DISCHARGE TO
ELIMINATE DAMAGE OF VALVE.
FINISHED GRADE
4914.50'
INV IN
4908.25'
RIM 4914.75'
24" FIBERGLASS
ACCESS LID
30" ACCESS RISER
30" FIBERGLASS
ACCESS LID
CONCRETE DEADMEN SEE
TANK MANUFACTURER'S
GUIDELINES
2" PVC SCH 40 DISCHARGE
ASSEMBLY WITH CHECK VALVE,
GATE VALVE, AND QUICK
DISCONNECT FLEX HOSE
(TYP 2)
MAX. L. L.
FROM BUILDING
SANITARY SEWER
COLLECTION
TO FIELD 1
24" ACCESS
RISER
3"
BOTTOM
4904.52'
4" PVC
BAFFLE
TO FIELD 2
EXTERNAL
SPLICE BOX FOR
FLOATS ONLY
EXPLOSION PROOF
SPLICE BOX FOR
PUMPS ONLY
" WEEP
HOLE TO
ENALE
PLUMBING
TO DRAIN
26"
MIN. L. L.
SETTLING SIDE
VOLUME = 4015 GAL
DOSING OPERATIONAL
VOLUME= 2660 GAL.
PROJECT #
SHEET TITLE
PLOT DATE
DATEREV ISSUE
F17PS00661
17 OCT 2019
WW1.04
UNITED STATES
DEPARTMENT OF THE INTERIOR
US FISH & WILDLIFE
SERVICE
100% CONSTRUCTION
DOCUMENTS
DIVISION OF ENGINEERING
VALLE DE ORO
NATIONAL WILDLIFE
REFUGE
BERNALILLO COUNTY NEW MEXICO
HEADQUARTERS &
VISITOR CENTER
ARCHITECTURAL
WEDDLE GILMORE
6916 east fifth avenue scottsdale arizona 85251
480 517 5055
DESIGN ARCHITECT
PADILLA-BRYCON
134 rio rancho boulevard ne rio rancho new mexico 87124
505 916 0695
GENERAL CONTRACTOR
FORMATIVE ARCHITECTURE
209 gold avenue sw albuquerque new mexico 87102
505 510 4600
EXECUTIVE ARCHITECT
SURROUNDINGS
1611 paseo de peralta santa fe new mexico 87501
505 982 3454
LANDSCAPE ARCHITECT
BIOHABITATS INC
3600 cerrillos road #1102 santa fe new mexico 87507
505 988 7453
WETLAND / WASTE WATER
HIGH MESA CONSULTING GROUP
6010-b midway park boulevard ne albuquerque new mexico 87109
505 345 4250
CIVIL ENGINEER
RME ABQ, LLC
2715 broadbent parkway ne, suite D albuquerque new mexico 87107
505 889 3004
STRUCTURAL ENGINEER
BRIDGERS & PAXTON
4600-c montgomery boulevard ne albuquerque new mexico 87109
505 883 4111
MEP ENGINEER
IDEUM
2469 corrales road, building d corrales, new mexico 87048
505-792-1110
EXHIBIT DESIGN
IRRIGATION SERVICES, INC.
44 good drive belen new mexico 87002
505 861 1536
IRRIGATION DESIGN
Rev 1. 5-15-20 Maintenance Shop Septic Update to Invert and Models1 5-15-20
PRIMARY TREATMENT AND
DOSING TANK - VISITOR CENTER
SCALE: NONE
WW1.04
PRIMARY TREATMENT TANK AND DOSING TANK - VISITOR CENTER
sdominik Highlight sdominik Highlight sdominik Highlight sdominik Highlight sdominik Highlight sdominik Highlight sdominik Highlight Update to Invert and Models sdominik Highlight 5-15-20
NOTES:
N-1. TANK VOLUMES
OPERATING VOLUME: 2,000 GAL = @ MAXIMUM L.L.
N-2. PROVIDE WIRING BETWEEN CONTROL PANELS, PUMPS, AND
ACCESSORIES IN ACCORDANCE WITH MANUFACTURERS
RECOMMENDATIONS AND THE NEC. SEE ELECTRICAL SPECIFICATION
DIVISION 26.
N-3. INSULATE PIPES WHERE LESS THAN MINIMUM COVER. SEE SPEC 220719
N-4. ALL CONNECTIONS INTO AND OUT OF THE PRIMARY TREATMENT TANKS
INCLUDING RISERS MUST BE SEALED WATERTIGHT TO PREVENT
GROUNDWATER INFILTRATION.
N-5. CONTROL PANEL TO BE LOCATED ON 4" x 4" PRESSURE TREATED POST
OR ON NON-LIVING WALL OF BUILDING IN LOCATION APPROVED BY
ARCHITECT.
N-6. ALL UNIONS, BALL VALVES, FLOAT TREE ASSEMBLIES AND OTHER
EQUIPMENT USED DURING ROUTINE OPERATIONS SHALL BE
REMOVABLE FOR OPERATION AND MAINTENANCE AND MUST BE WITHIN
REACH OF THE RISER/VAULT OPENING. TYPICALLY 18" IS THE MAXIMUM
DISTANCE PERMITTABLE, THOUGH 12" IS PREFERABLE. EFFLUENT
FILTER HANDLE TO BE EXTENDED TO WITHIN 6" OF TOP OF RISER.
MAX. L. L.
3"
4" PVC SCH 40
INFLOW
4" FLEXIBLE
CONNECTION
INV IN
3" (TYP)
RIM
SLOPE GROUND
AWAY FROM RISER
(TYP)
TOP OF TANK
24" ACCESS RISER
24" FIBERGLASS ACCESS LID
18"
1CONCRETE TANK
75"
BOTTOM
FINISHED GRADE
PART TABLE
1. CONCRETE TANK
NMED PRE-APPROVED
2,000 GAL.: H7'-8" x L9' x W7' (OUTSIDE DIMENSIONS)
AVAILABLE FROM: ALBUQUERQUE VAULT CO.
SEE SPEC. 333600
2. 24" FIBERGLASS ACCESS LID
WITH RISER TO LID ADAPTER
HEXAGONAL BOLTS OR LOCKABLE
MODEL: FLD24GVCFI2
AVAILABLE FROM: ORENCO SYSTEMS INC.
SEE SPEC. 333600
3. 24" ACCESS RISER
BOND TO TANK ADAPTER WITH RECOMMENDED ADHESIVE.
MODEL: RR24XX
(XX = CONTRACTOR VERIFIED HEIGHT)
AVAILABLE FROM: ORENCO SYSTEMS INC.
SEE SPEC. 333600
4. EFFLUENT FILTER
MODEL: FT1260-36
AVAILABLE FROM: ORENCO SYSTEMS INC.
SEE SPEC. 333600
5. EXTERNAL SPLICE BOX
MODEL: SBEX SERIES
AVAILABLE FROM: ORENCO SYSTEMS, INC.
SEE SPEC. 333600
EFFLUENT
FILTER
4" PVC SCH 40
FITTINGS
SUPPORT EFFLUENT
FILTER PER
MANUFACTURER'S
RECOMMENDATIONS
72"
INV OUT
2"
ALARM
FLOAT
24" ACCESS RISER
24" FIBERGLASS ACCESS LID
CONDUIT TO
CONTROL
PANEL
EXTERNAL
SPLICE BOX
96"
72"
4" INLET FROM
BUILDING
3"
8"
6"
6"
92"
PROJECT #
SHEET TITLE
PLOT DATE
DATEREV ISSUE
F17PS00661
17 OCT 2019
WW1.05
UNITED STATES
DEPARTMENT OF THE INTERIOR
US FISH & WILDLIFE
SERVICE
100% CONSTRUCTION
DOCUMENTS
DIVISION OF ENGINEERING
VALLE DE ORO
NATIONAL WILDLIFE
REFUGE
BERNALILLO COUNTY NEW MEXICO
HEADQUARTERS &
VISITOR CENTER
ARCHITECTURAL
WEDDLE GILMORE
6916 east fifth avenue scottsdale arizona 85251
480 517 5055
DESIGN ARCHITECT
PADILLA-BRYCON
134 rio rancho boulevard ne rio rancho new mexico 87124
505 916 0695
GENERAL CONTRACTOR
FORMATIVE ARCHITECTURE
209 gold avenue sw albuquerque new mexico 87102
505 510 4600
EXECUTIVE ARCHITECT
SURROUNDINGS
1611 paseo de peralta santa fe new mexico 87501
505 982 3454
LANDSCAPE ARCHITECT
BIOHABITATS INC
3600 cerrillos road #1102 santa fe new mexico 87507
505 988 7453
WETLAND / WASTE WATER
HIGH MESA CONSULTING GROUP
6010-b midway park boulevard ne albuquerque new mexico 87109
505 345 4250
CIVIL ENGINEER
RME ABQ, LLC
2715 broadbent parkway ne, suite D albuquerque new mexico 87107
505 889 3004
STRUCTURAL ENGINEER
BRIDGERS & PAXTON
4600-c montgomery boulevard ne albuquerque new mexico 87109
505 883 4111
MEP ENGINEER
IDEUM
2469 corrales road, building d corrales, new mexico 87048
505-792-1110
EXHIBIT DESIGN
IRRIGATION SERVICES, INC.
44 good drive belen new mexico 87002
505 861 1536
IRRIGATION DESIGN
Rev 1. 5-15-20 Maintenance Shop Septic Update to Invert and Models1 5-15-20
PRIMARY TREATMENT TANK -
MAINTENENCE SHOP
SCALE: NONE
WW1.05
PRIMARY TREATMENT TANK - MAINTENANCE SHOP
sdominik Highlight
CONCRETE TANK
NMED PRE-APPROVED
2,000 GAL.: H7'-8" x L9' x W7' (OUTSIDE DIMENSIONS)
AVAILABLE FROM: ALBUQUERQUE VAULT CO.
SEE SPEC. 333600
sdominik Highlight
N-1. TANK VOLUMES
OPERATING VOLUME: 2,000 GAL = @ MAXIMUM L.L.
sdominik Highlight 72" sdominik Highlight 96" sdominik Highlight 92" sdominik Highlight 75" sdominik Highlight 72" sdominik Highlight 5-1 sdominik Highlight Update to Invert and Models sdominik Highlight Update to Invert and Models 1 5-15-2
3"
RIM
EXTERNAL
SPLICE BOX
A
B
C
" WEEP HOLE TO
ENABLE PLUMBING
TO DRAIN
(TYP)
SLOPE GROUND
AWAY FROM RISER
(TYP)
FLOW INDUCER TOWER AND
CAP PER MANUFACTURERS
INSTRUCTIONS
CONDUIT TO
CONTROL PANEL
PUMP DISCHARGE
ASSEMBLY
PART TABLE
1. CONCRETE TANK
NMED PRE-APPROVED
1,000 GAL.: H6'-0" x L7'-9" x W4'-6" (OUTSIDE DIMENSIONS)
AVAILABLE FROM: ALBUQUERQUE VAULT CO.
SEE SPEC. 333600
2. 24" FIBERGLASS ACCESS LID
WITH RISER TO LID ADAPTER
HEXAGONAL BOLTS OR LOCKABLE
MODEL: FLD24GVCFI2
AVAILABLE FROM: ORENCO SYSTEMS INC.
SEE SPEC. 333600
3. 24" ACCESS RISER
BOND TO TANK ADAPTER WITH RECOMMENDED ADHESIVE.
MODEL: RR24XX
(XX = CONTRACTOR VERIFIED HEIGHT)
AVAILABLE FROM: ORENCO SYSTEMS INC.
SEE SPEC. 333600
4. 30" FIBERGLASS ACCESS LID
WITH RISER TO LID ADAPTER
HEXAGONAL BOLTS OR LOCKABLE
MODEL: FLD30GVCFI2
AVAILABLE FROM: ORENCO SYSTEMS INC.
SEE SPEC. 333600
5. 30" ACCESS RISER
BOND TO TANK ADAPTER WITH RECOMMENDED ADHESIVE.
MODEL: RR30XX+SX+XD
AVAILABLE FROM: ORENCO SYSTEMS INC.
SEE SPEC. 333600
6. HIGH HEAD EFFLUENT PUMP (TYP 2)
0.5 HP, 208 V, 3.7 A, x 3 PHASE, 53.1 GPM @ 40.2 TDH MIN.
MODEL: PF50053200
AVAILABLE FROM: ORENCO SYSTEMS INC.
7. 2" PUMP DISCHARGE ASSEMBLY
MODEL: HV200CXQ WITH VG2000S
AVAILABLE FROM: ORENCO SYSTEMS, INC.
SEE SPEC. 221336
8. FLOW INDUCER
MODEL: FITD-D78-CUSTOM WITHOUT PUMP PLATES
AVAILABLE FROM: ORENCO SYSTEMS INC.
SEE SPEC. 333600
9. EXTERNAL SPLICE BOX
MODEL: SBEX SERIES
AVAILABLE FROM: ORENCO SYSTEMS INC.
SEE SPEC. 333600
10. INTERNAL EXPLOSION PROOF SPLICE BOX
WITH CONDUIT SEAL KIT
MODEL: SBX-D
AVAILABLE FROM: ORENCO SYSTEMS, INC.
SEE SPEC. 333600
NOTES:
N-1. TANK VOLUMES
OPERATING VOLUME: 1000 GAL = @ MAXIMUM L.L.
N-2. DESIGNED FOR H-20 LOADING
N-3. PROVIDE WIRING BETWEEN CONTROL PANELS, PUMPS, AND
ACCESSORIES IN ACCORDANCE WITH MANUFACTURERS
RECOMMENDATIONS AND THE NEC. SEE ELECTRICAL SPECIFICATION
DIVISION 26.
N-4. INSULATE PIPES WHERE LESS THAN MINIMUM COVER. SEE SPEC 220719
N-5. ALL CONNECTIONS INTO AND OUT OF THE PRIMARY TREATMENT TANKS
INCLUDING RISERS MUST BE SEALED WATERTIGHT TO PREVENT
GROUNDWATER INFILTRATION.
N-6. CONTROL PANEL TO BE LOCATED ON 4" X 4" PRESSURE TREATED POST
OR ON NON-LIVING WALL OF BUILDING IN LOCATION APPROVED BY
ARCHITECT.
N-7. ALL UNIONS, BALL VALVES, FLOAT TREE ASSEMBLIES AND OTHER
EQUIPMENT USED DURING ROUTINE OPERATIONS SHALL BE
REMOVABLE FOR OPERATION AND MAINTENANCE AND MUST BE WITHIN
REACH OF THE RISER/VAULT OPENING. TYPICALLY 18" IS THE MAXIMUM
DISTANCE PERMITTABLE, THOUGH 12" IS PREFERABLE. EFFLUENT
FILTER HANDLE TO BE EXTENDED TO WITHIN 6" OF TOP OF RISER.
ENSURE FLOOD ELEVATION IS SUFFICIENT BELOW AIR GAP.
N-8. LOCATE CHECK VALVES ADEQUATE DISTANCE FROM PUMP DISCHARGE
TO ELIMINATE DAMAGE OF VALVE.
24"
MIN. L.L.
4" INLET FROM
PRIMARY TANK
2" OUTLET TO
LOW PRESSURE
PIPE DRAINFIELD -
MAINTENANCE
NYLON ROPE OR
NON-CORROSIVE
CHAIN FOR PUMP
REMOVAL
LAND APPLICATION DOSING TANK FLOAT TABLE (SEE SPEC. 221336)
FLOAT FUNCTION LOCATION
A HIGH LEVEL ALARM AT INVERT IN
B OVERRIDE TIMER ENABLE / DISABLE 9" BELOW INVERT IN
C TIMER ENABLE / DISABLE 24" ABOVE TANK FLOOR
D REDUNDANT OFF/ LOW LEVEL ALARM 22" ABOVE TANK FLOOR
30"
OPERATIONAL
DOSING VOLUME
= 542 GAL.
D
2" FLEX
HOSE
FINISHED GRADE
MAX. L. L.
HIGH HEAD
EFFLUENT PUMP
(TYP 2)
48"
87"
3"
4" PVC SCH 40
INFLOW
4" FLEXIBLE
CONNECTION
INV IN
TOP OF TANK
18"
BOTTOM
(OUTSIDE)
60"
INSULATE PIPE WHERE LESS
THAN MINIMUM COVER
INTERNAL
EXPLOSION PROOF
SPLICE BOX
CONDUIT TO
CONTROL
PANEL
3"
3"
72"
PROJECT #
SHEET TITLE
PLOT DATE
DATEREV ISSUE
F17PS00661
17 OCT 2019
WW1.06
UNITED STATES
DEPARTMENT OF THE INTERIOR
US FISH & WILDLIFE
SERVICE
100% CONSTRUCTION
DOCUMENTS
DIVISION OF ENGINEERING
VALLE DE ORO
NATIONAL WILDLIFE
REFUGE
BERNALILLO COUNTY NEW MEXICO
HEADQUARTERS &
VISITOR CENTER
ARCHITECTURAL
WEDDLE GILMORE
6916 east fifth avenue scottsdale arizona 85251
480 517 5055
DESIGN ARCHITECT
PADILLA-BRYCON
134 rio rancho boulevard ne rio rancho new mexico 87124
505 916 0695
GENERAL CONTRACTOR
FORMATIVE ARCHITECTURE
209 gold avenue sw albuquerque new mexico 87102
505 510 4600
EXECUTIVE ARCHITECT
SURROUNDINGS
1611 paseo de peralta santa fe new mexico 87501
505 982 3454
LANDSCAPE ARCHITECT
BIOHABITATS INC
3600 cerrillos road #1102 santa fe new mexico 87507
505 988 7453
WETLAND / WASTE WATER
HIGH MESA CONSULTING GROUP
6010-b midway park boulevard ne albuquerque new mexico 87109
505 345 4250
CIVIL ENGINEER
RME ABQ, LLC
2715 broadbent parkway ne, suite D albuquerque new mexico 87107
505 889 3004
STRUCTURAL ENGINEER
BRIDGERS & PAXTON
4600-c montgomery boulevard ne albuquerque new mexico 87109
505 883 4111
MEP ENGINEER
IDEUM
2469 corrales road, building d corrales, new mexico 87048
505-792-1110
EXHIBIT DESIGN
IRRIGATION SERVICES, INC.
44 good drive belen new mexico 87002
505 861 1536
IRRIGATION DESIGN
Rev 1. 5-15-20 Maintenance Shop Septic Update to Invert and Models1 5-15-20
DOSING TANK -
MAINTENANCE SHOP
SCALE: NONE
WW1.06
DOSING TANK - MAINTENANCE SHOP
sdominik Highlight
CONCRETE TANK
NMED PRE-APPROVED
1,000 GAL.: H6'-0" x L7'-9" x W4'-6" (OUTSIDE DIMENSIONS)
AVAILABLE FROM: ALBUQUERQUE VAULT CO.
SEE SPEC. 333600
sdominik Highlight
HIGH HEAD EFFLUENT PUMP (TYP 2
sdominik Highlight
0.5 HP, 208 V, 3.7 A, x 3 PHASE, 53.1 GPM @ 40.2 TDH MIN
sdominik Highlight
MODEL: PF50053200
sdominik Highlight
AVAILABLE FROM: ORENCO SYSTEMS INC
sdominik Highlight
2" PUMP DISCHARGE ASSEMBL
sdominik Highlight
MODEL: HV200CXQ WITH VG2000S
sdominik Highlight
AVAILABLE FROM: ORENCO SYSTEMS, INC
sdominik Highlight
SEE SPEC. 221336
sdominik Highlight
EXTERNAL SPLICE BOX
MODEL: SBEX SERIES
AVAILABLE FROM: ORENCO SYSTEMS INC.
SEE SPEC. 333600
sdominik Highlight
NTERNAL EXPLOSION PROOF SPLICE BOX
WITH CONDUIT SEAL KIT
MODEL: SBX-D
AVAILABLE FROM: ORENCO SYSTEMS, INC.
SEE SPEC. 333600
sdominik Highlight 87" sdominik Highlight 8" sdominik Highlight
" FLEX
HOSE
sdominik Highlight
2" OUTLET TO
LOW PRESSURE
PIPE DRAINFIELD -MAINTENANCE
sdominik Highlight
9" BELOW INVERT IN
sdominik Highlight
24" ABOVE TANK FLOOR
sdominik Highlight
22" ABOVE TANK FLOOR
sdominik Highlight
N-1. TANK VOLUMES
OPERATING VOLUME: 1000 GAL = @ MAXIMUM L.L.
sdominik Highlight
N-8. LOCATE CHECK VALVES ADEQUATE DISTANCE FROM PUMP DISCHARGE
TO ELIMINATE DAMAGE OF VALVE.
sdominik Highlight 60" sdominik Highlight
HIGH HEAD
EFFLUENT PUMP
(TYP 2)
sdominik Highlight sdominik
24"
MINIMUM COVER
FINAL BACKFILL
6'-12" COVER OVER PIPE
INITIAL BACKFILL
(SEE SPEC. 312000)
HAUNCHING
EMBEDMENT
MATERIAL
4"-6" OF BEDDING SAND
DETECTABLE WARNING TAPE (SPEC. 220553)
SAND FILL TO SPRINGLINE OF PIPE
FINISHED GRADE
NOTES:
N-1. ALL PIPE SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH ASTM D2321,
"STANDARD PRACTICE FOR UNDERGROUND INSTALLATION OF THERMOPLASTIC PIPE
FOR SEWERS AND OTHER GRAVITY FLOW APPLICATIONS", LATEST ADDITION.
N-2. MEASURES SHOULD BE TAKEN TO PREVENT MIGRATION OF NATIVE FINES INTO
BACKFILL MATERIAL, WHEN REQUIRED.
N-3. WARNING TAPE: DETECTABLE TAPE TO BE PLACED A MINIMUM OF 6" TO A MAXIMUM OF
12" BELOW THE FINISHED GRADE. A CONTINUOUS LENGTH OF 3-INCH WIDE
DETECTABLE TAPE SHALL BE PLACED IN A DIRECT LINE OVER ALL PIPE AS SHOWN.
TAPE COLOR SHALL BE AS FOLLOWS:
BLUE (WATER) - USA BLUEBOOK MD - 25815
GREEN (SEWER) - USA BLUEBOOK MD - 25825
YELLOW (ELECTRICAL)
PURPLE (RECLAIMED WATER)
N-4. FOUNDATION: WHERE THE TRENCH BOTTOM IS UNSTABLE, THE CONTRACTOR SHALL
EXCAVATE TO A DEPTH REQUIRED BY THE ENGINEER AND REPLACE WITH SUITABLE
MATERIAL AS SPECIFIED BY THE ENGINEER. AS AN ALTERNATIVE AND AT THE
DISCRETION OF THE DESIGN ENGINEER, THE TRENCH BOTTOM MAY BE STABILIZED
USING A GEOTEXTILE MATERIAL.
N-5. BEDDING: SUITABLE MATERIAL SHALL BE CLASS I, II, OR III. THE CONTRACTOR SHALL
PROVIDE DOCUMENTATION FOR MATERIAL SPECIFICATION TO ENGINEER. UNLESS
OTHERWISE NOTED BY THE ENGINEER, MINIMUM BEDDING THICKNESS SHALL BE 4" (100
MM) FOR 4" - 24" (100 MM - 600 MM); 6" (150 MM) FOR 30" - 60" (750 MM - 900 MM).
N-6. INITIAL BACKFILL: SUITABLE MATERIAL SHALL BE CLASS I, II, OR III IN THE PIPE ZONE
EXTENDING NOT LESS THAN 6" ABOVE CROWN OF PIPE. THE CONTRACTOR SHALL
PROVIDE DOCUMENTATION FOR MATERIAL SPECIFICATION TO ENGINEER. MATERIAL
SHALL BE INSTALLED AS REQUIRED IN ASTM D 2321, LATEST ADDITION.
RECOMMENDED MINIMUM
TRENCH WIDTH
PIPE SIZE
MINIMUM
TRENCH WIDTH
4" OR LESS 21"
6" 23"
8" 26"
TRENCH WIDTH
(SEE TABLE)
3"
NOTES
N-1. AIR RELEASE ASSEMBLIES SHALL BE PLACED AT ALL HIGH
POINTS IN THE COLLECTION LINE; LOCATE SLIGHTLY
DOWNSTREAM OF HIGH POINTS.
PART TABLE
1. 24" FIBERGLASS ACCESS LID
WITH RISER TO LID ADAPTER
HEXAGONAL BOLTS OR LOCKABLE LID
MODEL: FLD24GCFVI2
AVAILABLE FROM: ORENCO SYSTEMS INC.
SEE SPEC. 333600
2. 24" ACCESS RISER
MODEL: RR24XX
XX = CONTRACTOR VERIFIED HT.
AVAILABLE FROM: ORENCO SYSTEMS INC.
SEE SPEC. 333600
3. AIR RELEASE ASSEMBLY AND VALVE
WITH STAINLESS STEEL REINFORCING COLLAR
ASSEMBLY MODEL: ARA
VALVE MODEL: ARV21
AVAILABLE FROM: ORENCO SYSTEMS INC.
SEE SPEC. 220523.02
SLOPE GROUND
AWAY FROM RISER
18" VALVE EXTENSION HANDLE
6" DEPTH OF DRAINROCK BASE
1" HDPE TO PVC TRANSITION FITTING
(FOR HDPE SEWER MAINS)
1" HDPE SDR 17 (PRESSURE USE)
LINE SIZE SEWER MAIN
OPTIONAL SELF-TAPPING HDPE
SADDLE TO ATTACH LATERAL
TO AN EXISTING SEWER MAIN
2" BALL VALVE
MANUAL AIR RELEASE BALL VALVE
2'-6"
NPT PRESSURE GAUGE PORT
1" x 2" REDUCER
NOTES
N-1. CLEANOUTS TO MEET STATE AND
COUNTY STANDARDS.
N-2. PLACE CLEANOUTS OUTSIDE OF
BUILDING AS SHOWN ON PLANS.
N-3. 8" DIAMETER CAST IRON METER FRAME
AND COVER (TYPE C) WITH COVER
STAMPED "SEWER". AVAILABLE FROM:
BINGHAM & TAYLOR (TYP 2).
N-4. FOR LOAD BEARING LOCATIONS, CAST
FRAME INTO 6" DEEP x 50" SQUARE
CONCRETE PAD. FOR NON-LOAD
BEARING LOCATIONS, COMPACT DIRT
AROUND FRAME TO 85% MAXIMUM
DENSITY.
N-5. 6" DEPTH OF
" PEA GRAVEL.
COMPACT PER LOCAL REQUIREMENTS.
N-6. MINIMUM COVER
N-7. REACH DEPTH, 18" MAXIMUM
N-8. 18" DIAMETER METER BOX OR PVC SCH
40 PIPE (TYP 2)
N-6
N-7
P-1
N-4
P-2
N-3
N-8
P-3
P-6
P-5
P-4
N-5
PIPING NOTES
P-1. LINE SIZE PVC SCH 40 MPT END CAP. HAND
TIGHTEN ONLY (TYP 2).
P-2. LINE SIZE PVC SCH 40 FPT BALL VALVE (TYP 2)
P-3. LINE SIZE HDPE TO STAINLESS STEEL MPT
TRANSITION FITTING (TYP 2)
P-4. LINE SIZE HDPE PIPE (TYP 2)
P-5. LINE SIZE x LINE SIZE x LINE SIZE HDPE LONG
SWEEP SANITARY TEE (TYP 2)
P-6. LINE SIZE SEWER PIPE
NOTES
N-1. CLEANOUTS TO MEET STATE AND COUNTY
STANDARDS.
N-2. PLACE CLEANOUTS EVERY 300 FEET.
N-3. 8" DIAMETER CAST IRON METER FRAME AND COVER
(TYPE C) WITH COVER STAMPED "SEWER". AVAILABLE
FROM: BINGHAM & TAYLOR.
N-4. FOR LOAD BEARING LOCATIONS, CAST FRAME INTO 6"
DEEP x 30" SQUARE CONCRETE PAD. FOR NON-LOAD
BEARING LOCATIONS, COMPACT DIRT AROUND FRAME
TO 85% MAXIMUM DENSITY.
N-5. 6" DEPTH OF
" PEA GRAVEL. COMPACT PER LOCAL
REQUIREMENTS.
N-6. MINIMUM COVER
N-7. REACH DEPTH, 18" MAXIMUM
N-8. 18" DIAMETER METER BOX OR PVC SCH 40 PIPE
PIPING NOTES
P-1. LINE SIZE PVC SCH 40 MPT END CAP. HAND TIGHTEN
ONLY.
P-2. LINE SIZE PVC SCH 40 FPT BALL VALVE.
P-3. LINE SIZE HDPE TO STAINLESS STEEL MPT TRANSITION
FITTING
P-4. LINE SIZE HDPE PIPE
P-5. LINE SIZE HDPE LONG SWEEP 90° ELL
P-6. LINE SIZE SEWER PIPE
P-7. LINE SIZE CONTINUATION OF SEWER WITH SANITARY
TEE (IF NECESSARY)
N-6
N-7
N-4
P-2
P-3
N-8
N-5
P-5
P-6
P-7
P-4
P-1
N-3
PIPING NOTES
P-1. LINE SIZE PVC SCH 40 FPT END CAP.
HAND TIGHTEN ONLY (TYP 2).
P-2. LINE SIZE HDPE TO STAINLESS
STEEL MPT TRANSITION FITTING
(TYP 2)
P-3. LINE SIZE HDPE PIPE (TYP 2)
P-4. LINE SIZE x LINE SIZE x LINE SIZE
HDPE LONG SWEEP SANITARY TEE
(TYP 2)
P-5. LINE SIZE SEWER PIPE
P-3
P-5
P-4
N-5
N-3
N-4
P-2
N-6
N-8
N-7
NOTES
N-1. CLEANOUTS TO MEET STATE AND COUNTY STANDARDS.
N-2. PLACE CLEANOUTS OUTSIDE OF BUILDING AS SHOWN ON PLANS.
N-3. 8" DIAMETER CAST IRON METER FRAME AND COVER (TYPE C) WITH COVER STAMPED "SEWER". AVAILABLE
FROM: BINGHAM & TAYLOR (TYP 2).
N-4. FOR LOAD BEARING LOCATIONS, CAST FRAME INTO 6" DEEP x 50" SQUARE CONCRETE PAD. FOR NON-LOAD
BEARING LOCATIONS, COMPACT DIRT AROUND FRAME TO 85% MAXIMUM DENSITY.
N-5. 6" DEPTH OF
" PEA GRAVEL. COMPACT PER LOCAL REQUIREMENTS.
N-6. MINIMUM COVER
N-7. REACH DEPTH, 12" MAXIMUM
N-8. 18" DIAMETER METER BOX OR PVC SCH 40 PIPE (TYP 2)
P-1
UNISTRUT
METAL FRAME
UNISTRUT
METAL FRAME
METAL ROOFING (FABRAL OR EQUAL),
30# FELT, DECK AND 3/4" PLYWOOD
NEMA 4x PUMP
CONTROL, MOUNT
AT EYE LEVEL
(SEE SPEC. 409000)
NOTES:
N-1. PUMP CONTROL SHALL BE LOCATED WITHIN SIGHT
OF THE TANK.
N-2. CONTRACTOR SHALL REVIEW LAYOUT OF PANELS
WITH OWNER / ARCHITECT.
N-3. HEIGHT AND WIDTH OF FRAME TO BE DETERMINED
BY CONTRACTOR.
N-4. GROUNDING PER NEC.
FRONT VIEW SIDE VIEW
3,000 PSI CONCRETE
12" DIA. x 24" DEEP
(TYP 2)
TO PUMP
FROM POWER
SUPPLY
TO HLA
AT MAINTENANCE SHOP
SEPTIC TANK
PROJECT #
SHEET TITLE
PLOT DATE
DATEREV ISSUE
F17PS00661
17 OCT 2019
WW1.07
UNITED STATES
DEPARTMENT OF THE INTERIOR
US FISH & WILDLIFE
SERVICE
100% CONSTRUCTION
DOCUMENTS
DIVISION OF ENGINEERING
VALLE DE ORO
NATIONAL WILDLIFE
REFUGE
BERNALILLO COUNTY NEW MEXICO
HEADQUARTERS &
VISITOR CENTER
ARCHITECTURAL
WEDDLE GILMORE
6916 east fifth avenue scottsdale arizona 85251
480 517 5055
DESIGN ARCHITECT
PADILLA-BRYCON
134 rio rancho boulevard ne rio rancho new mexico 87124
505 916 0695
GENERAL CONTRACTOR
FORMATIVE ARCHITECTURE
209 gold avenue sw albuquerque new mexico 87102
505 510 4600
EXECUTIVE ARCHITECT
SURROUNDINGS
1611 paseo de peralta santa fe new mexico 87501
505 982 3454
LANDSCAPE ARCHITECT
BIOHABITATS INC
3600 cerrillos road #1102 santa fe new mexico 87507
505 988 7453
WETLAND / WASTE WATER
HIGH MESA CONSULTING GROUP
6010-b midway park boulevard ne albuquerque new mexico 87109
505 345 4250
CIVIL ENGINEER
RME ABQ, LLC
2715 broadbent parkway ne, suite D albuquerque new mexico 87107
505 889 3004
STRUCTURAL ENGINEER
BRIDGERS & PAXTON
4600-c montgomery boulevard ne albuquerque new mexico 87109
505 883 4111
MEP ENGINEER
IDEUM
2469 corrales road, building d corrales, new mexico 87048
505-792-1110
EXHIBIT DESIGN
IRRIGATION SERVICES, INC.
44 good drive belen new mexico 87002
505 861 1536
IRRIGATION DESIGN
Rev 1. 5-15-20 Maintenance Shop Septic Update to Invert and Models1 5-15-20
COLLECTION…