ATTACHMENT 13
Scope of Existing DAS Installation
Current DAS As Built This section describes the as built condition of the facility and the DAS system. The purpose is to convey how the existing facility is constructed, how various aspects of its construction may impact DAS performance beyond what is considered ‘normal’ building construction and how the existing DAS is assembled and connected.
Building Construction Specifics The campus is comprised of 11 buildings and 2 parking garages. The following table documents the typical construction of each building. The facility is heavily built and fortified against blast, hurricane, and progressive collapse. The construction of the facility should not be considered typical as compared to standard office building construction. This information is being provided in lieu of providing a large set of complex construction documents and drawings.
Partition Schedule For all buildings assume all wallboard is comprised of paperless/Fiberglass covered, mold resistant, high impact 5/8” gypsum.
All interior walls framed with typical metal studs.
Confirmation All existing conditions shown or mentioned in Attachments A, B, C and D shall be verified by the contractor prior to start of work. Changes may have been made that are not noted in this information section (s).
| Partition Type |
| Construction |
| Typical Wall (No Rating) |
| 1 Layer 5/8" Paperless (Fiberglass) High Impact Gypsum on both sides |
| 1 Hour Fire/Smoke Rated |
| 1 Layer 5/8" Paperless (Fiberglass) High Impact Gypsum on both sides |
| 2 Hour Fire/Smoke Rated |
| 2 Layers 5/8" Paperless (Fiberglass) High Impact Gypsum on both sides |
| 3 Hour Fire Rated |
| 6” Concrete Masonry Unit (CMU) Filled |
| 4 Hour Fire Rated |
| 8” Concrete Masonry Unit (CMU) Filled |
| Stairwells |
| 2 Layers 5/8" Paperless (Fiberglass) High Impact Gypsum on one side and 1 Shaft liner Panel on the other |
| Elevator Shafts |
| 2 Layers 5/8" Paperless (Fiberglass) High Impact Gypsum on one side and 1 Shaft liner Panel on the other |
| Exterior Skin |
| Precast Concrete, Metal Panel, Glass |
| MRI Space |
| M6 Silicon Steel and 3oz Copper |
| Typical Floor |
| 4” Concrete, 18GA Corrugated Steel Decking with flooring material |
| Roofs |
| 4” Concrete, 18GA Corrugated Steel Decking |
4” Lightweight Concrete, 3 Layer Bituminous Torch Down Roofing
| Security Office Space / Command Centers |
| 1 Layer 5/8" Paperless (Fiberglass) High Impact Gypsum on both sides with 9 gauge expanded steel beneath wallboard |
Special Partition Shielding
| Name |
| Room (New) |
| Type |
| North wall |
| East Wall |
| South Wall |
| West Wall |
| Floor |
| Ceiling |
| Radiology |
| 2D235 |
| Lead |
| 1/16' |
| 1/32" |
| 1/16' |
| 1/32" |
| None |
| None |
| Radiology |
| 2E129 |
| Lead |
| 1/32" |
| 1/16" |
| 1/32" |
| 1/32" |
| None |
| None |
| Radiology |
| 2E125 |
| Lead |
| 1/32" |
| 1/16' |
| 1/32" |
| 1/32" |
| None |
| None |
| Radiology |
| 2F112 |
| Lead |
| 1/32" |
| 1/16" |
| 1/32" |
| 1/16" |
| None |
| None |
| Radiology |
| 2F116 |
| Lead |
| 1/32" |
| 1/32" |
| 1/32" |
| 1/16" |
| None |
| None |
| Radiology |
| 2F120 |
| Lead |
| 1/32" |
| 1/32" |
| 1/16" |
| 1/16" |
| None |
| None |
| Radiology |
| 2F124 |
| Lead |
| 1/32" |
| 1/32" |
| 1/16" |
| 1/16" |
| None |
| None |
| Radiology |
| 2F121 |
| Lead |
| 1/32" |
| 1/16" |
| 1/32" |
| 1/32" |
| None |
| None |
| Radiology |
| 2F117 |
| Lead |
| 1/32" |
| 1/16" |
| 1/32" |
| 1/32" |
| None |
| None |
| Radiology |
| 2F144 |
| Lead |
| 1/32" |
| 1/32" |
| 1/32" |
| 1/16" |
| None |
| None |
| Radiology |
| 2F148 |
| Lead |
| 1/32" |
| 1/32" |
| 1/32" |
| 1/32" |
| None |
| None |
| CT Scan |
| 2E126 |
| Lead |
| 1/16" |
| 1/16" |
| 1/16" |
| 1/16" |
| None |
| None |
| CT Scan |
| 2E136 |
| Lead |
| 1/16" |
| 1/16" |
| 1/16" |
| 1/16" |
| None |
| None |
| CT Scan |
| 2E133 |
| Lead |
| 1/16" |
| 1/16" |
| 1/16" |
| 1/16" |
| None |
| None |
| NUC MED |
| 2G216 |
| Lead |
| 1/32" |
| 3/32" |
| 3/32" |
| 1/16" |
| None |
| None |
| PET-CT |
| 2G310 |
| Lead |
| 7/32" |
| 1/16" |
| 1/32" |
| 1/16" |
| None |
| None |
| Cardiac Cath |
| 3F202 |
| Lead |
| 1/32" |
| 1/32" |
| 1/32" |
| 1/32" |
| None |
| None |
| Cardiac Cath |
| 3F204 |
| Lead |
| 1/32" |
| 1/32" |
| 1/32" |
| 1/32" |
| None |
| None |
| Cardiac Cath |
| 3F206 |
| Lead |
| 1/32" |
| 1/32" |
| 1/32" |
| 1/32" |
| None |
| None |
| Interventional Radiology Procedure |
| 3F201 |
| Lead |
| 1/32" |
| 1/32" |
| 1/32" |
| 1/32" |
| None |
| None |
| Interventional Radiology Procedure |
| 3F203 |
| Lead |
| 1/32" |
| 1/32" |
| 1/32" |
| 1/32" |
| None |
| None |
| Procedure EP Room |
| 3F205 |
| Lead |
| 1/32" |
| 1/32" |
| 1/32" |
| 1/32" |
| None |
| None |
| Procedure Bronch |
| 3G232 |
| Lead |
| 1/32" |
| 1/32" |
| 1/16" |
| 1/32" |
| None |
| None |
| ERCP |
| 3G229 |
| Lead |
| 1/32" |
| 1/32" |
| 1/32" |
| 1/32" |
| None |
| None |
| Procedure (PB) |
| 3J268 |
| Lead |
| 1/32" |
| 1/32" |
| 1/32" |
| 1/32" |
| None |
| None |
| Procedure (PB) |
| 3J267 |
| Lead |
| 1/32" |
| 1/32" |
| 1/32" |
| 1/32" |
| None |
| None |
| Procedure (PB) |
| 3J278 |
| Lead |
| 1/32" |
| 1/32" |
| 1/32" |
| 1/32" |
| None |
| None |
| Pain |
| 3E100A |
| Lead |
| 1/32" |
| 1/32" |
| 1/32" |
| 1/32" |
| None |
| None |
| Pain |
| 3E100B |
| Lead |
| 1/32" |
| 1/32" |
| 1/32" |
| 1/32" |
| None |
| None |
| Pain |
| 3E100C |
| Lead |
| 1/32" |
| 1/32" |
| 1/32" |
| 1/32" |
| None |
| None |
| Dose Admin |
| 2G219 |
| Lead |
| 7/32" |
| 7/32" |
| 7/32" |
| 7/32" |
| None |
| None |
| Animal X-Ray |
| 4P176 |
| Lead |
| none |
| 1/32" |
| 1/32" |
| 1/32" |
| None |
| None |
2G134
| Layers of M6 Silicon Steel / Layers of 3oz Copper |
| 12/1 |
| 12/1 |
| 12/1 |
| 12/1 |
| 6/1 |
| 6/1 |
7J409 7J406 7J497
| Layers of M-36 Silicon Steel |
| 5 |
| 5 |
| 5 |
| 5 |
| 4 |
| 10 |
2P185A
| Layers of M-36 Silicon Steel |
| 6 |
| 6 |
| 6 |
| 6 |
| 5 |
| 10 |
Existing DAS Equipment The following tables list the equipment used in the current installation.
| Power Dividers - PIM Certified |
| CSI |
| ClearLink-SPD2/698-2.7K-LP/N |
| Directional Coupler |
| CSI |
| ClearLink-DC6/698-2.7K/N |
| Directional Coupler |
| Pulsar |
| C1-10-414 |
| Connector |
| Times Microwave |
| Straight Plug EZ-600-NMH-D |
| Connector |
| Times Microwave |
| Straight Plug EZ-600-NMH-PL-D |
| Connector |
| Trilogy |
| AirCell® 1/2" Type N Male Connector |
| Antenna Cable |
| Trilogy |
| AirCell APC012J50 |
| Antenna Cable |
| Trilogy |
| AirCell AT012FX50 |
| Antenna Cable |
| Commscope |
| HELIAX AL4RPV-50 |
| Antenna Cable |
| Commscope |
| HELIAX LDF2-50 |
| Jumper Cable |
| Times Microwave |
| LMR-600-LLPL |
| Cellular/PS Antenna |
| CSS |
| TRU-Omni S727 |
| VHF Antenna |
| PulseLARSEN |
| PSIBVU78 |
| LWIN Yagi Antenna |
| CSI |
| CSI-AY/806-960/14 |
| Termination |
| CSI |
| CSI-TRM6N-2W |
| Digital Signal Booster - Public Safety (LWIN) |
| fiplex |
| DH730-2-004 |
| Duplexer |
| fiplex |
| ddbp7566chhs2 |
| Splitter |
| Microlab |
| D2-41FN |
| 2Way Divider + Diplexer |
| SOLiD |
| ZLD-SMDR/2Way |
| Remote AC Power Supply (RPSU) |
| SOLiD |
| ROU_C_AC |
| Remote Optical Unit (ROU) |
| SOLiD |
| Optic Distribution Unit (ODU) |
| SOLiD |
| Optic Expansion Unit (OEU) |
| SOLiD |
| BTS Interface Unit (BIU) |
| SOLiD |
| Main Drive BTS Unit (MDBU) |
| SOLiD |
| Main Com/Div Unit (MCDU) |
| SOLiD |
| Main Central Processor Unit (MCPU) |
| SOLiD |
| Main Power Supply Unit (MPSU) |
| SOLiD |
| 800MHz & 900MHz Amplifier Module |
| SOLiD |
| RDU_800PS_900I_PA |
| 850MHz & 700Mhz Public Safety Amplifier Module |
| SOLiD |
| RDU_850C_700PS(D) |
| 1900Mhz & 2100/1700Mhz AWS Amplifier Module |
| SOLiD |
| RDU_1900P_AWS13 |
| Remote Optic Module |
| SOLiD |
| R-OPTIC REL6.0 |
| Remote Central Processor Unit |
| SOLiD |
| RCPU |
| 150MHz VHF & 450MHz UHF Amplifier Module |
| SOLiD |
| RDU_150_450 |
| 700MHz LTE Full Band SISO Amplifier Module |
| SOLiD |
| RDU_700LTE_S |
| AC Power Supply |
| SOLiD |
| Add on ROU_AC |
| Combiner Unit |
| SOLiD |
| Multiplexer |
| 1W Low Power Remote Optic Unit (LROU) |
| SOLiD |
| Alliance |
| DMS Management System |
| SOLiD |
| DMS-1200 |
DAS Cabinet Configurations The remote units are comprised of 3 different configurations.
| Cabinet Type |
| Equipment |
| Description |
| A |
| ROU Cabinet |
| Wall Mounted Cabinet |
| RCPU |
| Remote Central Processor Unit |
| R-OPTIC REL6.0 |
| Remote Optic Module |
| RDU_800PS_900I_PA |
| 800MHz & 900MHz Amplifier Module |
| RDU_850C_700PS(D) |
| 850MHz & 700Mhz Public Safety Amplifier Module |
| RDU_1900P_AWS13 |
| 1900Mhz & 2100/1700Mhz AWS Amplifier Module |
| B |
| ROU Cabinet |
| Wall Mounted Cabinet |
| RCPU |
| Remote Central Processor Unit |
| R-OPTIC REL6.0 |
| Remote Optic Module |
| RDU_150_450 |
| 150MHz VHF & 450MHz UHF Amplifier Module |
| RDU_700LTE_S |
| 700MHz LTE Full Band SISO Amplifier Module |
| C |
| AOU Cabinet |
| Wall Mounted Cabinet |
| ROU_C_AC |
| Add On ROU AC Power Supply |
| RDU_700LTE_S |
| 700MHz LTE Full Band SISO Amplifier Module |
DAS Cabinet Locations The following table shows the room the remote units are housed, their configuration and which sector they belong.
| Room |
| Sector |
| Building |
| Area |
| Floor |
| Cabinet Type(s) |
7J301
| 3 |
| J |
| 7 |
| Head End / Radio Room / Carrier Equipment |
2Q133
4Q136
1B114B
2B110B
3B110B
4B114B
1D110
2D106
3D104
4D104
5D112
| 1F106 |
| 2 |
| 2 |
| F |
| 1 |
| A, B + A, B |
2F105A
3F111
4F103
1J334
2J334
3J334
6J334
7J334
2H102B
2M109
3M111
1N117
2N121
2N132
4N109
1P123
4P104
| Building Name |
| In Scope |
| Building Number / Areas |
| Construction Type |
| Interstitial Space |
| Floors |
| Typical Antenna Height |
| Floor to Floor Height |
B, C Steel Frame 4” Concrete Floor 18ga Deck Glass Exterior
| Diagnostic and Treatment (D&T) |
| Yes |
| 2 |
D, E, F, G Steel Frame 4” Concrete Floor 18ga Deck Precast Concrete Skin
| Yes |
| 5 |
| 9’ |
| Floor to Interstitial: |
19’ Interstitial to Floor: 7’4”
H, J1, J2 Steel Frame 4” Concrete Floor 18ga Deck Glass Exterior
| No |
| 8 |
| 9’6” |
| Level 1-4 – 19’ |
Level 4-7 – 16’ Level 7-8 – 19’
| Patient Parking |
| Elevator Lobbies Only |
| 4 |
K Pre-Cast Concrete Lobby: Steel Frame 4” Concrete Floor 18ga Deck
| Staff Parking |
| Elevator Lobbies Only |
| 5 |
L Pre-Cast Concrete Lobby: Steel Frame 4” Concrete Floor 18ga Deck
| Transitional Living (TLR) |
| Yes |
| 6 |
M Steel Frame 4” Concrete Floor 18ga Deck Glass Exterior
| Central Energy Plant (CEP) |
| Yes |
| 7 |
N1, N2 Cast in Place Concrete Precast & Metal Panel Exterior
Level 2-3 – 17’4” Level 3-4 – 17’ Level 4-5 – 20’4”
P New Research: Cast in Place Concrete Metal Panel Exterior Old Dixie: Brick
Level 2-3 – 17’ Level 3-4 – 16’ Level 4-5 – 18’
Q Steel Frame Concrete Floor Glass/Concrete Exterior
Level 1-2 – 13’6” Level 2-3 – 14’ Level 3-4 – 14’ Level 4-5 – 14’ Level 5-PH – 14’
| Shotgun Houses |
| No |
| 10 |
| Wood Frame |
| No |
| 2 |
12’
| Concourse |
| Yes |
| 00 |
| Steel Frame |
4” Concrete Floor w 18ga Deck Glass Exterior
Yes
Level 1-2 – 19’ Level 2-3 – 19’ Level 3-4 – 19’ Level 4-4i – 10’4”’ Level 4i-5 – 7’4”’ Level 5-5i – 10’4”
Typical Equipment Installation Photos Head End Units (Sectors )
Public Safety (LWIN) BDA AT&T Installation
Radio / Pager / DAS Service Bay 7th Floor Building 3 (Outpatient) Room 7J301
Typical Cellular/PS Antenna Installation
Typical VHF Antenna Installation
Typical Wall Mounted Remote Units
As Built One Line Diagram Head End
Non-Cellular Frequency List The following frequencies are currently being broadcast by the DAS in addition to cellular services.
| Transmit |
| Receive |
| Alpha Tag |
| Description |
| Service Tag |
| VA Serial Number |
| 173.175000 |
| 164.962500 |
| VA Hosp PD |
| Hospital Police |
| Federal |
| 130089 |
| 168.487500 |
| 163.250000 |
| VA Hosp Ops |
| Hospital Operations |
Patient Guide
| 172.300000 |
| 166.212500 |
| VA Hosp Engineering |
| Hospital Engineering |
| Federal |
| 161616 |
| 168.237500 |
| 166.762500 |
| VA Hosp Emergency Management |
| Hospital Emergency Management |
| Federal |
| 030440 |
168.525000
| Paging |
| Code Blue Paging |
| Federal |
| 030439 |
Public Safety
(NOPD/NOFD)
Louisiana Wireless Information Network (LWIN)
Trunked Frequencies
TX
| RX |
| Pan American Life - Iberia Bank - N.O. |
| Louisiana Wireless Information Network (LWIN) |
| State Police/NOPD/NOFD/EMS |