Att 02_Specifications (230502).doc

DOC document 32 KB Posted

Attached to
MTF -- ACW Chemical Storage Building Federal contract opportunity
Solicitation number
12445523Q0109
Issued by
Department of Agriculture Forest Service

About this file

This document outlines specifications for a chemical storage building to be installed on federal land. The building must be a minimum of 176 square feet with 8'4" ceilings and constructed of metal siding and roofing. Interior walls must be 20 gauge galvanized steel with a 3 inch air space and R11 insulation. The building requires a double door on the short end that is primed, painted, and has an accessible lockset. An electrical package with a 100 amp panel, explosion proof switch and three lights is also specified. The building will have four adjustable vents and the government will provide a stone or concrete pad. The successful contractor must visit the site and install the building by the location marked by the government. Minimum design loads and a 15 year warranty are also required. The related federal contract opportunity is issued by the USDA Forest Service for one chemical storage building to be installed at the Ava/Cassville/Willow Springs Ranger District in Douglas County, Missouri.

View the file

Other files for this federal contract opportunity

Other files attached to MTF -- ACW Chemical Storage Building, newest first.
File Type Posted
Amendment 01 12445523Q0109 (230628).pdf PDF
Att 01_Schedule of Items (230615).docx DOCX document
Sol 12445523Q0109 (230623).pdf PDF
Att 03_Wage Rates (230616).pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SPECIFICATION

Statement of Work Chemical Storage Buildings

Ava/Cassville/Willow Springs Ranger District

Douglas County

Missouri

A. SCOPE OF WORK: Contractor shall provide all equipment, labor and materials necessary to furnish and install in place one (1) Chemical Storage Buildings including (3) Explosion proof light fixtures (3) Tier wall shelving and with (4) adjustable building ventilations.

B. Building shall be constructed of metal and meet the following specifications:

1. The dimensions of the building shall be a minimum of 176 square feet (22’ x 8’), with a minimum 8’ 4”ceiling.

2. Metal:

i. Exterior Wall: 12-16 gauge Galvanized Steel.

ii. Interior wall: 20 gauge Galvanized Steel.

iii. Minimum of a 3 inch air space.

iv. Minimum of 3 layers ¾” Gypsum Fire rated panels.

v. Insulation minimum of R11.

vi. Roof shall be noncombustible, permanently attached to the building, constructed of steel, and sloped to facilitate runoff.

3. Building shall have a double door (60”W x 80”H) with 36” active leaf located on the SHORT END of building, primed and painted. Doors shall open to the outside and have locking accessible locksets.

4. Buildings shall have a basic electrical package consisting of 12 space 100 amp main breaker NEMA 3R panel with an explosion-proof switch and three explosion-proof lights.

5. Building shall be ventilated with (4) adjustable 18”W x 18”H vents with insulated covers.

6. Government will provide a pad of compacted crushed stone or concrete pad as a base for the buildings.

7. The Government shall mark the location of the building on the ground prior to contractors delivery of the building.

8. Building shall have a minimum 4 hour fire rating.

9. Minimum design loads shall be

i. Wall Wind Load: 70 mph

ii. Roof Live Load: 40 psf

iii. Floor Live Load 250 psf

10. Provide a minimum manufacturer’s warranty of 15 years.

11. Government will require a contractor site visit prior to installation.

Building needs to have door on the short end, not wide end of building.

File details come from the government source that posted it. Updated .