Requirements_tables_for_heating_cooling_products.docx

DOCX document 25 KB Posted

Attached to
Mogollon Rim Modular Crew Quarters Federal contract opportunity
Solicitation number
AG-94TZ-S-17-0009
Issued by
Department of Agriculture Forest Service R3-Southwestern Region

About this file

Requirements table

View the file

Other files for this federal contract opportunity

Other files attached to Mogollon Rim Modular Crew Quarters, newest first.
File Type Posted
MRRDModulars_FY17_qtrs_specsrev.pdf PDF
SF30.pdf PDF
MRRDMODULARS_17_ALL.pdf PDF
SF1442.pdf PDF
Solicitation1.docx DOCX document
Wage_determination.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MINIMUM EFFICIENCY REQUIREMENTS TABLES FOR HEATING AND COOLING PRODUCT CATEGORIES The Federal Energy Management Program (FEMP) created tables that mirror American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) 90.1-2013 tables, which include minimum efficiency requirements for FEMP-designated and ENERGY STAR-qualified heating and cooling product categories.

Air-Source Heat Pumps (Residential), Central Air Conditioners (Residential), Geothermal Heat Pumps (Residential), and Light Commercial Heating and Cooling Equipment Electrically Operated Unitary Heat Pumps: Minimum Efficiency Requirements

Equipment Type
Size Category
Heating Section Type
Subcategory or Rating Condition
Minimum Efficiency
Air-cooled (cooling mode)
<65,000 Btu/h
All
Split system
14 SEER; 11 EER; 8.2 HSPF (three phase)

14.5 SEER; 12 EER; 8.2 HSPF (single phase)

Single package
14 SEER; 11 EER; 8.0 HSPF (three phase)

14 SEER; 11 EER; 8.0 HSPF (single phase)

≥65,000 Btu/h and <135,000 Btu/h
Electric resistance (or none)
Split system and single package
11.3 EER; 11.4 IEER; 3.35 COP
≥135,000 Btu/h and <240,000 Btu/h
Electric resistance (or none)
Split system and single package
10.9 EER; 11 IEER; 3.25 COP
≥240,000 Btu/ha
Electric resistance (or none)
Split system and single package
9.5 EER; 10.6 IEER

Geothermal, closed loop water-to-air

17.1 EER; 3.6 COP (single phase)

Geothermal, open loop water-to-air

21.1 EER; 4.1 COP (single phase)

Geothermal, closed loop water-to-water

16.1; 3.1 COP (single phase)

Geothermal, open loop water-to-water

20.1; 3.5 COP (single phase)

Geothermal, DGX

16.0 EER; 3.6 COP (single phase)

a Heat pumps with size equal to or greater than 240,000 Btu/h are not covered by federal purchasing requirements. Minimum efficiency presented is consistent with ASRHAE 90.1-2013.

Central Air Conditioners and Light Commercial Heating and Cooling Equipment Electrically Operated Unitary Air Conditioners: Minimum Efficiency Requirements

Equipment Type
Size Category
Heating Section Type
Subcategory or Rating Condition
Minimum Efficiency
Air conditioners, air-cooled
<65,000 Btu/h
All
Split system
14.5 SEER and 12 EER (single phase)

14 SEER and 12 EER (three phase)

Single package
14 SEER and 11 EER (single phase)

14 SEER and 11 EER (three phase)

≥65,000 Btu/h and <135,000 Btu/h
Electric resistance (or none)
Split system and single package
11.7 EER and 11.8 IEER
All other
Split system and single package
11.5 EER and 11.6 IEER
≥135,000 Btu/h and <240,000 Btu/h
Electric resistance (or none)
Split system and single package
11.7 EER and 11.8 IEER
All other
Split system and single package
11.5 and 11.6 IEER
≥240,000 Btu/h and <760,000 Btu/ha
Electric resistance (or none)
Split system and single package
12.4 EER and 13.6 IEER
All other
Split system and single package
12.2 EER and 13.4 IEER
≥760,000 Btu/ha
Electric resistance (or none)
Split system and single package
12.2 EER and 13.5 IEER
All other
Split system and single package
12.0 EER and 13.3 IEER

a Air conditioners with size equal to or greater than 240,000 Btu/h are not covered by federal purchasing requirements. Minimum efficiency presented is consistent with ASRHAE 90.1-2013.

Boilers (Residential) and Boilers (Commercial) Gas- and Oil-Fired Boilers: Minimum Efficiency Requirements

Equipment Type
Subcategory or Rating Condition
Size Category (Input)
Efficiency Metric
Minimum Efficiency
Boilers, hot water
Gas-fired
<300,000 Btu/h
AFUE
90%
≥300,000 Btu/h and ≤2,500,000 Btu/h
Eta
94%
>2,500,000 Btu/h and ≤10,000,000 Btu/h
Et
94%
>10,000,000 Btu/hb
Ec
82%
Oil-fired
<300,000 Btu/h
AFUE
87%
≥300,000 Btu/h and <2,500,000 Btu/h
Et
85.5%
>2,500,000 Btu/h and ≤10,000,000 Btu/h
Et
85.5%
>10,000,000 Btu/hb
Ec
84%
Boilers, steam
Gas-fired
<300,000 Btu/h
AFUE
90%
Gas-fired (all, except natural draft)
≥300,000 Btu/h and ≤2,500,000 Btu/h
Et
80%
>2,500,000 Btu/h and ≤10,000,000 Btu/h
Et
80%
>10,000,000 Btu/hb
Et
79%
Gas-fired, natural draft
≥300,000 Btu/h and ≤2,500,000 Btu/h
Et
80%
>2,500,000 Btu/h and ≤10,000,000 Btu/h
Et
80%
>10,000,000 Btu/hb
Et
77%
Oil-fired
<300,000 Btu/h
AFUE
87%
≥300,000 Btu/h and ≤2,500,000 Btu/h
Et
83.5%
>2,500,000 Btu/h and ≤10,000,000 Btu/h
Et
83.5%
>10,000,000 Btu/hb
Et
81%

a Thermal efficieny (Et) is based on Hydronics Institute, Method to Determine Efficiency of Commercial Space Heating Boilers (HI BTS-2000, Rev. 06.07).

b Boilers with input greater than 10,000,000 Btu/h are not covered by federal purchasing requirements. Minimum efficiency presented is consistent with ASRHAE 90.1-2013 Table 6.8.1-6.

Electric Chillers, Air-Cooled and Water-Cooled Water-Chilling Packages: Minimum Efficiency Requirements

Equipment Type
Size Category
Units
Minimum Efficiency
Path A (Full-Load Optimized Applications)
Path B (Part-Load Optimized Applications)
Air-cooled
<150 t
EER (Btu/W)
≥10.40 FL
≥9.56 FL
≥12.50 IPLV
≥15.39 IPLV
Air-cooled
≥150 t
EER (Btu/W)
≥10.40 FL
≥9.56 FL
≥12.75 IPLV
≥15.07 IPLV
Water-cooled, electrically operated positive displacement
< 75 t
kW/t
≤0.75 FL
≤0.80 FL
≤0.63 IPLV
≤0.60 IPLV
Water-cooled, electrically operated positive displacement
≥75 t and <150 t
kW/t
≤0.71 FL
≤0.79 FL
≤0.61 IPLV
≤0.51 IPLV
Water-cooled, electrically operated positive displacement
≥150 t and <300 t
kW/t
≤0.68 FL
≤0.72 FL
≤0.58 IPLV
≤0.50 IPLV
Water-cooled, electrically operated positive displacement
≥ 300 t and <600 t
kW/t
≤0.58 FL
≤0.64 FL
≤0.54 IPLV
≤0.48 IPLV
Water-cooled, electrically operated positive displacement
≥600 t
kW/t
≤0.58 FL
≤0.64 FL
≤0.54 IPLV
≤0.48 IPLV
Water-cooled, electrically operated centrifugal
< 150 t
kW/t
≤0.62 FL
≤0.64 FL
≤0.60 IPLV
≤0.36 IPLV
Water-cooled, electrically operated centrifugal
≥150 t and <300 t
kW/t
≤0.59 FL
≤0.64 FL
≤0.60 IPLV
≤0.35 IPLV
Water-cooled, electrically operated centrifugal
≥300 t and <400 t
kW/t
≤0.56 FL
≤0.60 FL
≤0.55 IPLV
≤0.36 IPLV
Water-cooled, electrically operated centrifugal
≥400 t and <600 t
kW/t
≤0.56 FL
≤0.60 FL
≤0.55 IPLV
≤0.36 IPLV
Water-cooled, electrically operated centrifugal
≥ 600 t
kW/t
≤0.55 FL
≤0.57 FL
≤0.40 IPLV
≤0.350 IPLV

Electric Resistance Water Heaters, Gas Storage Water Heaters, Gas Water Heaters, Heat Pump Water Heaters, and Solar Water Heaters Water-Heating Equipment: Performance Requirements

Equipment Type
Size Category (Input)
Subcategory or Rating Condition
Performance Required
Electric water heaters
≤12 kW
Resistance ≤55 gal
0.93 EFa or greater and 4,721 kWh or less annual energy useb
≤12 kW
Resistance >55 gal
0.92 EF or greater and 4,773 kWh or less annual energy use
≤24 A and ≤250 V
Heat pump ≤55 gal
EF ≥2.0 and FHR ≥50 gal/h
Heat pump >55 gal and ≤120 gal
EF ≥2.2 and FHR ≥50 gal/h
Gas storage water heaters
≤75,000 Btu/h
≥20 gal and ≤55 gal
EF ≥0.67 and FHR ≥67 gal/h
>55 gal and ≤100 gal
EF ≥0.77 and FHR ≥67 gal/h
>75,000 Btu/h
>100 gal and ≤140 gal
TE ≥0.94 or EF ≥0.93 and SL ≤0.84 * [(input rate/800) + 100√volume)] Btu/h
Gas instantaneous water heaters
≥50,000 Btu/h and <200,000 Btu/h
<4,000 (Btu/h)/gal
EF ≥0.90 and GPM ≥2.5 over a 77-deg rise
≥200,000 Btu/h
≥4,000 (Btu/h)/gal
TE ≥0.94 or EF ≥0.93
Solar water heaters
≤75,000 Btu/h
Electric backup
SEF ≥1.8
Gas backup
SEF ≥1.2

a Energy factor (EF) is an efficiency ratio of the energy supplied in heater water divided by the energy input to the water heater.

b Based on U.S. Department of Energy test procedure (10 CFR 430, Subpart B, Appendix E).

Gas Furnaces Warm-Air Furnaces: Minimum Efficiency Requirements

Equipment Type
Size Category (Input)
Subcategory or Rating Condition
Minimum Efficiency
Warm-air furnace, gas fired
<225,000 Btu/h
Maximum capacity
≥95.0% (U.S. North/Canada)

≥90.0% (U.S. South)

≥225,000 Btu/ha
Maximum capacity
80% Et
Warm-air furnace, oil fired
<225,000 Btu/h
Maximum capacity
≥85% AFUE
≥225,000 Btu/ha
Maximum capacity
81% Et

a Furnaces with input equal to or greater than 225,000 Btu/h are not covered by federal purchasing requirements. Minimum efficiency presented is consistent with ASRHAE 90.1-2013.

Room Air Conditioners Electrically Operated Room Air Conditioners: Minimum Efficiency Requirements

Equipment Type
Size Category (Input)
Subcategory or Rating Condition
Minimum Efficiency
Room air conditioners with louvered sides
<6,000 Btu/h
-
11.2 EER and 11.0 CEER
≥6,000 Btu/h and <8,000 Btu/h
-
11.2 EER and 11.0 CEER
≥8,000 Btu/h and <14,000 Btu/h
-
11.3 EER and 11.2 CEER
≥14,000 Btu/h and <20,000 Btu/h
-
11.2 EER and 11.1 CEER
≥20,000 Btu/h
-
9.8 EER and 9.8 CEER
Room air conditioners without louvered sides
≤8,000 Btu/h
-
10.4 EER and 10.2 CEER
≥8,000 Btu/h and <20,000 Btu/h
-
9.8 EER and 9.7 CEER
≥20,000 Btu/h and <28,000 Btu/h
-
9.8 EER and 9.7 CEER
≥28,000,000 Btu/h
-
9.8 EER and 9.8 CEER
Room air-conditioner heat pumps with louvered sides
<20,000 Btu/h
-
10.4 EER and 10.3 CEER
≥20,000 Btu/h
-
9.8 EER and 9.8 CEER
Room air-conditioner heat pumps without louvered sides
<14,000 Btu/h
-
9.8 EER and 9.7 CEER
≥14,000 Btu/h
-
9.2 EER and 9.1 CEER
Room air conditioner, casement only
All capacities
-
10.0 EER and 9.9 CEER
Room air conditioner, casement slider
All capacities
-
10.9 EER and 10.8 CEER

File details come from the government source that posted it. Updated .