HVAC_LIST_OF_WORK.docx
DOCX document 22 KB Posted
- Attached to
- PRESCOTT NF HVAC MAINTENANCE SERVICES Federal contract opportunity
- Solicitation number
- AG-8191-S-15-0005
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| AG-8191-S-15-0005.pdf | ||
| AG-8191-S-15-0005.pdf | ||
| Past_Performance_Questionnaire.docx | DOCX document | |
| Prescott_Fire_Plan.pdf | ||
| SERVICE_WAGE_DECISION.pdf | ||
| HVAC_EQUIPMENT_LIST.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
List of Work Prescott National Forest Service HVAC Preventive Maintenance
Note: this list is based on preventive maintenance service calls twice each year, at the beginning of heating season and beginning of cooling season.
| Preventive Maintenance Task |
| Heating |
Season Cooling Season
| Change or clean return air filter |
| X |
| X |
| Check and clean burners, check burner operation; adjust as necessary |
| X |
| Check combustion exhaust flue |
| X |
Check and clean condenser unit, including fins
X
Check compressor, including mounting hardware
X
| Check and clean exchangers |
| X |
| X |
| Check outside air flow; clean louvers and screens; check economizer operation if equipped |
| X |
| X |
| Check fan operation; clean blades if necessary |
| X |
| X |
| Check all electrical and gas connections are tight |
| X |
| X |
| Measure motor amperage and voltage on fans and compressors, record readings on service order |
| X |
| X |
| Check air flow in air handler unit |
| X |
| X |
| Check belts and pulleys, adjust as necessary |
| X |
| X |
| Check bearings; check bearing and shaft seals |
| X |
| X |
| Drain evaporative cooler and water supply line; winterize cooler unit |
| X |
Replace or clean evaporative cooler pads
X
Check water level and float operation in evaporative cooler pans; adjust as necessary
X
Check operation of water pump and circulation system, adjust for even water distribution on cooler pads
X
| Lubricate moving parts and motors, if recommended |
| X |
| X |
| Check safety controls for limit cutouts and proper operation |
| X |
| X |
| Check operation of user controls through complete heat, cool or exhaust cycle; adjust user controls for appropriate season if control does not perform automatic cutover between heating and cooling |
| X |
| X |
| Check air flow at supply registers |
| X |
| X |
Check for air flow through exhaust system (exhaust fans)
X
File details come from the government source that posted it. Updated .