AG-3142-S-10-0072 - DWGS Bid Set.pdf

PDF 11 MB Posted

Attached to
RECOVERY -- REPLACEMENT OF CHILLER 1 SYSTEM Federal contract opportunity
Solicitation number
AG-3142-S-10-0072
Issued by
Department of Agriculture Office of Procurement and Property Management

About this file

SOLICITATION RELEASED - DRAWINGS

View the file

Other files for this federal contract opportunity

Other files attached to RECOVERY -- REPLACEMENT OF CHILLER 1 SYSTEM, newest first.
File Type Posted
Amendment No. 0003 07.06.10 SF30.pdf PDF
Amendment No. 0002 07.01.10 SF30.pdf PDF
Amendment No. 0002 07.01.10 ATTACHMENT.pdf PDF
Amendment No. 0001 06.15.10 SF30.pdf PDF
Amendment No. 0001 06.15.10 ATTACHMENT.pdf PDF
AG-3142-S-10-0072 - SOLICITATION BODY.pdf PDF
AG-3142-S-10-0072 - SF1442.pdf PDF
AG-3142-S-10-0072 - SPEC Bid Set.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AHU NO. SERVE SYMBOL TONAGE LOCATION TYPE SIZE NEW NOTE

WHITTEN BUILDING

CONF. ROOM BSMT 2W W1 2.5 BSMT A SECT. 3-WAY 25 25 PNEUMATIC

CONF. ROOM BSMT 3W W1 2.5 BSMT A SECT. 3-WAY 25 25 PNEUMATIC

COPIER STATION W2 5 BSMT A SECT. 3-WAY 31.25 31.25 PNEUMATIC

A-11-6 BSMT CENTER CAFÉ W3 25 MR 14A BSMT 3-WAY 75 75 PNEUMATIC

A-11-7 SECRETARY'S SUITE W4 20 MR 4A BSMT 3-WAY 62.5 62.5 PNEUMATIC

A-11-8 UNDER SECRETARY'S SUITE W5 20 MR 20A BSMT 3-WAY 62.5 62.5 PNEUMATIC

A-11-9 BSMT IMPRESS FUND W6 3 MR 4A BSMT 3-WAY 31.25 31.25 PNEUMATIC

6A SPACE GUARD ROOM W7 3 BSMT A SECT. 3-WAY 31.25 31.25 PNEUMATIC

1ST FL. 104A/107A CONF. R W8 5 1ST FL. A SECT. 3-WAY 31.25 31.25 PNEUMATIC

A-11-12 AHU SERV. 2ND FL. A OFCS W9 10 MR 345A,3RD F 3-WAY 37.5 37.5 PNEUMATIC

A-11-15 3RD FLOOR BUFFET A SECT. W10 15 IN 3RD FL. KIT. 3-WAY 37.5 37.5 PNEUMATIC

FCUS IN 320A, 324A, 326A W11 4 3RD FL. A SECT. 2-WAY NR ABV CEIL.

ROOM 301A W12 5 3RD FL. A SECT. 2-WAY NR ABV CEIL.

5TH FL. OFFICE FCUS W13 5TH FL. A SECT. 2-WAY NR ABV CEIL.

SOUTH BUILDING

AHU A-11-3 W1 SUB BSMT NR NR NOT IN USE

AHU A-11-4 S3 20 W1 SUB BSMT 3-WAY 75 ELECTRIC

S143 AHU IN SOUTH MR S4 15 W1 SUB BSMT 3-WAY 75 75 PNEUMATIC

C-41 MAIL ROOM COURT 4 S5 MR S-502 SUBB 2-WAY 100 NR PNEUMATIC

C-42 SUITE 1406 COURT 4 S6 MR S-502 SUBB 2-WAY 37.5 NR PNEUMATIC

A-11-32 PRINTING PLANT S7 10 MR S-502 SUBB 2-WAY 37.5 NR PNEUMATIC

A-11-36 PRINTING PLANT S7 20 MR 0556 SUBB 2-WAY 50 NR PNEUMATIC

PRINT. PL. SOUTH OFFICES S7 5 W5 BSMT SOU. 3-WAY 31.25 31.25 PNEUMATIC

A-11-39 FMD S228 W3 SBSMT S8 25 W3 SUB BSMT 2-WAY 50 NR PNEUMATIC

OPERATION CENTER FCUS S9 30 W3 SUB BSMT 2-WAY 62.5 NR ELECTRIC

A-11-45 SOUND STAGE S10 15 MR 1623 1ST FL 2-WAY 62.5 NR PNEUMATIC

A-11-46 NFC TRAINING ROOMS S11 20 MR 1623 1ST FL 3-WAY 62.5 62.5 PNEUMATIC

A-11-47 JEFFERSON AUDITORIUM S12 56 MR S0073 SUBB 3-WAY 100 100 PNEUMATIC

A-11-53 FIRING RANGE W1 SBSMT S13 10 W1 SUB BSMT 3-WAY 37.5 37.5 PNEUMATIC

A-11-54 FIRING RANGE W1 SBSMT S13 10 W1 SUB BSMT 3-WAY 37.5 37.5 PNEUMATIC

COMPUTER ROOM 0061 S14 3.5 W4 BSMT HH 2-WAY NR

COMPUTER ROOM 0061 S14 2 W4 BSMT HH 2-WAY NR

A-11-50 NATI SHOP S16 20 W3 SUBB S237 2-WAY NR PNEUMATIC

NOTES:

1.CONTRACTOR SHALL VERIFY VALVE TYPES (PNEUMATIC OR ELCETRIC) AND SIZE IN FIELD; NR: NOT

REQUIERED, NO WORK

2. CONTRACTOR SHALL VERIFY VALVE AND PIPING SIZES IN FIELD. VALVE CONSTRUCTION MATERIALS

(BODY, SEAT, STEM, ETC.) SHALL MATCH THOSE BEING REPLACED.

3. RECONNECT EX ACTUATION TO NEW VALVE TO MODULATE ACCORDING TO EXISTNG CONTROL

SIGNAL

4. COORDINATE ELEC/PNEUMATIC REQUIREMENT.

3-WAY VALVE REPLACEMENT SCHEDULE

5. ALL 3-WAY VALVE REPLACEMENT SHALL BE PERFORMED AFTER HOURS, WHICH IS THE WEEKEND

OR BETWEEN 6PM AND 6AM WEEKDAYS. THE VALVE CHANGE, ONCE STARTED , HAS TO BE

COMPLETED WITHIN THE SAME NIGHT OR WEEKEND SO THAT AFFECTED AHUS ARE OPERATIONAL BY 6AM OF THE NEXT OCCUPIED HOURS. USDA WILL HANDLE THE DRAINING OF CHILLED WATER AND

CONTRACTOR SHALL COORDINATE.

SYSTEM POINT

DESCRIPTION

G R A P H

IC

T E M P E R A T U R E

P R E S S U R E

K W

B T U /H R

G P M

C F M

P E R C E N T

S E T P O

IN

T

M O D U L A T E

S E T P O

IN

T A D J

P N E U T R A N S D U C E R

S T A T U S O N O F F

F

IL

T E R S T A T U S

P O W E R S T A T U S A M P S

S T A T U S

O P E N C L S D

S T A T U S

N O O F S T A R T S

O F F O N

O P E N C L O S E D

L O C K O U T

E N A B L E D

IS

A B L E

E N D S W

IT

C H

H

IG

H A N A L O G

L O W A N A L O G

H

IG

H B

IN

A R Y

L O W B

IN

A R Y

P R O O F

S E N S O R F A

IL

F L O W F A

IL

C O M M F A

IL

D

IA

G N O S T

IC

S

T

IM

E S C H E D U L

IN

G

D E M A N D L

IM

IT

IN

G

O P S T A R T /S T O P

R E S E T

E V E N T P R O G R A M

A L A R M I N S T R U C T

M A

IN

T W K O R D E R

R U N T

IM

E

S E T B A C K S E T U P

N

IG

H T P U R G E

C H

IL

L E R S E Q U E N C

IN

G

T O T A L

IZ

IN

G

R E P L A C E A C T U A T O R

R E P L A C E S E N S O R

OUTSIDE AIR TEMP X DRY BULB AND WET BULB TEMP

GLYCOL SYSTEM X

V-1 X X X

ICE INVENTORY SENSOR X X X

WL-1 X

BUBBLER AIR PUMP X X

THERMAL STORAGE LVG GLYCOL FM X X

V-2 X X X

BYPASS FM X X

GP-1 X X X X

GP-2 X X X X

GLYCOL RETURN FM X X

GLYCOL ENTERING TEMP X

GLYCOL LEAVING TEMP X

WL-1 ICE TANK X

CONDENSER WATER X

V-15 X X

CWP-C X X

CWP-C VFD X X X X

V-14 X X

CH-2 CWR FM X X

V-11 X X

CT-2 ELECTRIC WATER TREATMENT X X X

V-12/V-13 X X X

CT-2A/2B LWT X X

CT-2A FAN VFD X X X X X

CT-2B FAN VFD X X X X X

CT-2A BASIN HEATER X CTRL VIA TOWER PANEL

CT-2B BASIN HEATER X CTRL VIA TOWER PANEL

CT-2A WATER LEVEL CONTROL X CTRL VIA TOWER PANEL

CT-2B WATER LEVEL CONTROL X CTRL VIA TOWER PANEL

CT-2 SOLIDS SEPARATOR BLEED VALVE X X

V-25 X X

CWP-B X X

CWP-B VFD X X X X

CH-1 CONDENSER FLOW SWITCH X

V-20/V-21 X X X

V-22 X X

CT-2 ELECTRIC WATER TREATMENT X X X

V-23/24 X X X

CT-1A/1B LWT X X SETPOINT VIA CH-1 HEAD PR CONTROL

CT-1A FAN VFD X X X X X

CT-1B FAN VFD X X X X X

CT-1A BASIN HEATER X CTRL VIA TOWER PANEL

CT-1B BASIN HEATER X CTRL VIA TOWER PANEL

CT-1A WATER LEVEL CONTROL X CTRL VIA TOWER PANEL

CT-1B WATER LEVEL CONTROL X CTRL VIA TOWER PANEL

CT-1 SOLIDS SEPARATOR BLEED VALVE X X

CWP-A X X

CWP-A VFD X X X X

V-26

HX-2 CONDENSER EWT X

HX-2 CONDENSER LWT X

CHILLED WATER X X X X X X

WHITTEN BLDG SYSTEM DPT X X

SOUTH BLDG SYSTEM DPT X X

CHWR TEMP SENSOR X

V-30 X X X

CHWP-1 X X

CHWP-1 VFD X X X X

CHWP-2 X X

CHWP-2 VFD X X X X

V-31 X X X

V-31 FM X

V-32 X X X

HX-2 X

HX-2 CHW EWT X

HX-2 CHW LWT X X

V-33 X X X

V-34 X X X

V-35 X X X

CH-1 X X X X X X X X X X PROVIDED VIA COMM TO DDC

CH-1 LWT X X

CH-1 DPT X X

V-36 X X X

HX-1 DPT X X

HX-1 FM X

V-37 SYSTEM BYPASS X X X X

CHWS TEMP SENSOR X

CHWS FLOW METER X

NOTES:

OUTPUT INPUT OUTPUT ALARMS PROGRAMS

NOTES:

1. ALL VALVE ACTUATORS 150MM AND LARGER TO BE 120V

SYSTEM POINT LIST

SYSTEM POINT

NUMBER

ANALOG BINARY SYSTEM FEATURES

INPUT

SYSTEM POINT

DESCRIPTION

G R

A P

H

IC

T E

M P

E R

A T U

R E

P R

E S

S U

R E

K W

B T U

/H R

G P

M C

F M

P E

R C

E N

T S

E T P

O

IN

T M

O D

U L A

T E

S E

T P

O

IN

T A

D J

P N

E U

T R

A N

S D

U C

E R

S T A

T U

S O

N O

F F

F

IL

T E

R S

T A

T U

S P

O W

E R

S T A

T U

S A

M P

S

S T A

T U

S

O

P E

N C

L S

D

S T A

T U

S N

O O

F S

T A

R T S

O F F O

N O

P E

N C

L O

S E

D L O

C K

O U

T E

N A

B L E

D

IS

A

B L E

E N

D S

W

IT

C H

H

IG

H A

N A

L O

G L O

W A

N A

L O

G H

IG

H

B

IN

A R

Y L O

W B

IN

A

R Y

P R

O O

F S

E N

S O

R F

A

IL

F L O

W F

A

IL

C O

M M

F A

IL

D

IA

G

N O

S T

IC

S T

IM

E S

C H

E D

U L

IN

G D

E M

A N

D L

IM

IT

IN

G

O P

S

T A

R T /S

T O

P R

E S

E T

E V

E N

T P

R O

G R

A M

A L A

R M

M A

IN

T W

K O

R D

E R

R U

N T

IM

E

S E

T B

A C

K S

E T U

P N

IG

H

T P

U R

G E

C H

IL

L E

R S

E Q

U E

N C

IN

G

T O

T A

L

IZ

IN

G

R E

P L A

C E

A C

T U

A T O

R R

E P

L A

C E

S E

N S

O R

HEATING X

HX-3 STEAM CONTROL VALVE X X

HX-3 LEAVING WATER TEMP X

HWP-1 X X

HWP-1 VFD X X X X

UH-1 & 2 FAN MOTOR X

UH-1 & 2 HW CONTROL VALVE X

SPACE EXHAUST X

OUTSIDE AIR INTAKE DAMPER X X X

CH-1 & 2 EXHAUST DAMPER X X

ROOM EXHAUST DAMPERS (2) X X

EF-1 X X

EF-1 VFD X X X

REFRIGERANT DETECTORS CH-1 X

REFRIGERANT DETECTORS CH-2 X

REFRIGERANT ALARMS (2) X X

SPACE TEMPERATURE SENSOR X

NOTES:

SYSTEM POINT LIST

SYSTEM POINT

NUMBER

ANALOG BINARY SYSTEM FEATURES

INPUT OUTPUT INPUT OUTPUT ALARMS PROGRAMS

NOTES:

MAX.

OCP

(A)

1406 KW 36.6

400 TONS MAX

NOTES:

1. MARINE CONNECTIONS

60 DIRECT - - MCQUAY- 251 1,426 208 30.00025 1 807 6,075

MICROPROCESSOR

COMM TO DDC

UNIT1034 2 75.7 31.0 29.3 1,0222 50.5 12.2 5.6 21.5 0.00001CH-1 0.628 0.606

123 OR

134A

- 1034

TYPE MTG.

MOUNT. TYPE

ELECTRICAL

CHAR.

V PH HZ

MINIMUM

CIRCUIT

AMPACITY

(A)

POWER

INPUT

(KW)

POWER

CONN.

CHILLER ELECTRICAL REQUIREMENTS VIBRATION ISOLATION

DATA

BASIS OF SELECTION

OPER.

WEIGHT

(KG) MFGRDEFLECT.

(MM)

MOTOR CONTROLLER

NO. OF

PASS.

FLOW

RATE

(L/S)

EWT

(C°)

LWT

(C°)

MAX.

PD

(KPA)

FOULING

FACTOR

NO. OF

COMP.

RATED

LOAD

AMPS

(RLA)

LOCKED

ROTOR

AMPS

(LRA)

TYPE

QTY

(KG)

PRESS.

RATING

(KPA)

NO. OF

PASS.

EVAPORATOR DATAREFRIGERANT

FLOW

RATE

(L/S)

EWT

(C°)

LWT

(C°)

MAX. PD

(KPA)

2. MANUFACTURER TO PROVIDE REFRIGERANT DETECTION SYSTEM. INTERCONNECT WITH DDC AND EF-1.

CHILLER SCHEDULE (CENTRIFUGAL TYPE)

UNIT

NO.

CAP.

KW/TONS

FULL LOAD

EFFICIENCY

(KW/TON)

PART LOAD

EFFICIENCY /

NPLV

(KW/TON)

FOULING

FACTOR

PRESS.

RATING

(KPA)

CONDENSER DATA COMPRESSOR DATA

AIR

11.2 BAC VTL-095K

VFD ALTERNATIVE MANUFACTURERS MUST CERTIFY COMPATIBILITY WITH EXISTING AVAILABLE SPACE.

29.8 BAC VTL-227-O

VFD ALTERNATIVE MANUFACTURERS MUST CERTIFY COMPATIBILITY WITH EXISTING AVAILABLE SPACE.

11.2 INSTALL NEW MOTOR AND VFD IN EXISTING COOLING TOWER CELL

VFD PROVIDE NEW MOUNTING BRACKETS AND SHEAVES.

29.8 INSTALL NEW MOTOR AND VFD IN EXISTING COOLING TOWER CELL

VFD PROVIDE NEW MOUNTING BRACKETS AND SHEAVES.

NOTES:

2. ELECTRIC WATER LEVEL CONTROL

3. EXTENDED LUBRICATION LINES

11. STAINLESS STEEL INLET SCREENS

1,846

1,846

1. VIBRATION CUTOUT SWITCH

1 AT 4 KW

1 AT 7 KW

REMOVE EXISTING

INSTALL 1 AT 4 KW

REMOVE EXISTING

INSTALL 1 AT 4 KW

NONE

NONE

36.6

36.6

31.0

31.0

21972

25.6

25.6

18.9

37.9

22.3

53.4

OPEN

CENTER FAN

OPEN

CENTER FAN

OPEN

CENTER FAN

OPEN

CENTER FAN

CT CELL 1A

CT CELL 1B

CT CELL 2B

EXISTING

CT CELL 2A

EXISTING

CHILLER 2

CHILLER 2

CH-1 AND FUTURE

HX-2

CH-1 AND FUTURE

HX-2

TYPE

DELEC

TION

(MM)

BASIN HEATER

OPERATING

WEIGHT (KG)

BASIS OF SELECTION

VIBRATION

EWT (°C) LWT (°C)

AIRFLOW

L/S

CONDENSER WATER DATA FAN MOTOR DATA

EXT SP

(PA) KW (EA.) V PH

ELECTRICAL DATA

TYPESERVICEUNIT NO.

EWB (°C) MIN L/S MAX L/S

COOLING TOWER SCHEDULE

4. TERMINAL BOX

5. GALVANIZED DRIFT ELIMINATORS

6. NEMA 3R ENCLOSURE WITH VENTILATION

7. SP BASED ON CATALOG AIRFLOW, 37.4 INLET, 24.9

8. STAINLESS STEEL SUMP

9. SAFETY DISONNECT

PROVIDE THE FOLLOWING:

10. BYPASS AND EQUALIZER CONNECTIONS FOR NEW COOLING TOWER

NOMINAL

CAPACITY

(KW)

LENGTH WIDTH HEIGHT

NOTES:

0.0002 TRANTER UFX

1. DIMENSIONS INCLUDE ENTIRE ASSEMBLY

2111 622 1800 WATER1,034.2 0.0002

MANUFACTURER /

MODEL SERIES

1054.1 WATER 75.7 4.4 7.8 44.5 6.7 21.050.5 11.7

PRESS.

RATING

(KPA)

FOULING

FACTOR

L/S

EWT

(°C) L/S

EWT

(°C)

LWT

(°C)

MAX.

PD

(KPA)

1,034.2

CHILLED WATER

LWT

(°C)

MAX.

PD

(KPA)

PRESS.

RATING

(KPA)

FOULING

FACTOR

APPROX. DIMENSIONS (MM)

FLUID

HEAT EXCHANGER SCHEDULE (WATER-TO-WATER TYPE)

UNIT NO.

PLATE

FRAME

WATER SIDE

ECONOMIZER

HX-2

TYPE SERVICE

CAPACITY

(KW) FLUID

CONDENSER WATER

HX-3 HEATING HOT WATER SHELL & TUBE 227 68.9 82 93 3.2 29.9 254 1829 1.8 BELL & GOSSETT SU

NOTES:

1. EXCHANGERS SIZED WITH A FOULING FACTOR OF .001

HEAT EXCHANGER SCHEDULE (STEAM-TO-WATER TYPE)

STEAM WATER

MARK SERVICE TYPE

INPUT

(KG/HR)

INPUT

PRESSURE

(KPA)

MAX

VELOCITY

(M/S)

BASIS OF SELECTION

EWT

(°C)

LWT

(°C) L/S

PRESS.

DROP

(KPA)

MAX

DIAMETER

(MM)

MAX

LENGTH

(MM)

NOTES:

FAN SCHEDULE

PERFORMANCE MOTOR DATA

BASIS FOR

SELECTIONTYPE FAN

SERVICE REMARKS

1. FACTORY DISCONNECT

EF-1 PLANT

RPMKW

1,634

UNIT

NO.

MAX

(BKW)

3 60 PROVIDE VFD

GREENHECK

SQ-160A

CENTRIFUGAL IN

LINE DIRECT DRIVE

1,7251.49 2081,890 249 1.19

HZPH.VOLTS

MAX

RPM

TOTAL

SP (PA)

AIRFLOW

(L/S)

VFD

B&G SERIES 60 1-1/2 X 7

VFD

1. CONTRACTOR TO MODIFY EXISTING PAD AS REQUIRED TO COORDINATE WITH EXACT EQUIPMENT PROVIDED.

B&G HSC-S 6X8X17M

VFD

B&G HSC-S 6X8X17M

VFD

B&G HSC-S 8X10X20S

VFD

B&G HSC-S 8X10X20S

DIRECT

DIRECT

DIRECT

DIRECT

DIRECT

NOTE 1

NOTE 1

NOTE 1

NOTE 1

74.6

74.6

29.8

29.8

1.1

HORIZ. SPLIT

HORIZ. SPLIT

HORIZ. SPLIT

HORIZ. SPLIT

IN LINE

56.47

20.66

22.39

0.74

1,780

1,780

1,180

1,180

1,750

28.56

284 13

75.7

83.3

3.2

CWP-A

CWP-B

HWP-1

CHILLED

CHILLED

CT-1A/B & HX-2

CT-1A/B & CH-1

CT-2-A/B & CH-2

CWP-C CT-2-A/B & CH-2

MTG.

TYPE

BASE

TYPE

MANUFACTURER / BASIS OF

SELECTION

CHWP-1

CHWP-2

56.4781.5

81.5

PUMP SCHEDULE

UNIT NO. SERVICE L/S

TDH

(KPA)

REQ

NPSH

(KPA)

BKW RPM TYPE PH

REMARKSPERFORMANCE DATA CONSTRUCTION DATA MOTOR DATA MOUNTING

NOTES:

SUCT.

SIZE

(MM)

DISCH.

SIZE

(MM)

KW V

77.3 3 DIRECT NOTE 1

B&G HSC-S 8X10X20S

VFD

1,180 HORIZ. SPLIT 254 203 37.3 208

HOT WATER UNIT HEATER SCHEDULE

NOTES:

HV-120 -

1. FACTORY PROVIDE DISCONNECT

67.3 1.45 93.3 82.2 15.6

6.27 15.6 - TRANE

- TRANE

HV-120 -

60 6.27UH-2

2,360

2,360

1,100

1,100

67.3

MFGR

BASIS OF SELECTION

REMARKSMODEL

SERIES

WATER DATA

UH-1 373 1.45 93.3 82.2

HEATING

CAPACITY

(KW)

WATER

FLOW

(L/S)

EWT

(°C)

LWT

(°C)

MAX. PD

(KPA)

EAT

(°C)

AIR DATA

LAT

(°C)

NOMINAL

AIRFLOW

(L/S)

UNIT NO.

FAN DATA

RPM

POWER

(W)

VOLTS PH HZ

PIPE SIZE (MM) CABLE CAPACITY (W/M)

12.5 - 62.5 9.8

75 - 150 16.4

20 - 300 26.2

NOTES:

HEAT TRACE CABLE SIZE SCHEDULE

PROJECT: USDA SUB-CENTRAL BUILDING PANEL VOLTAGE: 208/120V AIC RATING:

PANEL: "MDP-1" PHASE & WIRE: 3PH,4W MOUNTING: SURFACE

LOCATION: CHILLER PLANT BUS/MAIN (AMPS): 800A MLO NOTES: FEED THRU LUGS

CKT OCD LOAD (KVA) 3 PH SEQUENCE LOAD (KVA) OCD CKT

NO. A P DESCRIPTION MISC REC LTG A B C MISC REC LTG DESCRIPTION A P NO.

1 400 3 CHWP-1 32.8 46.5 13.7 GLYCOL GP-1 200 3 2

3 -- -- (100 HP) 32.8 46.5 13.7 (40 HP) -- -- 4

5 -- -- --- 32.8 46.5 13.7 --- -- -- 6

7 200 3 CWP-A 13.7 30.9 17.2 CWP-C 225 3 8

9 -- -- (40 HP) 13.7 30.9 17.2 (50 HP) -- -- 10

11 -- -- --- 13.7 30.9 17.2 --- -- -- 12

13 70 3 CT-1A 5.6 11.2 5.6 CT-2A 70 3 14

15 -- -- (15 HP) 5.6 11.2 5.6 (15 HP) -- -- 16

17 -- -- --- 5.6 11.2 5.6 --- -- -- 18

19 30 3 GLYCOL AIR BUBBLER 2.0 15.7 13.7 QUINCY AIR-COMPRESSOR 200 3 20

21 -- -- (5 HP) 2.0 15.7 13.7 (40 HP) -- -- 22

23 -- -- --- 2.0 15.7 13.7 --- -- -- 24

25 20 1 MOTORIZED VALVES 1.5 2.9 1.4 CT-2A BASIN HEATER 20 3 26

27 20 1 MOTORIZED VALVES 1.5 2.9 1.4 (4 KW) -- -- 28

29 20 1 MOTORIZED VALVES 1.5 2.9 1.4 --- -- -- 30

31 20 3 CT-1A BASIN HEATER 1.4 1.4 SPACE 3 32

33 -- -- (4 KW) 1.4 1.4 --- -- -- 34

35 -- -- --- 1.4 1.4 --- -- -- 36

37 20 2 CHEMICAL TREATMENT #1 1.2 1.2 SPACE 3 38

39 -- -- --- 1.2 1.2 --- -- -- 40

41 20 1 GFCI CB FOR HEAT TRACE 1.5 1.5 --- -- -- 42

CONNECTED LOAD (KVA) 174.9 0.0 0.0 109.8 109.8 110.1 154.8 0.0 0.0

TOTAL CONNECTED LOAD (KVA) 329.7 0.0 0.0

DEMAND FACTOR 0.80 0.5 1.00 TOTAL DEMAND (KVA) 264

TOTAL DEMAND LOAD (KVA) 263.8 0.0 0.0 LINE CURRENT (AMPS) 732

65,000

PROJECT: USDA SUB-CENTRAL BUILDING PANEL VOLTAGE: 208/120V AIC RATING:

PANEL: "NL-A" PHASE & WIRE: 3PH,4W MOUNTING: SURFACE

LOCATION: SWBD ROOM BUS/MAIN (AMPS): 100A MLO NOTES:

CKT OCD LOAD (KVA) 3 PH SEQUENCE LOAD (KVA) OCD CKT

NO. A P DESCRIPTION MISC REC LTG A B C MISC REC LTG DESCRIPTION A P NO.

1 20 1 GEN SET HEATER 1.5 1.5 FIRE ALARM 20 1 2

3 20 1 GEN SET CHARGER 0.5 0.5 FIRE ALARM 20 1 4

5 20 1 GEN SET SPARE 1.6 1.6 LIGHTING 20 1 6

7 20 1 R-CONVENIENCE 1.2 2.5 1.3 LIGHTING 20 1 8

9 20 1 R-CONVENIENCE 1.4 2.5 1.1 LIGHTING 20 1 10

11 20 1 R-CONVENIENCE 1.2 2.0 0.8 R- SUMP PUMP #1 20 1 12

13 20 1 R- ELECTRIC ROOMS 1.0 1.8 0.8 R- SUMP PUMP #2 20 1 14

15 20 1 R- SUMP PUMP #4 0.8 1.6 0.8 R- SUMP PUMP #3 20 1 16

17 20 1 SPARE 0.0 SPARE 20 1 18

19 20 1 SPARE 0.0 SPARE 20 1 20

21 20 1 SPARE 0.0 SPARE 20 1 22

23 20 1 SPARE 0.0 SPARE 20 1 24

25 20 1 SPARE 0.0 SPARE 20 1 26

27 20 1 SPARE 0.0 SPARE 20 1 28

29 20 1 SPARE 0.0 SPARE 20 1 30

31 60 2 ULTR-AIR COMPRESSOR 4.7 4.7 32

33 -- -- (1 HP) 4.7 4.7 34

35 0.0 36

37 0.0 38

39 0.0 40

41 0.0 42

CONNECTED LOAD (KVA) 12.2 4.8 0.0 10.5 9.3 3.6 2.4 0.0 4.0

TOTAL CONNECTED LOAD (KVA) 14.6 4.8 4.0

DEMAND FACTOR 0.80 0.5 1.00 TOTAL DEMAND (KVA) 18

TOTAL DEMAND LOAD (KVA) 11.7 2.4 4.0 LINE CURRENT (AMPS) 50

NOTE: 1. DECRIPTIONS SHOWN IN BOLD ARE "NEW" CIRCUITS BEING CONNECTED TO THIS PANEL. CONNECT TO EXISTING BREAKERS.

NOTE: 2. WHERE BREAKERS ARE SHOWN IN BOLD THEY ARE "NEW" BREAKERS TO BE PROVIDED. NEW BREAKERS SHALL MATCH EXISTING BREAKERS IN RATING..

10,000

PROJECT: USDA SUB-CENTRAL BUILDING PANEL VOLTAGE: 208/120V AIC RATING:

PANEL: "MDP-2" PHASE & WIRE: 3PH,4W MOUNTING: SURFACE

LOCATION: CHILLER PLANT BUS/MAIN (AMPS): 800A MLO NOTES: FEED THRU LUGS

CKT OCD LOAD (KVA) 3 PH SEQUENCE LOAD (KVA) OCD CKT

NO. A P DESCRIPTION MISC REC LTG A B C MISC REC LTG DESCRIPTION A P NO.

1 400 3 CHWP-2 32.8 46.5 13.7 GLYCOL GP-2 200 3 2

3 -- -- (100 HP) 32.8 46.5 13.7 (40 HP) -- -- 4

5 -- -- --- 32.8 46.5 13.7 --- -- -- 6

7 200 3 CWP-B 13.7 27.4 13.7 CT-2B 200 3 8

9 -- -- (40 HP) 13.7 27.4 13.7 (40 HP) -- -- 10

11 -- -- --- 13.7 27.4 13.7 --- -- -- 12

13 200 3 CT-1B 13.7 14.6 0.9 EF-1 15 3 14

15 -- -- (40 HP) 13.7 14.6 0.9 (2 HP) -- -- 16

17 -- -- --- 13.7 14.6 0.9 --- -- -- 18

19 30 3 DUPLEX SUMP PUMP 1.8 3.3 1.5 MOTORIZED VALVES 20 1 20

21 -- -- (2- 2 HP) 1.8 3.3 1.5 MOTORIZED VALVES 20 1 22

23 -- -- --- 1.8 3.3 1.5 MOTORIZED VALVES 20 1 24

25 30 3 CT-1B BASIN HEATER 2.4 2.4 SPARE 20 1 26

27 -- -- (7 KW) 2.4 2.4 SPARE 20 1 28

29 -- -- --- 2.4 2.4 SPARE 20 1 30

31 3 SPACE 0.0 CT-2B BASIN HEATER 30 3 32

33 -- -- --- 0.0 (7 KW) -- -- 34

35 -- -- --- 0.0 --- -- -- 36

37 20 2 CHEMICAL TREATMENT #2 1.2 1.2 SPACE 3 38

39 -- -- --- 1.2 1.2 --- -- -- 40

41 20 1 GFCI CB FOR HEAT TRACE 1.5 1.5 --- -- -- 42

CONNECTED LOAD (KVA) 197.1 0.0 0.0 95.4 95.4 95.7 89.4 0.0 0.0

TOTAL CONNECTED LOAD (KVA) 286.5 0.0 0.0

DEMAND FACTOR 0.80 0.5 1.00 TOTAL DEMAND (KVA) 229

TOTAL DEMAND LOAD (KVA) 229.2 0.0 0.0 LINE CURRENT (AMPS) 636

65,000

LIGHTING FIXTURE SCHEDULE

APER. INPUT

TYPE DESCRIPTION LAMP MANUFACTURER CATALOG NUMBER VOLTS CONE SIZE FINISH MOUNTING WATTAGE REMARKS

A 1200mm FLUORESCENT INDUSTRIAL 2-F25T8 LITHONIA AF10225-120-GEB10RS 120 -- -- WHITE PENDANT 50 PROVIDE CHAIN HANGER; TWIST LOCK CORD CONNECTION

WITH 10% UPLIGHT

A1 1200mm FLUORESCENT GASKETED SURFACE 2-25T8 LITHONIA DM-2-25-120-GEB10RS 120 -- -- WHITE WALL/CEILING 50 DAMP LOCATION RATED, BALLAST AND LAMPS

SHALL BE LOW TEMPERATURE RATED

B 1200mm WALL-MOUNTED FLUORESCENT 2-25T8 LITECONTROL W-ID-4600-2-4-25T8-BW-CWM-ELB-10-120 120 -- -- WHITE WALL 50

LED EXIT SIGN LONG LIFE HUBBELL LXURWE 120 -- -- -- WALL/CEILING RED LEGEND, SINGLE/DOUBLE FACE AS INDICATED

LED LAMP DUAL/LITE DIRECTIONAL ARROWS AS INDICATED

BATTERRY BACK N1806 LITHONIA ELT36-120-N1806 120 -- -- -- WALL

BASIS OF DESIGN LIGHT FIXTURE MANUFACTURER AND PRODUCT NUMBER ARE IDENTIFIED FOR EACH LIGHT FIXTURE TYPE. FOR EACH LIGHT FIXTURE, PROVIDE EITHER THE BASIS OF DESIGN LIGHT FIXTURE, OR PROVIDE AN EQUAL PRODUCT FROM ANOTHER MANUFACTURER.

LIGHTING FIXTURE SCHEDULE

APER. INPUT

TYPE DESCRIPTION LAMP MANUFACTURER CATALOG NUMBER VOLTS CONE SIZE FINISH MOUNTING WATTAGE REMARKS

A 1200mm FLUORESCENT INDUSTRIAL 2-F25T8 LITHONIA AF10225-120-GEB10RS 120 -- -- WHITE PENDANT 50 PROVIDE CHAIN HANGER; TWIST LOCK CORD CONNECTION

WITH 10% UPLIGHT

A1 1200mm FLUORESCENT GASKETED SURFACE 2-25T8 LITHONIA DM-2-25-120-GEB10RS 120 -- -- WHITE WALL/CEILING 50 DAMP LOCATION RATED, BALLAST AND LAMPS

SHALL BE LOW TEMPERATURE RATED

B 1200mm WALL-MOUNTED FLUORESCENT 2-25T8 LITECONTROL W-ID-4600-2-4-25T8-BW-CWM-ELB-10-120 120 -- -- WHITE WALL 50

LED EXIT SIGN LONG LIFE HUBBELL LXURWE 120 -- -- -- WALL/CEILING RED LEGEND, SINGLE/DOUBLE FACE AS INDICATED

LED LAMP DUAL/LITE DIRECTIONAL ARROWS AS INDICATED

BATTERRY BACK N1806 LITHONIA ELT36-120-N1806 120 -- -- -- WALL

BASIS OF DESIGN LIGHT FIXTURE MANUFACTURER AND PRODUCT NUMBER ARE IDENTIFIED FOR EACH LIGHT FIXTURE TYPE. FOR EACH LIGHT FIXTURE, PROVIDE EITHER THE BASIS OF DESIGN LIGHT FIXTURE, OR PROVIDE AN EQUAL PRODUCT FROM ANOTHER MANUFACTURER.

C-CH1-010.PDF
Bid Set 032910.pdf
4-CH1-102 dtls.PDF
4-CH1-103 dtls.PDF
C-CH1-001.PDF
C-CH1-010.PDF
C-CH1-020.PDF
E CH1 001-SBM04004.pdf
E CH1 001-SBM04004.dwg
E CH1 001-SBM04004
E CH1 201-SBM04004.pdf
E CH1 201-SBM04004.dwg
E CH1 201-SBM04004
E CH1 301-SBM04004.pdf
E CH1 301-SBM04004.dwg
E CH1 301-SBM04004
EL CH1 301-SBM04004.pdf
EL CH1 301-SBM04004.dwg
EL CH1 301-SBM04004
M CH1 001-SBM04004.pdf
M CH1 001-SBM04004.dwg
M CH1 001-SBM04004
M CH1 201-SBM04004.pdf
M CH1 201-SBM04004.dwg
M CH1 201-SBM04004
M CH1 202-SBM04004.pdf
M CH1 202-SBM04004.dwg
M CH1 202-SBM04004
M CH1 301-SBM04004.pdf
M CH1 301-SBM04004.dwg
M CH1 301-SBM04004
M CH1 302-SBM04004.pdf
M CH1 302-SBM04004.dwg
M CH1 302-SBM04004
M CH1 303-SBM04004.pdf
M CH1 303-SBM04004.dwg
M CH1 303-SBM04004
M CH1 401-SBM04004.pdf
M CH1 401-SBM04004.dwg
M CH1 401-SBM04004
M CH1 402-SBM04004.pdf
M CH1 402-SBM04004.dwg
M CH1 402-SBM04004
M CH1 411-SBM04004.pdf
M CH1 411-SBM04004.dwg
M CH1 411-SBM04004
M CH1 412-SBM04004.pdf
M CH1 412-SBM04004.dwg
M CH1 412-SBM04004
M CH1 413-SBM04004.pdf
M CH1 413-SBM04004.dwg
M CH1 413-SBM04004
M CH1 414-SBM04004.pdf
M CH1 414-SBM04004.dwg
M CH1 414-SBM04004
M CH1 415-SBM04004.pdf
M CH1 415-SBM04004.dwg
M CH1 415-SBM04004
M CH1 416-SBM04004.pdf
M CH1 416-SBM04004.dwg
M CH1 416-SBM04004
M CH1 417-SBM04004.pdf
M CH1 417-SBM04004.dwg
M CH1 417-SBM04004
M CH1 418-SBM04004.pdf
M CH1 418-SBM04004.dwg
M CH1 418-SBM04004
M CH1 501-SBM04004.pdf
M CH1 501-SBM04004.dwg
M CH1 501-SBM04004
M CH1 502-SBM04004.pdf
M CH1 502-SBM04004.dwg
M CH1 502-SBM04004
M CH1 801-SBM04004.pdf
M CH1 801-SBM04004.dwg
M CH1 801-SBM04004
2-CH1-101 DEMO.PDF
3-CH1-111 1st flr pln.PDF
3-CH1-120 roof pln.PDF
3-CH1-311 RCP.PDF
4-CH1-101 sections.PDF

File details come from the government source that posted it. Updated .