This document is an Addendum No. 1 for the Springfield Township Civic Center Standby Generator project (AEW Project No. 0172-0048), issued by Anderson, Eckstein and Westrick, Inc. The project involves installing a natural gas standby generator at the Springfield Township Civic Center, with sealed bids to be received on Friday, October 27, 2023, at 1:30 p.m. The work includes utility fee allowance, mobilization, sidewalk removal and replacement, erosion control, concrete generator pad installation, site restoration, and audio visual documentation of the construction area. The project is scheduled for substantial completion by December 6, 2024, with final payment due by December 20, 2024.
The addendum includes several key modifications to the original bid documents, such as changing the "Reimbursed Permit Fees" pay item to "Utility Fee Allowance" to cover DTE and Consumers Energy costs, adding sidewalk removal and replacement pay items, and clarifying site restoration requirements. The utility fee allowance is set at $25,000, and the project will require a bid security of at least 5% of the bid amount. The township reserves the right to reject any or all bids and is subject to obtaining necessary legal, financial, and grant approvals before proceeding with the project. Bidders are required to have attended a mandatory pre-bid meeting and must submit various forms including a Statement of Qualification, Subcontractor Listing, Project Reference, and List of Suppliers.
View the file
Other files for this state and local contract opportunity
| File | Type | Posted |
|---|---|---|
| 0172-0048_Spec Complete_230926.pdf | ||
| 0172-0048_Const Plan_Bid Set_230926.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Addendum No. 1
AEW Project No. 0172-0048 Springfield Twp. Civic Center Standby Generator
October 20, 2023
ADDENDUM NO. 1
SPRINGFIELD TOWNSHIP
Civic Center Standby Generator
The following changes to and/or clarifications of the Contract Documents will be incorporated in said Contract Documents and such changes shall be allowed for in the price bid by the Contractor, such that the price indicated in the Proposal shall represent the conditions as set forth in the original Contract Documents as modified by this Addendum.
Acknowledgment of receipt of this Addendum and the Bidder’s Acceptance of these revised conditions prior to submittal of his bid shall be indicated by adding the Addendum number on the Bid Form.
The following additions, changes, and clarifications are made:
Bidder Inquiries and Responses:
1. Installation mentions grade mounted transfer switch, please confirm wall mounted is okay per walkthrough. Ref. TRANSFER SWITCHES 26 36 00 - 8, 3.1 INSTALLATION A. Grade-Mounted Switch: Anchor to base by bolting. Wall Mounting is also acceptable
2. Will a power outage and full system transfer be required during the return trip within the three months for the training session? Ref. 26 32 13 - 20, 3.6 Demonstration (C1 and C2) No
3. Does this have to be done at a specific time, or is any time to take the generator offline to do the full load test okay? Ref. 26 32 13 - 20, 3.5 FIELD QUALITY CONTROL (C1) Coordinate with the owner, but this can likely be done during normal business hours.
4. Does infrared scanning pertain to the whole job, transformer and the entire main service, or just the generator, transfer switch, and wiring and terminations the contractor installed for the installation. Ref. 26 32 13 - 20, 3.5 FIELD QUALITY CONTROL (L) New equipment only
5. Where will the generator annunciation panel be located? No generator annunciator is required
6. Will wiring and tie into the fire alarm panel be required? No
7. Will wiring and tie into building management system be required? No
8. Will (1) 1" spare conduit be required from generator pad to the emergency electrical room? Ref
E501, generator wiring connection detail. No, this requirement may be removed
9. If so, what room or location is the emergency electrical room? this requirement may be removed
10. Will the generator feeds be directional bored or trenched per detail? Ref E501 Directional boring is preferred to prevent damage to the new parking lot. We anticipate changing this in the addendum.
11. What are the blackout dates for the county? (elections, no work times) 2024 blackout dates are not finalized. Dates will be coordinated with the awarded contractor
12. Will the allowance for permits be deleted? Ref. 26 00 10 - 3, 1.5 codes, permits, and fees, (A) Township related fees will be waived. However, DTE and Consumer Energy fees will be included in the new pay item “Utility Fee Allowance”.
13. Does the existing electrical service switch (1200A) need to have its fuses removed and replaced with 600-amps? This section has been removed and replaced in the Addendum.
14. Is a contact switch in the transfer switch required for the elevators? A construction note has been added to provide a spare conduit between the transfer switch and electrical room for future connection by others.
i. If so, do we need to run wire and connect wire/ test in this contract? Not part of this contract.
15. Do we need to replace shrubbery that we removed for excavations? Contract states replacing any miscellaneous landscaping items encountered during the work. Ref. page 9 Plants and
Springfield Twp. Civic Center Standby Generator shrubbery do not need to be replaced. The Township will address plant replacement themselves.
16. Will a water source be provided, or will the contractor be required to provide the water source to establish growth? Contractor shall be required to provide water.
17. The new transfer switch doesn't show a disconnecting means integral to the unit or before the transfer switch on the one line. In the future, if service is required or a fault occurs, the only way to turn power off before the transfer switch will require the utility to shut down the transformer.
Will this be redrawn? This has been re-configured in the Addendum.
i. If a 600-amp main service switch is installed in the transfer switch, or before the transfer switch, the fire pump will not be connected directly to the transformer as previously drawn and installed. See response above.
ii. Will the new 600A transfer switch be required to have a fire pump-rated transfer device installed? See response above.
18. Will sheets 144 through 161 on document 0172-0048_Spec Complete_230926 be removed and not be required? They appear to not pertain to scope of work. Sheets 144 through 161 will remain.
19. Will contractors be required to work around the emergency police vehicles parked next to the generator construction site? We coordinate to have the vehicles moved away from the work site.
20. Can another area be designated for these vehicles as not to disturb construction and emergency operations? See response above.
21. Will DTE and Consumers fees be covered by the Township? As we discussed, this will put all bidders on a level playing field as it will be very difficult to obtain accurate costs prior to the bid. The “Reimbursed Permit Fee” pay item has been changed to “Utility Fee Allowance” to cover DTE and Consumers Energy costs including the new gas meter.
22. Will landscape restoration by the building be handled by the Township? Plants and shrubbery do not need to be replaced. The Township will address plant replacement themselves.
Contractor will be required to re-establish grade and any boulders.
23. Can spoils be graded and left on site? Assuming this question is regards to the concrete generator pad spoils. Some of the spoils will be used to regrade around the pad. Excess spoils will need to be removed and disposed by the contractor.
24. Will the generator pad be adjusted to avoid the existing as line? The generator pad has been shifted. See revised plan sheet C002.
25. Please confirm the amount of 1" conduits running from the generator to the building. See revised plan sheet E501.
Mandatory Pre-Bid Sign-In Sheet:
Pre-Bid Sign-In sheet is included within the Addendum.
Change: Bid Opening
1. The bid opening date and time has been changed to Friday, October 27, 2023 at 1:30p.m. Springfield Township will receive sealed bids at the offices of the Township Supervisor, Springfield, 12000 Davisburg Road, Davisburg, Michigan 48350, at which time and place all bids will be publicly opened and read aloud.
Specifications and Contract Documents
1. Advertisement has been revised to reflect new Bid Opening Date and Time
2. Bid Form Changes:
a. “Reimbursed Permit Fees” pay item to “Utility Fee Allowance”. This will
Springfield Twp. Civic Center Standby Generator cover fees required by DTE or Consumers Energy including the gas meter.
b. Added “Sidewalk, Rem” and “Sidewalk, Conc, 4 inch” pay items for removing and replacing the existing walk located near the gas meter.
3. The revised Bid Form document is included within for reference. Bidders must use the revised document when submitting their bids.
4. Special Provision “Site Restoration and Cleanup” has been revised to indicate plantings removed near the building as a result of the work will be replaced by the Owner. Also, the SP has revised to state, water will be provided by the contractor.
Construction Plans
1. See Sheet C002
a. Moved concrete generator pad
b. Added Sidewalk removal and replacement. Added related detail.
c. Added bituminous expansion joint between concrete pads.
2. See Sheet E003
a. Added construction note #1
b. Shifted the generator pad location due to underground utilities. Refer to civil plans for exact location.
3. See Sheet E501
a. Removed conduit burial and grounding detail.
b. Adjusted generator wiring connection detail.
c. Relocated generator ATS connection points
d. Removed requirement for a service entrance rated transfer switch.
e. Called for demolition of the 1200A Main Switch Section of the switchboard and installation of a new section from Siemens. See construction note 1
f. Added construction note 2 for a spare conduit between the transfer switch and electrical room.
Clarification: Pay Item “Audio Visual Record of Construction Area”
1. The intent of this pay item is to video the existing conditions of the work area and areas just outside of the construction influence.
END OF ADDENDUM NO. 1
ADDENDUM NO. 1 ISSUED OCTOBER 20, 2023
A.- 1
ADVERTISEMENT FOR BIDS
SPRINGFIELD TOWNSHIP CIVIC CENTER
STANDBY GENERATOR
AEW PROJECT NO. 0172-0048
RECEIPT OF BIDS
Springfield Township will receive sealed bids until 1:30p.m., local time on Friday, October 27, 2023, at the offices of the Township Supervisor, Springfield Township, 12000 Davisburg Road, Davisburg, Michigan 48350, at which time and place all bids will be publicly opened and read aloud.
DESCRIPTION OF WORK
The approximate quantities for the major items of work involved in this project are as follows:
Natural Gas Standby Generator, Complete 1 LSUM
PLANS AND SPECIFICATIONS
Plans and specifications must be obtained through BidNet, formerly the Michigan Intergovernmental Trade Network (MITN), at https://www.bidnetdirect.com, after 2:00p.m., Tuesday, September 26, 2023. Obtaining Bid Documents from any source not identified herein may result in failure to receive addenda, corrections, or other revisions that may be issued. Bids may be rejected unless made on the forms included with the bidding documents.
Please contact Michael D. Smith by email at msmith@aewinc.com for any bidder inquiries.
PRE-BID CONFERENCE
A mandatory pre-bid meeting will be held at the Springfield Township Civic Center, 12000 Davisburg Road, Davisburg, Michigan 48350 at 2:00p.m., on Tuesday, October 3, 2023.
Prospective bidders will check in at the Supervisor’s counter and be provided further instructions.
This is a mandatory meeting and no bids will be accepted from those bidders who do not attend.
BID SECURITY
A certified check, or the included Bid Bond, executed by the Bidder and a surety company, payable to Springfield Charter Township, in an amount at least equal to five
A.- 2 percent (5%) of the bid, shall be submitted with each bid.
WITHDRAWAL OF BIDS
No bid may be withdrawn for a period of sixty (60) calendar days after the receipt of bids.
AWARD OF CONTRACT
Springfield Charter Township reserves the right to reject any or all bids and/or to waive any irregularities in the bidding. The successful Bidder will be required to furnish satisfactory performance, payment, maintenance and guarantee bonds and insurance certificates.
BY: Joan Rusch, Planning Administrator/Supervisor’s Assistant Springfield Township 12000 Davisburg Road Davisburg, MI 48350
DATED: October, 2023
SPRINGFIELD TOWNSHIP
SPECIAL PROVISION
FOR
SITE RESTORATION AND CLEANUP
AEW:mds 1 of 2 0172-0048
a. Description. This work consists of final grading, project cleanup and restoring vegetative areas disturbed by this project and as designated by the Engineer by applying topsoil, fertilizer, seed, mulch to disturbed areas. All work shall be performed in accordance with Section 816 of the MDOT 2020 Standard Specifications for Construction, except as modified herein.
b. Materials. All materials used for the Surface Restoration shall meet the requirements of Section 917 of the MDOT 2020 Standard Specifications for Construction.
Materials included in Surface Restoration, Seeding are:
• Seed Mixture TUF (Turf Urban Freeway) (917.12)
• Fertilizer, Chemical Nutrient, Cl A (917.10.B.1)
• Topsoil Surface, Furn, 3 inch (917.07)
• Mulch and Mulch Anchoring (917.15) shall be used on flat slopes on this project.
• Mulch Blankets shall be used on steep slopes on this project. Mulch Blankets shall be Futerra F4 Netless or approved equal.
c. Construction. All restoration areas shall be prepared and compacted per Section 816 of the MDOT 2020 Standard Specifications for Construction. Place topsoil to the minimum depth indicated above to meet finish grade. If the area being restored requires more than the minimum depth of topsoil to meet the finish grade, this additional depth must be filled using topsoil, or at the Contractor’s option, suitable embankment material may be used. Furnishing, placing and compacting this additional material is included in this item of work.
All areas disturbed by the Contractor and/or his Subcontractor beyond the normal construction limits of this project shall be restored according to this special provision at the direction of the Engineer. No additional payment will be made for restoration beyond the normal construction limits.
d. Measurement and Payment.
Contract Item (Pay Item) Pay Unit
Site Restoration and Cleanup Lump Sum
AEW:mds 2 of 2 0172-0048
Delayed Acceptance. The Township will not pay for corrective action required for delayed acceptance, including removal and replacement of failed surface restoration.
The Township will delay final acceptance of completed surface restoration work until the surface restoration is fully established. During this time, the Township will inspect the surface restoration at its discretion. The Township will not accept surface restoration if less than 90% of the surface restoration area is well established, weed free, growing, vigorous, and contains the species required by the seeding mixture, and will require the Contractor to replace the defective areas.
Surface restoration work will be paid according to the following schedule:
Initial Placement 50% Final Acceptance 100%
The pay item Site Restoration and Cleanup shall include the necessary equipment, materials and labor to perform final grading, place the topsoil, fertilizer, seed, mulch, and/or mulch blankets. Watering will be required as necessary to establish growth and will not be paid for separately. Contractor will be required to provide water.
The pay item of work shall also include replacing any miscellaneous landscaping items such as rocks, boulders, pavers, etc. encountered during the work. Any plantings located near the building that are removed as a result of the work will be replaced by the Owner.
B.M.#1
CIVIC CENTER BUILDING
1'-0"
4'-0"
7' -0
19'-0"
#5 @ 12" O.C. TOP AND BOT
PAD SUPPORT PIER
6 REQUIRED (1'-0" DIA.)
ALL CONDUIT MAX.
HEIGHT ABOVE PAD 1 1/2"
BARS
1' -6
1'-6"
CONTROL JOINT, TYP
CONDUIT STUB-UP
AREA VERIFY WITH
GENERATOR
MANUFACTURER
EXISTING CONCRETE PAD
MATCH EXISTING GRADE
(INSTALL 1/2" FIBER EXPANSION
JOINT BETWEEN EXISTING AND
PROPOSED CONCRETE PADS)PROPOSED
GENERATOR PAD
GRADE BEYOND
SEE PLAN
1' -6
#5 @ 12" O.C. TOP
AND BOT
℄ PIER
1'-0" DIA. DRILLED PIER W / 4 - #4
VERTICAL BARS AND #3
CIRCULAR TIES @ 12" OC
(PROVIDE CASING AS REQUIRED)
4 - #4 DOWELS INTO
CONCRETE PAD
3' -0
3' -6
(M
IN
BENCH MARKS
(NAVD88 DATUM)
BENCH MARK NO. 1
"X" ON E. RIM OF CATCH
BASIN @ SPILLWAY ON THE
W. SIDE OF THE EAST
PARKING LOT
ELEVATION: 984.48
BENCH MARK NO. 2
MAG NAIL IN W. CONCRETE
LIGHT POLE BASE IN ISLAND
@ THE N.E. CORNER OF THE
E. PARKING LOT
ELEVATION: 988.37
BENCH MARK NO. 3
MAG NAIL IN E. CONCRETE
LIGHT POLE BASE @ S. END
OF LARGE ISLAND IN W.
PARKING LOT
ELEVATION: 985.02
BENCH MARK NO. 4
"X" ON S. SIDE OF BOTTOM
FLANGE OF GATE POST ON
THE NORTH SIDE OF THE
DRIVE TO THE BASIN
PRESERVE
ELEVATION: 993.33
BENCH MARK NO. 5
"□" ON N. SIDE CONCRETE
LIGHT POLE BASE @
DAVISBURG ELEMENTARY, S.
SIDE DAVISBURG RD., W.
SIDE OF THE STAFF AND BUS
PARKING LOT
ELEVATION: 1001.95
CIVIL SITE &
DETAILS PLAN
C002
ESR MDS JUNE 2023
1" = 20'
10 20 40
09-26-2023 BID ISSUE
10-20-2023 ADDENDUM NO. 1
0172-0048
CIVIC CENTER
STANDBY GENERATOR
SPRINGFIELD TOWNSHIP
SHEET TITLE:
COPYRIGHT, 2021, ANDERSON, ECKSTEIN AND WESTRICK, INC.
CHECKED BY:DRAWN BY:
SCALE:
PRELIMINARY
DATE SUBMITTALS/REVISIONS
PROJECT NO.
SHEET NO.
CLIENT:
PROJECT NAME:
CONSTRUCTION RECORD
DATE:
02_const--10/20/2023 8:47:57 AM
M:\0172\0172-0048\CIVIL\CAD\DRAWINGS\ENG\00_CONST PLANS.DWG
Know what's below.
72 hours before you dig.
Call R
Phone 586 726 1234 Fax 586 726 8780
51301 Schoenherr Road Shelby Township Michigan 48315
CIVIL ENGINEERS SURVEYORS ARCHITECTS
ENGINEERING STRONG COMMUNITIES
www.aewinc.com
ANDERSON, ECKSTEIN AND
WESTRICK, INC.
Peter Basso Associates Inc
NOTES:
1. SEE SIM-ESIG PAGES 3-6-9 & 3-6-10 FOR PAD AND GROUND ROD INSTALLATION DETAILS
AND 3-7-11 FOR MINIMUM CLEARANCES TO OBSTRUCTIONS.
2. CONCRETE MIX 6 BAGS PER YARD.
3. MINIMUM COMPRESSIVE STRENGTH 3500 PSI AT 28 DAYS.
4. SEE SPECIFICATIONS FOR ADDITIONAL GENERATOR REQUIREMENTS. COORDINATE
PAD SIZE WITH ACTUAL PURCHASED GENERATOR AND ACCEPTED OPTIONS BEFORE
POURING OF CONCRETE PAD.
COORDINATE PAD PLACEMENT
AND FACING DIRECTION WITH
GENERATOR MANUFACTURER
AND OWNER
CONCRETE GENERATOR PAD
SCALE 1" = 5'
PROPOSED 19'x7' CONCRETE
GENERATOR PAD. (SEE CONCRETE
PAD DETAIL THIS SHEET)
(SEE ELECTRICAL AND
MECHANICAL PLANS FOR
GENERATOR DETAILS)
CROSS SECTION A-A
SCALE 1" = 5'
SIDEWALK, REM AND
SIDEWALK, CONC, 4 INCH
INSTALL 2" WIDE BITUMINOUS
EXPANSION JOINT BETWEEN
SLABS (COST INCLUDED IN
CONCRETE GENERATOR PAD)
ADDENDUM NO. 1
ADDENDUM NO. 1
ADDENDUM NO. 1
4" NON REINFORCED CONCRETE
TYPICAL 4" CONCRETE
SIDEWALK SECTION
NOT TO SCALE
EXISTING SAND SUBGRADE OR NEW
CLASS II SAND (COMPACTED IN PLACE)
COMPACTED
SUBGRADE
before you dig.
Know what's below .
Call before you dig.
5145 Livernois, Suite 100
Fax: 248-879-0007 Troy, Michigan 48098-3276
Tel: 248-879-5666 www.PeterBassoAssociates.com
CONSULTING ENGINEERS
Peter Basso Associates Inc
PBA Project No.: 2023.0221
COPYRIGHT, 2023, ANDERSON, ECKSTEIN AND WESTRICK, INC.
SHEET TITLE:
CHECKED BY:DRAWN BY:
SCALE:
PRELIMINARY
DATE SUBMITTALS/REVISIONS
PROJECT NO.
SHEET NO.
CLIENT:
PROJECT NAME:
CONSTRUCTION RECORD
DATE:
0172-0048
SPRINGFIELD TOWNSHIP
09/22/2023
95% OWNER REVIEW08-16-2023
Know what's below.
72 hours before you dig.
Call R
FINAL PLAN SET09-06-2023
CIVIL ENGINEERS SURVEYORS ARCHITECTS
ENGINEERING STRONG COMMUNITIES
ANDERSON, ECKSTEIN AND
WESTRICK, INC.
Phone 586 726 1234 Fax 586 726 8780
51301 Schoenherr Road Shelby Township Michigan 48315 www.aewinc.com
Springfield Township Civic Center Standby
G:\2023\2023-0221-00\CAD\2023-0221-E0-SPN.dwg
Generator Installation
BID ISSUE09-26-2023
EMGQOT
ELECTRICAL NEW
WORK SITE PLAN
E003
1"=20'
ADDENDUM NO. 110-20-2023
AutoCAD SHX Text
2" DECIDUOUS 11
AutoCAD SHX Text 75017
AutoCAD SHX Text 980.22
AutoCAD SHX Text
2" DECIDUOUS 6
AutoCAD SHX Text 75028
AutoCAD SHX Text 984.34
AutoCAD SHX Text
2" DECIDUOUS 6
AutoCAD SHX Text 75029
AutoCAD SHX Text 984.49
AutoCAD SHX Text
2" DECIDUOUS 6
AutoCAD SHX Text 75030
AutoCAD SHX Text 984.55
AutoCAD SHX Text
2" DECIDUOUS 6
AutoCAD SHX Text 75031
AutoCAD SHX Text 985.52
AutoCAD SHX Text
2" DECIDUOUS 6
AutoCAD SHX Text 75032
AutoCAD SHX Text 985.88
AutoCAD SHX Text
2" DECIDUOUS 6
AutoCAD SHX Text 75033
AutoCAD SHX Text 984.13
AutoCAD SHX Text
2" DECIDUOUS 6
AutoCAD SHX Text 75035
AutoCAD SHX Text 983.22
AutoCAD SHX Text
2" DECIDUOUS 6
AutoCAD SHX Text 75036
AutoCAD SHX Text 982.45
AutoCAD SHX Text
2" DECIDUOUS 6
AutoCAD SHX Text 75048
AutoCAD SHX Text 986.57
AutoCAD SHX Text
2" DECIDUOUS 6
AutoCAD SHX Text 75050
AutoCAD SHX Text 985.32
AutoCAD SHX Text
11" DECIDUOUS
AutoCAD SHX Text 75129
AutoCAD SHX Text 975.68
AutoCAD SHX Text
8" DECIDUOUS
AutoCAD SHX Text 75132
AutoCAD SHX Text 975.82
AutoCAD SHX Text
8" DECIDUOUS
AutoCAD SHX Text 75138
AutoCAD SHX Text 976.38
AutoCAD SHX Text O505 2
AutoCAD SHX Text 75144
AutoCAD SHX Text 975.54
AutoCAD SHX Text
8" DECIDUOUS
AutoCAD SHX Text 75229
AutoCAD SHX Text 974.98
AutoCAD SHX Text
6" DECIDUOUS
AutoCAD SHX Text 75240
AutoCAD SHX Text 975.64
AutoCAD SHX Text
8" DECIDUOUS
AutoCAD SHX Text 75259
AutoCAD SHX Text 973.47
AutoCAD SHX Text
11" DECIDUOUS
AutoCAD SHX Text 75423
AutoCAD SHX Text 985.23
AutoCAD SHX Text
8" DECIDUOUS
AutoCAD SHX Text 75463
AutoCAD SHX Text 984.24
AutoCAD SHX Text
8" DECIDUOUS
AutoCAD SHX Text 75583
AutoCAD SHX Text 985.75
AutoCAD SHX Text
2" DECIDUOUS 8
AutoCAD SHX Text 75639
AutoCAD SHX Text 980.84
AutoCAD SHX Text
2" DECIDUOUS 8
AutoCAD SHX Text 75640
AutoCAD SHX Text 980.94
AutoCAD SHX Text
2" DECIDUOUS 12
AutoCAD SHX Text 75652
AutoCAD SHX Text 981.20
AutoCAD SHX Text
8" DECIDUOUS
AutoCAD SHX Text 75676
AutoCAD SHX Text 975.17
AutoCAD SHX Text
7" DECIDUOUS
AutoCAD SHX Text 80282
AutoCAD SHX Text 987.03
AutoCAD SHX Text
6" DECIDUOUS
AutoCAD SHX Text 80288
AutoCAD SHX Text 986.56
AutoCAD SHX Text
7" DECIDUOUS
AutoCAD SHX Text 80291
AutoCAD SHX Text 987.02
AutoCAD SHX Text
12" DECIDUOUS
AutoCAD SHX Text 80492
AutoCAD SHX Text 988.79
AutoCAD SHX Text
4" DECIDUOUS
AutoCAD SHX Text 80501
AutoCAD SHX Text 989.07
AutoCAD SHX Text
4" DECIDUOUS
AutoCAD SHX Text 80513
AutoCAD SHX Text 987.54
AutoCAD SHX Text
8" STUMP
AutoCAD SHX Text 80575
AutoCAD SHX Text 987.01
AutoCAD SHX Text
6" STUMP
AutoCAD SHX Text 80629
AutoCAD SHX Text 986.79
AutoCAD SHX Text
6" DECIDUOUS
AutoCAD SHX Text 80660
AutoCAD SHX Text 986.08
AutoCAD SHX Text
6" DECIDUOUS
AutoCAD SHX Text 80700
AutoCAD SHX Text 987.61
AutoCAD SHX Text
6" DECIDUOUS
AutoCAD SHX Text 80714
AutoCAD SHX Text 986.73
AutoCAD SHX Text
6" DECIDUOUS
AutoCAD SHX Text 80783
AutoCAD SHX Text 985.50
AutoCAD SHX Text
6" DECIDUOUS
AutoCAD SHX Text 80784
AutoCAD SHX Text 985.58
AutoCAD SHX Text
4" DECIDUOUS
AutoCAD SHX Text 80854
AutoCAD SHX Text 983.69
AutoCAD SHX Text
6" DECIDUOUS
AutoCAD SHX Text 80860
AutoCAD SHX Text 984.22
AutoCAD SHX Text
6" DECIDUOUS
AutoCAD SHX Text 80867
AutoCAD SHX Text 985.14
AutoCAD SHX Text 449 6
AutoCAD SHX Text
AutoCAD SHX Text
(E) UTILITY TRANSFORMER
AutoCAD SHX Text T
AutoCAD SHX Text
(E) PANEL F.P.
AutoCAD SHX Text GENERATOR POWER CONNECTIONS: RECEPTACLE, PANEL-FP-17 BATTERY CHARGER, PANEL-FP-17 COOLANT JACKET HEATER, PANEL-FP-12 OIL HEATER, PANEL-FP-12 BLOCK HEATER, PANEL-FP-14,16,18
AutoCAD SHX Text
NEW STANDBY GENERATOR
AutoCAD SHX Text
FIRE PUMP HOUSE
AutoCAD SHX Text
(E) GENERATORGENERATOR
AutoCAD SHX Text
GENERATOR EMERGENCY STOP
AutoCAD SHX Text
ATS
AutoCAD SHX Text
CT CABINET
AutoCAD SHX Text
(E) MAIN SWITCHBOARD
AutoCAD SHX Text
AutoCAD SHX Text
%%UCONSTRUCTION KEY NOTES:
AutoCAD SHX Text
AutoCAD SHX Text
1. UTILIZE DIRECTIONAL DRILLING FOR ALL CONDUITS UNDER PARKING LOT. THIS UTILIZE DIRECTIONAL DRILLING FOR ALL CONDUITS UNDER PARKING LOT. THIS METHOD CAN ALSO BE USED UNDER SIDEWALKS AND CONCRETE AREAS. NO DAMAGE/SAWCUTTING/PATCHING SHALL TAKE PLACE TO CONCRETE OR ASHPHALT AREA. REFER TO MDOT SECTION 818 (ELECTRICAL) FOR DIRECTION DRILLING
AutoCAD SHX Text
%%USITE PLAN GENERAL NOTES:
AutoCAD SHX Text
1. THESE NOTES ARE GENERIC GUIDELINES ONLY. ELECTRICAL CONTRACTOR'S THESE NOTES ARE GENERIC GUIDELINES ONLY. ELECTRICAL CONTRACTOR'S PERSONNEL ON SITE SHALL BE THOROUGHLY FAMILIAR WITH THE PUBLISHED SPECIFICATIONS FOR EXACT DESCRIPTIONS OF SCOPE, METHODS, AND MATERIAL. 2. THESE DRAWINGS REPRESENT THE GENERAL EXTENT AND ARRANGEMENT OF THESE DRAWINGS REPRESENT THE GENERAL EXTENT AND ARRANGEMENT OF SYSTEMS. COORDINATE EXACT EQUIPMENT LOCATIONS, ELEVATIONS, AND FINAL CONNECTION REQUIREMENTS. PROVIDE EACH SYSTEM COMPLETE, INCLUDING ALL NECESSARY COMPONENTS, FITTINGS AND OFFSETS. 3. CONDUCT A SURVEY TO IDENTIFY ALL UNDERGROUND UTILITIES. CALL 811 PRIOR TO CONDUCT A SURVEY TO IDENTIFY ALL UNDERGROUND UTILITIES. CALL 811 PRIOR TO EXCAVATION. 4. UTILITIES SHOWN ON THESE DRAWINGS ARE FOR REFERENCE ONLY. COORDINATE UTILITIES SHOWN ON THESE DRAWINGS ARE FOR REFERENCE ONLY. COORDINATE EXACT LOCATION OF ALL EXISTING UTILITIES, AND ROUTING OF ALL NEW UNDERGROUND UTILITIES PRIOR TO EXCAVATION. 5. DEWATER TRENCHES PRIOR TO INSTALLATION OF CONDUITS. PROVIDE WATER TIGHT DEWATER TRENCHES PRIOR TO INSTALLATION OF CONDUITS. PROVIDE WATER TIGHT FITTINGS ON ALL UNDERGROUND CONDUITS. 6. COORDINATE DEMOLITION WORK, AND ELECTRICAL AND TELEPHONE SERVICES TO THE COORDINATE DEMOLITION WORK, AND ELECTRICAL AND TELEPHONE SERVICES TO THE SITE, WITH THE RESPECTIVE LOCAL UTILITY COMPANY REPRESENTATIVES PRIOR TO COMMENCEMENT OF WORK. INCLUDE ALL ASSOCIATED COST/FEES BY THE UTILITY COMPANIES IN THE BID PRICE. 7. INSTALL UNDERGROUND CONDUITS 42" BELOW FINISHED GRADE, MINIMUM, UNLESS INSTALL UNDERGROUND CONDUITS 42" BELOW FINISHED GRADE, MINIMUM, UNLESS NOTED OTHERWISE. 8. COORDINATE SERVICE SHUT-DOWNS WITH ALL TRADES INVOLVED ON SITE AND COORDINATE SERVICE SHUT-DOWNS WITH ALL TRADES INVOLVED ON SITE AND OBTAIN WRITTEN AUTHORIZATION FROM OWNER 72 HOURS PRIOR TO ANY ELECTRICAL AND/OR TELEPHONE SHUT-DOWN. 9. REMOVE ALL DE-ENERGIZED CONDUCTORS FROM SITE AT COMPLETION OF THE REMOVE ALL DE-ENERGIZED CONDUCTORS FROM SITE AT COMPLETION OF THE PROJECT. 10. OUTDOOR LIGHTING BRANCH CIRCUIT WIRING SHALL BE MINIMUM #8 AWG OUTDOOR LIGHTING BRANCH CIRCUIT WIRING SHALL BE MINIMUM #8 AWG CONDUCTORS (XHHW-2), IN MINIMUM 1" DIA. CONDUIT, UNLESS NOTED OTHERWISE. 11. SPARE CONDUITS SHALL INCLUDE PULL STRING AND SHALL BE TERMINATED WITH A SPARE CONDUITS SHALL INCLUDE PULL STRING AND SHALL BE TERMINATED WITH A CAP. 12. EXCAVATE THE ENTIRE LENGTH OF TRENCH TO PROPERLY SET DUCT ELEVATIONS.EXCAVATE THE ENTIRE LENGTH OF TRENCH TO PROPERLY SET DUCT ELEVATIONS.
AutoCAD SHX Text R
AutoCAD SHX Text G:\2023\2023-0221-00\CAD\2023-0221-E0-SPN.dwg, E003, 10/20/2023 7:58:13 AM, Eric M. Graettinger, Peter Basso Associates Inc., E003, 10/20/2023 7:58:13 AM, Eric M. Graettinger, Peter Basso Associates Inc.E003, 10/20/2023 7:58:13 AM, Eric M. Graettinger, Peter Basso Associates Inc., 10/20/2023 7:58:13 AM, Eric M. Graettinger, Peter Basso Associates Inc.10/20/2023 7:58:13 AM, Eric M. Graettinger, Peter Basso Associates Inc., Eric M. Graettinger, Peter Basso Associates Inc.Eric M. Graettinger, Peter Basso Associates Inc., Peter Basso Associates Inc.
AutoCAD SHX Text
THE FOLLOWING DIMENSION EQUALS ONE INCH WHEN PRINTED TO SCALE.
AutoCAD SHX Text 1"
AutoCAD SHX Text UTILITY INFORMATION, AS SHOWN, INDICATES APPROXIMATE INFORMATION, AS SHOWN, INDICATES APPROXIMATE INFORMATION, AS SHOWN, INDICATES APPROXIMATE AS SHOWN, INDICATES APPROXIMATE AS SHOWN, INDICATES APPROXIMATE SHOWN, INDICATES APPROXIMATE SHOWN, INDICATES APPROXIMATE INDICATES APPROXIMATE INDICATES APPROXIMATE APPROXIMATE APPROXIMATE LOCATIONS AND TYPES OF EXISTING FACILITIES ONLY, AS AND TYPES OF EXISTING FACILITIES ONLY, AS AND TYPES OF EXISTING FACILITIES ONLY, AS TYPES OF EXISTING FACILITIES ONLY, AS TYPES OF EXISTING FACILITIES ONLY, AS OF EXISTING FACILITIES ONLY, AS OF EXISTING FACILITIES ONLY, AS EXISTING FACILITIES ONLY, AS EXISTING FACILITIES ONLY, AS FACILITIES ONLY, AS FACILITIES ONLY, AS ONLY, AS ONLY, AS AS AS DISCLOSED BY RECORDS PROVIDED TO THIS FIRM FROM BY RECORDS PROVIDED TO THIS FIRM FROM BY RECORDS PROVIDED TO THIS FIRM FROM RECORDS PROVIDED TO THIS FIRM FROM RECORDS PROVIDED TO THIS FIRM FROM PROVIDED TO THIS FIRM FROM PROVIDED TO THIS FIRM FROM TO THIS FIRM FROM TO THIS FIRM FROM THIS FIRM FROM THIS FIRM FROM FIRM FROM FIRM FROM FROM FROM THE VARIOUS UTILITY COMPANIES. NO GUARANTEE IS VARIOUS UTILITY COMPANIES. NO GUARANTEE IS VARIOUS UTILITY COMPANIES. NO GUARANTEE IS UTILITY COMPANIES. NO GUARANTEE IS UTILITY COMPANIES. NO GUARANTEE IS COMPANIES. NO GUARANTEE IS COMPANIES. NO GUARANTEE IS NO GUARANTEE IS NO GUARANTEE IS NO GUARANTEE IS GUARANTEE IS GUARANTEE IS IS IS GIVEN OR IMPLIED AS TO THE COMPLETENESS OR OR IMPLIED AS TO THE COMPLETENESS OR OR IMPLIED AS TO THE COMPLETENESS OR IMPLIED AS TO THE COMPLETENESS OR IMPLIED AS TO THE COMPLETENESS OR AS TO THE COMPLETENESS OR AS TO THE COMPLETENESS OR TO THE COMPLETENESS OR TO THE COMPLETENESS OR THE COMPLETENESS OR THE COMPLETENESS OR COMPLETENESS OR COMPLETENESS OR OR OR ACCURACY THEREOF. PRIOR TO CONSTRUCTION, ALL LOCATIONS AND DEPTHS OF TO CONSTRUCTION, ALL LOCATIONS AND DEPTHS OF TO CONSTRUCTION, ALL LOCATIONS AND DEPTHS OF CONSTRUCTION, ALL LOCATIONS AND DEPTHS OF CONSTRUCTION, ALL LOCATIONS AND DEPTHS OF ALL LOCATIONS AND DEPTHS OF ALL LOCATIONS AND DEPTHS OF LOCATIONS AND DEPTHS OF LOCATIONS AND DEPTHS OF AND DEPTHS OF AND DEPTHS OF DEPTHS OF DEPTHS OF OF OF EXISTING OVERHEAD AND UNDERGROUND UTILITIES (IN OVERHEAD AND UNDERGROUND UTILITIES (IN OVERHEAD AND UNDERGROUND UTILITIES (IN AND UNDERGROUND UTILITIES (IN AND UNDERGROUND UTILITIES (IN UNDERGROUND UTILITIES (IN UNDERGROUND UTILITIES (IN UTILITIES (IN UTILITIES (IN (IN (IN (IN CONFLICT WITH THE CONSTRUCTION OF THESE PROPOSED WITH THE CONSTRUCTION OF THESE PROPOSED WITH THE CONSTRUCTION OF THESE PROPOSED THE CONSTRUCTION OF THESE PROPOSED THE CONSTRUCTION OF THESE PROPOSED CONSTRUCTION OF THESE PROPOSED CONSTRUCTION OF THESE PROPOSED OF THESE PROPOSED OF THESE PROPOSED THESE PROPOSED THESE PROPOSED PROPOSED PROPOSED IMPROVEMENTS) SHALL BE VERIFIED IN THE FIELD. DURING SHALL BE VERIFIED IN THE FIELD. DURING SHALL BE VERIFIED IN THE FIELD. DURING BE VERIFIED IN THE FIELD. DURING BE VERIFIED IN THE FIELD. DURING VERIFIED IN THE FIELD. DURING VERIFIED IN THE FIELD. DURING IN THE FIELD. DURING IN THE FIELD. DURING THE FIELD. DURING THE FIELD. DURING FIELD. DURING FIELD. DURING DURING DURING THE CONSTRUCTION, THE CONTRACTOR SHALL PROTECT CONSTRUCTION, THE CONTRACTOR SHALL PROTECT CONSTRUCTION, THE CONTRACTOR SHALL PROTECT THE CONTRACTOR SHALL PROTECT THE CONTRACTOR SHALL PROTECT CONTRACTOR SHALL PROTECT CONTRACTOR SHALL PROTECT SHALL PROTECT SHALL PROTECT PROTECT PROTECT AND SUPPORT ALL UTILITIES THAT ARE ENCOUNTERED. SUPPORT ALL UTILITIES THAT ARE ENCOUNTERED. SUPPORT ALL UTILITIES THAT ARE ENCOUNTERED. ALL UTILITIES THAT ARE ENCOUNTERED. ALL UTILITIES THAT ARE ENCOUNTERED. UTILITIES THAT ARE ENCOUNTERED. UTILITIES THAT ARE ENCOUNTERED. THAT ARE ENCOUNTERED. THAT ARE ENCOUNTERED. ARE ENCOUNTERED. ARE ENCOUNTERED. ENCOUNTERED. ENCOUNTERED. (ALL COSTS FOR UTILITY LOCATION VERIFICATION, SUPPORT COSTS FOR UTILITY LOCATION VERIFICATION, SUPPORT COSTS FOR UTILITY LOCATION VERIFICATION, SUPPORT FOR UTILITY LOCATION VERIFICATION, SUPPORT FOR UTILITY LOCATION VERIFICATION, SUPPORT UTILITY LOCATION VERIFICATION, SUPPORT UTILITY LOCATION VERIFICATION, SUPPORT LOCATION VERIFICATION, SUPPORT LOCATION VERIFICATION, SUPPORT VERIFICATION, SUPPORT VERIFICATION, SUPPORT SUPPORT SUPPORT AND PROTECTION SHALL BE INCLUDED IN THE PROPOSED PROTECTION SHALL BE INCLUDED IN THE PROPOSED PROTECTION SHALL BE INCLUDED IN THE PROPOSED SHALL BE INCLUDED IN THE PROPOSED SHALL BE INCLUDED IN THE PROPOSED BE INCLUDED IN THE PROPOSED BE INCLUDED IN THE PROPOSED INCLUDED IN THE PROPOSED INCLUDED IN THE PROPOSED IN THE PROPOSED IN THE PROPOSED THE PROPOSED THE PROPOSED PROPOSED PROPOSED PAY ITEM CONFLICTING WITH THAT UTILITY). DURING CONSTRUCTION, THE CONTRACTOR SHALL USE CONSTRUCTION, THE CONTRACTOR SHALL USE CONSTRUCTION, THE CONTRACTOR SHALL USE THE CONTRACTOR SHALL USE THE CONTRACTOR SHALL USE CONTRACTOR SHALL USE CONTRACTOR SHALL USE SHALL USE SHALL USE USE USE EXTREME CAUTION WHEN OPERATING NEAR ANY AND ALL CAUTION WHEN OPERATING NEAR ANY AND ALL CAUTION WHEN OPERATING NEAR ANY AND ALL WHEN OPERATING NEAR ANY AND ALL WHEN OPERATING NEAR ANY AND ALL OPERATING NEAR ANY AND ALL OPERATING NEAR ANY AND ALL NEAR ANY AND ALL NEAR ANY AND ALL ANY AND ALL ANY AND ALL AND ALL AND ALL ALL ALL OVERHEAD AND / OR BURIED UTILITIES.
AutoCAD SHX Text
SCALE: 1" = 20'
AutoCAD SHX Text
%%UELECTRICAL NEW WORK SITE PLAN
5145 Livernois, Suite 100
Fax: 248-879-0007 Troy, Michigan 48098-3276
Tel: 248-879-5666 www.PeterBassoAssociates.com
CONSULTING ENGINEERS
Peter Basso Associates Inc
PBA Project No.: 2023.0221
COPYRIGHT, 2023, ANDERSON, ECKSTEIN AND WESTRICK, INC.
SHEET TITLE:
CHECKED BY:DRAWN BY:
SCALE:
PRELIMINARY
DATE SUBMITTALS/REVISIONS
PROJECT NO.
SHEET NO.
CLIENT:
PROJECT NAME:
CONSTRUCTION RECORD
DATE:
0172-0048
SPRINGFIELD TOWNSHIP
09/22/2023
95% OWNER REVIEW08-16-2023
Know what's below.
72 hours before you dig.
Call R
FINAL PLAN SET09-06-2023
CIVIL ENGINEERS SURVEYORS ARCHITECTS
ENGINEERING STRONG COMMUNITIES
ANDERSON, ECKSTEIN AND
WESTRICK, INC.
Phone 586 726 1234 Fax 586 726 8780
51301 Schoenherr Road Shelby Township Michigan 48315 www.aewinc.com
Springfield Township Civic Center Standby
G:\2023\2023-0221-00\CAD\2023-0221-E5-DG.dwg
Generator Installation
BID ISSUE09-26-2023
EMGQOT
ONE LINE DIAGRAM
AND ELECTRICAL
DETAILS
E501
NONE
ADDENDUM NO. 110-20-2023
AutoCAD SHX Text
%%UCONSTRUCTION KEY NOTES:
AutoCAD SHX Text
AutoCAD SHX Text
1. REMOVE EXISTING MAIN METERING SECTION, INCLUDING 1200A MAIN BPS, GROUND REMOVE EXISTING MAIN METERING SECTION, INCLUDING 1200A MAIN BPS, GROUND FAULT, AND ANALOG METERS. REPLACE ENTIRE SWITCHBOARD SECTION WITH A NEW SIEMENS SB2 SWITCHBOARD SECTION OF SAME DIMENSIONS TO INCLUDE A 600A MAIN CIRCUIT BREAKER, ADDITIONAL SET OF LUGS AFTER THE MAIN FOR LANDING TRANSFER SWITCH NORMAL FEED, AND A SET OF LUGS FOR LANDING THE TRANSFER SWITCH OUTPUT TO THE DISTRIBUTION SECTION. INCLUDE HORIZONTAL BUSSING TO EXISTING SECTIONS. CONTACT BRIAN MCVEIGH AT SIEMENS. BRIAN.MCVEIGH@SIEMENS.COM OR 734 502-5150. 2. INCLUDE (1) SPARE 3/4" CONDUIT BETWEEN TRANSFER SWITCH AND STUBBED INTO INCLUDE (1) SPARE 3/4" CONDUIT BETWEEN TRANSFER SWITCH AND STUBBED INTO THE 1ST FLOOR ELECTRICAL ROOM CEILING WITH PULLSTRING FOR FUTURE USE
AutoCAD SHX Text
%%UDIAGRAM GENERAL NOTES:
AutoCAD SHX Text
1. THESE DRAWINGS REPRESENT THE GENERAL EXTENT AND ARRANGEMENT OF THESE DRAWINGS REPRESENT THE GENERAL EXTENT AND ARRANGEMENT OF SYSTEMS. COORDINATE EXACT EQUIPMENT LOCATIONS, ELEVATIONS, AND FINAL CONNECTION REQUIREMENTS. PROVIDE EACH SYSTEM COMPLETE, INCLUDING ALL NECESSARY COMPONENTS, FITTINGS AND OFFSETS. 2. FEEDER AND BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED IN ACCORDANCE WITH FEEDER AND BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED IN ACCORDANCE WITH THE "FEEDER AND BRANCH CIRCUIT SIZING SCHEDULE-GENERAL PURPOSE" ON THE "ELECTRICAL STANDARD SCHEDULES DRAWING" UNLESS SPECIFICALLY NOTED OTHERWISE. 3. BASIS OF DESIGN IS ASCO TRANSFER SWITCHES. IF THE CONTRACTOR ELECTS TO BASIS OF DESIGN IS ASCO TRANSFER SWITCHES. IF THE CONTRACTOR ELECTS TO PROVIDE EQUIPMENT FROM OTHER APPROVED MANUFACTURERS, THE CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE THE LAYOUT AND CLEARANCE REQUIREMENTS IN ALL SPACES CONTAINING ELECTRICAL EQUIPMENT AND PROVIDE EQUIPMENT MEETING THE SPECIFICATIONS AND ACHIEVING CODE REQUIRED CLEARANCES WITHIN THE SPACE PROVIDED.
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
DP-1 208Y/120V 3%%C, 4W, 1200A
AutoCAD SHX Text 30A 3P
AutoCAD SHX Text 30A 3P
AutoCAD SHX Text 60A 3P
AutoCAD SHX Text 60A 3P
AutoCAD SHX Text 100A 3P
AutoCAD SHX Text 100A 3P
AutoCAD SHX Text 200A 3P
AutoCAD SHX Text 600A 3P
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
MAIN SWITCHBOARD 480Y/277V 3%%C, 4W, 1200A
AutoCAD SHX Text 30A 3P
AutoCAD SHX Text 60A 3P
AutoCAD SHX Text 60A 3P
AutoCAD SHX Text 100A 3P
AutoCAD SHX Text 200A 3P
AutoCAD SHX Text 400A 3P
AutoCAD SHX Text 200A 3P
AutoCAD SHX Text 200A 3P
AutoCAD SHX Text 400A 3P
AutoCAD SHX Text 1200A 3P
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
FIRE PUMP CONTROLLER
AutoCAD SHX Text
FIRE PUMP 25HP
AutoCAD SHX Text G
AutoCAD SHX Text 85kW/106.2kVA 480Y/277V 3PH
AutoCAD SHX Text M
AutoCAD SHX Text
EXISTING DTE TRANSFORMER 300KVA 13.2 - 480Y/277V X.XX%Z
AutoCAD SHX Text
METERING SECTION
AutoCAD SHX Text
MAIN SERVICE DISCONNECT
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
HUMIDIFIER
AutoCAD SHX Text
HVU
AutoCAD SHX Text
ELEVATOR
AutoCAD SHX Text
RTU-1
AutoCAD SHX Text
SEPTIC LIFT STATION
AutoCAD SHX Text
PANEL LP-1 250A MLO 208Y/120V 3 ,4W
AutoCAD SHX Text
PANEL LP-2
AutoCAD SHX Text
PHASE MONITOR
AutoCAD SHX Text 150kVA 480Y- 208Y/120V 3 5.6%Z IMP
AutoCAD SHX Text
PANEL 1B
AutoCAD SHX Text
PANEL 2B
AutoCAD SHX Text
PANEL 1A 250A MLO 208Y/120V 3 ,4W
AutoCAD SHX Text
PANEL 2A
AutoCAD SHX Text
PANEL F.P. 60A MCB 208Y/120V 3 ,4W
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
ECUH-1
AutoCAD SHX Text
ECUH-2
AutoCAD SHX Text
SUMP PUMP
AutoCAD SHX Text 200A 3P
AutoCAD SHX Text 200A 3P
AutoCAD SHX Text 200A 3P
AutoCAD SHX Text
CB
AutoCAD SHX Text
FIRE PUMP CONTROLLER TRANSFER SWITCH
AutoCAD SHX Text
PANEL 1A1 125A MLO 208Y/120V 3 ,4W
AutoCAD SHX Text
PANEL F.P. TRANSFER SWITCH
AutoCAD SHX Text
WELL PUMP CONTROL TRANSFER SWITCH
AutoCAD SHX Text
WELL PUMP
AutoCAD SHX Text
30A 30AF
AutoCAD SHX Text G
AutoCAD SHX Text GENERAC SG250 14.2L NATURAL GAS STANDBY POWER GENERATOR 250kW/313kVA 60Hz 480Y/277V 3 @ 0.8pf376A
AutoCAD SHX Text
ASCO SERIES 300 ATS, NEMA 3R. 480Y/277V 3 , 4W65,000 AIC
AutoCAD SHX Text
500A OUTPUT BREAKER
AutoCAD SHX Text 100A 3P
AutoCAD SHX Text 100A 3P
AutoCAD SHX Text 200A 3P
AutoCAD SHX Text
STANDBY GENERATOR - NATURAL GAS
AutoCAD SHX Text J
AutoCAD SHX Text
SPARE
AutoCAD SHX Text 400A 3P
AutoCAD SHX Text
3 SETS OF 4#600 KCMIL - 4"PVC 1-4" PVC SPARE
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
%%UONE LINE DIAGRAM
AutoCAD SHX Text
3 POLE OUTPUT BREAKER SERVING
AutoCAD SHX Text
GENERATOR CONTROL PANEL
AutoCAD SHX Text COOLANT JACKET HEATER, 1500W MINIMUM, 120V-1 , , VERIFY EXACT SIZE AND WIRING REQUIREMENTS WITH MANUFACTURER
AutoCAD SHX Text
FEEDER REFER TO ONE-LINE DIAGRAM FOR SIZE
AutoCAD SHX Text BLOCK HEATER, 6000W BASIS OF DESIGN, 208V-3 , , VERIFY EXACT SIZE AND WIRING REQUIREMENTS WITH MANUFACTURER
AutoCAD SHX Text
BATTERY CHARGER
AutoCAD SHX Text
1"C SPARE TO MAIN ELECTRICAL ROOM
AutoCAD SHX Text
1"C WITH 4#12 AND 2#16 SHIELDED TWISTED PAIR CABLE TO ATS
AutoCAD SHX Text NOTES: 1. VERIFY ALL WIRING WITH SELECTED GENERATOR MANUFACTURERS DRAWINGS AND WIRING DIAGRAMSVERIFY ALL WIRING WITH SELECTED GENERATOR MANUFACTURERS DRAWINGS AND WIRING DIAGRAMS
AutoCAD SHX Text
GENERATOR WIRING CONNECTION DETAIL NO SCALE
AutoCAD SHX Text
EXISTING PANEL F.P.
AutoCAD SHX Text
AutoCAD SHX Text
LOAD TYPE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
CB TYPE
AutoCAD SHX Text
CB
AutoCAD SHX Text
VA
AutoCAD SHX Text
ØA
AutoCAD SHX Text
ØB
AutoCAD SHX Text
ØC
AutoCAD SHX Text
VA
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB TYPE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
LOAD TYPE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text L
AutoCAD SHX Text
EXISTING LOAD
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING LOAD
AutoCAD SHX Text
NC
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NC
AutoCAD SHX Text
EXISTING LOAD
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NC
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NC
AutoCAD SHX Text
EXISTING LOAD
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NC
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NC
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING LOAD
AutoCAD SHX Text
NC
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NC
AutoCAD SHX Text
EXISTING LOAD
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING LOAD
AutoCAD SHX Text
NC
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NC
AutoCAD SHX Text
EXISTING LOAD
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NEW
AutoCAD SHX Text
GENERATOR - COOLANT JACKET HEATER
AutoCAD SHX Text
NC
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NC
AutoCAD SHX Text
EXISTING LOAD
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NEW
AutoCAD SHX Text
GENERATOR - BLOCK HEATER
AutoCAD SHX Text
NC
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NC
AutoCAD SHX Text
EXISTING LOAD
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NEW
AutoCAD SHX Text
NC
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NC
AutoCAD SHX Text
GENERATOR - RECEPT AND CHARGER
AutoCAD SHX Text
NEW
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NEW
AutoCAD SHX Text
NC
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ØA
AutoCAD SHX Text
ØB
AutoCAD SHX Text
ØC
AutoCAD SHX Text
FEEDER AND OVERCURRENT SIZING
AutoCAD SHX Text
PANELBOARD INFORMATION
AutoCAD SHX Text
DEMAND FACTOR
AutoCAD SHX Text
CALCULATED LOAD
AutoCAD SHX Text
VOLTAGE:
AutoCAD SHX Text 240/120
AutoCAD SHX Text
BRANCH CIRCUIT CONNECTED LOAD
AutoCAD SHX Text
NOTES:
AutoCAD SHX Text
BUS AMPACITY:
AutoCAD SHX Text 225A
AutoCAD SHX Text
CONTINUOUS LOAD (C)
AutoCAD SHX Text 100%
AutoCAD SHX Text 125%
AutoCAD SHX Text
MAIN TYPE:
AutoCAD SHX Text
60A MCB
AutoCAD SHX Text
ELECTRIC HEAT (E)
AutoCAD SHX Text 100%
AutoCAD SHX Text 100%
AutoCAD SHX Text
MINIMUM A.I.C.:
AutoCAD SHX Text
NON-CONTINUOUS LOAD (NC)
AutoCAD SHX Text 16710
AutoCAD SHX Text 100%
AutoCAD SHX Text 16710
AutoCAD SHX Text 100%
AutoCAD SHX Text 16710
AutoCAD SHX Text
MOUNTING:
AutoCAD SHX Text
SURFACE
AutoCAD SHX Text
KITCHEN LOAD (K)
AutoCAD SHX Text 100%
AutoCAD SHX Text 100%
AutoCAD SHX Text
RECEPTACLE BASE LOAD (R)
AutoCAD SHX Text 100%
AutoCAD SHX Text 100%
AutoCAD SHX Text
FEED-THROUGH LUGS
AutoCAD SHX Text
RECEPTACLE DEMAND LOAD (R)
AutoCAD SHX Text 50%
AutoCAD SHX Text 100%
AutoCAD SHX Text
DOUBLE LUGS
AutoCAD SHX Text
LIGHTING LOAD (L)
AutoCAD SHX Text
AutoCAD SHX Text 100%
AutoCAD SHX Text
AutoCAD SHX Text 125%
AutoCAD SHX Text
AutoCAD SHX Text
INTEGRAL SPD
AutoCAD SHX Text
ADDITIONAL TRACK LIGHTING LOAD
AutoCAD SHX Text 100%
AutoCAD SHX Text
MOTORS, HIGHEST LOAD (MH)
AutoCAD SHX Text 125%
AutoCAD SHX Text 100%
AutoCAD SHX Text
PANELBOARD LOCATION
AutoCAD SHX Text
MOTORS, REMAINING LOAD (M)
AutoCAD SHX Text 100%
AutoCAD SHX Text 100%
AutoCAD SHX Text
NOTE: DEMAND AND SIZING INFORMATION IS CALCULATED FROM CONNECTED LOAD
AutoCAD SHX Text
TOTAL(KVA):
AutoCAD SHX Text 17.21
AutoCAD SHX Text
TOTAL (AMPS):
AutoCAD SHX Text
AutoCAD SHX Text
TOTAL (AMPS):
AutoCAD SHX Text
AutoCAD SHX Text Copyright 2021 by Peter Basso Associates, Inc
AutoCAD SHX Text
FIRE PUMP SWITCH
AutoCAD SHX Text 600A 3P
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text G:\2023\2023-0221-00\CAD\2023-0221-E5-DG.dwg, E501, 10/20/2023 7:58:20 AM, Eric M. Graettinger, Peter Basso Associates Inc., E501, 10/20/2023 7:58:20 AM, Eric M. Graettinger, Peter Basso Associates Inc.E501, 10/20/2023 7:58:20 AM, Eric M. Graettinger, Peter Basso Associates Inc., 10/20/2023 7:58:20 AM, Eric M. Graettinger, Peter Basso Associates Inc.10/20/2023 7:58:20 AM, Eric M. Graettinger, Peter Basso Associates Inc., Eric M. Graettinger, Peter Basso Associates Inc.Eric M. Graettinger, Peter Basso Associates Inc., Peter Basso Associates Inc.
AutoCAD SHX Text UTILITY INFORMATION, AS SHOWN, INDICATES APPROXIMATE INFORMATION, AS SHOWN, INDICATES APPROXIMATE INFORMATION, AS SHOWN, INDICATES APPROXIMATE AS SHOWN, INDICATES APPROXIMATE AS SHOWN, INDICATES APPROXIMATE SHOWN, INDICATES APPROXIMATE SHOWN, INDICATES APPROXIMATE INDICATES APPROXIMATE INDICATES APPROXIMATE APPROXIMATE APPROXIMATE LOCATIONS AND TYPES OF EXISTING FACILITIES ONLY, AS AND TYPES OF EXISTING FACILITIES ONLY, AS AND TYPES OF EXISTING FACILITIES ONLY, AS TYPES OF EXISTING FACILITIES ONLY, AS TYPES OF EXISTING FACILITIES ONLY, AS OF EXISTING FACILITIES ONLY, AS OF EXISTING FACILITIES ONLY, AS EXISTING FACILITIES ONLY, AS EXISTING FACILITIES ONLY, AS FACILITIES ONLY, AS FACILITIES ONLY, AS ONLY, AS ONLY, AS AS AS DISCLOSED BY RECORDS PROVIDED TO THIS FIRM FROM BY RECORDS PROVIDED TO THIS FIRM FROM BY RECORDS PROVIDED TO THIS FIRM FROM RECORDS PROVIDED TO THIS FIRM FROM RECORDS PROVIDED TO THIS FIRM FROM PROVIDED TO THIS FIRM FROM PROVIDED TO THIS FIRM FROM TO THIS FIRM FROM TO THIS FIRM FROM THIS FIRM FROM THIS FIRM FROM FIRM FROM FIRM FROM FROM FROM THE VARIOUS UTILITY COMPANIES. NO GUARANTEE IS VARIOUS UTILITY COMPANIES. NO GUARANTEE IS VARIOUS UTILITY COMPANIES. NO GUARANTEE IS UTILITY COMPANIES. NO GUARANTEE IS UTILITY COMPANIES. NO GUARANTEE IS COMPANIES. NO GUARANTEE IS COMPANIES. NO GUARANTEE IS NO GUARANTEE IS NO GUARANTEE IS NO GUARANTEE IS GUARANTEE IS GUARANTEE IS IS IS GIVEN OR IMPLIED AS TO THE COMPLETENESS OR OR IMPLIED AS TO THE COMPLETENESS OR OR IMPLIED AS TO THE COMPLETENESS OR IMPLIED AS TO THE COMPLETENESS OR IMPLIED AS TO THE COMPLETENESS OR AS TO THE COMPLETENESS OR AS TO THE COMPLETENESS OR TO THE COMPLETENESS OR TO THE COMPLETENESS OR THE COMPLETENESS OR THE COMPLETENESS OR COMPLETENESS OR COMPLETENESS OR OR OR ACCURACY THEREOF. PRIOR TO CONSTRUCTION, ALL LOCATIONS AND DEPTHS OF TO CONSTRUCTION, ALL LOCATIONS AND DEPTHS OF TO CONSTRUCTION, ALL LOCATIONS AND DEPTHS OF CONSTRUCTION, ALL LOCATIONS AND DEPTHS OF CONSTRUCTION, ALL LOCATIONS AND DEPTHS OF ALL LOCATIONS AND DEPTHS OF ALL LOCATIONS AND DEPTHS OF LOCATIONS AND DEPTHS OF LOCATIONS AND DEPTHS OF AND DEPTHS OF AND DEPTHS OF DEPTHS OF DEPTHS OF OF OF EXISTING OVERHEAD AND UNDERGROUND UTILITIES (IN OVERHEAD AND UNDERGROUND UTILITIES (IN OVERHEAD AND UNDERGROUND UTILITIES (IN AND UNDERGROUND UTILITIES (IN AND UNDERGROUND UTILITIES (IN UNDERGROUND UTILITIES (IN UNDERGROUND UTILITIES (IN UTILITIES (IN UTILITIES (IN (IN (IN (IN CONFLICT WITH THE CONSTRUCTION OF THESE PROPOSED WITH THE CONSTRUCTION OF THESE PROPOSED WITH THE CONSTRUCTION OF THESE PROPOSED THE CONSTRUCTION OF THESE PROPOSED THE CONSTRUCTION OF THESE PROPOSED CONSTRUCTION OF THESE PROPOSED CONSTRUCTION OF THESE PROPOSED OF THESE PROPOSED OF THESE PROPOSED THESE PROPOSED THESE PROPOSED PROPOSED PROPOSED IMPROVEMENTS) SHALL BE VERIFIED IN THE FIELD. DURING SHALL BE VERIFIED IN THE FIELD. DURING SHALL BE VERIFIED IN THE FIELD. DURING BE VERIFIED IN THE FIELD. DURING BE VERIFIED IN THE FIELD. DURING VERIFIED IN THE FIELD. DURING VERIFIED IN THE FIELD. DURING IN THE FIELD. DURING IN THE FIELD. DURING THE FIELD. DURING THE FIELD. DURING FIELD. DURING FIELD. DURING DURING DURING THE CONSTRUCTION, THE CONTRACTOR SHALL PROTECT CONSTRUCTION, THE CONTRACTOR SHALL PROTECT CONSTRUCTION, THE CONTRACTOR SHALL PROTECT THE CONTRACTOR SHALL PROTECT THE CONTRACTOR SHALL PROTECT CONTRACTOR SHALL PROTECT CONTRACTOR SHALL PROTECT SHALL PROTECT SHALL PROTECT PROTECT PROTECT AND SUPPORT ALL UTILITIES THAT ARE ENCOUNTERED. SUPPORT ALL UTILITIES THAT ARE ENCOUNTERED. SUPPORT ALL UTILITIES THAT ARE ENCOUNTERED. ALL UTILITIES THAT ARE ENCOUNTERED. ALL UTILITIES THAT ARE ENCOUNTERED. UTILITIES THAT ARE ENCOUNTERED. UTILITIES THAT ARE ENCOUNTERED. THAT ARE ENCOUNTERED. THAT ARE ENCOUNTERED. ARE ENCOUNTERED. ARE ENCOUNTERED. ENCOUNTERED. ENCOUNTERED. (ALL COSTS FOR UTILITY LOCATION VERIFICATION, SUPPORT COSTS FOR UTILITY LOCATION VERIFICATION, SUPPORT COSTS FOR UTILITY LOCATION VERIFICATION, SUPPORT FOR UTILITY LOCATION VERIFICATION, SUPPORT FOR UTILITY LOCATION VERIFICATION, SUPPORT UTILITY LOCATION VERIFICATION, SUPPORT UTILITY LOCATION VERIFICATION, SUPPORT LOCATION VERIFICATION, SUPPORT LOCATION VERIFICATION, SUPPORT VERIFICATION, SUPPORT VERIFICATION, SUPPORT SUPPORT SUPPORT AND PROTECTION SHALL BE INCLUDED IN THE PROPOSED PROTECTION SHALL BE INCLUDED IN THE PROPOSED PROTECTION SHALL BE INCLUDED IN THE PROPOSED SHALL BE INCLUDED IN THE PROPOSED SHALL BE INCLUDED IN THE PROPOSED BE INCLUDED IN THE PROPOSED BE INCLUDED IN THE PROPOSED INCLUDED IN THE PROPOSED INCLUDED IN THE PROPOSED IN THE PROPOSED IN THE PROPOSED THE PROPOSED THE PROPOSED PROPOSED PROPOSED PAY ITEM CONFLICTING WITH THAT UTILITY). DURING CONSTRUCTION, THE CONTRACTOR SHALL USE CONSTRUCTION, THE CONTRACTOR SHALL USE CONSTRUCTION, THE CONTRACTOR SHALL USE THE CONTRACTOR SHALL USE THE CONTRACTOR SHALL USE CONTRACTOR SHALL USE CONTRACTOR SHALL USE SHALL USE SHALL USE USE USE EXTREME CAUTION WHEN OPERATING NEAR ANY AND ALL CAUTION WHEN OPERATING NEAR ANY AND ALL CAUTION WHEN OPERATING NEAR ANY AND ALL WHEN OPERATING NEAR ANY AND ALL WHEN OPERATING NEAR ANY AND ALL OPERATING NEAR ANY AND ALL OPERATING NEAR ANY AND ALL NEAR ANY AND ALL NEAR ANY AND ALL ANY AND ALL ANY AND ALL AND ALL AND ALL ALL ALL OVERHEAD AND / OR BURIED UTILITIES.
EJCDC® C-410, Bid Form for Construction Contracts.
Copyright © 2013 National Society of Professional Engineers, American Council of Engineering Companies, and American Society of Civil Engineers. All rights reserved. Page i
BID FORM
SPRINGFIELD TOWNSHIP CIVIC CENTER
STANDBY GENERATOR
AEW PROJECT NO. 0172-0048
BID SUBMITTED BY:___________________________
Company Name
Copyright © 2013 National Society of Professional Engineers, American Council of Engineering Companies, and American Society of Civil Engineers. All rights reserved. Page ii
TABLE OF CONTENTS
Page
Article 1 – Bid Recipient
Article 2 – Bidder’s Acknowledgements
Article 3 – Bidder’s Representations
Article 4 – Bidder’s Certification
Article 5 – Basis of Bid
Article 6 – Time of Completion
Article 7 – Attachments to this Bid
Article 8 – Defined Terms
Article 9 – Bid Submittal
Copyright © 2013 National Society of Professional Engineers, American Council of Engineering Companies, and American Society of Civil Engineers. All rights reserved. Page 1
ARTICLE 1 – BID RECIPIENT
1.01 This Bid is submitted to:
Joan Rusch, Planning Administrator/Supervisor’s Assistant Springfield Charter Township 12000 Davisburg Road Davisburg, Michigan 48350
1.02 The undersigned Bidder proposes and agrees, if this Bid is accepted, to enter into an Agreement with Owner in the form included in the Bidding Documents to perform all Work as specified or indicated in the Bidding Documents for the prices and within the times indicated in this Bid and in accordance with the other terms and conditions of the Bidding Documents.
ARTICLE 2 – BIDDER’S ACKNOWLEDGEMENTS
2.01 Bidder accepts all of the terms and conditions of the Instructions to Bidders, including without limitation those dealing with the disposition of Bid security. This Bid will remain subject to acceptance for sixty [60] days after the Bid opening, or for such longer period of time that Bidder may agree to in writing upon request of Owner.
ARTICLE 3 – BIDDER’S REPRESENTATIONS
3.01 In submitting this Bid, Bidder represents that:
A. Bidder has examined and carefully studied the Bidding Documents, and any data and reference items identified in the Bidding Documents, and hereby acknowledges receipt of the following Addenda:
Addendum No. Addendum, Date
B. Bidder has visited the Site, conducted a thorough, alert visual examination of the Site and adjacent areas, and become familiar with and satisfied itself as to the general, local, and Site conditions that may affect cost, progress, and performance of the Work.
C. Bidder is familiar with and has satisfied itself as to all Laws and Regulations that may affect cost, progress, and performance of the Work.
D. Bidder has carefully studied all: (1) reports of explorations and tests of subsurface conditions at or adjacent to the Site, if any, and all drawings of physical conditions relating to existing surface or subsurface structures at the Site, if any, that have been identified in the Supplementary Conditions, especially with respect to Technical Data in such reports and drawings, and (2) reports and drawings relating to Hazardous Environmental Conditions, if