Ted Stevens Marine Research Institute Lena Point, Juneau, Alaska
TSMRI FIRE ALARM SYSTEMS:
PART 1 - GENERAL:
1.1 SECTION INCLUDES:
A. Fire alarm control panels.
B. Manual fire alarm stations.
C. Automatic smoke and heat detectors.
D. Fire alarm signaling appliances.
E. Auxiliary fire alarm equipment.
1.2 REFERENCES:
A. NFPA 70 - National Electrical Code, latest published edition.
B. NFPA 72 - National Fire Alarm Code.
C. NFPA 101 - Life Safety Code.
D. UL 467 - Grounding and Bonding Equipment.
E. IBC - International Building Code.
1.3 SYSTEM DESCRIPTION:
A. Fire Alarm System: NFPA 72, manual and automatic local fire alarm system with connections to municipal system.
1.4 REGULATORY REQUIREMENTS:
A. Conform to requirements of NFPA 70, latest published edition, NFPA 72, NFPA 101, and IBC.
B. Furnish products listed and classified by UL and classified by Underwriters Laboratories, Inc. or an independent testing firm acceptable to authority having jurisdiction as suitable for purpose specified and shown.
1.5 QUALIFICATIONS:
A. Manufacturer: Company specializing in manufacturing the products specified in this section with minimum three years documented experience, and with service facilities within 24 hours of Project.
B. Installer: Company specializing in installing the products specified in this section with minimum three years documented experience, and certified by State as fire alarm installer.
1.6 QUALITY ASSURANCE:
A. Perform Work in accordance with NECA "Standard of Installation."
B. Maintain one copy of document on site.
Fire Alarm Systems Specifications - 1
1.7 SUBMITTALS:
A. Shop Drawings: Provide annunciator layout and system wiring each device and wiring connection required.
B. Product Data: Provide electrical characteristics and connection requirements.
C. Test Reports: Indicate satisfactory completion of required tests and inspections.
D. Manufacturer's Installation Instructions: Indicate application conditions and limitations of use stipulated by product testing agency. Include instructions for storage, handling, protection, examination, preparation, installation, and starting of products.
1.8 PROJECT RECORD DOCUMENTS:
A. Record actual locations of panels, annunciators, initiating devices, signaling appliances, and end-of-line devices.
1.9 PROJECT CONDITIONS:
A. Verify locations of panels and devices prior to installation.
1.10 OPERATION AND MAINTENANCE DATA:
A. Operation Data: Operating instructions.
B. Maintenance Data: Maintenance and repair procedures.
1.11 MAINTENANCE SERVICE:
A. Furnish service and maintenance of fire alarm system for one year from Date of Final Acceptance.
1.12 EXTRA MATERIALS:
A. Provide six keys of each type.
B. Provide three of each type of automatic smoke detector and base.
PART 2 - PRODUCTS:
2.1 FIRE ALARM AND SMOKE DETECTION CONTROL PANEL:
A. Control Panel: Modular construction with lockable wall-mounted enclosure.
TSMRI - 2 Fire Alarm Systems
B. Power supply: Adequate to supply control panel modules, remote detectors, remote annunciators, door holders, smoke dampers, relays, and alarm signaling devices. Include battery-operated emergency power supply with capacity for operating system in standby mode for 24 hours followed by alarm mode for 5 minutes.
C. System Supervision: Component, wiring or power supply failure places system in trouble mode.
D. Initiating Device Circuits: Supervised zone module with alarm and trouble indication; occurrence of single ground or open condition places circuit in trouble mode but does not disable that circuit from initiating an alarm.
E. Indicating Appliance Circuits: Supervised signal module, sufficient for signal devices connected to system;
occurrence of single ground or open condition places circuit in trouble mode but does not disable that circuit from signaling an alarm.
F. Remote Station Signal Transmitter: Electrically supervised digital alarm communicator transmitter, capable of transmitting alarm and trouble signals over telephone lines to central station receiver.
G. Auxiliary Relays: Provide sufficient SPDT auxiliary relay contacts for each detection zone to provide accessory functions specified.
H. Provide TROUBLE ACKNOWLEDGE, DRILL, and ALARM SILENCE switch.
I. Trouble Sequence of Operation: System or circuit trouble places system in trouble mode, which causes the following system operations:
1. Visual and audible trouble alarm indicated by zone at fire alarm control panel.
2. Visual and audible trouble alarm indicated at remote annunciator panel.
3. Trouble signal transmitted to central station.
4. Manual acknowledge function at fire alarm control panel silences audible trouble alarm; visual alarm is displayed until initiating failure or circuit trouble is cleared.
J. Alarm Sequence of Operation: Actuation of initiating device places circuit in alarm mode, which causes the following system operations:
1. Sound and display local fire alarm signaling devices.
2. Transmit non-coded signal to central station.
3. Indicate location of alarm zone on fire alarm control panel and on remote annunciator panel.
4. Transmit signals to building elevator control panels to initiate return to main or alternate floor.
5. Transmit signal to building mechanical systems to initiate shutdown of fans and damper operation.
6. Transmit signal to release door hold-open devices by zone.
K. Alarm Reset: System remains in alarm mode until manually reset with key-accessible reset function; system resets only if initiating circuits are out of alarm mode.
L. Lamp Test: Manual lamp test function causes alarm indication at each zone at fire alarm control panel and at annunciator panel, but does not cause alarm or trouble signals to be sounded or transmitted off site.
M. Drill Sequence of Operation: Manual drill function causes alarm mode operation as described above.
N. Zoning: As indicated.
2.2 INITIATING DEVICES: Installed devices may be reutilized if compatible with new system. (Provide
Explosion Proof devices where noted as “EP”) A. Manual Pull Station: Semi-Flush mounted, non-coded type, single action manual station.
B. Spot Heat Detector: Fixed temperature, Combination rate-of-rise and fixed temperature, rated 57 degrees C except as shown on drawings.
C. Ceiling Mounted Smoke Detector: NFPA 72, photoelectric type with adjustable sensitivity, plug-in base, auxiliary relay contact, integral thermal element rated 57 degrees C, and visual indication of detector actuation, suitable for mounting on 102 mm outlet box. Provide two-wire detector with common power supply and signal circuits unless coordinated otherwise.
D. Duct Mounted Smoke Detector: NFPA 72, photoelectric type with auxiliary SPDT relay contact, key-operated NORMAL-RESET-TEST switch, duct sampling tubes extending width of duct, and visual indication of detector actuation, in duct-mounted housing. Provide two-wire detector with common power supply and signal circuits unless coordinated otherwise.
Fire Alarm Systems Specifications - 3
2.3 SIGNALING APPLIANCES: (Provide Explosion Proof devices where noted as “EP”) A. Reutilize existing signaling devices when practical.
B. Building System Mini-Combination Horn/Strobe: NFPA 72, semi-recessed, non-projection, type fire alarm horn. Sound Rating: 82 dB at 10 feet. Provide integral strobe lamp and flasher with red lettered "FIRE" on white lens. Strobe intensity shall be minimum of 75cd and comply with ADA requirements.
C. Building System Alarm Lights: NFPA 72, strobe lamp and flasher with red lettered "FIRE" on white lens.
Strobe intensity shall be minimum of 75cd and comply with ADA requirements.
D. Remote Graphic Annunciator: Provide supervised remote graphic annunciator including audible and visual indication of fire alarm by zone, and audible and visual indication of system trouble. Install in flush wall-mounted enclosure.
PART 3 - EXECUTION:
3.1 INSTALLATION:
A. Install products in accordance with manufacturer's instructions.
B. Use 16 or 14 AWG minimum size conductors for fire alarm detection and signal circuit conductors. Install wiring in conduit.
C. Mount end-of-line device if required “electrically” beyond the last inline device.
D. Make conduit and wiring connections to door release devices, sprinkler flow switches, sprinkler valve tamper switches, fire suppression system control panels, duct smoke detectors, and all other equipment and systems.
E. Automatic Detector Installation: Conform to NFPA 72.
F. Ground and bond system under provisions of Section 16170.
3.2 FIELD QUALITY CONTROL:
A. Test in accordance with NFPA 72 and local fire department requirements.
3.3 MANUFACTURER'S FIELD SERVICES:
A. Include services of certified technician to supervise installation, adjustments, final connections, and system testing.
3.4 FIRE ALARM WIRE AND CABLE COLOR CODE:
A. Provide fire alarm circuit conductors with insulation color coded as follows, or use colored tape at each conductor termination and in each junction box.
B. Power Branch Circuit Conductors: Black, red, white.
C. Initiating Device Circuit: Black, red.
D. Detector Power Supply: Violet, brown.
E. Signal Device Circuit: Blue (positive), white (negative).
F. Door Release: Gray, gray.
G. Municipal Trip Circuit: Orange, orange.
TSMRI - 4 Fire Alarm Systems
H. Municipal Fire Alarm Loop: Black, white.
3.5 SYSTEM VERIFICATION:
A. Fire alarm equipment supplier shall provide a thorough inspection of the completely installed fire alarm system including all components such as manual stations, thermal detectors, products-of-combustion detectors, sprinkler flow valves and switches, alarm stations, controls, to insure the following:
1. Complete and functional integral system conforming with requirements of authorities having jurisdiction and local alarm monitoring service.
2. Compliance with Underwriters' Laboratories requirements and the provisions and requirements of the
NFPA.
3. Installation is in accordance with manufacturer's recommendations and instructions.
4. Adherence to requirements and regulations covering supervision of components.
B. Provide corrective measures necessary to conform with requirements in items 1 through 4 above in conjunction with technical assistance from the manufacturer.
3.6 DEMONSTRATION:
A. Demonstrate normal and abnormal modes of operation, and required responses to each.
END OF SPECIFICATIONS
Fire Alarm Systems Specifications - 5
THIS PAGE HAS BEEN INTENTIONALLY LEFT BLANK
TSMRI - 6 Fire Alarm Systems
| PART 1 - GENERAL: |
| 1.1 SECTION INCLUDES: |
| 1.2 REFERENCES: |
| 1.3 SYSTEM DESCRIPTION: |
| 1.4 REGULATORY REQUIREMENTS: |
| 1.5 QUALIFICATIONS: |
| 1.6 QUALITY ASSURANCE: |
| 1.7 SUBMITTALS: |
| 1.8 PROJECT RECORD DOCUMENTS: |
| 1.9 PROJECT CONDITIONS: |
| 1.10 OPERATION AND MAINTENANCE DATA: |
| 1.11 MAINTENANCE SERVICE: |
| 1.12 EXTRA MATERIALS: |
| PART 2 - PRODUCTS: |
| 2.1 FIRE ALARM AND SMOKE DETECTION CONTROL PANEL: |
| PART 3 - EXECUTION: |
| 3.1 INSTALLATION: |
| 3.2 FIELD QUALITY CONTROL: |
| 3.3 MANUFACTURER'S FIELD SERVICES: |
| 3.4 FIRE ALARM WIRE AND CABLE COLOR CODE: |
| 3.5 SYSTEM VERIFICATION: |
| 3.6 DEMONSTRATION: |
| END OF SPECIFICATIONS |