This document provides specifications for a diesel generator required by the Department of the Interior Fish and Wildlife Service. The generator must be a 60Hz, 40KW-Standby Rating unit compliant with NFPA 110 Level 1 requirements and EPA Tier 3 emissions standards, producing 277/480V, 3 phase power. It must include a digital display and control panel with monitoring and diagnostic functions, alarms, and programmable I/O. The generator is to be equipped with an exhaust silencer, flexible fuel and exhaust lines, battery charger, and sub-base fuel tank providing a minimum of 48 hours run time. The solicitation also requires field service and start-up including load testing, along with owner training and manuals. The related opportunity is for replacing the generator at the TX-SAN MARCOS AQUATIC facility, issued under solicitation 140FS223Q0190.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| B03_Wage_Determination_2015-5215_REV_26_06302023_Bastrop__Caldwell__Hays__Travis__Williamson.pdf | ||
| A04_RFQ__Statement__of__Work_Install_of__generator__and__switch__final.pdf | ||
| Sol_140FS223Q0190.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
One (1) Genset-Diesel, 60Hz, 40 KW-Standby Rating
Duty Rating-Standby Power
NFPA 110 Type 10 Level 1 Capable
Listing-UL 2200
Emissions Certification, EPA, Tier 3, NSPS CI Stationary Emergency
Voltage- 277/480v, 3 phase, 40 KW, 50 KVA, 120 amps 60 hz. 4 wire.
Local Data Access with digital display and menu control. Apm 402/ dec3000 2 inputs/ 5 outputs.
Modbus protocol supported.
Controller/ Display: Auto, Manual, Off selector. Audible alarm. Digital display, menu control, system monitoring and system diagnostics. To include but not limited to Oil pressure/ temp. coolant temp, fuel level/ pressure (where applicable) engine speed, DC battery voltage, run time hours, generator voltage, amperage, frequency, power, and power factor.
Alarms: low or high voltage, low or high battery voltage indicator, low or high oil pressure, high oil temp, low water level, high water temp. Critical low fuel level, overload, over crank, over and under speed programmable I/O module.
Air intake assembly 40/50/60/ kw
Exhaust silencer
Exhaust connector- flexible
Radiator duct flange
Display Language- English
Engine Governor- Electronic
Receptacles- 120v GFCI and 240v receptacles.
Engine Starter-
Stop Switch- Emergency
Control Mounting- Right Side
Separator- Oil/ water
Skid base
Tank fuel- UL 142 subbase dual wall basic diesel fuel tank 48 hour minimum.
Battery Charger Equalize/ float type.
Engine cooling – High ambient Air Temp.
Fuel indicator- mechanical
Lcb, 90a, hdp, therm mag. 100%
Mtg, lcb
Shunt trip, 12 vdc, hd/jd/dg frame
Shunt trip wiring, apm403/dec3000
Neutral, 300a 4p
Block heater- 120v 1000w
Battery- 12v 650 CCA wet.
Generator heater120/240v 200w
Run relay- 12v
Oil drain- extension
Coolant drain- extension
Fuel Lines- Flexible
Field Service/ Start up service- Full tank of fuel.
Field Service/ Start up service- Add recommended amount of coolant as per manufacturer.
Field Service/ Start up service- Add recommended amount of oil as per manufacturer.
Field Service/ Start up- NFPA 110 testing. (2-hour building load transfer test and 2-hour load bank test)
Warranty- comprehensive
Owner training
Manuals- (3) three sets.
Automatic transfer switch:
KCS-AMTA 01042 or equivalent
Lit kit ats overhaul KCS/KCP/ KCC
Warranty- standard
Packing material- ATS
Door, small ats
Enclosure, small
Dwg, assy ats logic
Contactor, ot 30/70/104a 3 p 440-480v
External battery supply module
Multi schedule engine exerciser
Accessory mounting assembly
Warranty- standard.
Programmable input/output module.
High Current output module
Please note: The government is not a subject matter expert on generators or the install, hence, these specifications do not limit what the contracting officer can determine is needed or is a better option for the requirement. Vendors are encouraged to put their best specification forward at time of initial offer.