A04_Oasis_Fuel_System_(Electrical_Power_Supply)_Performance_Work_Statement__.pdf

PDF 4 MB Posted

Attached to
OASIS FUEL SYSTEM ELECTRICAL POWER Federal contract opportunity
Solicitation number
140P5223R0025
Issued by
Department of the Interior National Park Service Southeast Region

About this file

This performance work statement outlines requirements for providing electrical power to an aviation fuel system at Big Cypress National Preserve in Florida. The contractor shall run an electrical power supply line from an electrical breaker box 150 to 175 feet to connect to the fuel system. The line must be buried underground in 1.5-inch electrical conduit at a depth of 18 to 24 inches. The system must be grounded and bonded according to the fuel system manufacturer's requirements. The contractor must complete the work during normal business hours and coordinate schedules with the contracting officer and contracting officer's representative. The work is to be finished within a specified number of days after receiving a notice to proceed. The contractor will be responsible for project management, safety compliance, and developing and implementing quality control plans. Insurance requirements and other operational specifications are provided.

View the file

Other files for this federal contract opportunity

Other files attached to OASIS FUEL SYSTEM ELECTRICAL POWER, newest first.
File Type Posted
Fuel_Tank_Slab_Drawing_REVISED_2023_06_01_0002.pdf PDF
Sol_140P5223R0025_Amd_0002.pdf PDF
Sol_140P5223R0025_Amd_0001.pdf PDF
B03_DOL_SOL_Wages.pdf PDF
B09_QUESTIONNAIRE.pdf PDF
Sol_140P5223R0025.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Performance Work Statement (PWS)

Aviation Fuel System- Oasis Airfield

1. Background. The Big Cypress National Preserve is in South Florida. and encompasses729,000 acres. The preserve was established by Congress on October 11, 1974.

The Fire and Aviation Division at Big Cypress NP purchased a new fuel system. This new fuel system is expected to be delivered sometime in August to the Oasis Airfield, located behind the Oasis Visitors Center. This new fuel system will need to be supplied by electrical power.

2. Required Services. The contractor shall provide all labor, tools, equipment, materials and supervision required to Provide electrical power to UL2085 Skid Mounted Aviation fuel system

3. Contractor Responsibilities:

• Run electrical power supply line from electrical breaker box 150’ to 175’ to UL2085

JET-A AIRCRAFT FUELING SYSTEM, connecting point for the fuel system is a

1.5 inches electrical power conduit stub. Will need seal offs on both ends of the 1.5 inches underground conduit. Underground conduit buried at 18-24 inches deep and

20 feet of rigid pipe on both ends, where it starts from the control panel & where it ends at the tank. The system will need to be grounded and bonded to the earth.

4. Government Furnished Property, Materials & Supplies. None.

5. Business Hours. The contractor shall complete on-site work during normal business hours of

7:30 am to 4:30 pm, Monday through Friday, excluding Federal holidays. The contractor shall coordinate specific on-site work schedule with the Contracting Officer and Contracting Officer

Representative (COR) five days prior to performance start date. While on site, the COR may be reached by mobile phone during normal business hours. Work shall be completed within ## days after Contracting Officer issues notice to proceed. Any work outside of normal business hours shall be pre-approved by the Contracting Officer and COR.

6. Management. The contractor shall manage the total work effort in accordance with effective and efficient management principles and safe working practices to ensure on-time completion of this contract.

7. Safety & Environmental Compliance.

• The contractor shall comply with pertinent provisions of the Occupational Safety and

Health Act (OSHA), and state, local, safety, laws.

• The contractor shall comply with pertinent Environmental Protection Agency laws and regulations.

• The Park safety officer has the authority to issue restraint or cease-and-desist orders to the contractor when violations or unsafe acts are present and threaten Government and contractor employees or damage to Government property.

• The contractor shall immediately report to the Contracting Officer, COR and Park safety officer all accidents resulting in employee injury or death or damage to property while performing this contract.

8. Insurance. The Contractor shall be insured in accordance with State of Florida insurance regulations. The Government is not responsible for damage to Contractor’s equipment, vehicles, tools or materials or their employees and the personal property brought on-site. The Government will not accept any liability due to contractor employee negligence.

• Workers Compensation: The contractor shall furnish proof of workers compensation insurance to the Contracting Officer for those employees performing work related to this contract and shall comply with the Workman’s Compensation Laws of the State of

Florida.

• Liability: The Contractor shall maintain a level of insurance that will protect the contractor and the Government from any claims as a result of bodily injury (including death) and property damage which may arise from and during the performance of this contract and shall submit proof of insurance to the Contracting Officer.

9. Performance Requirements Summary (PRS). The contractor performance requirements are summarized into required services that relates directly to successful contract completion.

The performance standard identifies the minimum acceptable levels of service allowed.

PWS

Section

Required

Service Standard

Monitorin g

Method

Incentive/

Disincentive

1.

Establish circuit breaker connection from electrical breaker box.

electrical power.

100% compliance

Random

Inspection Performance

Evaluation

2.

Run electrical lines underground thru conduit

100% compliance

Random

Inspection

Performance

Evaluation

3. Connect electrical lines to new fuel system

100% compliance

Random

Inspection

Performance

Evaluation

4. Provide grounding and bonding as required by fuel system manufacturer

100% compliance

Random

Inspection

Performance

Evaluation

10. Motor Vehicle & Traffic Regulations. Contractor employees operating motor vehicles shall possess a valid driver's license. Driver and vehicle permits, licenses, registrations and proof of insurance shall be maintained in the vehicle at all times and made available upon request.

Contractor employees shall comply with federal vehicle motor law requiring seat belts be worn at all times. Contractor employees shall adhere to the posted speed limits.

11. Employee Badges/Parking. All contractor employees shall comply with parking procedures published for the Park. Contractor employees shall return any PARK issued personal or vehicle identification badges immediately upon termination of employment or completion of this contract.

12. Replacement of Contractor Employee for Security Reasons. The Government retains the right to request removal of the contractor’s employee(s), regardless of prior clearances.

13. Non-Payment for Additional Work. Any additional contractor performed services not specified in contract, either at its own volition or at the request of an individual other than an appointed Contracting Officer, except as may be explicitly authorized in the contract, shall be performed at the financial risk of the contractor. Only an appointed Contracting Officer is authorized to bind the Government to a change in specifications, contract terms, or conditions.

14. Conflict of Interest. The contractor shall not employ off-duty COR’s or other Government employees if such employment would create a conflict of interest or be contrary to the policies contained in conflict-of-interest directives.

15. Quality Control. The contractor shall establish and maintain a Quality Control Plan (QCP) to ensure the work performed conforms to the contract requirements. The Performance

Requirements Summary establishes performance standards that are the minimum requirements for acceptable performance of required services. The contractor’s QCP shall address methods for remedying poor performance. The Contractor shall develop QCP and submit with proposal package. The Contractor’s QCP includes:

• Required services identified in Performance Requirements Summary

• Contractor’s surveillance methodology

• Method and timeframe for responding to COR or customer complaints

• Progress meetings with Government stakeholders

16. Quality Assurance. The COR will monitor the contractor’s performance under this contract using the quality assurance procedures specified in the Government’s Quality Assurance

Surveillance Plan (QASP). The QASP may be modified after contract award upon review and acceptance of the contractor’s QCP to ensure both plans are mutually supportive. The purpose of the QASP is to ensure that the required services are performed in accordance with the contract requirements. The plan ensures reliable and continued operation by precluding unnecessary complaints and unacceptable performance. Government’s QASP includes:

• Acceptance of the contractor’s quality control plan

• Random inspection of the contractor’s work

• Communicating customer complaints

• Progress meetings with the contractor

The implementation of this QASP does not relieve the contractor of its responsibility to implement and abide by the QCP incorporated into this contract, and to provide acceptable performance of all required services listed herein. At the CO’s discretion, the contractor may incur a payment deduction for lack of compliance with the QCP, PWS or PRS.

17. Contractor’s Proposal Package. The following deliverables are to be submitted with offer in response to RFQ.

• Technical approach to perform required services.

• Contractor safety plan.

• Contractor’s QCP

• Proof of Insurance–Business Liability & Workers Compensation.

18. Inspection. The Government will conduct inspection upon completion of required services.

Final payment will be processed upon confirming that all noted contractor performance deficiencies have been satisfactorily corrected.

ABA-CON INC.

P.O. BOX 308

TITUSVILLE, FL 32781

PHONE: (321) 567-4967

FAX: (321) 607 6805

WEB:

www.aba-con.com

TI

TL

E:

C O

VE

R

P

AG

E

JOB NUMBER:

CVR

DRAWING NUMBER:

PROJECT CONTRACTOR:

PROPRIETARY AND CONFIDENTIAL

The information contained in this drawing is the sole property of ABA-CON Aviation Services. Any reproducton in part or as a whole is prohibited without written permission of ABA-CON Aviation Services.

DATE:

REVISIONS

DATE DESCRIPTION

SCALE: XX:XX

KM

DRAWN BY:

APPROVED BY:

SCALED FOR ANSI B

7,500 GALLON UL2085 DOUBLE WALL FIREGUARD

ENCLOSED CANOPY DESIGN AST

120/25 GPM JET-A AIRCRAFT FUELING SYSTEM

FOR

BIG CYPRESS NATIONAL PRESERVE

52105 TAMIAMI TRAIL EAST

OCHOPEE, FL 34141

LIST OF DRAWINGS:

CVR: COVER PAGE

G-10: NOTES

FT-20: JET-A TANK AND EQUIPMENT

E-30: JET-A TANK ELECTRICAL SCHEMATIC

M-40: JET-A P&ID

10/7/2022

MAVEN CONSTRUCTION

& ENVIRONMENTAL, LLC

6550 ST. AUGUSTINE

ROAD SUITE 202

JACKSONVILLE, FL 32217

AB

TITUSVILLE, FL 32781

PHONE: (321) 567-4967

FAX: (321) 607 6805

WEB:

www.aba-con.com

TI

TL

E:

N O

TE

S

JOB NUMBER:

G-10

DRAWING NUMBER:

PROJECT CONTRACTOR:

PROPRIETARY AND CONFIDENTIAL

The information contained in this drawing is the sole property of ABA-CON Aviation Services. Any reproducton in part or as a whole is prohibited without written permission of ABA-CON Aviation Services.

DATE:

REVISIONS

DATE DESCRIPTION

SCALE: XX:XX

KM

DRAWN BY:

APPROVED BY:

SCALED FOR ANSI B

10/7/2022

MAVEN CONSTRUCTION

& ENVIRONMENTAL, LLC

6550 ST. AUGUSTINE

ROAD SUITE 202

JACKSONVILLE, FL 32217

PIPING:

1. System Pipe 1.0" and Larger: 304/304L, ASTM A312, SCH10 Stainless steel, flanges 304/304L, 150#, RF, ASTM A182 Elbow 90-45, reducers 304/304L, ASTM A403 SCH10

2. System Pipe 1.0" and smaller: 304/304L, ASTM A312, SCH40, Stainless steel fittings 304/304L, ASTM A182

3. System Instrument Tubing: ASTM A269, grade TP316 stainless .035 wall seamless

4. Compression Fittings: DK-LOK 316 stainless steel

5. Systems piping shall be cleaned internally before final assembly

SYSTEM PERFORMACE REQUIREMENTS:

Minimum Working Pressure Ratings*

1. Aboveground Steel Fuel Oil Piping 150 psig

2. Vent, Gauge, and Fill Piping: 100 psig

3. Fuel Storage Tank: 5 psig

4. Fuel Storage Tank, Secondary Containment Shell Walls: 5 psig

5. Fuel Control/Operating Valves: 250psi

6. Jet-A Tank Fuel Unloading Rate: 120gpm

7. Jet-A Tank Recirculation Rate: 120gpm

8. Jet-A Aircraft Dispensing Rate: 25gpm

OPERATION MANUALS:

Provide (1) copies of Operation and Maintenance manuals for all equipment including parts list, instruction sheets, and other literature that is provided with systems components

DELIVERY, INSTALLATION AND START-UP:

1. Contractor shall provide safe delivery of tank system.

REGULATORY REQUIREMENTS:

1. NFPA 30 Flammable and Combustible Liquid Code

2. NFPA 70 National Electrical Code (NEC)

3. NFPA 77 Recommended Practice for Static Electricity

4. NFPA 407 Standard for Aircraft Fuel Servicing

5. UL 142 Standard for Safety, Steel AST's for Flammable and Combustible Liquids

6. UL 842 Standard for Valves for Flammable Fluids

7. ANSI/UL 87, Power Operated Dispensing Devises for Petroleum Products

8. ANSI/UL 913, Standard for Intrinsically Safe Apparatus and Associated Apparatus for Use in Class I, II, and III Division 1 Hazardous (Classification) Locations

9. American Petroleum Institute (API) Standards. Regulations and Publications, including Appendices for design, cleaning, construction, installation of tanks, piping, and dispensing system

10. API Bulletin 1500, 1542, 1581, 2000

11. API Bulletin 1529 Aviation Hose

12. API Bulletin 1540 Design, Construction, Operation, and Maintenance of aviation Fueling Facilities

13. PEI Standards RP-200, RP-100-90, RP-300, RP-400, and RP1300

14. ATA-103 Standard for Jet Fuel Quality Control at Airports

15. Applicable Local, State, and Federal Codes and Regulations

16. Local and State Dept. of Environmental Management

17. Approvals by Authority Having Jurisdiction

AVIATION STORAGE TANK

SYSTEMS

TITUSVILLE, FL 32781

PHONE: (321) 567-4967

FAX: (321) 607 6805

WEB:

www.aba-con.com

TI

TL

E:

JE

T-

A

TA

N K

AN

D

E Q

U

IP

M

EN

T

QUOTE NUMBER:

FT-20

DRAWING NUMBER:

PROJECT CONTRACTOR:

PROPRIETARY AND CONFIDENTIAL

The information contained in this drawing is the sole property of ABA-CON Aviation Services. Any reproducton in part or as a whole is prohibited without written permission of ABA-CON Aviation Services.

DATE:

REVISIONS

DATE DESCRIPTION

SCALE: AS NOTED

KM

DRAWN BY:

APPROVED BY:

SCALED FOR ANSI B

GENERAL NOTES:

1. CAPACITY 7,500 GALLONS NOMINAL

2. DOUBLE WALL, TYPE II CONSTRUCTION, 360 DEGREE WRAP, UL-2085

3. SHOP TEST WITH AIR AT 3 - 5 PSI, USE DOUBLE WALL TESTING PROCEDURES

4. ATTACH TANK LABELS AS FOLLOWS:

A. "UL-2085"

B. THIS TANK REQUIRES EMERGENCY RELIEF VENTING CAPACITY NOT LESS THAN 344,340 CU. FT./HR.

C. THIS TANK IS PROVIDED WITH AN INTEGRAL STEEL FOUNDATION AND IS INTENDED FOR STATIONARY INSTALLATION ONLY

5. MATERIAL: CARBON STEEL

6. OVERFILL PREVENTION:

A. WARNING: AT 90% CAPACITY, CLOCK GAUGE (ITEM 6) PROVIDES AN AUDIBLE AND VISUAL ALARM AT ANNUNCIATOR PANEL (ITEM 7).

B. SHUTOFF: AT 95% CAPACITY, FLOAT VALVE (ITEM 13) CLOSES BONNET VENT OF HIGH LEVEL SHUTOFF VALVE (ITEM 12) WHICH THEN

CLOSES, PREVENTING FURTHER FUEL INPUT

7. OVERSPILL PROTECTION: TRANSPORT CONNECTION, PUMP, AND PIPING ARE ALL WITHIN INTEGRAL EQUIPMENT DECK. APPROXIMATE CAPACITY: 250 GAL, FITTED WITH NORMALLY CLOSED MANUALLY OPERATED DRAIN VALVE (ITEM 14)

8. (ITEM 8) - (ITEM 12)

(ITEM 12)THIS VALVE AND EQUIPMENT ARE USED TO SHUT OFF FUEL FLOW AT 95% TANK CAPACITY. (ITEM #8) IS THE ANTI-SIPHON SOLENOID

VALVE THAT PREVENTS FUEL FROM BEING SIPHONED FROM THE TANK SUCTION PIPING.

THE VALVE OPERATES AS FOLLOWS. THE 3" N/C 115VAC SOLENOID VALVE IS ALWAYS CLOSED UNTIL THE PUMP SWITCH IS ACTIVATED.

32"0" 16"

EQUIPMENT PLAN VIEW

1:32

FT-20

40"0" 20"

FRONT VIEW

1:40

FT-20

60"0" 30"

TOP VIEW

1:60

FT-20

60"0" 30"

LEFT VIEW

1:60

FT-20

40"0" 20"

BACK SECTIONED VIEW

1:40

FT-20

10/7/2022

MAVEN CONSTRUCTION

& ENVIRONMENTAL, LLC

6550 ST. AUGUSTINE

ROAD SUITE 202

JACKSONVILLE, FL 32217

1 345 610

34 34

24" MANWAY

THERMAL

INSULATION

FILL PORT

THERMAL

INSULATION

FILL PORT

1717 32

19A

21A 21B

22A 22B

21A 21B

21A22A

19A

19B

21A 21B

22B

22A

19A

19B

5 25

25 26

JET-A NFPA PLACARD

FT-20

20'-6" 6' 26'-6"

8'-6"

6" 4"

12' MINIMUM

INTERIOR RUNG

LADDER

AB

ITEM QTY DESCRIPTION PART NUMBER MANUFACTURER

1 1 JET-A TANK 7,500 GALLON, UL-2085 FIREGUARD, 96" PRIMARY DIA. 102" SECONDARY DIA. 20'-6" LONG, + 72" ENCLOSED CANOPY/EQUIPMENT DECK AREA WITH SPILL CONTAIMENT OF 250 GALLONS. BOX SKID SUPPORTS, TANK INTERIOR SANDBLASTED TO SSPC-SP10 EPOXY LINED INTERNATIONAL INTERLINE 850 WHITE EPOXY, EXTERIOR SANDBLASTED TO SSPC-SP6 DEVOE 235 EPOXY PRIME, FINISHED PAINTED INTERNATIONAL DEVTHANE 379K1000 WHITE URETHANE GLOSS ENAMEL, REAR RUNG LADDER, ONE

EACH 24" MANWAY, INTERIOR LADDER, FOUR (4) ANCHOR POINTS

7,500 GALLON UL-2085

DOUBLE WALL

STI FIREGUARD

FLORIDA EQ-352

Modern Welding

2 2 EARTH GROUNDING CONNECTION. COPPER-BONDED GROUNDING LUG, 5/8" X 2-1/2" LONG (MIG-WELDED TO TANK SUPPORT) 615800 (5/8" X 2.5" LONG) ERITECH

3 1 VENT 3" TANK VENT WITH STAINLESS STEEL RISER PIPE 354-0300-AV Morrison

4 2 8", 8oz/sq.in. EMERGENCY VENT-FLANGED, w/O-RING (PRIMARY & SECONDARY E.VENTS) 244OF-0100-AV Morrison

5 1 ADAPTER-4" ALUMINUM (MANUAL STICK GAUGE & FUEL SAMPLE PORT) 400-A-AL DIXON

1 DUST CAP-4" LOCKING (MANUAL STICK GAUGE & FUEL SAMPLE PORT LIQUID TIGHT CAP) 400-DC-LAL DIXON

6 1 CLOCK GAUGE (TANK LEVEL GAUGE) 918-0400-AG

FLORIDA EQ-527 Morrison

7 1 ALARM ANNUCIATOR (90% TANK CAPACITY ALARM WITH TEST BUTTON) 918-0400-AG

FLORIDA EQ-527 Morrison

8 1 VALVE,SOLENOID, 3", N/C 120VAC COIL, EXPLOSION PROOF, WEATHER TIGHT W/TEFLON SEALS, STAINLESS STEEL, FLANGED (ANTI-SIPHON VALVE N/C) 710FSS3300 1V Morrison

9 1 ADAPTER-4" ALUMINUM (TANK FILL CONNECTION) 400-A-AL DIXON

1 DUST CAP-4" LOCKING (TANK FILL CONNECTION LIQUID TIGHT CAP) 400-DC-LAL DIXON

10 1 HAND PUMP (TANK BOTTOM SUMP PUMP) 114000-5HP-100-NUL GPI

1 SPR. RETURN 3/4" BALL VALVE STAINLESS (HAND PUMP ANTI-SIPHON VALVE N/C) 22-061-41 LANCE

1 VALVE BALL 3/4" STAINLESS (MAINTENANCE VALVE) 22-061 LANCE

1 ADAPTOR-3/4" (SUMP DISCHARGE) 75-A-AL DIXON

1 DUST CAP-3/4" (SUMP DISCHARGE LIQUID TIGHT CAP) 75-DC-AL DIXON

11 1 INTERSTITIAL TANK SPACE LEAK INDICATOR WITH GUARD 724-1200 AI

FLORIDA EQ-929 Morrison

12 1 VALVE HIGH LEVEL SHUT-OFF ANGLE VALVE 2" (95% TANK CAPACITY CONTROL VALVE HYDRAULICALLY OPERATED, DIAPHRAGM-ACTUATED, FAIL CLOSED, N/C) 265338 OCV

1 VALVE POSITION VISUAL INDICATOR 255700 OCV

1 INLINE STRAINER ((PROTECTS SYSTEM FROM SOLID CONTAMINANTS) 660704 OCV

1 FTG. 3/8 X 3/8 COMP MODIFIED S/S (CONTROLS OPENING AND CLOSING SPEED OF CONTROL VALVE) (TAMPER PROOF) 6-6-FBZ-SS ABA-CON MODIFIED Parker

1 SPR. OPEN BALL VALVE 1/4" STAINLESS (SYSTEM PRE-CHECK VALVE) 76-501-01A APOLLO

1 D-RING, STAINLESS STEEL, PRE-CHECK 3896T3 MC MASTER

1 CABLE, CLEAR VINYL COVERED GTP-1093 Gammon

13 1 95% VALVE & FLOAT (95% TANK CAPACITY MODULATING FLOAT PILOT) 230151 OCV

14 1 VALVE BALL 3/4" BRASS EQUIPMENT DECK SPILL CONTAINMENT DRAIN VALVE XV500P-12 Parker

15 1 3" WAFER CHECK VALVE, VITON SEAL CV41DSV0300 TITAN

16 4 BALL VALVE 2" FIRE SAFE, FLANGED, API-607 FS50114-RF-2" SHARPE

17 7 BALL VALVE 3" FIRE SAFE, FLANGED, API-607 FS50114-RF-3" SHARPE

18 1 LINE STRAINER FLANGED 3" 286FDI-3100-AS Morrison

19-A 1 PUMP GNX2.5A, 50PSI BY-PASS PRESSURE 120GPM GNX2.5A BLACKMER

1 GEAR REDUCER 2.65 RATIO PUMP SPEED 660 RPM BLACKMER

1 MOTOR, EXPLOSION PROOF 230VAC 1-PHASE 5-HP 1800 RPM CXL21542 BALDOR

19-B 1 PUMP GNX2.5A, 50PSI BY-PASS PRESSURE 120GPM GNX2.5A BLACKMER

1 GEAR REDUCER 2.65 RATIO PUMP SPEED 660 RPM BLACKMER

1 MOTOR, EXPLOSION PROOF 230VAC 1-PHASE 5-HP 1800 RPM CXL21542 BALDOR

20 2 Starter-NEMA 7-9 EXPLOSION PROOF ENCLOSURE, SIZE "1" STARTER MOTOR 14DUF32HAA4 Furnas

21-A 1 FILTER VESSEL EI 1581, 6TH EDTION FILTER SEPERATOR. CATEGORY-M TYPE-S. HCS-322-1424 FACET

3 CM SERIES COALESCER CARTRIDGES EI 1581 6th EDTION CAT. M CM-22SB-5 FACET

1 SM SERIES SEPARATOR CARTRIDGE EI 1581 6th EDTION CAT. M SM-424FB-5 FACET

1 ARMSTRONG MODEL 21AR, AIR VENT, CAST IRON, 208PSI 21AR ARMSTRONG

1 AIR ELIMINATOR CHECK VALVE 3/4" MNPT GTP-2916-10 Gammon

1 3/4" BALL VALVE STAINLESS, LOCKABLE 22-061-11 LANCE

1 SPR. RETURN 3/4" BALL VALVE STAINLESS 22-061-41 LANCE

1 ADAPTOR-3/4" (SUMP DISCHARGE) 75-A-AL DIXON

1 DUST CAP-3/4" (SUMP DISCHARGE LIQUID TIGHT CAP) 75-DC-AL DIXON

1 VALVE, PRESSURE RELIEF, STEEL, 75PSI 3CRV00F 75PSI HYDROSEAL

1 1CC WATER PROBE GTP-9330-1 Gammon

21-B 1 FILTER VESSEL EI 1581, 6TH EDTION FILTER SEPERATOR. CATEGORY-M TYPE-S. HCS-322-1424 FACET

3 CM SERIES COALESCER CARTRIDGES EI 1581 6th EDTION CAT. M CM-22SB-5 FACET

1 SM SERIES SEPARATOR CARTRIDGE EI 1581 6th EDTION CAT. M SM-424FB-5 FACET

1 ARMSTRONG MODEL 21AR, AIR VENT, CAST IRON, 208PSI 21AR ARMSTRONG

1 AIR ELIMINATOR CHECK VALVE 3/4" MNPT GTP-2916-10 Gammon

1 3/4" BALL VALVE STAINLESS, LOCKABLE 22-061-11 LANCE

1 SPR. RETURN 3/4" BALL VALVE STAINLESS 22-061-41 LANCE

1 ADAPTOR-3/4" (SUMP DISCHARGE) 75-A-AL DIXON

1 DUST CAP-3/4" (SUMP DISCHARGE LIQUID TIGHT CAP) 75-DC-AL DIXON

1 VALVE, PRESSURE RELIEF, STEEL, 75PSI 3CRV00F 75PSI HYDROSEAL

1 1CC WATER PROBE GTP-9330-1 Gammon

22-A 1 DIFFERENTIAL PRESSURE GAUGE GTP-534-PB-30A Gammon

1 PRESSURE GAUGE 4", LM, 160PSI, L/F, 1/4NPT, SS 9699257 WIKA

2 MILLIPORE TESTING PORTS IN-OUT FLOW KIT-7 Gammon

22-B 1 DIFFERENTIAL PRESSURE GAUGE GTP-534-PB-30A Gammon

1 PRESSURE GAUGE 4", LM, 160PSI, L/F, 1/4NPT, SS 9699257 WIKA

2 MILLIPORE TESTING PORTS IN-OUT FLOW KIT-7 Gammon

23 1 HOSE REEL ,115V, ALUM INTERN TOP RIGHT W/AUX CRANK V-EPJ-24-25-26 LF HANNAY

HOSE REEL HOSE ROLLER GUIDE C-2 HANNAY

1 COUPLING VICTAULIC 2" 77 2" Victaulic

1 AIRCRAFT FUELING NOZZLE 295SA-0138 OPW Fuel

1 DRY-BREAK ACTUATOR 1.5" MNPT GTP-920-2 Gammon

1 DRY-BREAK DUST CAP FOR 920-1 ACTUATOR GTP-1428 Gammon

1 DRY-BREAK DISCONNECT 1.5" FNPT GTP-919-1 Gammon

1 DRY-BREAK DUST CAP FOR 919-1 DISCONNECT GTP-1768 Gammon

1 HOSE EI-1529, AVIATION FUELING HOSE, COUPLER MXM, W, CERT SIZE: 1.0" X 75'

25 1 3" X 8' ALUMINUM FLOATING & SUCTION ASSEMBLY 3X8AFS ABA-CON

1 SWIVEL-3" ALUM FOR SUBMERGE SERVICE (DOUBLE) FLANGED 3640-FJ0302 OPW ENG.

1 3" WAFER CHECK VALVE, VITON SEAL, DUCTILE IRON, EXTERIOR EPOXY LINED V0315DVTLS RITEPRO

1 ADAPTER-2" ALUMINUM (FLOATING SUCTION TEST CABLE PORT) 200-F-AL DIXON

1 DUST CAP-2" LOCKING (FLOATING SUCTION TEST CABLE PORT LIQUID TIGHT CAP) 200-A-AL DIXON

1 1/8" BRAIDED 304 STAINLESS STEEL TEST CABLE

26 1 TOTAL CONTROLS (SPA). METER, VEEDER-ROOT MECHANICAL REGISTER 1/10 USG 70015SPA2T TOTAL CONTROL

27 1 120VAC DUAL SINGLE STAGE WATER CONTROL SYSTEM GTP-1750-5-1-2-1-3-3-3-5(X2) Gammon

28 1 3" VALVE EXTERNAL EMERGENCY VALVE, FLANGED, 165˚ FUSIBLE LINK VALVE 346DI-0300-AV Morrison

29 1 REEL, GROUND 100' SPR/REWIND HGR-100 17-80 Hannay

1 CABLE, NYLON COVERED 100' GTP-1093HOV Gammon

1 STOP BALL GTP-1486 Gammon

1 CABLE STOP BALL CLAMP GTP-1487 Gammon

1 CLAMP HEAVY DUTY, AIR FORCE TYPE GTP-1101 Gammon

30 1 LEFT SIDE MOUNTED LADDER / DECK PLATFORM, SPRING CLOSED GATE (PAINTED OSHA YELLOW) ABA-SMCW-102 ABA-CON

31 1 MANUAL ONE PIECE CALIBRATED GAUGE STICK 12' (NOT SHOWN) (MANUAL GAUGE STICK) 12-Jan BAGBY

32 2 VALVE BUTTERFLY 2" VITON 310200-1101038B BRAY

33 1 VALVE BUTTERFLY 3" VITON 310300-1101038B BRAY

34 2 SPARE PLUGGED FITTING - 4" FNPT

36 1 1.5" ELECTRICAL POWER CONDUIT STUB

37 1 EXPLOSION PROOF CANOPY LIGHT FIXTURE EMI120X2G KILLARK

38 2 VALVE SWING CHECK 3/4" STAINLESS 46635K65 MCMASTER

39 1 PUMP BY-PASS VALVE, STEEL, 20-40 PSI BV2A-1-2-W-W BLACKMER

40 1 NEMA 7-9 EXPLOSION PROOF ENCLOSURE FURNAS

2 EXPLOSION PROOF PUMP ON-OFF SWITCH w/GREEN INDICATOR LIGHT 51SA2AA / XLRL-GH FURNAS

1 EXPLOSION FUELING OPERATION SELECTION SWITCH 51SA2AA FURNAS

1 EXPLOSION PROOF CANOPY LIGHT FIXTURE ON-OFF SWITCH 51SA2AA FURNAS

41 1 ALUMINUM ROLL DOOR SATIN FINISH W/LOCK 58"H X 78"W GORTITE

42 PRODUCT PIPING 1.0" AND LARGER, SCH10 304/304L STAINLESS STEEL, ASTM SA312 USA

43 PRODUCT PIPING 1.0" AND SMALLER, SCH40 304/304L STAINLESS STEEL, ASTM SA312 USA

44 FLANGES 304/304L S/S, 150# RAISED FACE S/O FLANGE, ASTM SA182. ELBOW 90-45 REDUCERS, SCH10 304/304L S/S, ASTM SA403WPW. FLANGE GASKETS-C4401 1/16" NON-ASBESTOS. BOLTS ASTM A193 GRADE 5 STAINLESS STEEL. NUTS - HEXAGON ASTM A193 GRADE 5. USA

45 INSTRUMENT TUBING: ASTM A269, .035 WALL, 304 STAINLESS. COMPRESSION FITTINGS: DK-LOK TUBE FITTINGS 316 S/S. STAINLESS STEEL THREAD TAPE MIL-T-27730A. USA

TI

TL

E:

10/7/2022

MAVEN CONSTRUCTION

& ENVIRONMENTAL, LLC

6550 ST. AUGUSTINE

ROAD SUITE 202

JACKSONVILLE, FL 32217

FIELD WIRING TO BE SIZED BY ELECTRICIAN

ACCORDING TO LOAD, VOLTAGE, AND

DISTANCE FROM POWER SUPPLY

ABA-CON INC.

P.O. BOX 308

TITUSVILLE, FL 32781

PHONE: (321) 567-4967

FAX: (321) 607 6805

WEB:

www.aba-con.com

JE

T-

A

TA

N K

EL

EC

TR

IC

AL

S

C H

EM

AT

IC

JOB NUMBER:

E-30

DRAWING NUMBER:

PROJECT CONTRACTOR:

PROPRIETARY AND CONFIDENTIAL

The information contained in this drawing is the sole property of ABA-CON Aviation Services. Any reproducton in part or as a whole is prohibited without written permission of ABA-CON Aviation Services.

DATE:

REVISIONS

DATE DESCRIPTION

SCALE: XX:XX

KM

DRAWN BY:

APPROVED BY:

SCALED FOR ANSI BWARNING!

1. 3 PHASE CIRCUIT TO PUMP. IF ANY HIGH LEG,

CONNECT TO L3.

2. THERE MUST BE AN INDIVIDUAL BREAKER AND

CIRCUIT PER HOSE REEL.

3. THE CONTROL, HOSE REEL, VESSEL SUMP

HEATER CIRCUIT, AND OPTIONAL EQUIPMENT

(IF EQUIPPED) CANNOT BE CONNECTED TO THE

PUMP MOTOR CIRCUIT IN ANY WAY! DOING SO

WILL VOID WARRANTY.

4. ANY MODIFICATIONS TO ELECTRICAL SYSTEM

WITHOUT WRITTEN APPROVAL WILL VOID

WARRANTY.

R

ED

4G

A.

RED 14GA.

OVERLOAD

RELAY

2 T1 T2 T3

L1 L2 L3

V M W

95 96

PUMP

MTR

5 HP

230 VOLT

1PH

JET-A PUMP CIRCUIT 2

ISSUING

1 ɸ 230VAC

21 FULL LOAD AMPS

COIL STRAPPED

FOR 220VAC

BREAKER PANEL

(BY OTHERS)

NEUTRAL

JET-A FUELING CABINET

ANTI

SIPHON

VALVE

CLOCK

LEVEL

GAUGE

ALARM

COPPER

CLAD

GROUND

STUD

STARTER ENCLOSURETANK

RED 10GA.

BLU 10GA.

BLK 10GA.

ISSUING

PUMP

ON/OFF

SWITCH

RED 14GA.

WHT 14 GA.

GRN 14 GA.

90% TANK CAPACITY

BATTERY

ALARM

BOX

RED 14GA.

WHT 14 GA.

EARTH GROUND

(BY OTHERS)

BLK 8 GA.

R

ED

4G

A.

LIGHT CIRCUIT

1 ɸ 120VAC

20 FULL LOAD AMP

BREAKER REQUIRED

BL

K

8G A.

LIGHT

ON/OFF

SWITCH

JET-A CONT CIRCUIT

1 ɸ 120VAC

20 FULL LOAD AMP

BREAKER REQUIRED

E-STOP

SHUNT TRIP

DISCONNECTS

ENTIRE PANEL

WHT 14 GA.

BLK 8 GA.

BLK 8 GA.

GRN 14 GA.

WHT 14 GA.

BLU 8 GA.

RED 8 GA.

BLK 8 GA.

WHT 14 GA.

HOSE REEL

1ɸ 120VAC

20 FULL LOAD AMPS

BREAKER REQUIRED

FILTER SUMP 1

GAMMON

XXX VAC A B C D

A B C D

D

EAD

M

AN

W

ATER

D

EAD

M

AN

W

ATER

A

B

C

D

POWER ON

INTRINSICALLY SAFE INPUTS ONLY

B D

RELAY DIAGRAM

1 5

RELAY DIAGRAM

1 5

GAMMON

GTP 9330-1

WHT

BLK

WATER (B)

GTP-9316-3

WATER (D)

GTP-9316-3

WATER

IN-FUEL ID

LIGHT

WHT

BLK

GAMMON

GTP 9330-1

HEATER

BLK 8 GA.

WHT 12 GA.

BLK 12GA.

WHT 12GA.

RED 12GA.

BLU 12GA.

BLK 8GA.

HOSE REEL

MOTOR

R

ED

4G

A.

RED 14GA.

OVERLOAD

RELAY

2 T1 T2 T3

L1 L2 L3

V M W

95 96

PUMP

MTR

5 HP

230 VOLT

1PH

JET-A PUMP CIRCUIT 1

RECEIVING

1 ɸ 230VAC

21 FULL LOAD AMPS

COIL STRAPPED

FOR 220VAC

RED 10GA.

BLU 10GA.

BLK 10GA.

RECEIVING

PUMP

ON/OFF

SWITCH

R

ED

4G

A.

BLU 8 GA.

RED 8 GA.

BLK 8 GA.

WHT 14 GA.

PUMP ID

LIGHT

PUMP ID

LIGHT

FILTER SUMP 2

AB

AutoCAD SHX Text L1

AutoCAD SHX Text L2

AutoCAD SHX Text L3

AutoCAD SHX Text L1

AutoCAD SHX Text L1

AutoCAD SHX Text L1

AutoCAD SHX Text L1

AutoCAD SHX Text L2

AutoCAD SHX Text L3

TITUSVILLE, FL 32781

PHONE: (321) 567-4967

FAX: (321) 607 6805

WEB:

www.aba-con.com

TI

TL

E:

JE

T-

A P&

ID

JOB NUMBER:

M-40

DRAWING NUMBER:

PROJECT CONTRACTOR:

PROPRIETARY AND CONFIDENTIAL

The information contained in this drawing is the sole property of ABA-CON Aviation Services. Any reproducton in part or as a whole is prohibited without written permission of ABA-CON Aviation Services.

DATE:

REVISIONS

DATE DESCRIPTION

SCALE: XX:XX

KM

DRAWN BY:

APPROVED BY:

SCALED FOR ANSI B

JET-A TANK EQUIPMENT AREA

JET-A TANK

SR

TR

AN

SPO

R

T D

ELIVER

Y

MS MSF

OUTIN

T

LI

FLOATING SUCTION

TRANSPORT

SHUTOFF VALVE

*NOTE: 1 PER

SYSTEM

PR

TANK

FILL

SHUTOFF

VALVE

95%

SHUTOFF

VALVE

OVERFILL

VALVE

PRE-CHECK

95% CAPACITY

FLOAT VALVE

TANK

LEVEL

GAUGE

NOTE:

2 PER

SYSTEM

LOCKABLE

BALL VALVE

HAND

PUMP

TANK SUCTION

SHUT-OFF VALVE

A

90% ALARM

4"

TUBING

3/8"

TUBE

3/4"

PIPE

3/4"

PIPE

3/4"

PIPE

3"

PIPE

3"

PIPE

3"

PIPE

FLOW METER

C. V.STR

C. V.

C. V.

C. V.

FDP

FILTER

UPDRAFT

VENT

SPRING CLOSED

BALL VALVE

PUMP

ANTI-SIPHON

VALVE

FIRE

VALVE

FUEL HOSE

HOSE REEL

FUELING NOZZLE

LEGEND

FI LI

FLOW

INDICATOR

LEVEL

INDICATOR

FIRE

VALVE

RELAX

CHAMBER

RC

SUMP

RECOVERY

SR

PRESSURE

RELIEF

AIR

RELIEF

SPRING

CLOSED BALL

VALVE

MS

MILLIPORE

SAMPLE

VS

VISUAL

SAMPLER

HAND

PUMP

FILTER

VESSEL

F

FLOW

METER

FUEL

HOSE

PUMP

BALL

VALVE

LINE

STRAINER

ORIFICE FLOAT

VALVE

BUTTERFLY

VALVE

CHECK

VALVE

DIAPHRAGM

VALVE

ELECTRICALLY

ACTUATED

VALVE

T

CAMLOK

UPDRAFT

VENT

PRESSURE

VACUUM

VENT

EMERGENCY

VENT

VAPOR

RECOVERY

ADAPTER

PR

PRESSURE

GAUGE

FILTER

VESSEL

DIFFERENTIAL

PRESSURE

FILTER VESSEL

WATER

DETECTOR

PROBE

4" TUBING

8" TUBING

2" TUBING

4" PIPING

2" PIPE

3" PIPE

CONDUIT/

WIRING

HR

FUEL HOSE

HOSE REEL

FUELING NOZZLE

FILTER

SUMP

HEATER

BYPASS

VALVE

VA

VACUUM

GAUGE

IM

INTERSTITIAL

GAUGE / MONITOR

SP

SUBMERSIBLE

PUMP

MECHANICAL

FLOAT

ACTUATED

SHUT-OFF

VALVE

MECHANICAL

ANTI-SIPHON

VALVE

WT

WASTE

TANK

4" PIPE

1-1

4" PIPING

8" TUBING

1-1

2" PIPING

1" PIPING

2-1

2" PIPE

3-1

2" PIPE

6" PIPE

10/7/2022

MAVEN CONSTRUCTION

& ENVIRONMENTAL, LLC

6550 ST. AUGUSTINE

ROAD SUITE 202

JACKSONVILLE, FL 32217

PUMP

MS MSF

OUTIN

3/4"

PIPE

FDP

FILTER

AIRCRAFT

1" X 75' HOSE

HR

1/2"

TUBE

1/2"

TUBE

2"

PIPE

2"

PIPE

2"

PIPE

2"

PIPE

2"

PIPE

3"

PIPE

2"

PIPE

PR

C. V.

A06 Drawings - 7,500 GALLON UL2085 DOUBLE WALL_Big Cypress National Preserve.pdf
2227--CVR.pdf
Sheets and Views
-CVR
2227--10 NOTES.pdf
Sheets and Views
-10 NOTES
2227--20 JET-A TANK AND EQUIPMENT.pdf
Sheets and Views
-20 JET-A TANK AND EQUIPMENT
2227--30 JET-A TANK ELECTRICAL SCHEMATIC.pdf
Sheets and Views
-30 JET-A TANK ELECTRICAL SCHEMATIC
2227--40 JET-A P&ID.pdf
Sheets and Views
-40 JET-A P&ID

File details come from the government source that posted it. Updated .