SOW_FireDetectionSysInspTest.doc
DOC document 783 KB Posted
- Attached to
- Fire Detection System Inspect and Test Federal contract opportunity
- Solicitation number
- 70Z08524P225
About this file
This statement of work describes requirements for a contractor to inspect and test the fire detection system on a Coast Guard cutter. The contractor must inspect and test all field devices on the Consilium Marine fire alarm system, including the main control panel, detectors, pull stations, and bells. The inspection and testing must follow NFPA 72 standards and Coast Guard technical publication 9556. Annual testing requirements include checking panel functionality, batteries, horns, strobes, detectors, and replacing batteries as specified. The contractor must submit inspection reports and certify the system is operating properly after repairs. Technical representative support from Consilium Marine is required. The related solicitation is for this fire detection system inspection and testing work with the Department of Homeland Security Coast Guard as the agency.
View the file
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
43600_JSP_0623_(NSC 6 AF)
WORK ITEM 1: Fire Detection System, Inspect and Test
1. SCOPE
1.1 Intent. This work item describes the requirements for the Contractor to inspect and test Fire Detection System.
TABLE 1 – fire alarm system
| Model No./ MANUFACTURER |
| DESCRIPTION |
| coast guard drawing / tech pub |
| F400-101-101103A / Consilium Marine US |
| Fire Alarm System complete with Main Control and Display Panel, Control/Repeater Panel, Dual Optical Heat and Smoke Detectors, Optical Smoke Detectors, Analog Heat Detectors, Manual Call Points, Pull Stations, Bells, Field Server Profibus DP Gateway Complete in enclosure. |
| *750-WMSL-436-011 / 9556 |
*Applicable sheet are referenced as NF6-AF ONLY.
1.2 Government-furnished property.
None.
2. REFERENCES
Coast Guard Drawings
Coast Guard Drawing 418A-WMSL-100-001, Rev B, General Arrangements
Coast Guard Drawing 418A-WMSL-801-001, Rev A, Booklet of General Plans
Coast Guard Drawing 750-WMSL-436-011, Rev E, Fire Detection Sys Deck Plan (ASC436009)
Coast Guard Drawing 750-WMSL-436-013, Rev C, Fire Detection Sys Cable Running Sheets (ASC436010) Coast Guard Drawing 750-WMSL-436-014, Rev -, Fire Detection and Control System Schematic (ASC436028) Coast Guard Publications
Surface Forces Logistics Center Standard Specification 0000 (SFLC Std Spec 0000), 2022, General Requirements
Surface Forces Logistics Center Standard Specification 3041 (SFLC Std Spec 3041), 2022, Shipboard Electrical Cable Test
Surface Forces Logistics Center Standard Specification 3042 (SFLC Std Spec 3042), 2022, Shipboard Electrical Cable Removal, Relocation, Splice, Repair, and Installation
Surface Forces Logistics Center Standard Specification 6310 (SFLC Std Spec 6310), 2022, Requirements for Preservation of Ship Structures
Coast Guard Technical Publication (TP) 9556, SWSB 436, June 2018, Fire Detection System (For Hull 755)
Other References
National Fire Protection Association (NFPA) 72, 2019 Edition, National Fire Alarm and Signaling Code
3. REQUIREMENTS
3.1 General.
3.1.1 CIR. The Contractor must submit a CIR for the inspections listed in the following paragraph(s):
· 3.3 System inspect and test.
3.1.2 Tech Rep. The Contractor must provide the services of a Qualified Technical Representative, who is familiar with the Consilium Marine Fire Detection System (Herbert S. Hiller, a division of The Hiller Companies) to accomplish the following tasks – on site:
· Provide manufacturer's proprietary information, software, and tools pertinent to the equipment/system.
· Assist with proper repair methods, and ensure compliance with manufacturer's procedures and standards during disassembly, inspection, repair, modification, calibration, and reassembly of the equipment/system.
3.1.2.1 Ensure that the Tech Rep is a Qualified Technical Representative of Consilium-Marine Fire Detection System (Herbert S. Hiller, a division of The Hiller Companies).
3.1.2.2 Submit the Tech Rep’s name and résumé to the COR at the Arrival Conference.
3.1.2.3 Point of Contact:
· Mr. Magnus Edelius
· Service Manager
· Mobile: +1 954 257 1358
· Consilium Marine US
· e-Mail: Magnus.Edelius@consiliumsafety.com
OR
· Herbert S. Hiller
· A division of The Hiller Companies, Inc.
· 401 Commerce Point
· Harahan, LA 70123
· (504) 736-0008
3.1.3 Protective measures. The Contractor must furnish and install all protective measures in accordance with SFLC Std Spec 0000, paragraph 3.3.3 (Vessel component, space, and equipment protection).
3.1.4 Interferences. The Contractor must handle all interferences in accordance with SFLC Std Spec 0000, paragraph 3.3.5 (Interferences). Known interferences include, but are not limited to the below-listed:
· Sheathing
· Bulkhead insulation
· Piping
· Electrical Cables
3.1.5 Electrical work. The Contractor must accomplish all electrical work in accordance with SFLC Std Spec 3042, and test cables in accordance with SFLC Std Spec 3041.
NOTE
Coast Guard personnel will operate all shipboard machinery and equipment.
3.1.6 Operational test, initial. Prior to commencement of work, the Contractor must witness Coast Guard personnel perform an initial operational test of all items or shipboard devices to be disturbed, used, repaired, or altered, to demonstrate existing operational condition. Submit a CFR.
3.2 Fire detection system. The Fire Detection System components and zone loop wiring is shown on the Coast Drawing 750-WMSL-436-011. The Coast Drawings and Tech Pub referenced in the Para 2 provides information of the Fire Detection System on the Cutter.
3.2.1 Password protection. Fire alarm panel is password protected for software. Prior to start work on this item (i.e. Maximum 5 days prior to Tech Rep arrival) Tech Rep must request Password through Herbert S. Hiller a division of The Hiller Companies and Coast Guard Inspector.
3.3 Fire detection system inspect and test. The Contractor with Tech Rep support must perform inspection and test of the Fire Alarm System in accordance with NFPA-72 (i.e., National Fire Alarm and Signaling Code) and TP 7556. Annual Fire Alarm Testing requirement is listed in Table 1. The Contractor must perform 100 % test on all field devices (i.e., Alarm-Initiating Devices and Circuits) listed in Table 1. Submit CIR. Submit CIR.
TABLE 1 – NFPA-72 ANNUal fire alarm test
DESCRIPTION
Test and Visual Inspection of Panel Functionality
Test Panel Battery Charger
Battery Discharge Test
Test and Visual Inspection Horns, Strobes, Chimes and Bells
Test and Visual Inspection of Smoke Detectors
Test and Visual Inspection of Heat Detectors
Replace Sealed Lead Acid Battery every Five Years (Verify Expiration Date on the Battery and Submit a CFR)
Smoke and Heat Detectors: Replacement is recommended every 10 Years
NOTE
The Contractor must perform only applicable test on the Fire Alarm System. Some of the test identified on the attached Data Sheet may not be required on installed Fire Alarm System on the Cutter.
3.3.1 The Contractor must perform applicable test on Fire Alarm System with assistance from Tech Rep. Submit a CFR.
3.3.1.1 Perform applicable test as identified in Figure 1A-through Figure 1H (i.e. Annual Fire Alarm System Test and Inspection Records).
3.3.1.2 Verify signals from Fire Alarm Control Panel to Machinery Control and Monitoring System (i.e. MCMS) display console.
3.3.2 Certify that Fire Alarm System on the Cutter is operating properly (i.e. Figure 1H).
NOTE
Coast Guard personnel will operate all shipboard machinery and equipment.
3.4 Operational test – post repairs. After completion of work, the Contractor must witness an operational test (by Coast Guard personnel) of all items or shipboard devices that have been disturbed, used, repaired, altered, or installed, to prove that they are in satisfactory operating condition. Submit a CFR.
3.5 Touch-up preservation. The Contractor must prepare and coat all disturbed exterior and interior surfaces to match existing adjacent surfaces, in accordance with SFLC Std Spec 6310, Appendix A (Cutter and Boat Exterior Painting Systems) and Appendix B (Cutter and Boat Interior Painting Systems), respectively, and as applicable. Abide by all touch-up requirements outlined in SFLC Std Spec 0000, Appendix A (Requirements for Preservation of Ship Structures).
4. NOTES
Figure 1A: ANNUAL FIRE ALARM SYSTEM TEST AND INSPECTION RECORDS
Figure 1B: ANNUAL FIRE ALARM SYSTEM TEST AND INSPECTION RECORDS
Figure 1C: ANNUAL FIRE ALARM SYSTEM TEST AND INSPECTION RECORDS
Figure 1d: ANNUAL FIRE ALARM SYSTEM TEST AND INSPECTION RECORDS
Figure 1E: ANNUAL FIRE ALARM SYSTEM TEST AND INSPECTION RECORDS
Figure 1F: ANNUAL FIRE ALARM SYSTEM TEST AND INSPECTION RECORDS
Figure 1G: ANNUAL FIRE ALARM SYSTEM TEST AND INSPECTION RECORDS
Figure 1H: ANNUAL FIRE ALARM SYSTEM TEST AND INSPECTION RECORDS
File details come from the government source that posted it. Updated .