50014-0003B.pdf
PDF 10 MB Posted
- Attached to
- Boiler Replacement To Replace Boiler State and local contract opportunity
- Solicitation number
- 50014-0003B
- Issued by
- Orleans Parish, New Orleans City, Louisiana
About this file
This is a comprehensive set of architectural and engineering design documents for a Boiler Replacement project at Southern University at New Orleans, specifically for the Arts, Humanities & Social Science Building and Gymnasium. The project is being managed by the State of Louisiana's Division of Administration, Office of Facility Planning and Control, under Governor Jeff Landry's administration. The documents detail the replacement of existing boilers with new condensing stainless steel firetube boilers (Lochinvar FCB 2000N models) in two locations - the Arts and Humanities building and the Gymnasium. The project number is 19-671-22-01, with state building IDs S27481 and S00303, and the site code is 1-36-007.
The design documents include detailed mechanical, electrical, and architectural plans for demolishing existing boiler systems and installing new boilers, associated pumps, air separators, compression tanks, and related infrastructure. The new boilers have a maximum input of 1,999,000 Btu/Hr, with an output of 1,923,000 Btu/Hr and high thermal efficiency of 96.2%. The project includes electrical connections, piping modifications, and supporting systems like variable speed pumps and combustion air fans. The design emphasizes energy efficiency, proper installation practices, and compliance with current building and mechanical codes. The documents are dated 06/18/2025 and were prepared by Parish Engineering, indicating a comprehensive approach to modernizing the university's heating infrastructure.
View the file
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET NUMBER
SHEET NAME
DATE:
REVISIONS
DRAWN BY:
CHECKED BY:
PROJECT #:
SHEET INFORMATION
SEAL
PROJECT INFORMATION
All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.
7600 Innovation Park Drive
Baton Rouge, LA 70820
225.332.0222 parisheng.com
COVER
COVER SHEET
CTD/SPG
LJB/SPG
06-18-2025
25-040
B O
IL
E
R R
E P
L A
C E
M E
N T
A R
T S
H
U M
A N
IT
IE
S
S O
C
IA
L S
C
IE
N C
E B
U
IL
D
IN
G
G Y
M N
A S
IU
M
S
U N
O N
E W
O R
L E
A N
S
L A
BOILER REPLACEMENT
ARTS, HUMANITIES & SOCIAL SCIENCE BUILDING & GYMNASIUM
SOUTHERN UNIVERSITY AT NEW ORLEANS
NEW ORLEANS, LOUISIANA
PROJECT NO.: 19-671-22-01, F.19002574
STATE BUILDING ID:
S27481 - ARTS, HUMAINTIES & SOCIAL SCIENCES
S00303 - GYMNASIUM
SITE CODE: 1-36-007
STATE OF LOUISIANA
JEFF LANDRY, GOVERNOR
DIVISION OF ADMINISTRATION
TAYLOR F. BARRAS, COMMISSIONER OF ADMINISTRATION
OFFICE OF FACILITY PLANNING AND CONTROL
ROGER E. HUSSER, JR., DIRECTOR
SOUTHERN UNIVERSITY SYSTEM
KENNETH DAWSON - SYSTEM DIRECTOR OF FACILITY PLANNING
BID DOCUMENTS
06/18/2025
VINCITY MAP
N
PROJECT AREA
SHEET INDEX
MECHANICAL
COVER COVER SHEET
M0.0 MECHANICAL COVER SHEET
M1.0 MECHANICAL PLAN
M1.1 ENLARGED MECHANICAL PLAN
M1.2 GYMNASIUM MECHANICAL PLAN
M1.3 GYMNASIUM ENLARGED MECHANICAL PLAN
M2.0 MECHANICAL DETAILS
M2.1 MECHANICAL DETAILS
M3.0 MECHANICAL SCHEDULES
ELECTRICAL
E0.0 ELECTRICAL COVER SHEET
E1.0 ARTS & HUMANITIES ELECTRICAL PLAN
E1.1 ARTS & HUMANITIES ENLARGED ELECTRICAL PLAN
E1.2 GYMNASIUM ELECTRICAL PLAN
E1.3 GYMNASIUM ENLARGED ELECTRICAL PLANS
E2.0 ELECTRICAL DETAILS
06/18/2025
MECHANICAL GENERAL NOTES
1. ALL WORK BY CONTRACTORS SHALL CONFORM TO ALL APPLICABLE FEDERAL, STATE AND LOCAL BUILDING CODES, INCLUDING THE CURRENT INTERNATIONAL ENERGY CONSERVATION CODE.
2. MATERIALS FURNISHED UNDER THE CONTRACT SHALL BE NEW & SHALL BEAR THE UL LABEL WHERE APPLICABLE, UNLESS NOTED OTHERWISE. ALL WORK SHALL BE GUARANTEED AGAINST DEFECTIVE MATERIALS & WORKMANSHIP FOR A PERIOD OF NOT LESS THAN ONE YEAR AFTER
COMPLETION & ACCEPTANCE BY THE OWNER, LONGER IF STATED OTHERWISE ELSEWHERE IN THE SPECIFICATION.
3. CONTRACTOR SHALL INSTALL SYSTEMS WITHOUT INTERFERENCE & PROVIDE MANUFACTURER'S RECOMMENDED AIR & SERVICE CLEARANCES. CONTRACTOR SHALL COORDINATE WITH ALL TRADES & DISCIPLINES.
4. MECHANICAL CONTRACTOR SHALL COORDINATE WITH GENERAL CONTRACTOR ON LOCATION OF ALL FIRE & SMOKE WALL PENETRATIONS. GENERAL CONTRACTOR SHALL FRAME OUT OPENING AS REQUIRED FOR LIFE SAFETY DAMPERS. PROVIDE LIFE SAFETY DAMPERS WHERE SHOWN ON
DRAWINGS AND WHERE REQUIRED BY NFPA AND LOCAL BUILDING CODES.
5. ALL FIRE DAMPERS SHALL BE 2-HOUR RATED UNLESS SPECIFIED OR NOTED OTHERWISE ON DRAWINGS AND/OR SPECIFICATIONS.
6. SEAL ALL FIRE WALL PENETRATIONS (DUCT, PIPE, ETC.) WITH UL-LISTED FIRE CAULK IN ACCORDANCE WITH NFPA 101.
7. MECHANICAL CONTRACTOR SHALL COORDINATE BETWEEN ELECTRICAL AND OTHER TRADES FOR PENETRATIONS AT WALLS, FLOORS AND ROOFS, EXACT EQUIPMENT LOCATIONS, AND REQUIRED EQUIPMENT SERVICE AND AIR FLOW CLEARANCE.
8. INSTALLATION OF DUCTWORK SHALL TAKE PRECEDENCE OVER INSTALLATION OF PLUMBING PIPING THAT IS NOT GRADE SENSITIVE (SEWER, STORM DRAINAGE, GREASE WASTE, ETC.) AND ELECTRICAL CONDUIT. CONTRACTOR TO COORDINATE CEILING SPACE AVAILABLE, EXACT
MECHANICAL ROOM LAYOUT, DUCT AND PIPE ROUTING AND EXACT EQUIPMENT LOCATIONS WITH GENERAL, ELECTRICAL, STRUCTURAL AND PLUMBING CONTRACTORS. PROVIDE OFFSETS AND TRANSITIONS AT OBSTRUCTIONS WHERE REQUIRED AT NO ADDITIONAL COST TO THE OWNER.
9. MECHANICAL CONTRACTOR SHALL COORDINATE WITH GENERAL CONTRACTOR AND ARCHITECT PRIOR TO INSTALLATION OF THERMOSTATS/TEMPERATURE SENSORS ON WALL. COORDINATE THERMOSTATS/TEMPERATURE SENSORS WITH ALL WALL MOUNTED FURNISHINGS (ART, SCREENS, FURNITURE, ETC.). LOCATE THERMOSTATS AND HUMIDISTATS 4' ABOVE FINISHED FLOOR UNLESS OTHERWISE NOTED.
10. CONTRACTOR SHALL VISIT THE SITE FOR INSPECTION REGARDING ANY WORK REQUIRED TO COMPLETE THE SCOPE OF WORK FOR THE PROJECT PRIOR TO BID. THERE SHALL BE NO ADDITIONAL COST TO THE OWNER FOR BIDDERS AWARDED THE WORK FOR FAILURE TO EXAMINE SITE
PRIOR TO BID.
11. CONTRACTOR SHALL REVIEW THE CONTRACT DOCUMENTS AND VISIT THE SITE AND COORDINATE DUCT, PIPE AND EQUIPMENT SIZES AND ROUTING. CONTRACTOR SHALL NOTIFY THE ARCHITECT AND ENGINEER WHERE DISCREPANCIES OCCUR BETWEEN CONTRACT DOCUMENTS AND
EXISTING CONDITIONS.
12. CONTRACTOR SHALL REVIEW CEILING SPACE AND MECHANICAL ROOM SPACE AVAILABLE FOR DUCT, PIPING AND EQUIPMENT AND MAKE REQUIRED ALLOWANCES FOR THE SIZE AND ROUTING OF DUCT, PIPING AND EQUIPMENT.
13. MECHANICAL CONTRACTOR TO REVIEW CEILING SPACE AVAILABLE AND VERIFY FIELD MEASUREMENTS AND COORDINATION DRAWINGS PRIOR TO FABRICATING DUCT. BRANCH DUCT RUNS SHOWN DIAGRAMMATICALLY; CONTRACTOR SHALL ROUTE BRANCH DUCT RUNS IN MOST DIRECT
MANNER.
14. COORDINATE EXACT LOCATION OF ALL SLAB, FLOOR, WALL AND ROOF PENETRATIONS WITH EXISTING STRUCTURAL BEAMS, JOIST AND COMPONENTS. DO NOT CUT OR MODIFY EXISTING STRUCTURAL COMPONENTS WITHOUT APPROVAL FROM STRUCTURAL ENGINEER.
15. CONTRACTOR SHALL VERIFY EQUIPMENT TO BE SUPPLIED TO PROJECT CAN BE INSTALLED IN SPACE PROVIDED AND ALL SERVICE AND AIRFLOW CLEARANCES MAINTAINED PRIOR TO ORDERING EQUIPMENT. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY MODIFICATIONS REQUIRED FOR
EQUIPMENT THAT IS SUPPLIED THAT IS DIFFERENT THAN EQUIPMENT THAT IS BASIS OF DESIGN.
16. UNDER NO CIRCUMSTANCES SHALL EQUIPMENT AND RELATED SYSTEM COMPONENTS FOUND POSITIVE FOR MOLD, MILDEW, ASBESTOS, HARMFUL BACTERIA OR ANY OTHER CONTAMINATION BE PLACED INTO SERVICE.
17. INSTALL DUCT SLEEVES IN WALLS AS HIGH AS POSSIBLE, DUCT SLEEVE SHALL EXTEND PAST WALL PENETRATION ON BOTH SIDES MINIMUM 24". RETURN AIR TRANSFER SLEEVES SHALL BE PROVIDED WITH TWO (2) DUCT ELBOWS.
18. COORDINATE ALL UNDERGROUND PIPING & WORK WITH EXISTING SYSTEMS, INCLUDING EXISTING UTILITIES, SEWER, GAS, DOMESTIC WATER, CHILLED/HEATING WATER, ELECTRIC DUCT BANKS AND POWER. NOT ALL EXISTING SYSTEMS SHOWN. COORDINATE ALL EXISTING SYSTEMS PRIOR
TO BEGINNING WORK. MARKED UTILITIES AND EXISTING SYSTEMS DAMAGED BY THE CONTRACTOR SHALL BE REPLACED AND REPAIRED BACK TO ORIGINAL CONDITION BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE CONSTRUCTION CONTRACT.
19. MODEL NUMBERS SCHEDULED/SPECIFIED REPRESENT THE TYPE AND QUALITY OF EQUIPMENT REQUIRED TO MEET THE DESIGN REQUIREMENTS. CONTRACTOR SHALL REVIEW SUBMITTALS AND VERIFY EQUIPMENT SIZES, QUALITY AND PERFORMANCE REQUIREMENTS MEET
SPECIFICATIONS PRIOR TO SUBMITTING FOR APPROVAL. EQUIPMENT THAT DIFFERS FROM BASIS OF DESIGN IS SUBJECT TO REJECTION. CONTRACTOR TO COORDINATE ALL DIFFERENCE IN EQUIPMENT WITH STRUCTURAL, ELECTRICAL AND PLUMBING CONTRACTORS.
20. ALL CONDENSATE LINES SHALL BE RIGID COPPER, INSULATED WITH CELLULAR FOAM UNLESS NOTED OTHERWISE OR SUBMITTED AND APPROVED BY MECHANICAL ENGINEER. SUPPORT WITH UNISTRUT PIPE EVERY 4' AND AT TURNS. PROVIDE NEOPRENE SLEEVES BETWEEN UNISTRUT AND
COPPER CONDENSATE LINE.
21. DUCT SIZES SHOWN ARE SHEET METAL SIZES. ALLOWANCES HAVE BEEN INCLUDED FOR INTERNAL LINER WHERE APPLICABLE.
22. COORDINATE EXACT LOCATION OF AIR DEVICES WITH NEW AND EXISTING LIGHTS TO BE INSTALLED PRIOR TO CONSTRUCTION.
23. EXPOSED DUCTWORK SHALL BE PAINT GRIPPED SHEET METAL UNLESS INDICATED OTHERWISE. ALL EXPOSED DUCT TO BE PAINTED IN FIELD BY PAINTING CONTRACTOR DURING CONSTRUCTION. COORDINATE WITH ARCHITECT & MECHANICAL ENGINEER PRIOR TO INSTALLATION OF
EXPOSED DUCT AND COLOR. EXPOSED DUCTWORK SHALL BE FREE OF SIZE MARKS OR ASSEMBLY CODE NUMBERS; ALL MARKS SHALL BE ON THE INSIDE OF DUCTWORK. KEEP OUTSIDE SURFACES OF DUCT CLEAN DURING FABRICATION. BANDS SHALL JOIN ON TOP, CONCEALED FROM NORMAL VIEW OF THE DUCT AND SPIRALS SHALL BE CONTINUOUS. THREADED RODS FROM HANGER STRAPS SHALL BE NEATLY CLIPPED AND SECURED WITHOUT EXCESS. GREATER ATTENTION TO APPEARANCE FOR EXPOSED DUCT IS EXPECTED AND DENTED/SCARRED DUCTS SHALL NOT
BE ACCEPTABLE.
24. PROVIDE ELECTRICAL DISCONNECTS FOR MECHANICAL EQUIPMENT (VAV BOXES, FANS, VFD'S, ETC.) FACTORY INSTALLED BY EQUIPMENT MANUFACTURER UNLESS NOTED OTHERWISE. COORDINATE WITH ELECTRICAL CONTRACTOR.
25. DO NOT ROUTE PIPING CONTAINING WATER OVER ELECTRICAL EQUIPMENT.
26. PROVIDE PERMANENT LABELS FOR ALL SCHEDULED EQUIPMENT. LABELS SHALL BE MINIMUM 3/8" ENGRAVED BLACK LETTERS ON WHITE BACKGROUND, CONSTRUCTED OF MINIMUM 1" WIDE, LENGTH AS REQUIRED LAMINATED PLASTIC. SECURELY FASTENED TO EQUIPMENT WITH STAINLESS
STEEL OR NONCORRODING HARDWARE. STICK ON LABELS NOT ACCEPTABLE.
27. EXHAUST OUTLETS SHALL BE LOCATED MINIMUM 10' FROM ANY AIR INTAKE OR OPERABLE BUILDING OPENING.
28. INDOOR MINISPLITS, FAN COIL UNITS AND CEILING CASSETTES SHALL HAVE GRAVITY DRAINAGE WHERE POSSIBLE. PROVIDE WITH INTEGRAL CONDENSATE PUMPS WHERE NOT POSSIBLE.
29. PROVIDE RETURN AIR GRILLES OPEN TO RETURN AIR PLENUM WITH SOUND ATTENUATING BOOT ON REAR OF GRILLE (RIGID DUCT WITH INSULATED LINER & TWO ELBOWS, END OPEN TO RETURN AIR PLENUM). CONTRACTOR HAS OPTION TO PROVIDE PRICE MODEL #RAC RETURN AIR
CANOPY ON REAR OF RETURN AIR GRILLES OPEN TO RA PLENUM IN LIEU OF SOUND ATTENUATING BOOT.
30. ELECTRONIC BALANCING DAMPERS : MANUAL DAMPER AT INACCESSIBLE LOCATIONS:
30.1. PROVIDE REMOTE BALANCING DAMPER WITH POSITION INDICATOR AT INACCESSIBLE MANUAL VOLUME DAMPERS
30.2. INACESSIBLE LOCATIONS:
30.2.1. ABOVE GYPSUM BOARD/HARD CEILING
30.2.2. WHERE LOCATED HIGHER THAN 4'-0" ABOVE ACCESSIBLE CEILING TILE
30.2.3. WHERE LOCATED ABOVE 14'-0" FROM FINISHED FLOOR
30.2.4. REFER TO ARCHITECTURAL REFLECTED CEILING DRAWINGS FOR REFLECTED CEILING PLAN
30.3. ELECTRONIC BALANCING DAMPER SHALL BE PROVIDED WITH POSITION INDICATOR AND SHALL BE GREENHECK MODEL RBDR-50 (ROUND) & RBD-10 (RECTANGULAR) OR APPROVED EQUAL, UNLESS INDICATED OTHERWISE.
30.4. REMOTE BALANCING DAMPER SHALL BE 12 VOLT DC POWER BALANCE SYSTEM ( DAMPER, PULSE ACTUATOR , CAT 5 CABLE, WALL OR CEILING PLATE AND HAND HELD POWER PACK). PROVIDE WALL/CEILING ACCESS PORT ON WALL WITHIN CLOSEST MECHANICAL ROOM OR ABOVE
ACCESSIBLE CEILING MOUNTED ON WALL. ALL ACCESS PORTS TO BE PROPERLY LABELED NUMERICALLY BY RESPECTIVE AIR SYSTEM & ROOM DAMPER SERVES. COORDINATE WITH MECHANICAL ENGINEER PRIOR TO LABELING & COORDINATE LOCATION WITH MECHANICAL ENGINEER & ARCHITECT PRIOR TO INSTALLING ANY ACCESS PORT ABOVE ACCESSIBLE CEILINGS. PROVIDE TILE IDENTIFICATION WHERE LOCATED ABOVE CEILING, PROVIDE DRAWING IDENTIFYING PORT LOCATION & PORT SCHEDULE AS PART OF CLOSE OUT DOCUMENTS.
31. PROVIDE U.L. LISTED SMOKE DETECTORS IN THE MAIN SUPPLY DUCT AND RETURN ON THE DOWNSTREAM SIDE OF THE FILTERS IN ALL RECIRCULATING AIR SYSTEMS HANDLING OVER 2000 C.F.M. NOTE: SMOKE DETECTORS TO BE WIRED TO BUILDING FIRE ALARM SYSTEM BY FIRE ALARM CONTRACTOR, FIRE ALARM CONTRACTOR IS TO PROVIDE AND INSTALL ALL WIRING, TERMINATIONS, ETC. TO PROVIDE A COMPLETE, PROPERLY FUNCTIONING AND OPERATING SYSTEM.
32. PROVIDE SMOKE DAMPER IN THE MAIN SUPPLY & RETURN DUCT IN ALL AIR HANDLING UNITS HANDLING OVER 15,000 CFM. SMOKE DAMPERS TO BE INTERCONNECTED TO SMOKE DETECTORS.
33. PROVIDE ACCESS PANELS FOR EQUIPMENT,VALVES, DAMPER, ETC. LOCATED ABOVE A NON ACCESSIBLE CEILING. ACCESS PANELS SHALL BE LARGE ENOUGH FOR ALL REQUIRED MAINTENANCE, ADJUSTMENT, ECT. PROVIDE MULTIPLE ACCESS PANELS AS REQUIRED. COORDINATE COLOR
AND LOCATIONS WITH ARCHITECT. PROVIDE FIRE AND/ OR SMOKE RATED ACCESS PANELS WHERE REQUIRED IN RATED CEILINGS. REFERENCE ARCHITECTURAL DRAWINGS FOR RATED CEILING LOCATIONS. WHERE ACCESS PANELS ARE SHOWN ON ARCHITECTURAL REFLECTED CEILING PLAN, COORDINATE EXACT LOCATION OF EQUIPMENT, DEVICES, ETC. WITH ACCESS PANEL LOCATIONS.
34. PROVIDE TEMPORARY CAPS/PLUGS/COVERING ON ALL OPEN ENDED PIPING & DUCT DURING CONSTRUCTION TO PREVENT DIRT/DEBRIS FROM ENTERING PIPE/DUCT SYSTEMS.
35. PROVIDE PROTECTIVE LOCKABLE THERMOSTAT COVERS FOR THERMOSTATS. COORDINATE WITH OWNER.
36. MECHANICAL CONTRACTOR SHALL COORDINATE WITH PLUMBING CONTRACTOR ON LOCATION OF ALL FLOOR DRAINS & HUB DRAINS AS NOT TO INTERFERE WITH EQUIPMENT & EQUIPMENT PADS. COORDINATE NEW FLOOR DRAIN & HUB LOCATION WHERE EQUIPMENT DOES NOT ALLOW
FOR THE INSTALLATION SHOWN FOR DRAIN. COORDINATE HEIGHT OF HUB DRAINS FOR FAN COIL UNITS & CEILING CASSETTES.
37. PROVIDE TRANSITIONS FROM REAR OF ALL GRILLES TO BRANCH DUCTS AND TO ALL EQUIPMENT AS REQUIRED. REFER TO CONSTRUCTION DOCUMENTS FOR SIZES OF GRILLES AND DUCTS.
38. PRESSURE TEST ALL REUSED/REROUTED PIPING SYSTEMS. TESTING SHALL BE PERFORMED AT NORMAL SYSTEM OPERATING PRESSURE UNLESS INDICATED/SPECIFIED OTHERWISE. REPAIR AND RETEST AS REQUIRED UNTIL SYSTEMS ARE PROVEN TIGHT WITHOUT LEAKS.
39. ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT OR PIPING INSULATION IS APPLIED.
40. LOCATE ALL TEMPERATURE PRESSURE AND FLOW MEASURING DEVICES IN ACCESSIBLE LOCATIONS WITH STRAIGHT SECTION OF PIPE OR DUCT UP AND DOWN STREAM AS RECOMMENDED BY THE MANUFACTURER.
41. REINFORCEMENT, DETAILING, AND PLACEMENT OF CONCRETE SHALL CONFORM TO ASTM 315 AND ACI 318. CONCRETE SHALL CONFORM TO ASTM C94. CONCRETE WORK SHALL CONFORM TO ACI318, PART ENTITLED “CONSTRUCTION REQUIREMENTS.” COMPRESSIVE STRENGTH IN 28 DAYS
SHALL BE 3,000 PSI. TOTAL AIR CONTENT OF EXTERIOR CONCRETE SHALL BE BETWEEN 5 AND 7 PERCENT BY VOLUME. SLUMP SHALL BE BETWEEN 3 AND 4 INCHES. CONCRETE SHALL BE CURED FOR 7 DAYS AFTER PLACEMENT.
42. COORDINATE ALL EQUIPMENT CONNECTION WITH MANUFACTURERS’ CERTIFIED DRAWINGS. COORDINATE AND PROVIDE ALL DUCT AND PIPING TRANSITIONS REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND COORDINATE ALL DUCT AND
PIPING DIMENSIONS BEFORE FABRICATION.
43. MINIMUM CONCRETE PAD THICKNESS SHALL BE 4 INCHES. PAD SHALL EXTEND BEYOND THE EQUIPMENT A MINIMUM OF 6 INCHES ON EACH SIDE UNLESS OTHERWISE DIRECTED IN THESE DOCUMENTS 15 LOCATIONS AND SIZES OF ALL FLOOR, WALL, AND ROOF OPENINGS SHALL BE
COORDINATED WITH ALL OTHER TRADES INVOLVED. REFER TO TYPICAL DETAILS FOR DUCTWORK, PIPING, AND EQUIPMENT INSTALLATION.
44. INSTALL TRANSITION DUCT FROM INLET AND OUTLET OF EQUIPMENT TO DUCT SIZE SHOWN ON PLANS; CONSULT EQUIPMENT MANUFACTURER FOR INLET AND OUTLET SIZE.
45. ALL DUCT ELBOWS, BENDS, AND TEES SHALL BE PROVIDED WITH DOUBLE THICKNESS TURNING VANES OR RADIUS ELBOWS UNLESS SHOWN OR NOTED OTHERWISE. ELBOWS IN DISHWASHER, KITCHEN, AND LAUNDRY EXHAUST SHALL BE UNVANED SMOOTH RADIUS CONSTRUCTION WITH A
RADIUS OF 1.5 TIMES THE WIDTH OF THE DUCT.
46. PROVIDE ESCUTCHEONS AT ALL EXPOSED LOCATIONS WHERE PIPE PENETRATES WALL.
47. THE CONDENSATE DRAIN LINE SHALL NOT DECREASE IN SIZE FROM THE DRAIN PAN CONNECTION TO THE FLOOR DRAIN; ELEVATE UNIT TO ACCOMMODATE P-TRAP.
48. ALL EQUIPMENT AND DEVICES TO BE FURNISHED AND INSTALLED PER THE REQUIREMENTS OF CONTRACT DRAWINGS, SPECIFICATIONS, MANUFACTURERS RECOMMENDATIONS, AND ACCORDING TO CODE.
49. PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS (SUPPLY, RETURN, AND EXHAUST) CONNECTED TO AIR HANDLING UNITS, FANS, AND OTHER EQUIPMENT WHICH REQUIRE VIBRATION ISOLATION. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AT THE POINT OF CONNECTION TO
THE EQUIPMENT UNLESS OTHERWISE DIRECTED IN THESE DOCUMENTS.
50. UNLESS OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD, TIGHT TO UNDERSIDE OF THE STRUCTURE, WITH SPACE FOR INSULATION.
51. ALL ROOF CURBS SHALL BE INSTALLED TO THE ROOFING STRUCTURE AND FINISH A MINIMUM 12" ABOVE THE FINISHED ROOF FOR COUNTER FLASH ENDORSED BY ROOF MANUFACTURER. ROOF CURBS SHALL BE PITCHED WHERE REQUIRED TO ENSURE EQUIPMENT IS INSTALLED LEVEL.
52. ALL MISCELLANEOUS ROOFTOP EQUIPMENT SUPPORTS SHALL BE ENDORSED BY BOTH THE RESPECTIVE EQUIPMENT MANUFACTURER AND ROOF SYSTEM MANUFACTURER.
53. ALL WALL APPLIED ITEMS SHALL BE INSTALLED PLUMB, LEVEL AND IN LOCATIONS DESIGNATED IN CONTRACT DOCUMENTS. ALL DEVICE COVERS AND TRIM SHALL FIT TIGHT TO WALL SURFACE ON ALL SIDES. WHERE SPECIFIC LOCATIONS FOR ITEMS NOT SHOWN OR CLEAR, CONTRACTOR
SHALL OBTAIN CLARIFICATION AND DIRECTION FROM ARCHITECT AND MECHANICAL ENGINEER PRIOR TO INSTALLATION.
54. ALL FLEX DUCT SERVING DIFFUSERS SHALL BE LIMITED TO RUNS OF 6'. FLEX DUCT SHALL BE FLEXMASTER 1M-R6 OR APPROVED EQUAL AND USE STAINLESS STEEL (OR NYLON IF APPROVED BY MECHANICAL ENGINEER) TO CONNECT FLEX TO DUCT AND GRILLES.
55. FLEXIBLE DUCT NOT ACCEPTABLE FOR EXHAUST, RETURN AND FRESH AIR SYSTEMS UNLESS SPECIFIED OR NOTED OTHERWISE. FLEX DUCT SHALL NOT PENETRATE ANY WALLS UNLESS SUBMITTED AND APPROVED ON TO BOTH THE ARCHITECT AND MECHANICAL ENGINEER.
56. PROVIDE ADDITIONAL SUSPENDED SUPPORTS AS REQUIRED TO PREVENT FLEXIBLE DUCT FROM CONTACTING THE CEILING MATERIAL AND/OR CEILING FRAME/GRID ASSEMBLY.
57. ALL ROUND TAPS OFF RECTANGULAR DUCTWORK TO DIFFUSERS SHALL BE MADE WITH HIGH EFFICIENCY SIDE TAKEOFFS WITH 2" INSULATION STANDOFF BRACKETS AND LOCKING QUADRANT, FLEXMASTER MODEL STOD-BO3 OR APPROVED EQUAL.
58. ALL GRILLES LOCATED IN LAY-IN CEILINGS SHALL HAVE 24x24 FRAMES, STYLES TO FIT THE GRID TYPE, EITHER 15/16" OR 9/16" GRID, VERIFY GRID WITH ARCHITECTURAL DRAWINGS. PROVIDE PLASTER FRAMES FOR SURFACE MOUNT APPLICATIONS, PRICE MODEL AMF OR APPROVED EQUAL.
59. PROVIDE MANUAL VOLUME DAMPERS IN ALL BRANCH DUCT CONNECTIONS TO LOW PRESSURE MAIN DUCTS.
60. ALL EQUIPMENTS SUPPLIED TO THE PROJECT SHALL BE PER SPECIFICATIONS. OBTAINING APPROVED SUBMITTALS DOES NOT RELIEVE THE CONTRACTOR/SUPPLIER OF PROVIDING ALL FEATURES, OPTIONS AND ACCESSORIES INCLUDED WITHIN THE CONSTRUCTION DOCUMENTS.
AC AIR CONDITIONING
ACCU AIR COOLED CONDENSING UNIT
AFF ABOVE FINISHED FLOOR
AFS AIR FLOW STATION
AHU AIR HANDLING UNIT
AMB AMBIENT
AS AIR SEPARATOR
AV AIR VENT
BAS BUILDING AUTOMATION SYSTEM
BDD BACKDRAFT DAMPER
BFP BACKFLOW PREVENTER
BOD BOTTOM OF DUCT
BTUH BRITISH THERMAL UNIT PER HOUR
CC COOLING COIL
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CH CHILLER
CHWCF CHILLED WATER CHEMICAL FEED
CHP CHILLED WATER PUMP
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
COMP COMPRESSOR
CP CIRCULATING PUMP
CU CONDENSING UNIT
CT COOLING TOWER
CV CONTROL VALVE
CW COLD WATER
CWCF CONDENSER WATER CHEMICAL FEED
CWR CONDENSER WATER RETURN
CWP CONDENSER WATER PUMP
CWS CONDENSER WATER SUPPLY
DB DRY BULB TEMP (DEG F)
DDC DIRECT DIGITAL CONTROL
DN DOWN
DP DIFFERENTIAL PRESSURE
DPS DIFFERENTIAL PRESSURE SWITCH
DWG DRAWING
DX DIRECT EXPANSION
EA EXHAUST AIR
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EL ELEVATION
ELEC ELECTRICAL
ENT ENTERING
ECU ELECTRIC CONDENSING UNIT
ERU ELECTRIC REFRIGERANT UNIT
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EUH ELECTRIC UNIT HEATER
EVAP EVAPORATOR
EX EXHAUST
EXT EXTERNAL
FA FRESH AIR
FC/FCUFAN COIL UNIT
FD FIRE DAMPER
FT FEET
FLA FULL LOAD AMPS
FPM FEET PER MINUTE
FV FACE VELOCITY
GALV GALVANIZED
GPM GALLONS PER MINUTE
GPH GALLONS PER HOUR
GUH GAS UNIT HEATER
HC HEATING COIL
HP HORSEPOWER
HR HOUR
HWS HEATING WATER SUPPLY
HWR HEATING WATER RETURN
ID INSIDE DIAMETER
IN INCHES
KW KILOWATTS
LVG LEAVING
MA MIXED AIR
MAX MAXIMUM
MD MOTORIZED DAMPER
MECH MECHANICAL
NG NATURAL GAS
MIN MINIMUM
MVD MANUAL VOLUME DAMPER
NC NORMALLY CLOSED
NFPA NATIONAL FIRE PROTECTION ASSOC.
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NOM NOMINAL
NTS NOT TO SCALE
OA OUTSIDE AIR
OAF OUTSIDE AIR FAN
OAU OUTSIDE AIR UNITS
OS&Y OUTSIDE STEM AND YOKE
OZ OUNCES (PRESSURE)
PD PRESSURE DROP
PTAC PACKAGED TERMINAL AIR CONDITIONER
PSI POUNDS PER SQUARE INCH
RA RETURN AIR
REF REFERENCE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RND ROUND
RPM REVOLUTIONS PER MINUTE
RTU ROOF TOP UNIT
SA SUPPLY AIR
SD SMOKE DAMPER
SEER SEASONAL ENERGY EFFICIENCY RATIO
SF SUPPLY AIR FAN
SP STATIC PRESSURE
SPEC SPECIFICATIONS
TEMP TEMPERATURE
TOD TOP OF DUCT
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
UG UNDERGROUND
UL UNDERWRITERS LISTED
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
W / WITH
W / O WITHOUT
WB WET BULB (DEG F)
ABBREVIATION LEGEND
DETAIL SYMBOL
GRID LINE
SECTION SYMBOL
DEMO NOTE
REVISION TAG
TIE INTOMATCHLINE
1 / M101
MATCHLINE
THERMOSTAT SYMBOLT99
NEW EQUIPMENT OR FIXTURE
EXISTING TO REMAIN
EXISTING TO BE DEMOLISHED
A-500 DIFFUSER TAG
MARK
NEW WORK
CFM
M101
M101
SECTION
DETAIL
SHEET NUMBER
SHEET NUMBER
1 GENERAL NOTE
RE: 1 / M101 SHEET REFERENCE TAG
SHEET NUMBER
VIEW NUMBER
MECHANICAL SYMBOL LEGEND
GENERAL
(REFER TO DRAWINGS AND SPECIFICATIONS FOR FURTHER REQUIREMENTS)
MITERED 90º ELBOW WITH DOUBLE DEFLECTION
TURNING VANES
RECTANGULAR TRANSITION; SYMMETRIC
RECTANGULAR TRANSITION; ASYMMETRIC
MITERED 45º ELBOW WITH DOUBLE DEFLECTION
TURNING VANES
DUCT WITH FLEXIBLE CONNECTION
45º RECTANGULAR TAP
ROUND EXHAUST DUCT UP
ROUND EXHAUST DUCT DOWN
CHANGE IN RECTANGULAR DUCT ELEVATION; RISE
CHANGE IN ROUND DUCT ELEVATION; DROP
4-WAY S/A DIFFUSER; SEE SCHEDULE FOR SIZE
3-WAY S/A DIFFUSER; SEE SCHEDULE FOR SIZE
2-WAY S/A DIFFUSER; SEE SCHEDULE FOR SIZE
1-WAY S/A DIFFUSER; SEE SCHEDULE FOR SIZE
R/A GRILLE; SEE SCHEDULE FOR SIZE
DUCT WITH MANUAL VOLUME DAMPER
DUCT WITH FIRE DAMPER
DUCT WITH SMOKE DAMPER
DUCT WITH COMBINATION FIRE/SMOKE DAMPER
DUCT WITH ACCESS DOOR
DUCT WITH MOTORIZED DAMPER
45º LEAD-IN WITH MANUAL VOLUME DAMPER
RADIUS ELBOW
E/A GRILLE; SEE SCHEDULE FOR SIZE
INTERNALLY INSULATED DUCT
SUPPLY DUCT
RETURN DUCT
EXHAUST DUCT
RECTANGULAR SUPPLY DUCT UP
RECTANGULAR EXHAUST DUCT DN
ROUND SUPPLY DUCT UP
ROUND SUPPLY DUCT DN
ROUND RETURN DUCT UP
ROUND RETURN DUCT DN
RECTANGULAR SUPPLY DUCT DN
RECTANGULAR RETURN DUCT UP
RECTANGULAR RETURN DUCT DN
RECTANGULAR EXHAUST DUCT UP
DUCT WITH HUMIDIFIER
R
D
DUCT WITH BACK DRAFT DAMPER
DUCTWORK
INLET
3/4" MAKE UP WATER
1/2" BLOWDOWN BALL
VALVE W/ NIPPLE
UNION
3/4" BALL VALVE
ANSI 125# FLANGE
OUTLET
TO PUMP SUCTION
STRAINER
HOUSING MOUNTING
FLANGE
WALL HOUSING WITH
OSHA APPROVED GUARD
W A
LL
-IN
TE
R
IO
R
-E X
TE
R
IO
R
90° WEATHERHOOD
W/ BIRDSCREEN
FOR SUPPLY FAN
BELT DRIVE
MOTOR
FAN BLADES
SECTION VIEWBACK VIEW
BELT DRIVE
MOTOR
WALL HOUSING WITH
OSHA APPROVED GUARD
FAN BLADES
AIRFLOW
MOTORIZED DAMPER WITH ACTUATOR.
DAMPER SHALL BE WIRED FOR SINGLE
POINT CONNECTION FROM FACTORY.
CAULK ALL AROUND PENETRATION
WITH CLEAR SILICON CAULKING
TO CREATE WEATHERPROOF SEAL
SHEET NUMBER
SHEET NAME
DATE:
REVISIONS
DRAWN BY:
CHECKED BY:
PROJECT #:
SHEET INFORMATION
SEAL
PROJECT INFORMATION
All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.
7600 Innovation Park Drive
Baton Rouge, LA 70820
225.332.0222 parisheng.com
M0.0
MECHANICAL COVER SHEET
CTD
LJB
06-18-2025
25-040
B O
IL
E
R R
E P
L A
C E
M E
N T
A R
T S
H
U M
A N
IT
IE
S
S O
C
IA
L S
C
IE
N C
E B
U
IL
D
IN
G
G Y
M N
A S
IU
M
S
U N
O N
E W
O R
L E
A N
S
L A
N.T.S.1 DETAIL - AIR SEPERATOR
N.T.S.2 DETAIL - BELT DRIVE PROPELLER SUPPLY FAN
INDEX - MECHANICAL SHEETS
M0.0 MECHANICAL COVER SHEET
M1.0 MECHANICAL PLAN
M1.1 ENLARGED MECHANICAL PLAN
M1.2 GYMNASIUM MECHANICAL PLAN
M1.3 GYMNASIUM ENLARGED MECHANICAL PLAN
M2.0 MECHANICAL DETAILS
M2.1 MECHANICAL DETAILS
M3.0 MECHANICAL SCHEDULES
3" H
H W
R
B-1(E) B-2
6"⌀
6"⌀
6"⌀
6"⌀
HHWS (E)
PM-4(E)
PM-5(E)
M1.1
3"HHWS
SHEET NUMBER
SHEET NAME
DATE:
REVISIONS
DRAWN BY:
CHECKED BY:
PROJECT #:
SHEET INFORMATION
SEAL
PROJECT INFORMATION
All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.
7600 Innovation Park Drive
Baton Rouge, LA 70820
225.332.0222 parisheng.com
M1.0
MECHANICAL PLAN
CTD
LJB
06-18-2025
25-040
B O
IL
E
R R
E P
L A
C E
M E
N T
A R
T S
H
U M
A N
IT
IE
S
S O
C
IA
L S
C
IE
N C
E B
U
IL
D
IN
G
G Y
M N
A S
IU
M
S
U N
O N
E W
O R
L E
A N
S
L A
1" = 10'-0"1 ARTS & HUMANITIES OVERALL PLAN
3" HHWR (E)
3" HHWS (E)
B-1(E)
B-2
6"⌀
6"⌀
6"⌀
6"⌀
PM-4(E)
PM-5(E)
3" H
H W
S (E
3" H
H W
S (E
3" H
H W
S (E
3" HHWR (E)
3" HHWR (E)
3" HHWR (E)
3" HHWR (E)
3" HHW
R (E)
3" HHW
S (E)
B-2B-1(E)
6"⌀
6"⌀ 6"⌀
6"⌀
3"HHWS
3"HHWS
3"HHWR
3" H
H W
R
3" H
H W
R
PM-4(E)
PM-5(E)
3" HHWS (E)
3" HHWR (E)
SHEET NUMBER
SHEET NAME
DATE:
REVISIONS
DRAWN BY:
CHECKED BY:
PROJECT #:
SHEET INFORMATION
SEAL
PROJECT INFORMATION
All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.
7600 Innovation Park Drive
Baton Rouge, LA 70820
225.332.0222 parisheng.com
M1.1
ENLARGED MECHANICAL
PLAN
CTD
LJB
06-18-2025
25-040
B O
IL
E
R R
E P
L A
C E
M E
N T
A R
T S
H
U M
A N
IT
IE
S
S O
C
IA
L S
C
IE
N C
E B
U
IL
D
IN
G
G Y
M N
A S
IU
M
S
U N
O N
E W
O R
L E
A N
S
L A
2 3D BOILER DIAGRAM
3/8" = 1'-0"1 ARTS & HUMANITIES ENLARGED
KEYNOTES:
PROVIDE NEW BOILER, B-2, EXISTING BOILER HAS BEEN REMOVED. CONNECT TO EXISTING HEATING
WATER VENT, INTAKE AIR, ELECTRICAL AND CONTROLS.
REPLACE EXISTING OUTDOOR AIR DAMPER.
M1.3
B-1 B-2
SHEET NUMBER
SHEET NAME
DATE:
REVISIONS
DRAWN BY:
CHECKED BY:
PROJECT #:
SHEET INFORMATION
SEAL
PROJECT INFORMATION
All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.
7600 Innovation Park Drive
Baton Rouge, LA 70820
225.332.0222 parisheng.com
M1.2
GYMNASIUM MECHANICAL
PLAN
CTD
LJB
06-18-2025
25-040
B O
IL
E
R R
E P
L A
C E
M E
N T
A R
T S
H
U M
A N
IT
IE
S
S O
C
IA
L S
C
IE
N C
E B
U
IL
D
IN
G
G Y
M N
A S
IU
M
S
U N
O N
E W
O R
L E
A N
S
L A
1/8" = 1'-0"1 GYMNASIUM OVERALL PLAN
4"HWR
4"HWR
4"HWR
3"HWS 3"HWS 3"HWS
4"HWS
12"⌀12"⌀
B-1(E) B-2(E) B-3(E)
2" NG (E)4" NG (E)
2" NG (E) 4" NG (E) 4" NG (E)
2" N
G (E
4"HWR
3"HWR3"HWR
4"HWS4"HWS
3/4"HWR ET-1(E)
EXISTING BOILER VENT FAN
EXISTING DOMESTIC
WATER HEATER
VENT FAN TO REMAIN
EXISTING DOMESTIC WATER
HEATERS TO REMAIN
EXISTING DOMESTIC
WATER HEATER VENT FAN
CONTROLLER TO REMAIN
EXISTING BOILER PUMP
MOTOR STARTERS (3)
EXISTING BOILER VENT
FAN CONTROLLER
3/4"CW(E)
EXISTING
BOILER PUMP EXISTING
BOILER PUMP
EXISTING
BOILER PUMP
4" HWR(E) FROM ABOVE
4"HWR
10"⌀ 8"⌀
2" NG (E)4" NG (E)
2" NG (E) 4" NG (E)
EXISTING DOMESTIC
WATER HEATER VENT FAN
EXISTING DOMESTIC WATER
HEATER VENT FAN CONTROLLER
EXISTING DOMESTIC WATER
HEATERS TO REMAIN
B-1 B-2
2"NG 2"NG
4" HWR(E) UP TO MEZZANINE
4"HWS
12"⌀12"⌀
4"HWS
3/4"CW
4"HWR
AS-1
SF-1
3/4"CW(E)
CT-1
4"HWR
CONNECT TO EXISTING
TO NEW HEATING
WATER MAKEUP
4" H
W R
4" H
W S
4"HWR
4"HWS
SHEET NUMBER
SHEET NAME
DATE:
REVISIONS
DRAWN BY:
CHECKED BY:
PROJECT #:
SHEET INFORMATION
SEAL
PROJECT INFORMATION
All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.
7600 Innovation Park Drive
Baton Rouge, LA 70820
225.332.0222 parisheng.com
M1.3
GYMNASIUM ENLARGED
MECHANICAL PLAN
CTD
LJB
06-18-2025
25-040
B O
IL
E
R R
E P
L A
C E
M E
N T
A R
T S
H
U M
A N
IT
IE
S
S O
C
IA
L S
C
IE
N C
E B
U
IL
D
IN
G
G Y
M N
A S
IU
M
S
U N
O N
E W
O R
L E
A N
S
L A
1/2" = 1'-0"1 GYMNASIUM DEMO PLAN 1/2" = 1'-0"2 GYMNASIUM RENO PLAN
DEMO KEY NOTES:
TWO EXISTING DOMESTIC WATER HEATERS AND ASSOCIATED VENT FAN, VENT FAN CONTROLLER, MIXING VALVE, EXPANSION TANK AND PIPING TO REMAIN.
REMOVE THREE EXISTING BOILERS AND ASSOCIATED PUMPS, MOTOR STARTERS, VENT FAN, VENT FAN CONTROLLER, HWS/R, AND GAS PIPING.
REMOVE EXISITNG COMBUSTION AIR FAN. PREPARE OPENING TO ACCEPT NEW FAN.
PREPARE EXISTING OPENING TO ACCEPT NEW BOILER FLUE.
RENO KEY NOTES:
EXISTING SECONDARY HEATING WATER PUMPS ARE LOCATED ON MEZZANINE ABOVE. REFER TO PIPING DIAGRAMS FOR SCOPE OF WORK. BALANCE EXISTING SECONDARY HEATING WATER PUMPS PER SCHEDULE.
PROVIDE BOILER STOP BUTTON AT DOORWAY.
LEGEND
AIR SEPARATOR
CIRCULATION
PUMP
FLOW CHECK VALVE
PRESSURE GAUGE
P
TEMPERATURE &
PRESSURE GAUGE
T P
SYSTEM SUPPLY
SENSOR
BACKFLOW
PREVENTER
MAGNETIC SEPARATOR WATER METER
PRESSURE STRAINER / FILTER
REDUCING VALVE
PRESSURE RELIEF
VALVE
BALL VALVE EXPANSION TANK
PIPING
DRAIN PORT
DIFFERENTIAL
PRESSURE
BYPASS VALVE
2 WAY MOTORIZED
VALVE (OPTIONAL)
MIXING VALVE
ANTI SCALD
FLOW SWITCH
OPTIONAL
WIRING
TO
SYSTEM
FROM
SYSTEM
P
MAKE UP
WATER
T P T P
BOILER 1 BOILER 2
SYSTEM SUPPLY
SENSOR
HANGER ROD SCHEDULE
PIPE SIZE ROD DIA.
1/4" - 2"
2-1/2" - 3-1/2"
3/8"
1/2"
GENERAL NOTES:
1. HANGERS IN CONTACT WITH COPPER SHALL BE COPPER PLATED OR TEFLON COATED.
2. MAXIMUM HORIZONTAL PIPE HANGER AND SUPPORT SPACING IS 5'-0".
ADJUSTABLE WROUGHT CLEVIS HANGER
16 GA. GALVANIZED SHEETMETAL PIPE INSULATION
PROTECTION SADDLE, MINIMUM 12" LONG
PROVIDE NON-METALLIC INSULATING MATERIAL IF PIPING AND
HANGER ARE DISSIMILAR METALS AND PIPING IS NOT INSULATED
ALL THREAD HANGER ROD
HEX HEAD NUT
REFRIGERANT PIPING
CONCRETE DECK ANCHORS
BAR JOIST ANCHORSI-BEAM ANCHORS
WOOD ANCHORS
WOOD TRUSS/JOIST
1/4"X1-1/4" HEX HEAD LAG
BOLT TO BE SECURED TO TOP
CHORD OF TRUSS/JOIST
HEX HEAD NUT
STEEL SIDE BEAM
BRACKET
ALL THREAD
HANGER ROD
ALL THREAD
HANGER ROD
HEX HEAD NUT
WITH WASHER
ADJUSTABLE SIDE
BEAM CLAMP
STEEL BEAM
ALL THREAD
HANGER ROD
C-CLAMP WITH
SET SCREW AND
LOCK NUT
RETAINING CLIP
UNIVERSAL C-CLAMP
WITH SET SCREW
AND JAM NUT
TOP/BOTTOM
FLANGE OF BAR
JOIST
ALL THREAD
HANGER ROD
UNIVERSAL C-CLAMP
WITH SET SCREW
AND JAM NUT
CONCRETE DECK
CONCRETE WEDGE
ANCHOR WITH HEX
HEAD NUT AND WASHER
WITH HANGER STRAP
STEEL BEAM
CONCRETE LAG SHIELD
ANCHOR OR CONCRETE
EXPANSION ANCHOR
WITH ALL THREAD ROD
AIR CONTROL TANK
FITTING TYPICAL
BALL
VALVE
PRESSURE RELIEF
75 P.S.I. SETTING
PRESSURE REDUCING
VALVE, SET TO 10 PSI
CONNECT
HW FILL LINE
SLOPE DOWN
NEW AIR
SEPARATOR
TO PUMPS
TO DRAIN
BALL
VALVE
TO DRAIN
3/4" VALVE WITH
GARDEN HOSE
CONNECTION
N.C.
STRAINER
SHUT-OFF BALL
VALVE (TYP)
BACKFLOW
PREVENTER
COMPRESSION TANK
N.T.S.1 DETAIL - REFRIGERANT PIPE SUPPORT HANGERS
N.T.S.3 DETAIL - DUCT/PIPE HANGER ANCHORS
SHEET NUMBER
SHEET NAME
DATE:
REVISIONS
DRAWN BY:
CHECKED BY:
PROJECT #:
SHEET INFORMATION
SEAL
PROJECT INFORMATION
All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.
7600 Innovation Park Drive
Baton Rouge, LA 70820
225.332.0222 parisheng.com
M2.0
MECHANICAL DETAILS
CTD
LJB
06-18-2025
25-040
B O
IL
E
R R
E P
L A
C E
M E
N T
A R
T S
H
U M
A N
IT
IE
S
S O
C
IA
L S
C
IE
N C
E B
U
IL
D
IN
G
G Y
M N
A S
IU
M
S
U N
O N
E W
O R
L E
A N
S
L A
N.T.S.4 DETAIL - BOILER PIPING DIAGRAM
N.T.S.2 DETAIL - AIR CONTROL SYSTEM PIPING
ET-1(E)
B-1(E) B-2(E) B-3(E)
AHU-10(E)
AHU-2(E)
AHU-3(E)
AHU-1(E) AHU-9(E)
AHU-5(E)AHU-6(E)AHU-7(E)AHU-8(E)
AHU-4(E)
PUMP CONTROLLER (E)
P-3(E) P-4(E) P-5(E)
P-6(E) P-7(E)
4"4"
4"
4" 4"
4"
4"
4"
4" 4"
4"
4"
4"
4"
3"
3"
3" 3"
3" 3"
3" 3"
3"3"
4"
4"
3"
3"
1" 1"
2"
2"
2"
2"
3"3"
1 1/2"
1 1/2"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
2"
2"
2"
2"
2"
2"
2" 2"
1" 1"
BACKFLOW
PREVENTER
4"
MIXING VALVE (E)
B-1 B-2
AHU-10(E)
AHU-2(E)
AHU-3(E)
AHU-1(E) AHU-9(E)
AHU-5(E)AHU-6(E)AHU-7(E)AHU-8(E)
AHU-4(E)
PUMP CONTROLLER (E)
P-6(E) P-7(E)
4"
4"
4"
4" 4"
4"
4"
4"
4"
3"
3"
3" 3"
3" 3"
3" 3"
3"3"
4"
4"
3"
3"
1" 1"
2"
2"
2"
2"
3"3"
1 1/2"
1 1/2"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
2"
2"
2"
2"
2"
2"
2" 2"
4"
GENERAL NOTES:
1. MODIFY EXISTING PIPING FOR NEW BOILERS, PUMPS, AND PIPE ROUTING.
BP-1 BP-2
4"
4" 4"
4"
HW UP TO MEZZANINE
SHEET NUMBER
SHEET NAME
DATE:
REVISIONS
DRAWN BY:
CHECKED BY:
PROJECT #:
SHEET INFORMATION
SEAL
PROJECT INFORMATION
All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.
7600 Innovation Park Drive
Baton Rouge, LA 70820
225.332.0222 parisheng.com
M2.1
MECHANICAL DETAILS
CTD
LJB
06-18-2025
25-040
B O
IL
E
R R
E P
L A
C E
M E
N T
A R
T S
H
U M
A N
IT
IE
S
S O
C
IA
L S
C
IE
N C
E B
U
IL
D
IN
G
G Y
M N
A S
IU
M
S
U N
O N
E W
O R
L E
A N
S
L A
N.T.S.1 EXISTING HEATING WATER FLOW - PIPING DIAGRAM
N.T.S.2 NEW HEATING WATER FLOW - PIPING DIAGRAM
NOTES:
1. PROVIDE INSULATED FAN HOUSING.
2. PROVIDE FACTORY MOUNTED AND WIRED SPEED CONTROLLERS FOR ALL DIRECT DRIVE FANS FOR AIR BALANCING.
3. PROVIDE INTEGRAL DISCONNECTING MEANS.
4. PROVIDE MOTORS WITH BUILT-IN THERMAL OVERLOAD PROTECTION FOR ALL FANS.
5. ALL EXHAUST AND SUPPLY FANS SHALL BE AMCA RATED FOR BOTH AIR AND SOUND.
6. PROVIDE FACTORY FINISHES ON ALL SURFACE EXPOSED TO VIEW.
SHEET NUMBER
SHEET NAME
DATE:
REVISIONS
DRAWN BY:
CHECKED BY:
PROJECT #:
SHEET INFORMATION
SEAL
PROJECT INFORMATION
All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.
7600 Innovation Park Drive
Baton Rouge, LA 70820
225.332.0222 parisheng.com
M3.0
MECHANICAL SCHEDULES
CTD
LJB
06-18-2025
25-040
B O
IL
E
R R
E P
L A
C E
M E
N T
A R
T S
H
U M
A N
IT
IE
S
S O
C
IA
L S
C
IE
N C
E B
U
IL
D
IN
G
G Y
M N
A S
IU
M
S
U N
O N
E W
O R
L E
A N
S
L A
SCHEDULE - BOILERS
MARK DESCRIPTION
CAPACITY WATER DUCT SIZE ELECTRICAL SERVICE EFFICIENCY
WEIGHT MANUFACTURER / MODEL
MAXIMUM MINIMUM
EWT LWT FLOW PD VENTILATION COMBUSTION VOLTS PH FREQ THERMAL COMBUSTIONINPUT OUTPUT INPUT
B-1(E) CREST BOILER 1000000.0 Btu/h 722000.0 Btu/h 50000.0 Btu/h 160 °F 180 °F 95 GPM 12.9 ftH2O 6" 6" 120 V 1 30 Hz 96.2% 96.4% 2000 lb FBN1001
B-2 CREST BOILER 1000000.0 Btu/h 722000.0 Btu/h 50000.0 Btu/h 160 °F 180 °F 95 GPM 12.9 ftH2O 6" 6" 120 V 1 30 Hz 96.2% 96.4% 2000 lb FBN1001
SCHEDULE - BOILERS
MARK DESCRIPTION
CAPACITY WATER VENTILATION ELECTRICAL SERVICE
MIN-MAX INLET
GAS PRESSURE
EFFICIENCY
WEIGHT MANUFACTURER / MODEL
MAXIMUM MINIMUM
INLET OUTLET
MIN
FLOW MAX FLOW VENT COMBUSTION VOLTS FLA PH FREQ THERMAL COMBUSTIONINPUT OUTPUT INPUT OUTPUT
B-1 CONDENSING STAINLESS STEEL FIRETUBE 1999000 Btu/Hr 1923000 Btu/Hr 80000 Btu/Hr 76920 Btu/Hr 4" 4" 25 GPM 350 GPM 8" 8" 120 13 1 60 4-14 In. W.C. 96.2% 96.4% 2700 lb LOCHINVAR FCB 2000N
B-2 CONDENSING STAINLESS STEEL FIRETUBE 1999000 Btu/Hr 1923000 Btu/Hr 80000 Btu/Hr 76920 Btu/Hr 4" 4" 25 GPM 350 GPM 8" 8" 120 13 1 60 4-14 In. W.C. 96.2% 96.4% 2700 lb LOCHINVAR FCB 2000N
SCHEDULE - PUMPS
MARK GPM PUMP HEAD RPM TYPE
ELECTRICAL SERVICE
TYPE LOCATION MANUFACTURER / MODELHP VOLTS PH
(E) P-6 165 65 ft. 1800 VERTICAL IN-LINE CENTRIFUGAL 7.5 208 3 VARIABLE SPEED PUMP NEAR BOILER ARMSTRONG 4380 3X3X10
(E) P-7 165 65 ft. 1800 VERTICAL IN-LINE CENTRIFUGAL 7.5 208 3 VARIABLE SPEED PUMP NEAR BOILER ARMSTRONG 4380 3X3X10
ARTS, HUMANITIES AND SCIENCE SCHEDULES:
SCHEDULE - FANS
MARK LOCATION
FAN FAN MOTOR
WEIGHT MANUFACTURER / MODELTYPE AIRFLOW MIN EXT ESP MAX SONES RPM DRIVE POWER VOLTS PH FREQ
SF-1 BOILER ROOM SIDE WALL PROP 1200 CFM 0.28 in-wg 11.3 1043 DIRECT 1/4 HP 120 V 1 60 Hz 200 lb GREENHECK MODEL AER-20-03-0610-VG
GYMNASIUM SCHEDULES:
NOTES:
1. PROVIDE VARIABLE SPEED PRIMARY BOILER PUMP FROM BOILER MANUFACTURER WITH EACH BOILER. PUMP SPEED SHALL BE CONTROLLED BY BOILER. PUMP MODEL SHALL BE LOCHINVAR 100208412.
2. PROVIDE CONDENSATE NEUTRALIZATION KIT WITH EACH BOILER.
3. PROVIDE ULTRA HIGH TURN DOWN NATURAL GAS REGULATOR ON EACH INCOMING BOILER GAS LINE. (IF GAS PRESSURE IS ABOVE ALLOWABLE PRESSURE RANGE)
4. PROVIDE BOILERMAG MAGNETIC FILTER / SEPERATOR IN HEATING WATER RETURN, UPSTREAM OF BOILERS OR AT INLET OF EACH BOILER.
NOTES:
1. PROVIDE VARIABLE SPEED PRIMARY BOILER PUMP FROM BOILER MANUFACTURER WITH EACH BOILER. PUMP SPEED SHALL BE CONTROLLED BY BOILER. PUMP MODEL SHALL BE LOCHINVAR 100208412.
2. PROVIDE CONDENSATE NEUTRALIZATION KIT WITH EACH BOILER.
3. PROVIDE ULTRA HIGH TURN DOWN NATURAL GAS REGULATOR ON EACH INCOMING BOILER GAS LINE. (IF GAS PRESSURE IS ABOVE ALLOWABLE PRESSURE RANGE)
4. PROVIDE BOILERMAG MAGNETIC FILTER / SEPERATOR IN HEATING WATER RETURN, UPSTREAM OF BOILERS OR AT INLET OF EACH BOILER.
SCHEDULE - COMPRESSION TANK
MARK DESCRIPTION CAPACITY WEIGHT MANUFACTURER / MODEL
CT-1 NEW COMPRESSION TANK 240 GALLONS 2500 lb BELL & GOSSETT 116672 OR PRIOR APPROVED EQUAL
SCHEDULE - AIR SEPARATOR
MARK SERVICE FLUID FLOW WEIGHT MANUFACTURER / MODEL
AS-1 HEATING WATER WATER 300 GPM 300 lb BELL & GOSSETT ROLAIRTROL R-4F OR PRIOR APPROVED EQUAL
NOTES:
1. SEPARATOR CONSTRUCTION:
A. SELF-SUPPORTING IN PIPING SYSTEM - MANUFACTURER REVIEW REQUIRED IF ANY PIPING LOADS SHALL BE PRESENT.
B. CARBON STEEL SHELL
C. 304 STAINLESS STEEL SYSTEM STRAINER WITH 3/16" PERFORATIONS AND 51% OPEN AREA.
D. DESIGNED AND CONSTRUCTED PER ASME SECTION VIII, DIVISION 1
2. STANDARD DESIGN PRESSURE AND TEMPERATURE SHALL BE 125 PSI AT 350°F.
ABOVE-COUNTER QUADRAPLEX RECEPTACLE;
MOUNT AT 4" ABOVE COUNTER OR BACKSPLASH
OR 44" (WHICHEVER IS LOWER)
QUADRAPLEX RECEPTACLE
JUNCTION BOX
FUSED SAFETY DISCONNECT SWITCH; LOCATE WITHIN
SIGHT OF THE EQUIPMENT SERVED WITH 36" MINIMUM
CLEAR WORKING SPACE IN FRONT OF THE SWITCH; DO
NOT MOUNT DIRECTLY TO EQUIPMENT
ABOVE-COUNTER GFCI DUPLEX RECEPTACLE;
MOUNT AT 4" ABOVE COUNTER OR BACKSPLASH
OR 44" (WHICHEVER IS LOWER)
JUNCTION BOX FOR MOTORIZED DAMPER
SPECIAL PURPOSE RECEPTACLE; VERIFY NEMA
CONFIGURATION WITH THE MANUFACTURER OF
THE EQUIPMENT SERVED
ABOVE-COUNTER DUPLEX RECEPTACLE;
MOUNT AT 4" ABOVE COUNTER OR BACKSPLASH
OR 44" (WHICHEVER IS LOWER)
GFCI DUPLEX RECEPTACLE
DUPLEX RECEPTACLE
ELECTRICAL SYMBOL LEGEND
M
J
ABOVE-SLAB CONDUIT & WIRE/CABLING
BELOW-SLAB CONDUIT & WIRE/CABLING;
3/4" MINIMUM CONDUIT SIZE UON
VOICE/DATA/POWER FLUSH FLOOR BOX
DUPLEX RECEPTACLE FLUSH FLOOR BOX
QUADRAPLEX RECEPTACLE FLUSH FLOOR BOX
DATA/VOICE OUTLET; PROVIDE 1"C TO AN
ACCESSIBLE LOCATION ABOVE CEILING, ONE (1)
BLUE AND ONE (1) WHITE CAT 6 CABLES FROM THE
OUTLET TO THE TELECOM TERMINAL BOARD
VOICE OUTLET; PROVIDE 1"C TO AN ACCESSIBLE
LOCATION ABOVE CEILING, ONE (1) WHITE CAT 6
CABLE FROM THE OUTLET TO THE TELECOM
TERMINAL BOARD
TV LEGRAND EVOLUTION 4-GANG OR APPROVED EQUAL
TV WALL BOX WITH ONE DUPLEX RECEPTACLE, ONE
DUPLEX DATA OUTLET, ONE COAX OUTLET, AND ONE
SPARE GANG; PROVIDE 1"C, TWO (2) BLUE CAT 6
CABLES AND 1"C, ONE (1) CATV CABLE FROM THE BOX
TO THE TELECOM TERMINA BOARD; PROVIDE CONDUIT
AND WIRE FOR POWER PER THE PANEL SCHEDULE.
WIRELESS ACCESS POINT (BY OWNER); PROVIDE 1"C
TO AN ACCESSIBLE LOCATION ABOVE CEILING, ONE
(1) BLUE CAT 6 CABLE FROM THE ACCESS POINT
LOCATION TO THE TELECOM TERMINAL BOARD
WAP
GENERATOR REMOTE ANNUNCIATOR PANEL; PROVIDE
CONDUIT/CABLING TO GENERATOR AS REQUIRED PER
THE MANUFACTURER'S SPECIFICATIONS.
GEN-ANNC
DUPLEX DATA OUTLET, AS ABOVE,
MOUNTED ABOVE COUNTER
DUPLEX DATA FLUSH FLOOR BOX; PROVIDE 1"C TO
AN ACCESSIBLE LOCATION ABOVE CEILING, ONE (1)
BLUE CAT 6 CABLE FROM THE OUTLET TO THE
TELECOM TERMINAL BOARD
PANELBOARD, SWITCHBOARD, OR OTHER DISTRIBUTION
EQUIPMENT AS NOTED; INSTALL WITH SUFFICIENT
WORKING SPACE AND CLEARANCES TO MEET ALL
REQUIREMENTS OF NEC SECTION 110.26.
GENERAL
KEYNOTE1
HOMERUN TO PANEL;
TICK MARKS INDICATED NUMBER OF WIRES
EQUIPMENT CONNECTIONS
MOTOR RATED SWITCH WITH THERMAL OVERLOAD; LOCATE
WITHIN SIGHT OF THE EQUIPMENT SERVED; DO NOT MOUNT
DIRECTLY TO EQUIPMENT; WHEN LOCATED ABOVE CEILING,
MOUNT TO STRUCTURAL MEMBER NEARBY.
M S
ELECTRICAL MOTOR, HORSEPOWER AS NOTED
POWER DEVICES
DUPLEX RECEPTACLE MOUNTED FLUSH TO CEILING OR
MOUNTED TO STRUCTURE IN AREAS WITH NO CEILING;
SUBSCRIPT (WHEN USED):
CR - CORD REEL
TELECOMMUNICATIONS
DUPLEX DATA OUTLET; PROVIDE 1"C TO AN
ACCESSIBLE LOCATION ABOVE CEILING, TWO (2)
BLUE CAT 6 CABLES FROM THE OUTLET TO THE
TELECOM TERMINAL BOARD
LIGHT FIXTURE; UPPERCASE LETTER(S) INDICATE FIXTURE
TYPE; LOWERCASE LETTER(S) INDICATE ASSOCIATED
CONTROLS ID; SEE LIGHTING FIXTURE SCHEDULE FOR
FIXTURE DESCRIPTIONS AND MOUNTING TYPES
EXIT LIGHT FIXTURE. ARROWS (IF USED) INDICATE
DIRECTION. FILLED IN QUADRANT(S) INDICATE NUMBER
AND ORIENTATION OF ILLUMINATED FACES. LETTER(S)
INDICATE FIXTURE TYPE. SEE LIGHTING FIXTURE
SCHEDULE FOR FIXTURE DESCRIPTION.
CEILING MOUNTED OCCUPANCY SENSOR WITH 360°
COVERAGE. LOCATE AND INSTALL PER THE
MANUFACTURER'S RECOMMENDATIONS; TEST AND
ADJUST SENSITIVITY AFTER INSTALLATION AND SET TIME
DELAY AS REQUIRED BY THE OWNER
Aa
X
OS
PHOTOELECTRIC CELL, EXTERIOR RATED; AIM AND
SHIELD SENSOR FROM INTERIOR AND EXTERIOR
ARTIFICIAL LIGHT SOURCES
CEILING MOUNTED OCCUPANCY SENSOR, AS ABOVE,
CONFIGURED FOR VACANCY OPERATION
VS
LIGHTING
SWITCH;
SUBSCRIPT (WHEN USED):
NONE - SINGLE POLE TOGGLE SWITCH
3 - THREE-WAY SWITCH
D - LINEAR SLIDE DIMMER SWITCH
3D - THREE-WAY LINEAR SLIDE DIMMER SWITCH
O - WALL MOUNTED OCCUPANCY SENSOR
3O - THREE-WAY SWITCH WITH OCCUPANCY SENSOR
a,b,c etc. - SWITCH ID
S
DUPLEX DATA OUTLET, AS ABOVE, MOUNTED FLUSH
TO CEILING OR MOUNTED TO STRUCTURE IN AREAS
WITH NO CEILING
P
TV LEGRAND EVOLUTION 4-GANG OR APPROVED EQUAL
COMBO RECESSED FLOOR BOX WITH TWO (2)
DUPLEX RECEPTACLES, FOUR (4) DATA OUTLETS
(UNDER A SINGLE PLATE), AND SPEAKER
CONNECTIONS; PROVIDE 1-1/4"C TO AN ACCESSIBLE
LOCATION ABOVE CEILING, FOUR (4) BLUE CAT 6
CABLES FROM THE BOX TO THE TELECOM TERMINAL
BOARD. ROUTE 1"EC WITH PULLSTRING FROM THE
BOX TO THE TV WALL BOX IN THE SAME ROOM FOR
SPEAKER CABLING. PROVIDE CONDUIT AND WIRE
FOR POWER PER THE PANEL SCHEDULE.
WIRE, CONDUIT, AND RACEWAY
DISTRIBUTION
PA
V
I
PUBLIC ADDRESS
PA SYSTEM SPEAKER
PA SYSTEM SPEAKER VOLUME CONTROL
PA SYSTEM SPEAKER MOUNT CALL-IN SWITCH
(REFER TO DRAWINGS AND SPECIFICATIONS FOR FURTHER REQUIREMENTS)
(PROVIDE CONDUIT AND WIRE PER THE PANEL SCHEDULE)
(PROVIDE CONDUIT AND WIRE PER THE PANEL SCHEDULE FOR POWER
AND PER THE MANUFACTURER'S SPECIFICATIONS FOR CONTROLS)
(JACKET COLORS TO BE PER THE OWNER'S STANDARDS IF APPLICABLE)
(PROVIDE 3/4"EC WITH PULL STRING FROM THE DEVICE LOCATION SHOWN
ON THE DRAWINGS TO AN ACCESSIBLE LOCATION ABOVE CEILING)
CIRCUIT TAG; PANEL AND CIRCUIT DESIGNATION
AS INDICATED; E.G. PANEL "A", CIRCUIT #1,3
A-1,3
TELECOM TERMINAL BOARD; 0'-1" THICK AC INDOOR
GRADE, FIRE RETARDANT PLYWOOD, PAINTED AS
SPECIFIED BY THE ARCHITECT OR OWNER
(PROVIDE CONDUIT AND WIRE PER THE PANEL SCHEDULE)
RECEPTACLE SWITCHING; EDGE SHADING INDICATES:
NONE - DEVICE NOT SWITCHED
LEFT - BOTTOM (DUPLEX) OR LEFT TWO (QUAD) SWITCHED
RIGHT - TOP (DUPLEX) OR RIGHT TWO (QUAD) SWITCHED
ABBREVIATIONS
AMPERE(S)A
ABOVE COUNTER (6" ABOVE BACKSPLASH)AC
AMPERE(S) FUSEDAF
ARC FAULT CIRCUIT INTERRUPTERAFCI
ABOVE FINISHED FLOORAFF
ABOVE FINISHED GRADEAFG
AMPERE(S) TRIPAT
AMERICAN WIRE GAUGEAWG
BELOW GRADEBG
BUILDINGBLDG
BREAKERBKR
CONDUITC
CATEGORYCAT
CABLE TELEVISIONCATV
CIRCUIT BREAKERCB
CIRCUITCKT
CLGCLG
CORRIDORCORR
CURRENT TRANSFORMERCT
CONTROLLERCTRL
DISCONNECTDISC.
DISTRIBUTIONDIST.
DRAWINGDWG
EMPTY CONDUITEC
ENCLOSED CIRCUIT BREAKERECB
EXHAUST FANEF
EQUIPMENT GROUNDING CONDUCTOREGC
EMERGENCYEMER.
ELECTRICAL METALLIC TUBINGEMT
EQUALEQ
EQUIPMENTEQUIP.
ELECTRIC WATER COOLEREWC
ELECTRIC WATER HEATEREWH
EXISTINGEXIST.
FIRE ALARM CONTROL PANELFACP
FIRE ALARM CONTROL PANEL REMOTE ANNUNCIATORFACPRA
FOOTCANDLEFC
FAN COIL UNITFCU
FULL LOAD AMPERE(S)FLA
FIBER OPTIC CABLEFOC
GROUNDG, GND
GROUNDING ELECTRODE CONDUCTORGEC
GROUND FAULT CIRCUIT INTERRUPTERGFCI
GALVANIZED RIGID STEELGRS
HANDHOLEHH
HORSEPOWERHP
1,000 AMP SYMMETRICAL INTERRUPTING CAPACITY RMSKAIC
1,000 WATT HOURSKWH
1,000 VOLT AMPERESKVA
LOCAL AREA NETWORKLAN
LIGHTINGLTG
MINIMUM CIRCUIT AMPACITYMCA
MAIN CIRCUIT BREAKERMCB
1,000 CIRCULAR MILSMCM/KCMIL
MECHANICALMECH.
MANHOLEMH
MAIN LUGS ONLYMLO
MAXIMUM OVERCURRENT PROTECTIONMOCP
MOUNTEDMTD
MOUNTINGMTG
NATIONAL ELECTRICAL CODENEC
NEUTRALNEU
NOT IN CONTRACTNIC
NON-FUSEDNF
NORMALLY OPENNO
OVERHEADOH
OVERHEAD ELECTRICALOHE
OUTSIDE PLANTOSP
UTILITY POWER POLEUPP
PULL BOXPB
PHASEPH
PANELPNL
PHOTOVOLTAICPV
POLYVINYL CHLORIDEPVC
QUANTITYQTY
RECEPTACLERCPT
REQUIREDREQ'D
SUPPLY FANSF
SOLID NEUTRALS/N
SURGE PROTECTIVE DEVICESPD
STANDARDSTD
TELEPHONETEL
TELECOMMUNICATIONSTELECOM
TELECOMMUNICATIONS GROUND BUSTGB
TELECOMMUNICATIONS MAIN GROUND BUSTMGB
TELECOM TERMINAL BOARDTTB
TELEVISIONTV
TRANSIENT VOLTAGE SURGE SUPPRESSIONTVSS
TYPICALTYP.
UNIT HEATERUH
UNDERWRITER'S LABORATORY, INC.UL
UNDERGROUNDUG
UNDERGROUND PRIMARYUGP
UNDERGROUND SECONDARYUGS
UNLESS OTHERWISE NOTEDUON
VOLTSV
VOLTS ALTERNATING CURRENTVAC
VOLTS DIRECT CURRENTVDC
VARIABLE FREQUENCY DRIVEVFD
WATER HEATERWH
WEATHERPROOFWP
TRANSFORMERXFMR
EXISTING TO REMAINE
TO BE DEMOLISHEDD
LIGHTING CONTACTORLC
AMP SYMMETRICAL INTERRUPTING CAPACITY RMSAIC
NIGHT LIGHTNL
NORMALLY CLOSEDNC
WEATHERPROOF IN-USE COVERNU
FIRE ALARM SYSTEM PULL STATION
FIRE ALARM SYSTEM HORN/STROBE
FIRE ALARM SYSTEM CEILING MOUNT HORN/STROBE
FIRE ALARM SYSTEM CEILING MOUNT STROBE
DOCTOR'S DICTATION
FLOOR MOUNTED MICROPHONE OUTLET
CEILING MOUNTED SPEAKER
WALL MOUNTED SPEAKER
F
FIRE ALARM SYSTEM CHIME/STROBE
FIRE ALARM SYSTEM STROBE
FIRE ALARM SYSTEM SPEAKER/STROBE
FIRE ALARM SYSTEM CEILING MOUNT SPEAKER/STROBE
FIRE ALARM SYSTEM THERMAL DETECTOR
FIRE ALARM SYSTEM CARBON MONOXIDE DETECTOR
FIRE ALARM SYSTEM CEILING MOUNT CHIME/STROBE
C
H
S
C
H
S
C
T
FIRE ALARM SYSTEM DUCT SMOKE DETECTORD
JUNCTION BOX FOR DOOR OPERATOR; PROVIDE 3/4"EC
WITH PULL STRING FROM THE JUNCTION BOX TO AN
ACCESSIBLE LOCATION ABOVE CEILING NEAR THE
CONTROLLED DOOR
JUNCTION BOX FOR KEYPAD; INSTALL 48" AFF AND
PROVIDE 3/4"EC WITH PULL STRING FROM THE JUNCTION
BOX TO AN ACCESSIBLE LOCATION ABOVE CEILING
JUNCTION BOX FOR DOOR CONTACT (MAGNETIC LOCK);
PROVIDE 3/4"EC WITH PULL STRING FROM THE DOOR
FRAME TO THE JUNCTION BOX AND FROM THE JUNCTION
BOX TO AN ACCESSIBLE LOCATION ABOVE CEILING
JUNCTION BOX FOR CARD READER; PROVIDE 3/4"EC WITH
PULL STRING FROM THE JUNCTION BOX TO AN
ACCESSIBLE LOCATION ABOVE CEILING
JUNCTION BOX FOR ELECTRIC STRIKE LOCK; PROVIDE
3/4"EC WITH PULL STRING FROM THE DOOR FRAME TO THE
JUNCTION BOX AND FROM THE JUNCTION BOX TO AN
ACCESSIBLE LOCATION ABOVE CEILING
JUNCTION BOX FOR MOTION DETECTOR; PROVIDE 3/4"EC
WITH PULL STRING FROM THE JUNCTION BOX TO AN
ACCESSIBLE LOCATION ABOVE CEILING
JUNCTION BOX FOR CEILING MOUNTED CAMERA; PROVIDE
3/4"EC WITH PULL STRING FROM THE JUNCTION BOX TO
AN ACCESSIBLE LOCATION ABOVE CEILING
NURSE CALL SYSTEM EMERGENCY CALL-IN STATION
NURSE CALL SYSTEM BEDSIDE PATIENT STATION
NURSE CALL SYSTEM STAFF STATION
NURSE CALL SYSTEM CORRIDOR DOME LIGHT
NURSE CALL SYSTEM CODE BLUE STATION
D
M
KP
DC
CR
ES
MD
S
N
B
FIRE ALARM SYSTEM SMOKE DETECTORS
SP
SP
FIRE ALARM
SECURITY (EQUIPMENT PROVIDED BY OWNER/OTHERS)
JUNCTION BOX FOR WALL MOUNTED CAMERA; PROVIDE
3/4"EC WITH PULL STRING FROM THE JUNCTION BOX TO
AN ACCESSIBLE LOCATION ABOVE CEILING
SOUND
HEALTHCARE
FIRE ALARM CONTROL PANELFACP
(PROVIDE CONDUIT AND WIRE PER THE PANEL SCHEDULE FOR POWER
AND CONDUIT AND CABLING PER THE MANUFACTURER'S SPECIFICATIONS)
(EQUIPMENT PROVIDED BY OTHERS)
(PROVIDE 1"EC WITH PULL STRING FROM THE DEVICE LOCATION SHOWN
ON THE DRAWINGS TO AN ACCESSIBLE LOCATION ABOVE CEILING)
(PROVIDE 1"EC WITH PULL STRING FROM THE DEVICE LOCATION SHOWN
ON THE DRAWINGS TO AN ACCESSIBLE LOCATION ABOVE CEILING)
ELECTRICAL GENERAL NOTES
1. ALL ELECTRICAL WORK SHALL BE DONE IN STRICT ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL
CODE AS ADOPTED BY THE AHJ.
2. THE WORDS "PROVIDE" AND "PROVIDED" AS USED HEREIN SHALL BE UNDERSTOOD TO MEAN, "PROVIDE COMPLETE IN PLACE," THAT IS "FURNISH AND INSTALL". EQUIPMENT AND MATERIAL INDICATED TO BE PROVIDED SHALL BE NEW UNLESS OTHERWISE NOTED AND SHALL BE OF THE MOST SUITABLE GRADE FOR THE PURPOSE INTENDED.
3. ROUTE NEW CONDUIT AND WIRING CONCEALED IN WALLS AND CEILING WHERE POSSIBLE. COORDINATE INSTALLATION OF
EXPOSED CONDUIT AND WIRING WITH THE ARCHITECT.
4. CONTRACTOR SHALL PROVIDE ELECTRICAL SERVICE TO NEW HVAC UNITS AS FURNISHED BY THE MECHANICAL CONTRACTOR. VERIFY THE EXACT ELECTRICAL REQUIREMENTS WITH THE REVIEWED HVAC SUBMITTALS PRIOR TO
ORDERING ELECTRICAL EQUIPMENT.
5. BEFORE INSTALLATION, CONTRACTOR SHALL SUBMIT DETAILED DRAWINGS TO THE ENGINEER FOR REVIEW COVERING PROPOSED LOCATIONS, MOUNTING, AND ROUTING FOR ALL CONDUITS, SERVICES, FITTINGS, GROUND RODS, SUPPORTS, ETC.
6. CONTRACTOR IS RESPONSIBLE FOR OVER-CURRENT PROTECTIVE DEVICE SHORT CIRCUIT, COORDINATION, AND ARC-
FLASH STUDIES.
7. MATERIALS AND MANUFACTURERS NOTED ON DRAWINGS ARE TO BE USED AS BASIS OF DESIGN TO ESTABLISH QUALITY AND PERFORMANCE STANDARDS AND SHALL BE PROVIDED AS SPECIFIED. SUBSTITUTIONS WILL BE CONSIDERED WHERE SUFFICIENT PRODUCT INFORMATION IS PROVIDED TO MAKE A PROPER EVALUATION. REVIEW OF A SUBSTITUTION IS AT
THE SOLE DISCRETION OF THE PROFESSIONAL.
8. THE CONTRACTOR SHALL SUBMIT COPIES OF THE PRODUCT DATA, SHOP DRAWINGS, ETC. OF ALL MATERIALS NOTED ON THE DRAWINGS. ALL SUBMITTED PRODUCT DATA, SHOP DRAWINGS, ETC. SHALL BE MARKED WITH THE NAME OF THE PROJECT AND SHALL BEAR THE STAMP OF APPROVAL OF THE CONTRACTOR AS EVIDENCE THAT THE MATERIAL HAS BEEN
CHECKED BY THE CONTRACTOR.
9. DRAWINGS SPECIFIC TO THIS TRADE DO NOT LIMIT THE RESPONSIBILITY OR WORK REQUIRED BY THE CONTRACT DOCUMENTS. REFER TO DRAWINGS AND SPECIFICATIONS OF OTHER TRADES FOR COMPLETE INFORMATION PRIOR TO BID.
10. WHERE CONFLICTS EXIST AMONG DRAWINGS, SPECIFICATIONS, AND EQUIPMENT SCHEDULES, THE MOST STRINGENT REQUIREMENT OR QUANTITY SHALL APPLY. NOTIFY THE ARCHITECT/ENGINEER OF ALL CONFLICTS FOR RESOLUTION OR
INTERPRETATION.
11. NO EQUIPMENT SHALL BE ORDERED OR INSTALLED UNTIL THE PROJECT ENGINEER HAS RECEIVED A COPY STAMPED "NO EXCEPTIONS TAKEN." "NO EXCEPTIONS TAKEN" DOES NOT RELIEVE THE CONTRACTOR FROM CONFORMANCE WITH THE CONTRACT, EXTEND TO QUANTITIES OR DIMENSIONS, IMPLY THAT THE EQUIPMENT CAN BE INSTALLED OR OPERATE SATISFACTORILY, THAT THE EQUIPMENT CONTAINS ALL NECESSARY COMPONENTS, OR THAT IT WILL COORDINATE WITH
OTHER REVIEWED ITEMS.
12. OMISSION FROM THIS SHEET OF ANY ITEM SHOWN ELSEWHERE IN THE PLANS DOES NOT RELIEVE THE CONTRACTOR
FROM THE RESPONSIBILITY FOR ANY ASSOCIATED WORK.
13. COORDINATE INSTALLATION OF NEW ITEMS AND EQUIPMENT WITH THE OWNER'S REPRESENTATIVE AND THE WORK OF OTHER TRADES. THE CONTRACTOR SHALL INCUR ALL COSTS ASSOCIATED WITH THE RELOCATION OF EQUIPMENT
CONFLICTING WITH NEW WORK BY OTHER TRADES THAT HAS NOT BEEN COORDINATED.
14. COORDINATE ALL ASPECTS OF NEW SERVICE WITH UTILITY COMPANY AND INCLUDE ALL COSTS IN BID.
15. WARNING TAPE SHALL BE INSTALLED 12 TO 18 INCHES BELOW GRADE OVER ALL CONDUITS.
16. PROVIDE 1/4" MINIMUM DIAMETER PULL ROPE. PULL ROPE SHALL NOT BE NYLON STRING.
17. FOR SERVICE ENTRANCE CONDUITS, UTILIZE LONG RADIUS (36") CONDUIT BENDS.
18. ALL CONDUIT RISERS FROM UNDERGROUND SHALL HAVE RIGID METAL ELLS AND RISERS.
19. PRIOR TO CONSTRUCTION, VERIFY THE LOCATION OF ALL EXISTING UNDERGROUND UTILITIES. AVOID DISTURBANCE OF
EXISTING UTILITIES NOT INCLUDED IN THIS PROJECT.
20. SET SCREW CONDUIT FITTINGS SHALL NOT BE PERMITTED.
LIGHTING GENERAL NOTES
1. VERIFY THE EXACT LOCATION OF ALL LIGHTING SWITCHES WITH THE ARCHITECT PRIOR TO ROUGH-IN.
2. VERIFY THE EXACT LOCATION OF ALL LIGHTING FIXTURES WITH THE ARCHITECTURAL…
This is the start of the file's text. The full file is on GovTribe.