This is a comprehensive set of architectural and engineering design documents for a Boiler Replacement project at Southern University at New Orleans, specifically for the Arts, Humanities & Social Science Building and Gymnasium. The project is being managed by the State of Louisiana's Division of Administration, Office of Facility Planning and Control, under Governor Jeff Landry's administration. The documents detail the replacement of existing boilers with new condensing stainless steel firetube boilers (Lochinvar FCB 2000N models) in two locations - the Arts and Humanities building and the Gymnasium. The project number is 19-671-22-01, with state building IDs S27481 and S00303, and the site code is 1-36-007.

The design documents include detailed mechanical, electrical, and architectural plans for demolishing existing boiler systems and installing new boilers, associated pumps, air separators, compression tanks, and related infrastructure. The new boilers have a maximum input of 1,999,000 Btu/Hr, with an output of 1,923,000 Btu/Hr and high thermal efficiency of 96.2%. The project includes electrical connections, piping modifications, and supporting systems like variable speed pumps and combustion air fans. The design emphasizes energy efficiency, proper installation practices, and compliance with current building and mechanical codes. The documents are dated 06/18/2025 and were prepared by Parish Engineering, indicating a comprehensive approach to modernizing the university's heating infrastructure.

View the file

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SHEET NUMBER

SHEET NAME

DATE:

REVISIONS

DRAWN BY:

CHECKED BY:

PROJECT #:

SHEET INFORMATION

SEAL

PROJECT INFORMATION

All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.

7600 Innovation Park Drive

Baton Rouge, LA 70820

225.332.0222 parisheng.com

COVER

COVER SHEET

CTD/SPG

LJB/SPG

06-18-2025

25-040

B O

IL

E

R R

E P

L A

C E

M E

N T

A R

T S

H

U M

A N

IT

IE

S

S O

C

IA

L S

C

IE

N C

E B

U

IL

D

IN

G

G Y

M N

A S

IU

M

S

U N

O N

E W

O R

L E

A N

S

L A

BOILER REPLACEMENT

ARTS, HUMANITIES & SOCIAL SCIENCE BUILDING & GYMNASIUM

SOUTHERN UNIVERSITY AT NEW ORLEANS

NEW ORLEANS, LOUISIANA

PROJECT NO.: 19-671-22-01, F.19002574

STATE BUILDING ID:

S27481 - ARTS, HUMAINTIES & SOCIAL SCIENCES

S00303 - GYMNASIUM

SITE CODE: 1-36-007

STATE OF LOUISIANA

JEFF LANDRY, GOVERNOR

DIVISION OF ADMINISTRATION

TAYLOR F. BARRAS, COMMISSIONER OF ADMINISTRATION

OFFICE OF FACILITY PLANNING AND CONTROL

ROGER E. HUSSER, JR., DIRECTOR

SOUTHERN UNIVERSITY SYSTEM

KENNETH DAWSON - SYSTEM DIRECTOR OF FACILITY PLANNING

BID DOCUMENTS

06/18/2025

VINCITY MAP

N

PROJECT AREA

SHEET INDEX

MECHANICAL

COVER COVER SHEET

M0.0 MECHANICAL COVER SHEET

M1.0 MECHANICAL PLAN

M1.1 ENLARGED MECHANICAL PLAN

M1.2 GYMNASIUM MECHANICAL PLAN

M1.3 GYMNASIUM ENLARGED MECHANICAL PLAN

M2.0 MECHANICAL DETAILS

M2.1 MECHANICAL DETAILS

M3.0 MECHANICAL SCHEDULES

ELECTRICAL

E0.0 ELECTRICAL COVER SHEET

E1.0 ARTS & HUMANITIES ELECTRICAL PLAN

E1.1 ARTS & HUMANITIES ENLARGED ELECTRICAL PLAN

E1.2 GYMNASIUM ELECTRICAL PLAN

E1.3 GYMNASIUM ENLARGED ELECTRICAL PLANS

E2.0 ELECTRICAL DETAILS

06/18/2025

MECHANICAL GENERAL NOTES

1. ALL WORK BY CONTRACTORS SHALL CONFORM TO ALL APPLICABLE FEDERAL, STATE AND LOCAL BUILDING CODES, INCLUDING THE CURRENT INTERNATIONAL ENERGY CONSERVATION CODE.

2. MATERIALS FURNISHED UNDER THE CONTRACT SHALL BE NEW & SHALL BEAR THE UL LABEL WHERE APPLICABLE, UNLESS NOTED OTHERWISE. ALL WORK SHALL BE GUARANTEED AGAINST DEFECTIVE MATERIALS & WORKMANSHIP FOR A PERIOD OF NOT LESS THAN ONE YEAR AFTER

COMPLETION & ACCEPTANCE BY THE OWNER, LONGER IF STATED OTHERWISE ELSEWHERE IN THE SPECIFICATION.

3. CONTRACTOR SHALL INSTALL SYSTEMS WITHOUT INTERFERENCE & PROVIDE MANUFACTURER'S RECOMMENDED AIR & SERVICE CLEARANCES. CONTRACTOR SHALL COORDINATE WITH ALL TRADES & DISCIPLINES.

4. MECHANICAL CONTRACTOR SHALL COORDINATE WITH GENERAL CONTRACTOR ON LOCATION OF ALL FIRE & SMOKE WALL PENETRATIONS. GENERAL CONTRACTOR SHALL FRAME OUT OPENING AS REQUIRED FOR LIFE SAFETY DAMPERS. PROVIDE LIFE SAFETY DAMPERS WHERE SHOWN ON

DRAWINGS AND WHERE REQUIRED BY NFPA AND LOCAL BUILDING CODES.

5. ALL FIRE DAMPERS SHALL BE 2-HOUR RATED UNLESS SPECIFIED OR NOTED OTHERWISE ON DRAWINGS AND/OR SPECIFICATIONS.

6. SEAL ALL FIRE WALL PENETRATIONS (DUCT, PIPE, ETC.) WITH UL-LISTED FIRE CAULK IN ACCORDANCE WITH NFPA 101.

7. MECHANICAL CONTRACTOR SHALL COORDINATE BETWEEN ELECTRICAL AND OTHER TRADES FOR PENETRATIONS AT WALLS, FLOORS AND ROOFS, EXACT EQUIPMENT LOCATIONS, AND REQUIRED EQUIPMENT SERVICE AND AIR FLOW CLEARANCE.

8. INSTALLATION OF DUCTWORK SHALL TAKE PRECEDENCE OVER INSTALLATION OF PLUMBING PIPING THAT IS NOT GRADE SENSITIVE (SEWER, STORM DRAINAGE, GREASE WASTE, ETC.) AND ELECTRICAL CONDUIT. CONTRACTOR TO COORDINATE CEILING SPACE AVAILABLE, EXACT

MECHANICAL ROOM LAYOUT, DUCT AND PIPE ROUTING AND EXACT EQUIPMENT LOCATIONS WITH GENERAL, ELECTRICAL, STRUCTURAL AND PLUMBING CONTRACTORS. PROVIDE OFFSETS AND TRANSITIONS AT OBSTRUCTIONS WHERE REQUIRED AT NO ADDITIONAL COST TO THE OWNER.

9. MECHANICAL CONTRACTOR SHALL COORDINATE WITH GENERAL CONTRACTOR AND ARCHITECT PRIOR TO INSTALLATION OF THERMOSTATS/TEMPERATURE SENSORS ON WALL. COORDINATE THERMOSTATS/TEMPERATURE SENSORS WITH ALL WALL MOUNTED FURNISHINGS (ART, SCREENS, FURNITURE, ETC.). LOCATE THERMOSTATS AND HUMIDISTATS 4' ABOVE FINISHED FLOOR UNLESS OTHERWISE NOTED.

10. CONTRACTOR SHALL VISIT THE SITE FOR INSPECTION REGARDING ANY WORK REQUIRED TO COMPLETE THE SCOPE OF WORK FOR THE PROJECT PRIOR TO BID. THERE SHALL BE NO ADDITIONAL COST TO THE OWNER FOR BIDDERS AWARDED THE WORK FOR FAILURE TO EXAMINE SITE

PRIOR TO BID.

11. CONTRACTOR SHALL REVIEW THE CONTRACT DOCUMENTS AND VISIT THE SITE AND COORDINATE DUCT, PIPE AND EQUIPMENT SIZES AND ROUTING. CONTRACTOR SHALL NOTIFY THE ARCHITECT AND ENGINEER WHERE DISCREPANCIES OCCUR BETWEEN CONTRACT DOCUMENTS AND

EXISTING CONDITIONS.

12. CONTRACTOR SHALL REVIEW CEILING SPACE AND MECHANICAL ROOM SPACE AVAILABLE FOR DUCT, PIPING AND EQUIPMENT AND MAKE REQUIRED ALLOWANCES FOR THE SIZE AND ROUTING OF DUCT, PIPING AND EQUIPMENT.

13. MECHANICAL CONTRACTOR TO REVIEW CEILING SPACE AVAILABLE AND VERIFY FIELD MEASUREMENTS AND COORDINATION DRAWINGS PRIOR TO FABRICATING DUCT. BRANCH DUCT RUNS SHOWN DIAGRAMMATICALLY; CONTRACTOR SHALL ROUTE BRANCH DUCT RUNS IN MOST DIRECT

MANNER.

14. COORDINATE EXACT LOCATION OF ALL SLAB, FLOOR, WALL AND ROOF PENETRATIONS WITH EXISTING STRUCTURAL BEAMS, JOIST AND COMPONENTS. DO NOT CUT OR MODIFY EXISTING STRUCTURAL COMPONENTS WITHOUT APPROVAL FROM STRUCTURAL ENGINEER.

15. CONTRACTOR SHALL VERIFY EQUIPMENT TO BE SUPPLIED TO PROJECT CAN BE INSTALLED IN SPACE PROVIDED AND ALL SERVICE AND AIRFLOW CLEARANCES MAINTAINED PRIOR TO ORDERING EQUIPMENT. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY MODIFICATIONS REQUIRED FOR

EQUIPMENT THAT IS SUPPLIED THAT IS DIFFERENT THAN EQUIPMENT THAT IS BASIS OF DESIGN.

16. UNDER NO CIRCUMSTANCES SHALL EQUIPMENT AND RELATED SYSTEM COMPONENTS FOUND POSITIVE FOR MOLD, MILDEW, ASBESTOS, HARMFUL BACTERIA OR ANY OTHER CONTAMINATION BE PLACED INTO SERVICE.

17. INSTALL DUCT SLEEVES IN WALLS AS HIGH AS POSSIBLE, DUCT SLEEVE SHALL EXTEND PAST WALL PENETRATION ON BOTH SIDES MINIMUM 24". RETURN AIR TRANSFER SLEEVES SHALL BE PROVIDED WITH TWO (2) DUCT ELBOWS.

18. COORDINATE ALL UNDERGROUND PIPING & WORK WITH EXISTING SYSTEMS, INCLUDING EXISTING UTILITIES, SEWER, GAS, DOMESTIC WATER, CHILLED/HEATING WATER, ELECTRIC DUCT BANKS AND POWER. NOT ALL EXISTING SYSTEMS SHOWN. COORDINATE ALL EXISTING SYSTEMS PRIOR

TO BEGINNING WORK. MARKED UTILITIES AND EXISTING SYSTEMS DAMAGED BY THE CONTRACTOR SHALL BE REPLACED AND REPAIRED BACK TO ORIGINAL CONDITION BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE CONSTRUCTION CONTRACT.

19. MODEL NUMBERS SCHEDULED/SPECIFIED REPRESENT THE TYPE AND QUALITY OF EQUIPMENT REQUIRED TO MEET THE DESIGN REQUIREMENTS. CONTRACTOR SHALL REVIEW SUBMITTALS AND VERIFY EQUIPMENT SIZES, QUALITY AND PERFORMANCE REQUIREMENTS MEET

SPECIFICATIONS PRIOR TO SUBMITTING FOR APPROVAL. EQUIPMENT THAT DIFFERS FROM BASIS OF DESIGN IS SUBJECT TO REJECTION. CONTRACTOR TO COORDINATE ALL DIFFERENCE IN EQUIPMENT WITH STRUCTURAL, ELECTRICAL AND PLUMBING CONTRACTORS.

20. ALL CONDENSATE LINES SHALL BE RIGID COPPER, INSULATED WITH CELLULAR FOAM UNLESS NOTED OTHERWISE OR SUBMITTED AND APPROVED BY MECHANICAL ENGINEER. SUPPORT WITH UNISTRUT PIPE EVERY 4' AND AT TURNS. PROVIDE NEOPRENE SLEEVES BETWEEN UNISTRUT AND

COPPER CONDENSATE LINE.

21. DUCT SIZES SHOWN ARE SHEET METAL SIZES. ALLOWANCES HAVE BEEN INCLUDED FOR INTERNAL LINER WHERE APPLICABLE.

22. COORDINATE EXACT LOCATION OF AIR DEVICES WITH NEW AND EXISTING LIGHTS TO BE INSTALLED PRIOR TO CONSTRUCTION.

23. EXPOSED DUCTWORK SHALL BE PAINT GRIPPED SHEET METAL UNLESS INDICATED OTHERWISE. ALL EXPOSED DUCT TO BE PAINTED IN FIELD BY PAINTING CONTRACTOR DURING CONSTRUCTION. COORDINATE WITH ARCHITECT & MECHANICAL ENGINEER PRIOR TO INSTALLATION OF

EXPOSED DUCT AND COLOR. EXPOSED DUCTWORK SHALL BE FREE OF SIZE MARKS OR ASSEMBLY CODE NUMBERS; ALL MARKS SHALL BE ON THE INSIDE OF DUCTWORK. KEEP OUTSIDE SURFACES OF DUCT CLEAN DURING FABRICATION. BANDS SHALL JOIN ON TOP, CONCEALED FROM NORMAL VIEW OF THE DUCT AND SPIRALS SHALL BE CONTINUOUS. THREADED RODS FROM HANGER STRAPS SHALL BE NEATLY CLIPPED AND SECURED WITHOUT EXCESS. GREATER ATTENTION TO APPEARANCE FOR EXPOSED DUCT IS EXPECTED AND DENTED/SCARRED DUCTS SHALL NOT

BE ACCEPTABLE.

24. PROVIDE ELECTRICAL DISCONNECTS FOR MECHANICAL EQUIPMENT (VAV BOXES, FANS, VFD'S, ETC.) FACTORY INSTALLED BY EQUIPMENT MANUFACTURER UNLESS NOTED OTHERWISE. COORDINATE WITH ELECTRICAL CONTRACTOR.

25. DO NOT ROUTE PIPING CONTAINING WATER OVER ELECTRICAL EQUIPMENT.

26. PROVIDE PERMANENT LABELS FOR ALL SCHEDULED EQUIPMENT. LABELS SHALL BE MINIMUM 3/8" ENGRAVED BLACK LETTERS ON WHITE BACKGROUND, CONSTRUCTED OF MINIMUM 1" WIDE, LENGTH AS REQUIRED LAMINATED PLASTIC. SECURELY FASTENED TO EQUIPMENT WITH STAINLESS

STEEL OR NONCORRODING HARDWARE. STICK ON LABELS NOT ACCEPTABLE.

27. EXHAUST OUTLETS SHALL BE LOCATED MINIMUM 10' FROM ANY AIR INTAKE OR OPERABLE BUILDING OPENING.

28. INDOOR MINISPLITS, FAN COIL UNITS AND CEILING CASSETTES SHALL HAVE GRAVITY DRAINAGE WHERE POSSIBLE. PROVIDE WITH INTEGRAL CONDENSATE PUMPS WHERE NOT POSSIBLE.

29. PROVIDE RETURN AIR GRILLES OPEN TO RETURN AIR PLENUM WITH SOUND ATTENUATING BOOT ON REAR OF GRILLE (RIGID DUCT WITH INSULATED LINER & TWO ELBOWS, END OPEN TO RETURN AIR PLENUM). CONTRACTOR HAS OPTION TO PROVIDE PRICE MODEL #RAC RETURN AIR

CANOPY ON REAR OF RETURN AIR GRILLES OPEN TO RA PLENUM IN LIEU OF SOUND ATTENUATING BOOT.

30. ELECTRONIC BALANCING DAMPERS : MANUAL DAMPER AT INACCESSIBLE LOCATIONS:

30.1. PROVIDE REMOTE BALANCING DAMPER WITH POSITION INDICATOR AT INACCESSIBLE MANUAL VOLUME DAMPERS

30.2. INACESSIBLE LOCATIONS:

30.2.1. ABOVE GYPSUM BOARD/HARD CEILING

30.2.2. WHERE LOCATED HIGHER THAN 4'-0" ABOVE ACCESSIBLE CEILING TILE

30.2.3. WHERE LOCATED ABOVE 14'-0" FROM FINISHED FLOOR

30.2.4. REFER TO ARCHITECTURAL REFLECTED CEILING DRAWINGS FOR REFLECTED CEILING PLAN

30.3. ELECTRONIC BALANCING DAMPER SHALL BE PROVIDED WITH POSITION INDICATOR AND SHALL BE GREENHECK MODEL RBDR-50 (ROUND) & RBD-10 (RECTANGULAR) OR APPROVED EQUAL, UNLESS INDICATED OTHERWISE.

30.4. REMOTE BALANCING DAMPER SHALL BE 12 VOLT DC POWER BALANCE SYSTEM ( DAMPER, PULSE ACTUATOR , CAT 5 CABLE, WALL OR CEILING PLATE AND HAND HELD POWER PACK). PROVIDE WALL/CEILING ACCESS PORT ON WALL WITHIN CLOSEST MECHANICAL ROOM OR ABOVE

ACCESSIBLE CEILING MOUNTED ON WALL. ALL ACCESS PORTS TO BE PROPERLY LABELED NUMERICALLY BY RESPECTIVE AIR SYSTEM & ROOM DAMPER SERVES. COORDINATE WITH MECHANICAL ENGINEER PRIOR TO LABELING & COORDINATE LOCATION WITH MECHANICAL ENGINEER & ARCHITECT PRIOR TO INSTALLING ANY ACCESS PORT ABOVE ACCESSIBLE CEILINGS. PROVIDE TILE IDENTIFICATION WHERE LOCATED ABOVE CEILING, PROVIDE DRAWING IDENTIFYING PORT LOCATION & PORT SCHEDULE AS PART OF CLOSE OUT DOCUMENTS.

31. PROVIDE U.L. LISTED SMOKE DETECTORS IN THE MAIN SUPPLY DUCT AND RETURN ON THE DOWNSTREAM SIDE OF THE FILTERS IN ALL RECIRCULATING AIR SYSTEMS HANDLING OVER 2000 C.F.M. NOTE: SMOKE DETECTORS TO BE WIRED TO BUILDING FIRE ALARM SYSTEM BY FIRE ALARM CONTRACTOR, FIRE ALARM CONTRACTOR IS TO PROVIDE AND INSTALL ALL WIRING, TERMINATIONS, ETC. TO PROVIDE A COMPLETE, PROPERLY FUNCTIONING AND OPERATING SYSTEM.

32. PROVIDE SMOKE DAMPER IN THE MAIN SUPPLY & RETURN DUCT IN ALL AIR HANDLING UNITS HANDLING OVER 15,000 CFM. SMOKE DAMPERS TO BE INTERCONNECTED TO SMOKE DETECTORS.

33. PROVIDE ACCESS PANELS FOR EQUIPMENT,VALVES, DAMPER, ETC. LOCATED ABOVE A NON ACCESSIBLE CEILING. ACCESS PANELS SHALL BE LARGE ENOUGH FOR ALL REQUIRED MAINTENANCE, ADJUSTMENT, ECT. PROVIDE MULTIPLE ACCESS PANELS AS REQUIRED. COORDINATE COLOR

AND LOCATIONS WITH ARCHITECT. PROVIDE FIRE AND/ OR SMOKE RATED ACCESS PANELS WHERE REQUIRED IN RATED CEILINGS. REFERENCE ARCHITECTURAL DRAWINGS FOR RATED CEILING LOCATIONS. WHERE ACCESS PANELS ARE SHOWN ON ARCHITECTURAL REFLECTED CEILING PLAN, COORDINATE EXACT LOCATION OF EQUIPMENT, DEVICES, ETC. WITH ACCESS PANEL LOCATIONS.

34. PROVIDE TEMPORARY CAPS/PLUGS/COVERING ON ALL OPEN ENDED PIPING & DUCT DURING CONSTRUCTION TO PREVENT DIRT/DEBRIS FROM ENTERING PIPE/DUCT SYSTEMS.

35. PROVIDE PROTECTIVE LOCKABLE THERMOSTAT COVERS FOR THERMOSTATS. COORDINATE WITH OWNER.

36. MECHANICAL CONTRACTOR SHALL COORDINATE WITH PLUMBING CONTRACTOR ON LOCATION OF ALL FLOOR DRAINS & HUB DRAINS AS NOT TO INTERFERE WITH EQUIPMENT & EQUIPMENT PADS. COORDINATE NEW FLOOR DRAIN & HUB LOCATION WHERE EQUIPMENT DOES NOT ALLOW

FOR THE INSTALLATION SHOWN FOR DRAIN. COORDINATE HEIGHT OF HUB DRAINS FOR FAN COIL UNITS & CEILING CASSETTES.

37. PROVIDE TRANSITIONS FROM REAR OF ALL GRILLES TO BRANCH DUCTS AND TO ALL EQUIPMENT AS REQUIRED. REFER TO CONSTRUCTION DOCUMENTS FOR SIZES OF GRILLES AND DUCTS.

38. PRESSURE TEST ALL REUSED/REROUTED PIPING SYSTEMS. TESTING SHALL BE PERFORMED AT NORMAL SYSTEM OPERATING PRESSURE UNLESS INDICATED/SPECIFIED OTHERWISE. REPAIR AND RETEST AS REQUIRED UNTIL SYSTEMS ARE PROVEN TIGHT WITHOUT LEAKS.

39. ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT OR PIPING INSULATION IS APPLIED.

40. LOCATE ALL TEMPERATURE PRESSURE AND FLOW MEASURING DEVICES IN ACCESSIBLE LOCATIONS WITH STRAIGHT SECTION OF PIPE OR DUCT UP AND DOWN STREAM AS RECOMMENDED BY THE MANUFACTURER.

41. REINFORCEMENT, DETAILING, AND PLACEMENT OF CONCRETE SHALL CONFORM TO ASTM 315 AND ACI 318. CONCRETE SHALL CONFORM TO ASTM C94. CONCRETE WORK SHALL CONFORM TO ACI318, PART ENTITLED “CONSTRUCTION REQUIREMENTS.” COMPRESSIVE STRENGTH IN 28 DAYS

SHALL BE 3,000 PSI. TOTAL AIR CONTENT OF EXTERIOR CONCRETE SHALL BE BETWEEN 5 AND 7 PERCENT BY VOLUME. SLUMP SHALL BE BETWEEN 3 AND 4 INCHES. CONCRETE SHALL BE CURED FOR 7 DAYS AFTER PLACEMENT.

42. COORDINATE ALL EQUIPMENT CONNECTION WITH MANUFACTURERS’ CERTIFIED DRAWINGS. COORDINATE AND PROVIDE ALL DUCT AND PIPING TRANSITIONS REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND COORDINATE ALL DUCT AND

PIPING DIMENSIONS BEFORE FABRICATION.

43. MINIMUM CONCRETE PAD THICKNESS SHALL BE 4 INCHES. PAD SHALL EXTEND BEYOND THE EQUIPMENT A MINIMUM OF 6 INCHES ON EACH SIDE UNLESS OTHERWISE DIRECTED IN THESE DOCUMENTS 15 LOCATIONS AND SIZES OF ALL FLOOR, WALL, AND ROOF OPENINGS SHALL BE

COORDINATED WITH ALL OTHER TRADES INVOLVED. REFER TO TYPICAL DETAILS FOR DUCTWORK, PIPING, AND EQUIPMENT INSTALLATION.

44. INSTALL TRANSITION DUCT FROM INLET AND OUTLET OF EQUIPMENT TO DUCT SIZE SHOWN ON PLANS; CONSULT EQUIPMENT MANUFACTURER FOR INLET AND OUTLET SIZE.

45. ALL DUCT ELBOWS, BENDS, AND TEES SHALL BE PROVIDED WITH DOUBLE THICKNESS TURNING VANES OR RADIUS ELBOWS UNLESS SHOWN OR NOTED OTHERWISE. ELBOWS IN DISHWASHER, KITCHEN, AND LAUNDRY EXHAUST SHALL BE UNVANED SMOOTH RADIUS CONSTRUCTION WITH A

RADIUS OF 1.5 TIMES THE WIDTH OF THE DUCT.

46. PROVIDE ESCUTCHEONS AT ALL EXPOSED LOCATIONS WHERE PIPE PENETRATES WALL.

47. THE CONDENSATE DRAIN LINE SHALL NOT DECREASE IN SIZE FROM THE DRAIN PAN CONNECTION TO THE FLOOR DRAIN; ELEVATE UNIT TO ACCOMMODATE P-TRAP.

48. ALL EQUIPMENT AND DEVICES TO BE FURNISHED AND INSTALLED PER THE REQUIREMENTS OF CONTRACT DRAWINGS, SPECIFICATIONS, MANUFACTURERS RECOMMENDATIONS, AND ACCORDING TO CODE.

49. PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS (SUPPLY, RETURN, AND EXHAUST) CONNECTED TO AIR HANDLING UNITS, FANS, AND OTHER EQUIPMENT WHICH REQUIRE VIBRATION ISOLATION. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AT THE POINT OF CONNECTION TO

THE EQUIPMENT UNLESS OTHERWISE DIRECTED IN THESE DOCUMENTS.

50. UNLESS OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD, TIGHT TO UNDERSIDE OF THE STRUCTURE, WITH SPACE FOR INSULATION.

51. ALL ROOF CURBS SHALL BE INSTALLED TO THE ROOFING STRUCTURE AND FINISH A MINIMUM 12" ABOVE THE FINISHED ROOF FOR COUNTER FLASH ENDORSED BY ROOF MANUFACTURER. ROOF CURBS SHALL BE PITCHED WHERE REQUIRED TO ENSURE EQUIPMENT IS INSTALLED LEVEL.

52. ALL MISCELLANEOUS ROOFTOP EQUIPMENT SUPPORTS SHALL BE ENDORSED BY BOTH THE RESPECTIVE EQUIPMENT MANUFACTURER AND ROOF SYSTEM MANUFACTURER.

53. ALL WALL APPLIED ITEMS SHALL BE INSTALLED PLUMB, LEVEL AND IN LOCATIONS DESIGNATED IN CONTRACT DOCUMENTS. ALL DEVICE COVERS AND TRIM SHALL FIT TIGHT TO WALL SURFACE ON ALL SIDES. WHERE SPECIFIC LOCATIONS FOR ITEMS NOT SHOWN OR CLEAR, CONTRACTOR

SHALL OBTAIN CLARIFICATION AND DIRECTION FROM ARCHITECT AND MECHANICAL ENGINEER PRIOR TO INSTALLATION.

54. ALL FLEX DUCT SERVING DIFFUSERS SHALL BE LIMITED TO RUNS OF 6'. FLEX DUCT SHALL BE FLEXMASTER 1M-R6 OR APPROVED EQUAL AND USE STAINLESS STEEL (OR NYLON IF APPROVED BY MECHANICAL ENGINEER) TO CONNECT FLEX TO DUCT AND GRILLES.

55. FLEXIBLE DUCT NOT ACCEPTABLE FOR EXHAUST, RETURN AND FRESH AIR SYSTEMS UNLESS SPECIFIED OR NOTED OTHERWISE. FLEX DUCT SHALL NOT PENETRATE ANY WALLS UNLESS SUBMITTED AND APPROVED ON TO BOTH THE ARCHITECT AND MECHANICAL ENGINEER.

56. PROVIDE ADDITIONAL SUSPENDED SUPPORTS AS REQUIRED TO PREVENT FLEXIBLE DUCT FROM CONTACTING THE CEILING MATERIAL AND/OR CEILING FRAME/GRID ASSEMBLY.

57. ALL ROUND TAPS OFF RECTANGULAR DUCTWORK TO DIFFUSERS SHALL BE MADE WITH HIGH EFFICIENCY SIDE TAKEOFFS WITH 2" INSULATION STANDOFF BRACKETS AND LOCKING QUADRANT, FLEXMASTER MODEL STOD-BO3 OR APPROVED EQUAL.

58. ALL GRILLES LOCATED IN LAY-IN CEILINGS SHALL HAVE 24x24 FRAMES, STYLES TO FIT THE GRID TYPE, EITHER 15/16" OR 9/16" GRID, VERIFY GRID WITH ARCHITECTURAL DRAWINGS. PROVIDE PLASTER FRAMES FOR SURFACE MOUNT APPLICATIONS, PRICE MODEL AMF OR APPROVED EQUAL.

59. PROVIDE MANUAL VOLUME DAMPERS IN ALL BRANCH DUCT CONNECTIONS TO LOW PRESSURE MAIN DUCTS.

60. ALL EQUIPMENTS SUPPLIED TO THE PROJECT SHALL BE PER SPECIFICATIONS. OBTAINING APPROVED SUBMITTALS DOES NOT RELIEVE THE CONTRACTOR/SUPPLIER OF PROVIDING ALL FEATURES, OPTIONS AND ACCESSORIES INCLUDED WITHIN THE CONSTRUCTION DOCUMENTS.

AC AIR CONDITIONING

ACCU AIR COOLED CONDENSING UNIT

AFF ABOVE FINISHED FLOOR

AFS AIR FLOW STATION

AHU AIR HANDLING UNIT

AMB AMBIENT

AS AIR SEPARATOR

AV AIR VENT

BAS BUILDING AUTOMATION SYSTEM

BDD BACKDRAFT DAMPER

BFP BACKFLOW PREVENTER

BOD BOTTOM OF DUCT

BTUH BRITISH THERMAL UNIT PER HOUR

CC COOLING COIL

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CH CHILLER

CHWCF CHILLED WATER CHEMICAL FEED

CHP CHILLED WATER PUMP

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

COMP COMPRESSOR

CP CIRCULATING PUMP

CU CONDENSING UNIT

CT COOLING TOWER

CV CONTROL VALVE

CW COLD WATER

CWCF CONDENSER WATER CHEMICAL FEED

CWR CONDENSER WATER RETURN

CWP CONDENSER WATER PUMP

CWS CONDENSER WATER SUPPLY

DB DRY BULB TEMP (DEG F)

DDC DIRECT DIGITAL CONTROL

DN DOWN

DP DIFFERENTIAL PRESSURE

DPS DIFFERENTIAL PRESSURE SWITCH

DWG DRAWING

DX DIRECT EXPANSION

EA EXHAUST AIR

EDH ELECTRIC DUCT HEATER

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EL ELEVATION

ELEC ELECTRICAL

ENT ENTERING

ECU ELECTRIC CONDENSING UNIT

ERU ELECTRIC REFRIGERANT UNIT

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

EUH ELECTRIC UNIT HEATER

EVAP EVAPORATOR

EX EXHAUST

EXT EXTERNAL

FA FRESH AIR

FC/FCUFAN COIL UNIT

FD FIRE DAMPER

FT FEET

FLA FULL LOAD AMPS

FPM FEET PER MINUTE

FV FACE VELOCITY

GALV GALVANIZED

GPM GALLONS PER MINUTE

GPH GALLONS PER HOUR

GUH GAS UNIT HEATER

HC HEATING COIL

HP HORSEPOWER

HR HOUR

HWS HEATING WATER SUPPLY

HWR HEATING WATER RETURN

ID INSIDE DIAMETER

IN INCHES

KW KILOWATTS

LVG LEAVING

MA MIXED AIR

MAX MAXIMUM

MD MOTORIZED DAMPER

MECH MECHANICAL

NG NATURAL GAS

MIN MINIMUM

MVD MANUAL VOLUME DAMPER

NC NORMALLY CLOSED

NFPA NATIONAL FIRE PROTECTION ASSOC.

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NOM NOMINAL

NTS NOT TO SCALE

OA OUTSIDE AIR

OAF OUTSIDE AIR FAN

OAU OUTSIDE AIR UNITS

OS&Y OUTSIDE STEM AND YOKE

OZ OUNCES (PRESSURE)

PD PRESSURE DROP

PTAC PACKAGED TERMINAL AIR CONDITIONER

PSI POUNDS PER SQUARE INCH

RA RETURN AIR

REF REFERENCE

RH RELATIVE HUMIDITY

RHC REHEAT COIL

RND ROUND

RPM REVOLUTIONS PER MINUTE

RTU ROOF TOP UNIT

SA SUPPLY AIR

SD SMOKE DAMPER

SEER SEASONAL ENERGY EFFICIENCY RATIO

SF SUPPLY AIR FAN

SP STATIC PRESSURE

SPEC SPECIFICATIONS

TEMP TEMPERATURE

TOD TOP OF DUCT

TSP TOTAL STATIC PRESSURE

TYP TYPICAL

UG UNDERGROUND

UL UNDERWRITERS LISTED

VAV VARIABLE AIR VOLUME

VFD VARIABLE FREQUENCY DRIVE

W / WITH

W / O WITHOUT

WB WET BULB (DEG F)

ABBREVIATION LEGEND

DETAIL SYMBOL

GRID LINE

SECTION SYMBOL

DEMO NOTE

REVISION TAG

TIE INTOMATCHLINE

1 / M101

MATCHLINE

THERMOSTAT SYMBOLT99

NEW EQUIPMENT OR FIXTURE

EXISTING TO REMAIN

EXISTING TO BE DEMOLISHED

A-500 DIFFUSER TAG

MARK

NEW WORK

CFM

M101

M101

SECTION

DETAIL

SHEET NUMBER

SHEET NUMBER

1 GENERAL NOTE

RE: 1 / M101 SHEET REFERENCE TAG

SHEET NUMBER

VIEW NUMBER

MECHANICAL SYMBOL LEGEND

GENERAL

(REFER TO DRAWINGS AND SPECIFICATIONS FOR FURTHER REQUIREMENTS)

MITERED 90º ELBOW WITH DOUBLE DEFLECTION

TURNING VANES

RECTANGULAR TRANSITION; SYMMETRIC

RECTANGULAR TRANSITION; ASYMMETRIC

MITERED 45º ELBOW WITH DOUBLE DEFLECTION

TURNING VANES

DUCT WITH FLEXIBLE CONNECTION

45º RECTANGULAR TAP

ROUND EXHAUST DUCT UP

ROUND EXHAUST DUCT DOWN

CHANGE IN RECTANGULAR DUCT ELEVATION; RISE

CHANGE IN ROUND DUCT ELEVATION; DROP

4-WAY S/A DIFFUSER; SEE SCHEDULE FOR SIZE

3-WAY S/A DIFFUSER; SEE SCHEDULE FOR SIZE

2-WAY S/A DIFFUSER; SEE SCHEDULE FOR SIZE

1-WAY S/A DIFFUSER; SEE SCHEDULE FOR SIZE

R/A GRILLE; SEE SCHEDULE FOR SIZE

DUCT WITH MANUAL VOLUME DAMPER

DUCT WITH FIRE DAMPER

DUCT WITH SMOKE DAMPER

DUCT WITH COMBINATION FIRE/SMOKE DAMPER

DUCT WITH ACCESS DOOR

DUCT WITH MOTORIZED DAMPER

45º LEAD-IN WITH MANUAL VOLUME DAMPER

RADIUS ELBOW

E/A GRILLE; SEE SCHEDULE FOR SIZE

INTERNALLY INSULATED DUCT

SUPPLY DUCT

RETURN DUCT

EXHAUST DUCT

RECTANGULAR SUPPLY DUCT UP

RECTANGULAR EXHAUST DUCT DN

ROUND SUPPLY DUCT UP

ROUND SUPPLY DUCT DN

ROUND RETURN DUCT UP

ROUND RETURN DUCT DN

RECTANGULAR SUPPLY DUCT DN

RECTANGULAR RETURN DUCT UP

RECTANGULAR RETURN DUCT DN

RECTANGULAR EXHAUST DUCT UP

DUCT WITH HUMIDIFIER

R

D

DUCT WITH BACK DRAFT DAMPER

DUCTWORK

INLET

3/4" MAKE UP WATER

1/2" BLOWDOWN BALL

VALVE W/ NIPPLE

UNION

3/4" BALL VALVE

ANSI 125# FLANGE

OUTLET

TO PUMP SUCTION

STRAINER

HOUSING MOUNTING

FLANGE

WALL HOUSING WITH

OSHA APPROVED GUARD

W A

LL

-IN

TE

R

IO

R

-E X

TE

R

IO

R

90° WEATHERHOOD

W/ BIRDSCREEN

FOR SUPPLY FAN

BELT DRIVE

MOTOR

FAN BLADES

SECTION VIEWBACK VIEW

BELT DRIVE

MOTOR

WALL HOUSING WITH

OSHA APPROVED GUARD

FAN BLADES

AIRFLOW

MOTORIZED DAMPER WITH ACTUATOR.

DAMPER SHALL BE WIRED FOR SINGLE

POINT CONNECTION FROM FACTORY.

CAULK ALL AROUND PENETRATION

WITH CLEAR SILICON CAULKING

TO CREATE WEATHERPROOF SEAL

SHEET NUMBER

SHEET NAME

DATE:

REVISIONS

DRAWN BY:

CHECKED BY:

PROJECT #:

SHEET INFORMATION

SEAL

PROJECT INFORMATION

All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.

7600 Innovation Park Drive

Baton Rouge, LA 70820

225.332.0222 parisheng.com

M0.0

MECHANICAL COVER SHEET

CTD

LJB

06-18-2025

25-040

B O

IL

E

R R

E P

L A

C E

M E

N T

A R

T S

H

U M

A N

IT

IE

S

S O

C

IA

L S

C

IE

N C

E B

U

IL

D

IN

G

G Y

M N

A S

IU

M

S

U N

O N

E W

O R

L E

A N

S

L A

N.T.S.1 DETAIL - AIR SEPERATOR

N.T.S.2 DETAIL - BELT DRIVE PROPELLER SUPPLY FAN

INDEX - MECHANICAL SHEETS

M0.0 MECHANICAL COVER SHEET

M1.0 MECHANICAL PLAN

M1.1 ENLARGED MECHANICAL PLAN

M1.2 GYMNASIUM MECHANICAL PLAN

M1.3 GYMNASIUM ENLARGED MECHANICAL PLAN

M2.0 MECHANICAL DETAILS

M2.1 MECHANICAL DETAILS

M3.0 MECHANICAL SCHEDULES

3" H

H W

R

B-1(E) B-2

6"⌀

6"⌀

6"⌀

6"⌀

HHWS (E)

PM-4(E)

PM-5(E)

M1.1

3"HHWS

SHEET NUMBER

SHEET NAME

DATE:

REVISIONS

DRAWN BY:

CHECKED BY:

PROJECT #:

SHEET INFORMATION

SEAL

PROJECT INFORMATION

All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.

7600 Innovation Park Drive

Baton Rouge, LA 70820

225.332.0222 parisheng.com

M1.0

MECHANICAL PLAN

CTD

LJB

06-18-2025

25-040

B O

IL

E

R R

E P

L A

C E

M E

N T

A R

T S

H

U M

A N

IT

IE

S

S O

C

IA

L S

C

IE

N C

E B

U

IL

D

IN

G

G Y

M N

A S

IU

M

S

U N

O N

E W

O R

L E

A N

S

L A

1" = 10'-0"1 ARTS & HUMANITIES OVERALL PLAN

3" HHWR (E)

3" HHWS (E)

B-1(E)

B-2

6"⌀

6"⌀

6"⌀

6"⌀

PM-4(E)

PM-5(E)

3" H

H W

S (E

3" H

H W

S (E

3" H

H W

S (E

3" HHWR (E)

3" HHWR (E)

3" HHWR (E)

3" HHWR (E)

3" HHW

R (E)

3" HHW

S (E)

B-2B-1(E)

6"⌀

6"⌀ 6"⌀

6"⌀

3"HHWS

3"HHWS

3"HHWR

3" H

H W

R

3" H

H W

R

PM-4(E)

PM-5(E)

3" HHWS (E)

3" HHWR (E)

SHEET NUMBER

SHEET NAME

DATE:

REVISIONS

DRAWN BY:

CHECKED BY:

PROJECT #:

SHEET INFORMATION

SEAL

PROJECT INFORMATION

All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.

7600 Innovation Park Drive

Baton Rouge, LA 70820

225.332.0222 parisheng.com

M1.1

ENLARGED MECHANICAL

PLAN

CTD

LJB

06-18-2025

25-040

B O

IL

E

R R

E P

L A

C E

M E

N T

A R

T S

H

U M

A N

IT

IE

S

S O

C

IA

L S

C

IE

N C

E B

U

IL

D

IN

G

G Y

M N

A S

IU

M

S

U N

O N

E W

O R

L E

A N

S

L A

2 3D BOILER DIAGRAM

3/8" = 1'-0"1 ARTS & HUMANITIES ENLARGED

KEYNOTES:

PROVIDE NEW BOILER, B-2, EXISTING BOILER HAS BEEN REMOVED. CONNECT TO EXISTING HEATING

WATER VENT, INTAKE AIR, ELECTRICAL AND CONTROLS.

REPLACE EXISTING OUTDOOR AIR DAMPER.

M1.3

B-1 B-2

SHEET NUMBER

SHEET NAME

DATE:

REVISIONS

DRAWN BY:

CHECKED BY:

PROJECT #:

SHEET INFORMATION

SEAL

PROJECT INFORMATION

All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.

7600 Innovation Park Drive

Baton Rouge, LA 70820

225.332.0222 parisheng.com

M1.2

GYMNASIUM MECHANICAL

PLAN

CTD

LJB

06-18-2025

25-040

B O

IL

E

R R

E P

L A

C E

M E

N T

A R

T S

H

U M

A N

IT

IE

S

S O

C

IA

L S

C

IE

N C

E B

U

IL

D

IN

G

G Y

M N

A S

IU

M

S

U N

O N

E W

O R

L E

A N

S

L A

1/8" = 1'-0"1 GYMNASIUM OVERALL PLAN

4"HWR

4"HWR

4"HWR

3"HWS 3"HWS 3"HWS

4"HWS

12"⌀12"⌀

B-1(E) B-2(E) B-3(E)

2" NG (E)4" NG (E)

2" NG (E) 4" NG (E) 4" NG (E)

2" N

G (E

4"HWR

3"HWR3"HWR

4"HWS4"HWS

3/4"HWR ET-1(E)

EXISTING BOILER VENT FAN

EXISTING DOMESTIC

WATER HEATER

VENT FAN TO REMAIN

EXISTING DOMESTIC WATER

HEATERS TO REMAIN

EXISTING DOMESTIC

WATER HEATER VENT FAN

CONTROLLER TO REMAIN

EXISTING BOILER PUMP

MOTOR STARTERS (3)

EXISTING BOILER VENT

FAN CONTROLLER

3/4"CW(E)

EXISTING

BOILER PUMP EXISTING

BOILER PUMP

EXISTING

BOILER PUMP

4" HWR(E) FROM ABOVE

4"HWR

10"⌀ 8"⌀

2" NG (E)4" NG (E)

2" NG (E) 4" NG (E)

EXISTING DOMESTIC

WATER HEATER VENT FAN

EXISTING DOMESTIC WATER

HEATER VENT FAN CONTROLLER

EXISTING DOMESTIC WATER

HEATERS TO REMAIN

B-1 B-2

2"NG 2"NG

4" HWR(E) UP TO MEZZANINE

4"HWS

12"⌀12"⌀

4"HWS

3/4"CW

4"HWR

AS-1

SF-1

3/4"CW(E)

CT-1

4"HWR

CONNECT TO EXISTING

TO NEW HEATING

WATER MAKEUP

4" H

W R

4" H

W S

4"HWR

4"HWS

SHEET NUMBER

SHEET NAME

DATE:

REVISIONS

DRAWN BY:

CHECKED BY:

PROJECT #:

SHEET INFORMATION

SEAL

PROJECT INFORMATION

All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.

7600 Innovation Park Drive

Baton Rouge, LA 70820

225.332.0222 parisheng.com

M1.3

GYMNASIUM ENLARGED

MECHANICAL PLAN

CTD

LJB

06-18-2025

25-040

B O

IL

E

R R

E P

L A

C E

M E

N T

A R

T S

H

U M

A N

IT

IE

S

S O

C

IA

L S

C

IE

N C

E B

U

IL

D

IN

G

G Y

M N

A S

IU

M

S

U N

O N

E W

O R

L E

A N

S

L A

1/2" = 1'-0"1 GYMNASIUM DEMO PLAN 1/2" = 1'-0"2 GYMNASIUM RENO PLAN

DEMO KEY NOTES:

TWO EXISTING DOMESTIC WATER HEATERS AND ASSOCIATED VENT FAN, VENT FAN CONTROLLER, MIXING VALVE, EXPANSION TANK AND PIPING TO REMAIN.

REMOVE THREE EXISTING BOILERS AND ASSOCIATED PUMPS, MOTOR STARTERS, VENT FAN, VENT FAN CONTROLLER, HWS/R, AND GAS PIPING.

REMOVE EXISITNG COMBUSTION AIR FAN. PREPARE OPENING TO ACCEPT NEW FAN.

PREPARE EXISTING OPENING TO ACCEPT NEW BOILER FLUE.

RENO KEY NOTES:

EXISTING SECONDARY HEATING WATER PUMPS ARE LOCATED ON MEZZANINE ABOVE. REFER TO PIPING DIAGRAMS FOR SCOPE OF WORK. BALANCE EXISTING SECONDARY HEATING WATER PUMPS PER SCHEDULE.

PROVIDE BOILER STOP BUTTON AT DOORWAY.

LEGEND

AIR SEPARATOR

CIRCULATION

PUMP

FLOW CHECK VALVE

PRESSURE GAUGE

P

TEMPERATURE &

PRESSURE GAUGE

T P

SYSTEM SUPPLY

SENSOR

BACKFLOW

PREVENTER

MAGNETIC SEPARATOR WATER METER

PRESSURE STRAINER / FILTER

REDUCING VALVE

PRESSURE RELIEF

VALVE

BALL VALVE EXPANSION TANK

PIPING

DRAIN PORT

DIFFERENTIAL

PRESSURE

BYPASS VALVE

2 WAY MOTORIZED

VALVE (OPTIONAL)

MIXING VALVE

ANTI SCALD

FLOW SWITCH

OPTIONAL

WIRING

TO

SYSTEM

FROM

SYSTEM

P

MAKE UP

WATER

T P T P

BOILER 1 BOILER 2

SYSTEM SUPPLY

SENSOR

HANGER ROD SCHEDULE

PIPE SIZE ROD DIA.

1/4" - 2"

2-1/2" - 3-1/2"

3/8"

1/2"

GENERAL NOTES:

1. HANGERS IN CONTACT WITH COPPER SHALL BE COPPER PLATED OR TEFLON COATED.

2. MAXIMUM HORIZONTAL PIPE HANGER AND SUPPORT SPACING IS 5'-0".

ADJUSTABLE WROUGHT CLEVIS HANGER

16 GA. GALVANIZED SHEETMETAL PIPE INSULATION

PROTECTION SADDLE, MINIMUM 12" LONG

PROVIDE NON-METALLIC INSULATING MATERIAL IF PIPING AND

HANGER ARE DISSIMILAR METALS AND PIPING IS NOT INSULATED

ALL THREAD HANGER ROD

HEX HEAD NUT

REFRIGERANT PIPING

CONCRETE DECK ANCHORS

BAR JOIST ANCHORSI-BEAM ANCHORS

WOOD ANCHORS

WOOD TRUSS/JOIST

1/4"X1-1/4" HEX HEAD LAG

BOLT TO BE SECURED TO TOP

CHORD OF TRUSS/JOIST

HEX HEAD NUT

STEEL SIDE BEAM

BRACKET

ALL THREAD

HANGER ROD

ALL THREAD

HANGER ROD

HEX HEAD NUT

WITH WASHER

ADJUSTABLE SIDE

BEAM CLAMP

STEEL BEAM

ALL THREAD

HANGER ROD

C-CLAMP WITH

SET SCREW AND

LOCK NUT

RETAINING CLIP

UNIVERSAL C-CLAMP

WITH SET SCREW

AND JAM NUT

TOP/BOTTOM

FLANGE OF BAR

JOIST

ALL THREAD

HANGER ROD

UNIVERSAL C-CLAMP

WITH SET SCREW

AND JAM NUT

CONCRETE DECK

CONCRETE WEDGE

ANCHOR WITH HEX

HEAD NUT AND WASHER

WITH HANGER STRAP

STEEL BEAM

CONCRETE LAG SHIELD

ANCHOR OR CONCRETE

EXPANSION ANCHOR

WITH ALL THREAD ROD

AIR CONTROL TANK

FITTING TYPICAL

BALL

VALVE

PRESSURE RELIEF

75 P.S.I. SETTING

PRESSURE REDUCING

VALVE, SET TO 10 PSI

CONNECT

HW FILL LINE

SLOPE DOWN

NEW AIR

SEPARATOR

TO PUMPS

TO DRAIN

BALL

VALVE

TO DRAIN

3/4" VALVE WITH

GARDEN HOSE

CONNECTION

N.C.

STRAINER

SHUT-OFF BALL

VALVE (TYP)

BACKFLOW

PREVENTER

COMPRESSION TANK

N.T.S.1 DETAIL - REFRIGERANT PIPE SUPPORT HANGERS

N.T.S.3 DETAIL - DUCT/PIPE HANGER ANCHORS

SHEET NUMBER

SHEET NAME

DATE:

REVISIONS

DRAWN BY:

CHECKED BY:

PROJECT #:

SHEET INFORMATION

SEAL

PROJECT INFORMATION

All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.

7600 Innovation Park Drive

Baton Rouge, LA 70820

225.332.0222 parisheng.com

M2.0

MECHANICAL DETAILS

CTD

LJB

06-18-2025

25-040

B O

IL

E

R R

E P

L A

C E

M E

N T

A R

T S

H

U M

A N

IT

IE

S

S O

C

IA

L S

C

IE

N C

E B

U

IL

D

IN

G

G Y

M N

A S

IU

M

S

U N

O N

E W

O R

L E

A N

S

L A

N.T.S.4 DETAIL - BOILER PIPING DIAGRAM

N.T.S.2 DETAIL - AIR CONTROL SYSTEM PIPING

ET-1(E)

B-1(E) B-2(E) B-3(E)

AHU-10(E)

AHU-2(E)

AHU-3(E)

AHU-1(E) AHU-9(E)

AHU-5(E)AHU-6(E)AHU-7(E)AHU-8(E)

AHU-4(E)

PUMP CONTROLLER (E)

P-3(E) P-4(E) P-5(E)

P-6(E) P-7(E)

4"4"

4"

4" 4"

4"

4"

4"

4" 4"

4"

4"

4"

4"

3"

3"

3" 3"

3" 3"

3" 3"

3"3"

4"

4"

3"

3"

1" 1"

2"

2"

2"

2"

3"3"

1 1/2"

1 1/2"

1 1/4"

1 1/4"

1 1/4"

1 1/4"

1 1/4"

1 1/4"

2"

2"

2"

2"

2"

2"

2" 2"

1" 1"

BACKFLOW

PREVENTER

4"

MIXING VALVE (E)

B-1 B-2

AHU-10(E)

AHU-2(E)

AHU-3(E)

AHU-1(E) AHU-9(E)

AHU-5(E)AHU-6(E)AHU-7(E)AHU-8(E)

AHU-4(E)

PUMP CONTROLLER (E)

P-6(E) P-7(E)

4"

4"

4"

4" 4"

4"

4"

4"

4"

3"

3"

3" 3"

3" 3"

3" 3"

3"3"

4"

4"

3"

3"

1" 1"

2"

2"

2"

2"

3"3"

1 1/2"

1 1/2"

1 1/4"

1 1/4"

1 1/4"

1 1/4"

1 1/4"

1 1/4"

2"

2"

2"

2"

2"

2"

2" 2"

4"

GENERAL NOTES:

1. MODIFY EXISTING PIPING FOR NEW BOILERS, PUMPS, AND PIPE ROUTING.

BP-1 BP-2

4"

4" 4"

4"

HW UP TO MEZZANINE

SHEET NUMBER

SHEET NAME

DATE:

REVISIONS

DRAWN BY:

CHECKED BY:

PROJECT #:

SHEET INFORMATION

SEAL

PROJECT INFORMATION

All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.

7600 Innovation Park Drive

Baton Rouge, LA 70820

225.332.0222 parisheng.com

M2.1

MECHANICAL DETAILS

CTD

LJB

06-18-2025

25-040

B O

IL

E

R R

E P

L A

C E

M E

N T

A R

T S

H

U M

A N

IT

IE

S

S O

C

IA

L S

C

IE

N C

E B

U

IL

D

IN

G

G Y

M N

A S

IU

M

S

U N

O N

E W

O R

L E

A N

S

L A

N.T.S.1 EXISTING HEATING WATER FLOW - PIPING DIAGRAM

N.T.S.2 NEW HEATING WATER FLOW - PIPING DIAGRAM

NOTES:

1. PROVIDE INSULATED FAN HOUSING.

2. PROVIDE FACTORY MOUNTED AND WIRED SPEED CONTROLLERS FOR ALL DIRECT DRIVE FANS FOR AIR BALANCING.

3. PROVIDE INTEGRAL DISCONNECTING MEANS.

4. PROVIDE MOTORS WITH BUILT-IN THERMAL OVERLOAD PROTECTION FOR ALL FANS.

5. ALL EXHAUST AND SUPPLY FANS SHALL BE AMCA RATED FOR BOTH AIR AND SOUND.

6. PROVIDE FACTORY FINISHES ON ALL SURFACE EXPOSED TO VIEW.

SHEET NUMBER

SHEET NAME

DATE:

REVISIONS

DRAWN BY:

CHECKED BY:

PROJECT #:

SHEET INFORMATION

SEAL

PROJECT INFORMATION

All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.

7600 Innovation Park Drive

Baton Rouge, LA 70820

225.332.0222 parisheng.com

M3.0

MECHANICAL SCHEDULES

CTD

LJB

06-18-2025

25-040

B O

IL

E

R R

E P

L A

C E

M E

N T

A R

T S

H

U M

A N

IT

IE

S

S O

C

IA

L S

C

IE

N C

E B

U

IL

D

IN

G

G Y

M N

A S

IU

M

S

U N

O N

E W

O R

L E

A N

S

L A

SCHEDULE - BOILERS

MARK DESCRIPTION

CAPACITY WATER DUCT SIZE ELECTRICAL SERVICE EFFICIENCY

WEIGHT MANUFACTURER / MODEL

MAXIMUM MINIMUM

EWT LWT FLOW PD VENTILATION COMBUSTION VOLTS PH FREQ THERMAL COMBUSTIONINPUT OUTPUT INPUT

B-1(E) CREST BOILER 1000000.0 Btu/h 722000.0 Btu/h 50000.0 Btu/h 160 °F 180 °F 95 GPM 12.9 ftH2O 6" 6" 120 V 1 30 Hz 96.2% 96.4% 2000 lb FBN1001

B-2 CREST BOILER 1000000.0 Btu/h 722000.0 Btu/h 50000.0 Btu/h 160 °F 180 °F 95 GPM 12.9 ftH2O 6" 6" 120 V 1 30 Hz 96.2% 96.4% 2000 lb FBN1001

SCHEDULE - BOILERS

MARK DESCRIPTION

CAPACITY WATER VENTILATION ELECTRICAL SERVICE

MIN-MAX INLET

GAS PRESSURE

EFFICIENCY

WEIGHT MANUFACTURER / MODEL

MAXIMUM MINIMUM

INLET OUTLET

MIN

FLOW MAX FLOW VENT COMBUSTION VOLTS FLA PH FREQ THERMAL COMBUSTIONINPUT OUTPUT INPUT OUTPUT

B-1 CONDENSING STAINLESS STEEL FIRETUBE 1999000 Btu/Hr 1923000 Btu/Hr 80000 Btu/Hr 76920 Btu/Hr 4" 4" 25 GPM 350 GPM 8" 8" 120 13 1 60 4-14 In. W.C. 96.2% 96.4% 2700 lb LOCHINVAR FCB 2000N

B-2 CONDENSING STAINLESS STEEL FIRETUBE 1999000 Btu/Hr 1923000 Btu/Hr 80000 Btu/Hr 76920 Btu/Hr 4" 4" 25 GPM 350 GPM 8" 8" 120 13 1 60 4-14 In. W.C. 96.2% 96.4% 2700 lb LOCHINVAR FCB 2000N

SCHEDULE - PUMPS

MARK GPM PUMP HEAD RPM TYPE

ELECTRICAL SERVICE

TYPE LOCATION MANUFACTURER / MODELHP VOLTS PH

(E) P-6 165 65 ft. 1800 VERTICAL IN-LINE CENTRIFUGAL 7.5 208 3 VARIABLE SPEED PUMP NEAR BOILER ARMSTRONG 4380 3X3X10

(E) P-7 165 65 ft. 1800 VERTICAL IN-LINE CENTRIFUGAL 7.5 208 3 VARIABLE SPEED PUMP NEAR BOILER ARMSTRONG 4380 3X3X10

ARTS, HUMANITIES AND SCIENCE SCHEDULES:

SCHEDULE - FANS

MARK LOCATION

FAN FAN MOTOR

WEIGHT MANUFACTURER / MODELTYPE AIRFLOW MIN EXT ESP MAX SONES RPM DRIVE POWER VOLTS PH FREQ

SF-1 BOILER ROOM SIDE WALL PROP 1200 CFM 0.28 in-wg 11.3 1043 DIRECT 1/4 HP 120 V 1 60 Hz 200 lb GREENHECK MODEL AER-20-03-0610-VG

GYMNASIUM SCHEDULES:

NOTES:

1. PROVIDE VARIABLE SPEED PRIMARY BOILER PUMP FROM BOILER MANUFACTURER WITH EACH BOILER. PUMP SPEED SHALL BE CONTROLLED BY BOILER. PUMP MODEL SHALL BE LOCHINVAR 100208412.

2. PROVIDE CONDENSATE NEUTRALIZATION KIT WITH EACH BOILER.

3. PROVIDE ULTRA HIGH TURN DOWN NATURAL GAS REGULATOR ON EACH INCOMING BOILER GAS LINE. (IF GAS PRESSURE IS ABOVE ALLOWABLE PRESSURE RANGE)

4. PROVIDE BOILERMAG MAGNETIC FILTER / SEPERATOR IN HEATING WATER RETURN, UPSTREAM OF BOILERS OR AT INLET OF EACH BOILER.

NOTES:

1. PROVIDE VARIABLE SPEED PRIMARY BOILER PUMP FROM BOILER MANUFACTURER WITH EACH BOILER. PUMP SPEED SHALL BE CONTROLLED BY BOILER. PUMP MODEL SHALL BE LOCHINVAR 100208412.

2. PROVIDE CONDENSATE NEUTRALIZATION KIT WITH EACH BOILER.

3. PROVIDE ULTRA HIGH TURN DOWN NATURAL GAS REGULATOR ON EACH INCOMING BOILER GAS LINE. (IF GAS PRESSURE IS ABOVE ALLOWABLE PRESSURE RANGE)

4. PROVIDE BOILERMAG MAGNETIC FILTER / SEPERATOR IN HEATING WATER RETURN, UPSTREAM OF BOILERS OR AT INLET OF EACH BOILER.

SCHEDULE - COMPRESSION TANK

MARK DESCRIPTION CAPACITY WEIGHT MANUFACTURER / MODEL

CT-1 NEW COMPRESSION TANK 240 GALLONS 2500 lb BELL & GOSSETT 116672 OR PRIOR APPROVED EQUAL

SCHEDULE - AIR SEPARATOR

MARK SERVICE FLUID FLOW WEIGHT MANUFACTURER / MODEL

AS-1 HEATING WATER WATER 300 GPM 300 lb BELL & GOSSETT ROLAIRTROL R-4F OR PRIOR APPROVED EQUAL

NOTES:

1. SEPARATOR CONSTRUCTION:

A. SELF-SUPPORTING IN PIPING SYSTEM - MANUFACTURER REVIEW REQUIRED IF ANY PIPING LOADS SHALL BE PRESENT.

B. CARBON STEEL SHELL

C. 304 STAINLESS STEEL SYSTEM STRAINER WITH 3/16" PERFORATIONS AND 51% OPEN AREA.

D. DESIGNED AND CONSTRUCTED PER ASME SECTION VIII, DIVISION 1

2. STANDARD DESIGN PRESSURE AND TEMPERATURE SHALL BE 125 PSI AT 350°F.

ABOVE-COUNTER QUADRAPLEX RECEPTACLE;

MOUNT AT 4" ABOVE COUNTER OR BACKSPLASH

OR 44" (WHICHEVER IS LOWER)

QUADRAPLEX RECEPTACLE

JUNCTION BOX

FUSED SAFETY DISCONNECT SWITCH; LOCATE WITHIN

SIGHT OF THE EQUIPMENT SERVED WITH 36" MINIMUM

CLEAR WORKING SPACE IN FRONT OF THE SWITCH; DO

NOT MOUNT DIRECTLY TO EQUIPMENT

ABOVE-COUNTER GFCI DUPLEX RECEPTACLE;

MOUNT AT 4" ABOVE COUNTER OR BACKSPLASH

OR 44" (WHICHEVER IS LOWER)

JUNCTION BOX FOR MOTORIZED DAMPER

SPECIAL PURPOSE RECEPTACLE; VERIFY NEMA

CONFIGURATION WITH THE MANUFACTURER OF

THE EQUIPMENT SERVED

ABOVE-COUNTER DUPLEX RECEPTACLE;

MOUNT AT 4" ABOVE COUNTER OR BACKSPLASH

OR 44" (WHICHEVER IS LOWER)

GFCI DUPLEX RECEPTACLE

DUPLEX RECEPTACLE

ELECTRICAL SYMBOL LEGEND

M

J

ABOVE-SLAB CONDUIT & WIRE/CABLING

BELOW-SLAB CONDUIT & WIRE/CABLING;

3/4" MINIMUM CONDUIT SIZE UON

VOICE/DATA/POWER FLUSH FLOOR BOX

DUPLEX RECEPTACLE FLUSH FLOOR BOX

QUADRAPLEX RECEPTACLE FLUSH FLOOR BOX

DATA/VOICE OUTLET; PROVIDE 1"C TO AN

ACCESSIBLE LOCATION ABOVE CEILING, ONE (1)

BLUE AND ONE (1) WHITE CAT 6 CABLES FROM THE

OUTLET TO THE TELECOM TERMINAL BOARD

VOICE OUTLET; PROVIDE 1"C TO AN ACCESSIBLE

LOCATION ABOVE CEILING, ONE (1) WHITE CAT 6

CABLE FROM THE OUTLET TO THE TELECOM

TERMINAL BOARD

TV LEGRAND EVOLUTION 4-GANG OR APPROVED EQUAL

TV WALL BOX WITH ONE DUPLEX RECEPTACLE, ONE

DUPLEX DATA OUTLET, ONE COAX OUTLET, AND ONE

SPARE GANG; PROVIDE 1"C, TWO (2) BLUE CAT 6

CABLES AND 1"C, ONE (1) CATV CABLE FROM THE BOX

TO THE TELECOM TERMINA BOARD; PROVIDE CONDUIT

AND WIRE FOR POWER PER THE PANEL SCHEDULE.

WIRELESS ACCESS POINT (BY OWNER); PROVIDE 1"C

TO AN ACCESSIBLE LOCATION ABOVE CEILING, ONE

(1) BLUE CAT 6 CABLE FROM THE ACCESS POINT

LOCATION TO THE TELECOM TERMINAL BOARD

WAP

GENERATOR REMOTE ANNUNCIATOR PANEL; PROVIDE

CONDUIT/CABLING TO GENERATOR AS REQUIRED PER

THE MANUFACTURER'S SPECIFICATIONS.

GEN-ANNC

DUPLEX DATA OUTLET, AS ABOVE,

MOUNTED ABOVE COUNTER

DUPLEX DATA FLUSH FLOOR BOX; PROVIDE 1"C TO

AN ACCESSIBLE LOCATION ABOVE CEILING, ONE (1)

BLUE CAT 6 CABLE FROM THE OUTLET TO THE

TELECOM TERMINAL BOARD

PANELBOARD, SWITCHBOARD, OR OTHER DISTRIBUTION

EQUIPMENT AS NOTED; INSTALL WITH SUFFICIENT

WORKING SPACE AND CLEARANCES TO MEET ALL

REQUIREMENTS OF NEC SECTION 110.26.

GENERAL

KEYNOTE1

HOMERUN TO PANEL;

TICK MARKS INDICATED NUMBER OF WIRES

EQUIPMENT CONNECTIONS

MOTOR RATED SWITCH WITH THERMAL OVERLOAD; LOCATE

WITHIN SIGHT OF THE EQUIPMENT SERVED; DO NOT MOUNT

DIRECTLY TO EQUIPMENT; WHEN LOCATED ABOVE CEILING,

MOUNT TO STRUCTURAL MEMBER NEARBY.

M S

ELECTRICAL MOTOR, HORSEPOWER AS NOTED

POWER DEVICES

DUPLEX RECEPTACLE MOUNTED FLUSH TO CEILING OR

MOUNTED TO STRUCTURE IN AREAS WITH NO CEILING;

SUBSCRIPT (WHEN USED):

CR - CORD REEL

TELECOMMUNICATIONS

DUPLEX DATA OUTLET; PROVIDE 1"C TO AN

ACCESSIBLE LOCATION ABOVE CEILING, TWO (2)

BLUE CAT 6 CABLES FROM THE OUTLET TO THE

TELECOM TERMINAL BOARD

LIGHT FIXTURE; UPPERCASE LETTER(S) INDICATE FIXTURE

TYPE; LOWERCASE LETTER(S) INDICATE ASSOCIATED

CONTROLS ID; SEE LIGHTING FIXTURE SCHEDULE FOR

FIXTURE DESCRIPTIONS AND MOUNTING TYPES

EXIT LIGHT FIXTURE. ARROWS (IF USED) INDICATE

DIRECTION. FILLED IN QUADRANT(S) INDICATE NUMBER

AND ORIENTATION OF ILLUMINATED FACES. LETTER(S)

INDICATE FIXTURE TYPE. SEE LIGHTING FIXTURE

SCHEDULE FOR FIXTURE DESCRIPTION.

CEILING MOUNTED OCCUPANCY SENSOR WITH 360°

COVERAGE. LOCATE AND INSTALL PER THE

MANUFACTURER'S RECOMMENDATIONS; TEST AND

ADJUST SENSITIVITY AFTER INSTALLATION AND SET TIME

DELAY AS REQUIRED BY THE OWNER

Aa

X

OS

PHOTOELECTRIC CELL, EXTERIOR RATED; AIM AND

SHIELD SENSOR FROM INTERIOR AND EXTERIOR

ARTIFICIAL LIGHT SOURCES

CEILING MOUNTED OCCUPANCY SENSOR, AS ABOVE,

CONFIGURED FOR VACANCY OPERATION

VS

LIGHTING

SWITCH;

SUBSCRIPT (WHEN USED):

NONE - SINGLE POLE TOGGLE SWITCH

3 - THREE-WAY SWITCH

D - LINEAR SLIDE DIMMER SWITCH

3D - THREE-WAY LINEAR SLIDE DIMMER SWITCH

O - WALL MOUNTED OCCUPANCY SENSOR

3O - THREE-WAY SWITCH WITH OCCUPANCY SENSOR

a,b,c etc. - SWITCH ID

S

DUPLEX DATA OUTLET, AS ABOVE, MOUNTED FLUSH

TO CEILING OR MOUNTED TO STRUCTURE IN AREAS

WITH NO CEILING

P

TV LEGRAND EVOLUTION 4-GANG OR APPROVED EQUAL

COMBO RECESSED FLOOR BOX WITH TWO (2)

DUPLEX RECEPTACLES, FOUR (4) DATA OUTLETS

(UNDER A SINGLE PLATE), AND SPEAKER

CONNECTIONS; PROVIDE 1-1/4"C TO AN ACCESSIBLE

LOCATION ABOVE CEILING, FOUR (4) BLUE CAT 6

CABLES FROM THE BOX TO THE TELECOM TERMINAL

BOARD. ROUTE 1"EC WITH PULLSTRING FROM THE

BOX TO THE TV WALL BOX IN THE SAME ROOM FOR

SPEAKER CABLING. PROVIDE CONDUIT AND WIRE

FOR POWER PER THE PANEL SCHEDULE.

WIRE, CONDUIT, AND RACEWAY

DISTRIBUTION

PA

V

I

PUBLIC ADDRESS

PA SYSTEM SPEAKER

PA SYSTEM SPEAKER VOLUME CONTROL

PA SYSTEM SPEAKER MOUNT CALL-IN SWITCH

(REFER TO DRAWINGS AND SPECIFICATIONS FOR FURTHER REQUIREMENTS)

(PROVIDE CONDUIT AND WIRE PER THE PANEL SCHEDULE)

(PROVIDE CONDUIT AND WIRE PER THE PANEL SCHEDULE FOR POWER

AND PER THE MANUFACTURER'S SPECIFICATIONS FOR CONTROLS)

(JACKET COLORS TO BE PER THE OWNER'S STANDARDS IF APPLICABLE)

(PROVIDE 3/4"EC WITH PULL STRING FROM THE DEVICE LOCATION SHOWN

ON THE DRAWINGS TO AN ACCESSIBLE LOCATION ABOVE CEILING)

CIRCUIT TAG; PANEL AND CIRCUIT DESIGNATION

AS INDICATED; E.G. PANEL "A", CIRCUIT #1,3

A-1,3

TELECOM TERMINAL BOARD; 0'-1" THICK AC INDOOR

GRADE, FIRE RETARDANT PLYWOOD, PAINTED AS

SPECIFIED BY THE ARCHITECT OR OWNER

(PROVIDE CONDUIT AND WIRE PER THE PANEL SCHEDULE)

RECEPTACLE SWITCHING; EDGE SHADING INDICATES:

NONE - DEVICE NOT SWITCHED

LEFT - BOTTOM (DUPLEX) OR LEFT TWO (QUAD) SWITCHED

RIGHT - TOP (DUPLEX) OR RIGHT TWO (QUAD) SWITCHED

ABBREVIATIONS

AMPERE(S)A

ABOVE COUNTER (6" ABOVE BACKSPLASH)AC

AMPERE(S) FUSEDAF

ARC FAULT CIRCUIT INTERRUPTERAFCI

ABOVE FINISHED FLOORAFF

ABOVE FINISHED GRADEAFG

AMPERE(S) TRIPAT

AMERICAN WIRE GAUGEAWG

BELOW GRADEBG

BUILDINGBLDG

BREAKERBKR

CONDUITC

CATEGORYCAT

CABLE TELEVISIONCATV

CIRCUIT BREAKERCB

CIRCUITCKT

CLGCLG

CORRIDORCORR

CURRENT TRANSFORMERCT

CONTROLLERCTRL

DISCONNECTDISC.

DISTRIBUTIONDIST.

DRAWINGDWG

EMPTY CONDUITEC

ENCLOSED CIRCUIT BREAKERECB

EXHAUST FANEF

EQUIPMENT GROUNDING CONDUCTOREGC

EMERGENCYEMER.

ELECTRICAL METALLIC TUBINGEMT

EQUALEQ

EQUIPMENTEQUIP.

ELECTRIC WATER COOLEREWC

ELECTRIC WATER HEATEREWH

EXISTINGEXIST.

FIRE ALARM CONTROL PANELFACP

FIRE ALARM CONTROL PANEL REMOTE ANNUNCIATORFACPRA

FOOTCANDLEFC

FAN COIL UNITFCU

FULL LOAD AMPERE(S)FLA

FIBER OPTIC CABLEFOC

GROUNDG, GND

GROUNDING ELECTRODE CONDUCTORGEC

GROUND FAULT CIRCUIT INTERRUPTERGFCI

GALVANIZED RIGID STEELGRS

HANDHOLEHH

HORSEPOWERHP

1,000 AMP SYMMETRICAL INTERRUPTING CAPACITY RMSKAIC

1,000 WATT HOURSKWH

1,000 VOLT AMPERESKVA

LOCAL AREA NETWORKLAN

LIGHTINGLTG

MINIMUM CIRCUIT AMPACITYMCA

MAIN CIRCUIT BREAKERMCB

1,000 CIRCULAR MILSMCM/KCMIL

MECHANICALMECH.

MANHOLEMH

MAIN LUGS ONLYMLO

MAXIMUM OVERCURRENT PROTECTIONMOCP

MOUNTEDMTD

MOUNTINGMTG

NATIONAL ELECTRICAL CODENEC

NEUTRALNEU

NOT IN CONTRACTNIC

NON-FUSEDNF

NORMALLY OPENNO

OVERHEADOH

OVERHEAD ELECTRICALOHE

OUTSIDE PLANTOSP

UTILITY POWER POLEUPP

PULL BOXPB

PHASEPH

PANELPNL

PHOTOVOLTAICPV

POLYVINYL CHLORIDEPVC

QUANTITYQTY

RECEPTACLERCPT

REQUIREDREQ'D

SUPPLY FANSF

SOLID NEUTRALS/N

SURGE PROTECTIVE DEVICESPD

STANDARDSTD

TELEPHONETEL

TELECOMMUNICATIONSTELECOM

TELECOMMUNICATIONS GROUND BUSTGB

TELECOMMUNICATIONS MAIN GROUND BUSTMGB

TELECOM TERMINAL BOARDTTB

TELEVISIONTV

TRANSIENT VOLTAGE SURGE SUPPRESSIONTVSS

TYPICALTYP.

UNIT HEATERUH

UNDERWRITER'S LABORATORY, INC.UL

UNDERGROUNDUG

UNDERGROUND PRIMARYUGP

UNDERGROUND SECONDARYUGS

UNLESS OTHERWISE NOTEDUON

VOLTSV

VOLTS ALTERNATING CURRENTVAC

VOLTS DIRECT CURRENTVDC

VARIABLE FREQUENCY DRIVEVFD

WATER HEATERWH

WEATHERPROOFWP

TRANSFORMERXFMR

EXISTING TO REMAINE

TO BE DEMOLISHEDD

LIGHTING CONTACTORLC

AMP SYMMETRICAL INTERRUPTING CAPACITY RMSAIC

NIGHT LIGHTNL

NORMALLY CLOSEDNC

WEATHERPROOF IN-USE COVERNU

FIRE ALARM SYSTEM PULL STATION

FIRE ALARM SYSTEM HORN/STROBE

FIRE ALARM SYSTEM CEILING MOUNT HORN/STROBE

FIRE ALARM SYSTEM CEILING MOUNT STROBE

DOCTOR'S DICTATION

FLOOR MOUNTED MICROPHONE OUTLET

CEILING MOUNTED SPEAKER

WALL MOUNTED SPEAKER

F

FIRE ALARM SYSTEM CHIME/STROBE

FIRE ALARM SYSTEM STROBE

FIRE ALARM SYSTEM SPEAKER/STROBE

FIRE ALARM SYSTEM CEILING MOUNT SPEAKER/STROBE

FIRE ALARM SYSTEM THERMAL DETECTOR

FIRE ALARM SYSTEM CARBON MONOXIDE DETECTOR

FIRE ALARM SYSTEM CEILING MOUNT CHIME/STROBE

C

H

S

C

H

S

C

T

FIRE ALARM SYSTEM DUCT SMOKE DETECTORD

JUNCTION BOX FOR DOOR OPERATOR; PROVIDE 3/4"EC

WITH PULL STRING FROM THE JUNCTION BOX TO AN

ACCESSIBLE LOCATION ABOVE CEILING NEAR THE

CONTROLLED DOOR

JUNCTION BOX FOR KEYPAD; INSTALL 48" AFF AND

PROVIDE 3/4"EC WITH PULL STRING FROM THE JUNCTION

BOX TO AN ACCESSIBLE LOCATION ABOVE CEILING

JUNCTION BOX FOR DOOR CONTACT (MAGNETIC LOCK);

PROVIDE 3/4"EC WITH PULL STRING FROM THE DOOR

FRAME TO THE JUNCTION BOX AND FROM THE JUNCTION

BOX TO AN ACCESSIBLE LOCATION ABOVE CEILING

JUNCTION BOX FOR CARD READER; PROVIDE 3/4"EC WITH

PULL STRING FROM THE JUNCTION BOX TO AN

ACCESSIBLE LOCATION ABOVE CEILING

JUNCTION BOX FOR ELECTRIC STRIKE LOCK; PROVIDE

3/4"EC WITH PULL STRING FROM THE DOOR FRAME TO THE

JUNCTION BOX AND FROM THE JUNCTION BOX TO AN

ACCESSIBLE LOCATION ABOVE CEILING

JUNCTION BOX FOR MOTION DETECTOR; PROVIDE 3/4"EC

WITH PULL STRING FROM THE JUNCTION BOX TO AN

ACCESSIBLE LOCATION ABOVE CEILING

JUNCTION BOX FOR CEILING MOUNTED CAMERA; PROVIDE

3/4"EC WITH PULL STRING FROM THE JUNCTION BOX TO

AN ACCESSIBLE LOCATION ABOVE CEILING

NURSE CALL SYSTEM EMERGENCY CALL-IN STATION

NURSE CALL SYSTEM BEDSIDE PATIENT STATION

NURSE CALL SYSTEM STAFF STATION

NURSE CALL SYSTEM CORRIDOR DOME LIGHT

NURSE CALL SYSTEM CODE BLUE STATION

D

M

KP

DC

CR

ES

MD

S

N

B

FIRE ALARM SYSTEM SMOKE DETECTORS

SP

SP

FIRE ALARM

SECURITY (EQUIPMENT PROVIDED BY OWNER/OTHERS)

JUNCTION BOX FOR WALL MOUNTED CAMERA; PROVIDE

3/4"EC WITH PULL STRING FROM THE JUNCTION BOX TO

AN ACCESSIBLE LOCATION ABOVE CEILING

SOUND

HEALTHCARE

FIRE ALARM CONTROL PANELFACP

(PROVIDE CONDUIT AND WIRE PER THE PANEL SCHEDULE FOR POWER

AND CONDUIT AND CABLING PER THE MANUFACTURER'S SPECIFICATIONS)

(EQUIPMENT PROVIDED BY OTHERS)

(PROVIDE 1"EC WITH PULL STRING FROM THE DEVICE LOCATION SHOWN

ON THE DRAWINGS TO AN ACCESSIBLE LOCATION ABOVE CEILING)

(PROVIDE 1"EC WITH PULL STRING FROM THE DEVICE LOCATION SHOWN

ON THE DRAWINGS TO AN ACCESSIBLE LOCATION ABOVE CEILING)

ELECTRICAL GENERAL NOTES

1. ALL ELECTRICAL WORK SHALL BE DONE IN STRICT ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL

CODE AS ADOPTED BY THE AHJ.

2. THE WORDS "PROVIDE" AND "PROVIDED" AS USED HEREIN SHALL BE UNDERSTOOD TO MEAN, "PROVIDE COMPLETE IN PLACE," THAT IS "FURNISH AND INSTALL". EQUIPMENT AND MATERIAL INDICATED TO BE PROVIDED SHALL BE NEW UNLESS OTHERWISE NOTED AND SHALL BE OF THE MOST SUITABLE GRADE FOR THE PURPOSE INTENDED.

3. ROUTE NEW CONDUIT AND WIRING CONCEALED IN WALLS AND CEILING WHERE POSSIBLE. COORDINATE INSTALLATION OF

EXPOSED CONDUIT AND WIRING WITH THE ARCHITECT.

4. CONTRACTOR SHALL PROVIDE ELECTRICAL SERVICE TO NEW HVAC UNITS AS FURNISHED BY THE MECHANICAL CONTRACTOR. VERIFY THE EXACT ELECTRICAL REQUIREMENTS WITH THE REVIEWED HVAC SUBMITTALS PRIOR TO

ORDERING ELECTRICAL EQUIPMENT.

5. BEFORE INSTALLATION, CONTRACTOR SHALL SUBMIT DETAILED DRAWINGS TO THE ENGINEER FOR REVIEW COVERING PROPOSED LOCATIONS, MOUNTING, AND ROUTING FOR ALL CONDUITS, SERVICES, FITTINGS, GROUND RODS, SUPPORTS, ETC.

6. CONTRACTOR IS RESPONSIBLE FOR OVER-CURRENT PROTECTIVE DEVICE SHORT CIRCUIT, COORDINATION, AND ARC-

FLASH STUDIES.

7. MATERIALS AND MANUFACTURERS NOTED ON DRAWINGS ARE TO BE USED AS BASIS OF DESIGN TO ESTABLISH QUALITY AND PERFORMANCE STANDARDS AND SHALL BE PROVIDED AS SPECIFIED. SUBSTITUTIONS WILL BE CONSIDERED WHERE SUFFICIENT PRODUCT INFORMATION IS PROVIDED TO MAKE A PROPER EVALUATION. REVIEW OF A SUBSTITUTION IS AT

THE SOLE DISCRETION OF THE PROFESSIONAL.

8. THE CONTRACTOR SHALL SUBMIT COPIES OF THE PRODUCT DATA, SHOP DRAWINGS, ETC. OF ALL MATERIALS NOTED ON THE DRAWINGS. ALL SUBMITTED PRODUCT DATA, SHOP DRAWINGS, ETC. SHALL BE MARKED WITH THE NAME OF THE PROJECT AND SHALL BEAR THE STAMP OF APPROVAL OF THE CONTRACTOR AS EVIDENCE THAT THE MATERIAL HAS BEEN

CHECKED BY THE CONTRACTOR.

9. DRAWINGS SPECIFIC TO THIS TRADE DO NOT LIMIT THE RESPONSIBILITY OR WORK REQUIRED BY THE CONTRACT DOCUMENTS. REFER TO DRAWINGS AND SPECIFICATIONS OF OTHER TRADES FOR COMPLETE INFORMATION PRIOR TO BID.

10. WHERE CONFLICTS EXIST AMONG DRAWINGS, SPECIFICATIONS, AND EQUIPMENT SCHEDULES, THE MOST STRINGENT REQUIREMENT OR QUANTITY SHALL APPLY. NOTIFY THE ARCHITECT/ENGINEER OF ALL CONFLICTS FOR RESOLUTION OR

INTERPRETATION.

11. NO EQUIPMENT SHALL BE ORDERED OR INSTALLED UNTIL THE PROJECT ENGINEER HAS RECEIVED A COPY STAMPED "NO EXCEPTIONS TAKEN." "NO EXCEPTIONS TAKEN" DOES NOT RELIEVE THE CONTRACTOR FROM CONFORMANCE WITH THE CONTRACT, EXTEND TO QUANTITIES OR DIMENSIONS, IMPLY THAT THE EQUIPMENT CAN BE INSTALLED OR OPERATE SATISFACTORILY, THAT THE EQUIPMENT CONTAINS ALL NECESSARY COMPONENTS, OR THAT IT WILL COORDINATE WITH

OTHER REVIEWED ITEMS.

12. OMISSION FROM THIS SHEET OF ANY ITEM SHOWN ELSEWHERE IN THE PLANS DOES NOT RELIEVE THE CONTRACTOR

FROM THE RESPONSIBILITY FOR ANY ASSOCIATED WORK.

13. COORDINATE INSTALLATION OF NEW ITEMS AND EQUIPMENT WITH THE OWNER'S REPRESENTATIVE AND THE WORK OF OTHER TRADES. THE CONTRACTOR SHALL INCUR ALL COSTS ASSOCIATED WITH THE RELOCATION OF EQUIPMENT

CONFLICTING WITH NEW WORK BY OTHER TRADES THAT HAS NOT BEEN COORDINATED.

14. COORDINATE ALL ASPECTS OF NEW SERVICE WITH UTILITY COMPANY AND INCLUDE ALL COSTS IN BID.

15. WARNING TAPE SHALL BE INSTALLED 12 TO 18 INCHES BELOW GRADE OVER ALL CONDUITS.

16. PROVIDE 1/4" MINIMUM DIAMETER PULL ROPE. PULL ROPE SHALL NOT BE NYLON STRING.

17. FOR SERVICE ENTRANCE CONDUITS, UTILIZE LONG RADIUS (36") CONDUIT BENDS.

18. ALL CONDUIT RISERS FROM UNDERGROUND SHALL HAVE RIGID METAL ELLS AND RISERS.

19. PRIOR TO CONSTRUCTION, VERIFY THE LOCATION OF ALL EXISTING UNDERGROUND UTILITIES. AVOID DISTURBANCE OF

EXISTING UTILITIES NOT INCLUDED IN THIS PROJECT.

20. SET SCREW CONDUIT FITTINGS SHALL NOT BE PERMITTED.

LIGHTING GENERAL NOTES

1. VERIFY THE EXACT LOCATION OF ALL LIGHTING SWITCHES WITH THE ARCHITECT PRIOR TO ROUGH-IN.

2. VERIFY THE EXACT LOCATION OF ALL LIGHTING FIXTURES WITH THE ARCHITECTURAL…