50014-0002B.pdf
PDF 10 MB Posted
- Attached to
- Chiller Replacement To Replace Chiller State and local contract opportunity
- Solicitation number
- 50014-0002B
- Issued by
- Orleans Parish, New Orleans City, Louisiana
About this file
These are bid documents for a Chiller Replacement project at the Central Plant of Southern University at New Orleans (SUNO), prepared by Parish Engineering on behalf of the State of Louisiana, specifically the Division of Administration, Office of Facility Planning and Control. The project involves removing the existing Chiller 3 and installing a new water-cooled chiller (CH-3) in the central plant, with a cooling capacity of 780.0 tons. The project is identified by Project No. 19-671-22-01, State Building ID S00304, and Site Code 1-36-007, with bid documents dated 06/13/2025.
The project scope includes mechanical and electrical work to replace the existing chiller, involving demolition of the current equipment, reconnection of existing conduit and wiring to the new chiller, and integration with the existing condenser water pump (CP-3(E)) and cooling tower (CT-3(E)). The new chiller will be a York model YKK9K2H9_EVH with electrical service at 480V, 3-phase, 60 Hz. The renovation plans specify connecting the new chiller to existing chilled and condensing water piping, and performing test and balance procedures for the new chiller, pump, and cooling tower. The electrical renovation will involve verifying electrical requirements with the chiller provider and reconnecting existing electrical infrastructure.
View the file
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET NUMBER
SHEET NAME
DATE:
REVISIONS
DRAWN BY:
CHECKED BY:
PROJECT #:
SHEET INFORMATION
SEAL
PROJECT INFORMATION
All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.
7600 Innovation Park Drive
Baton Rouge, LA 70820
225.332.0222 parisheng.com
COVER
COVER SHEET
CTD/SPG
LJB/SPG
06/13/2025
19-671-22-01
C H
IL
L
E R
R E
P L
A C
E M
E N
T C
E N
T R
A L
P L
A N
T S
U N
O N
E W
O R
L E
A N
S
L A
CENTRAL PLANT WATER COOLED CHILLER REPLACEMENT
SOUTHERN UNIVERSITY AT NEW ORLEANS
NEW ORLEANS, LOUISIANA
PROJECT NO.: 19-671-22-01, F.19002575
STATE BUILDING ID: S00304 - CENTRAL PLANT
SITE CODE: 1-36-007
STATE OF LOUISIANA
JEFF LANDRY, GOVERNOR
DIVISION OF ADMINISTRATION
TAYLOR F. BARRAS, COMMISSIONER
OFFICE OF FACILITY PLANNING AND CONTROL
ROGER E. HUSSER, JR., DIRECTOR
SOUTHERN UNIVERSITY SYSTEM
KENNETH DAWSON, SYSTEM DIRECTOR OF FACILITY PLANNING
BID DOCUMENTS
06/13/2025
VINCITY MAP
N
PROJECT AREA
SHEET INDEX
MECHANICAL
COVER COVER SHEET
M0.0 MECHANICAL COVER SHEET
M1.0 MECHANICAL DEMOLITION PLAN
M1.1 MECHANICAL RENOVATION PLAN
M2.0 MECHANICAL PLAN 3D
ELECTRICAL
E0.0 ELECTRICAL COVER SHEET
E1.0 ELECTRICAL DEMOLITION PLAN
E1.1 ELECTRICAL RENOVATION PLAN
06/13/2025
MECHANICAL GENERAL NOTES
1. ALL WORK BY CONTRACTORS SHALL CONFORM TO ALL APPLICABLE FEDERAL, STATE AND LOCAL BUILDING CODES, INCLUDING THE CURRENT INTERNATIONAL ENERGY CONSERVATION CODE.
2. MATERIALS FURNISHED UNDER THE CONTRACT SHALL BE NEW & SHALL BEAR THE UL LABEL WHERE APPLICABLE, UNLESS NOTED OTHERWISE. ALL WORK SHALL BE GUARANTEED AGAINST DEFECTIVE MATERIALS & WORKMANSHIP FOR A PERIOD OF NOT LESS THAN ONE YEAR AFTER
COMPLETION & ACCEPTANCE BY THE OWNER, LONGER IF STATED OTHERWISE ELSEWHERE IN THE SPECIFICATION.
3. CONTRACTOR SHALL INSTALL SYSTEMS WITHOUT INTERFERENCE & PROVIDE MANUFACTURER'S RECOMMENDED AIR & SERVICE CLEARANCES. CONTRACTOR SHALL COORDINATE WITH ALL TRADES & DISCIPLINES.
4. MECHANICAL CONTRACTOR SHALL COORDINATE WITH GENERAL CONTRACTOR ON LOCATION OF ALL FIRE & SMOKE WALL PENETRATIONS. GENERAL CONTRACTOR SHALL FRAME OUT OPENING AS REQUIRED FOR LIFE SAFETY DAMPERS. PROVIDE LIFE SAFETY DAMPERS WHERE SHOWN ON
DRAWINGS AND WHERE REQUIRED BY NFPA AND LOCAL BUILDING CODES.
5. ALL FIRE DAMPERS SHALL BE 2-HOUR RATED UNLESS SPECIFIED OR NOTED OTHERWISE ON DRAWINGS AND/OR SPECIFICATIONS.
6. SEAL ALL FIRE WALL PENETRATIONS (DUCT, PIPE, ETC.) WITH UL-LISTED FIRE CAULK IN ACCORDANCE WITH NFPA 101.
7. MECHANICAL CONTRACTOR SHALL COORDINATE BETWEEN ELECTRICAL AND OTHER TRADES FOR PENETRATIONS AT WALLS, FLOORS AND ROOFS, EXACT EQUIPMENT LOCATIONS, AND REQUIRED EQUIPMENT SERVICE AND AIR FLOW CLEARANCE.
8. INSTALLATION OF DUCTWORK SHALL TAKE PRECEDENCE OVER INSTALLATION OF PLUMBING PIPING THAT IS NOT GRADE SENSITIVE (SEWER, STORM DRAINAGE, GREASE WASTE, ETC.) AND ELECTRICAL CONDUIT. CONTRACTOR TO COORDINATE CEILING SPACE AVAILABLE, EXACT
MECHANICAL ROOM LAYOUT, DUCT AND PIPE ROUTING AND EXACT EQUIPMENT LOCATIONS WITH GENERAL, ELECTRICAL, STRUCTURAL AND PLUMBING CONTRACTORS. PROVIDE OFFSETS AND TRANSITIONS AT OBSTRUCTIONS WHERE REQUIRED AT NO ADDITIONAL COST TO THE OWNER.
9. MECHANICAL CONTRACTOR SHALL COORDINATE WITH GENERAL CONTRACTOR AND ARCHITECT PRIOR TO INSTALLATION OF THERMOSTATS/TEMPERATURE SENSORS ON WALL. COORDINATE THERMOSTATS/TEMPERATURE SENSORS WITH ALL WALL MOUNTED FURNISHINGS (ART, SCREENS, FURNITURE, ETC.). LOCATE THERMOSTATS AND HUMIDISTATS 4' ABOVE FINISHED FLOOR UNLESS OTHERWISE NOTED.
10. CONTRACTOR SHALL VISIT THE SITE FOR INSPECTION REGARDING ANY WORK REQUIRED TO COMPLETE THE SCOPE OF WORK FOR THE PROJECT PRIOR TO BID. THERE SHALL BE NO ADDITIONAL COST TO THE OWNER FOR BIDDERS AWARDED THE WORK FOR FAILURE TO EXAMINE SITE
PRIOR TO BID.
11. CONTRACTOR SHALL REVIEW THE CONTRACT DOCUMENTS AND VISIT THE SITE AND COORDINATE DUCT, PIPE AND EQUIPMENT SIZES AND ROUTING. CONTRACTOR SHALL NOTIFY THE ARCHITECT AND ENGINEER WHERE DISCREPANCIES OCCUR BETWEEN CONTRACT DOCUMENTS AND
EXISTING CONDITIONS.
12. CONTRACTOR SHALL REVIEW CEILING SPACE AND MECHANICAL ROOM SPACE AVAILABLE FOR DUCT, PIPING AND EQUIPMENT AND MAKE REQUIRED ALLOWANCES FOR THE SIZE AND ROUTING OF DUCT, PIPING AND EQUIPMENT.
13. MECHANICAL CONTRACTOR TO REVIEW CEILING SPACE AVAILABLE AND VERIFY FIELD MEASUREMENTS AND COORDINATION DRAWINGS PRIOR TO FABRICATING DUCT. BRANCH DUCT RUNS SHOWN DIAGRAMMATICALLY; CONTRACTOR SHALL ROUTE BRANCH DUCT RUNS IN MOST DIRECT
MANNER.
14. COORDINATE EXACT LOCATION OF ALL SLAB, FLOOR, WALL AND ROOF PENETRATIONS WITH EXISTING STRUCTURAL BEAMS, JOIST AND COMPONENTS. DO NOT CUT OR MODIFY EXISTING STRUCTURAL COMPONENTS WITHOUT APPROVAL FROM STRUCTURAL ENGINEER.
15. CONTRACTOR SHALL VERIFY EQUIPMENT TO BE SUPPLIED TO PROJECT CAN BE INSTALLED IN SPACE PROVIDED AND ALL SERVICE AND AIRFLOW CLEARANCES MAINTAINED PRIOR TO ORDERING EQUIPMENT. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY MODIFICATIONS REQUIRED FOR
EQUIPMENT THAT IS SUPPLIED THAT IS DIFFERENT THAN EQUIPMENT THAT IS BASIS OF DESIGN.
16. UNDER NO CIRCUMSTANCES SHALL EQUIPMENT AND RELATED SYSTEM COMPONENTS FOUND POSITIVE FOR MOLD, MILDEW, ASBESTOS, HARMFUL BACTERIA OR ANY OTHER CONTAMINATION BE PLACED INTO SERVICE.
17. INSTALL DUCT SLEEVES IN WALLS AS HIGH AS POSSIBLE, DUCT SLEEVE SHALL EXTEND PAST WALL PENETRATION ON BOTH SIDES MINIMUM 24". RETURN AIR TRANSFER SLEEVES SHALL BE PROVIDED WITH TWO (2) DUCT ELBOWS.
18. COORDINATE ALL UNDERGROUND PIPING & WORK WITH EXISTING SYSTEMS, INCLUDING EXISTING UTILITIES, SEWER, GAS, DOMESTIC WATER, CHILLED/HEATING WATER, ELECTRIC DUCT BANKS AND POWER. NOT ALL EXISTING SYSTEMS SHOWN. COORDINATE ALL EXISTING SYSTEMS PRIOR
TO BEGINNING WORK. MARKED UTILITIES AND EXISTING SYSTEMS DAMAGED BY THE CONTRACTOR SHALL BE REPLACED AND REPAIRED BACK TO ORIGINAL CONDITION BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE CONSTRUCTION CONTRACT.
19. MODEL NUMBERS SCHEDULED/SPECIFIED REPRESENT THE TYPE AND QUALITY OF EQUIPMENT REQUIRED TO MEET THE DESIGN REQUIREMENTS. CONTRACTOR SHALL REVIEW SUBMITTALS AND VERIFY EQUIPMENT SIZES, QUALITY AND PERFORMANCE REQUIREMENTS MEET
SPECIFICATIONS PRIOR TO SUBMITTING FOR APPROVAL. EQUIPMENT THAT DIFFERS FROM BASIS OF DESIGN IS SUBJECT TO REJECTION. CONTRACTOR TO COORDINATE ALL DIFFERENCE IN EQUIPMENT WITH STRUCTURAL, ELECTRICAL AND PLUMBING CONTRACTORS.
20. ALL CONDENSATE LINES SHALL BE RIGID COPPER, INSULATED WITH CELLULAR FOAM UNLESS NOTED OTHERWISE OR SUBMITTED AND APPROVED BY MECHANICAL ENGINEER. SUPPORT WITH UNISTRUT PIPE EVERY 4' AND AT TURNS. PROVIDE NEOPRENE SLEEVES BETWEEN UNISTRUT AND
COPPER CONDENSATE LINE.
21. DUCT SIZES SHOWN ARE SHEET METAL SIZES. ALLOWANCES HAVE BEEN INCLUDED FOR INTERNAL LINER WHERE APPLICABLE.
22. COORDINATE EXACT LOCATION OF AIR DEVICES WITH NEW AND EXISTING LIGHTS TO BE INSTALLED PRIOR TO CONSTRUCTION.
23. EXPOSED DUCTWORK SHALL BE PAINT GRIPPED SHEET METAL UNLESS INDICATED OTHERWISE. ALL EXPOSED DUCT TO BE PAINTED IN FIELD BY PAINTING CONTRACTOR DURING CONSTRUCTION. COORDINATE WITH ARCHITECT & MECHANICAL ENGINEER PRIOR TO INSTALLATION OF
EXPOSED DUCT AND COLOR. EXPOSED DUCTWORK SHALL BE FREE OF SIZE MARKS OR ASSEMBLY CODE NUMBERS; ALL MARKS SHALL BE ON THE INSIDE OF DUCTWORK. KEEP OUTSIDE SURFACES OF DUCT CLEAN DURING FABRICATION. BANDS SHALL JOIN ON TOP, CONCEALED FROM NORMAL VIEW OF THE DUCT AND SPIRALS SHALL BE CONTINUOUS. THREADED RODS FROM HANGER STRAPS SHALL BE NEATLY CLIPPED AND SECURED WITHOUT EXCESS. GREATER ATTENTION TO APPEARANCE FOR EXPOSED DUCT IS EXPECTED AND DENTED/SCARRED DUCTS SHALL NOT
BE ACCEPTABLE.
24. PROVIDE ELECTRICAL DISCONNECTS FOR MECHANICAL EQUIPMENT (VAV BOXES, FANS, VFD'S, ETC.) FACTORY INSTALLED BY EQUIPMENT MANUFACTURER UNLESS NOTED OTHERWISE. COORDINATE WITH ELECTRICAL CONTRACTOR.
25. DO NOT ROUTE PIPING CONTAINING WATER OVER ELECTRICAL EQUIPMENT.
26. PROVIDE PERMANENT LABELS FOR ALL SCHEDULED EQUIPMENT. LABELS SHALL BE MINIMUM 3/8" ENGRAVED BLACK LETTERS ON WHITE BACKGROUND, CONSTRUCTED OF MINIMUM 1" WIDE, LENGTH AS REQUIRED LAMINATED PLASTIC. SECURELY FASTENED TO EQUIPMENT WITH STAINLESS
STEEL OR NONCORRODING HARDWARE. STICK ON LABELS NOT ACCEPTABLE.
27. EXHAUST OUTLETS SHALL BE LOCATED MINIMUM 10' FROM ANY AIR INTAKE OR OPERABLE BUILDING OPENING.
28. INDOOR MINISPLITS, FAN COIL UNITS AND CEILING CASSETTES SHALL HAVE GRAVITY DRAINAGE WHERE POSSIBLE. PROVIDE WITH INTEGRAL CONDENSATE PUMPS WHERE NOT POSSIBLE.
29. PROVIDE RETURN AIR GRILLES OPEN TO RETURN AIR PLENUM WITH SOUND ATTENUATING BOOT ON REAR OF GRILLE (RIGID DUCT WITH INSULATED LINER & TWO ELBOWS, END OPEN TO RETURN AIR PLENUM). CONTRACTOR HAS OPTION TO PROVIDE PRICE MODEL #RAC RETURN AIR
CANOPY ON REAR OF RETURN AIR GRILLES OPEN TO RA PLENUM IN LIEU OF SOUND ATTENUATING BOOT.
30. ELECTRONIC BALANCING DAMPERS : MANUAL DAMPER AT INACCESSIBLE LOCATIONS:
30.1. PROVIDE REMOTE BALANCING DAMPER WITH POSITION INDICATOR AT INACCESSIBLE MANUAL VOLUME DAMPERS
30.2. INACESSIBLE LOCATIONS:
30.2.1. ABOVE GYPSUM BOARD/HARD CEILING
30.2.2. WHERE LOCATED HIGHER THAN 4'-0" ABOVE ACCESSIBLE CEILING TILE
30.2.3. WHERE LOCATED ABOVE 14'-0" FROM FINISHED FLOOR
30.2.4. REFER TO ARCHITECTURAL REFLECTED CEILING DRAWINGS FOR REFLECTED CEILING PLAN
30.3. ELECTRONIC BALANCING DAMPER SHALL BE PROVIDED WITH POSITION INDICATOR AND SHALL BE GREENHECK MODEL RBDR-50 (ROUND) & RBD-10 (RECTANGULAR) OR APPROVED EQUAL, UNLESS INDICATED OTHERWISE.
30.4. REMOTE BALANCING DAMPER SHALL BE 12 VOLT DC POWER BALANCE SYSTEM ( DAMPER, PULSE ACTUATOR , CAT 5 CABLE, WALL OR CEILING PLATE AND HAND HELD POWER PACK). PROVIDE WALL/CEILING ACCESS PORT ON WALL WITHIN CLOSEST MECHANICAL ROOM OR ABOVE
ACCESSIBLE CEILING MOUNTED ON WALL. ALL ACCESS PORTS TO BE PROPERLY LABELED NUMERICALLY BY RESPECTIVE AIR SYSTEM & ROOM DAMPER SERVES. COORDINATE WITH MECHANICAL ENGINEER PRIOR TO LABELING & COORDINATE LOCATION WITH MECHANICAL ENGINEER & ARCHITECT PRIOR TO INSTALLING ANY ACCESS PORT ABOVE ACCESSIBLE CEILINGS. PROVIDE TILE IDENTIFICATION WHERE LOCATED ABOVE CEILING, PROVIDE DRAWING IDENTIFYING PORT LOCATION & PORT SCHEDULE AS PART OF CLOSE OUT DOCUMENTS.
31. PROVIDE U.L. LISTED SMOKE DETECTORS IN THE MAIN SUPPLY DUCT AND RETURN ON THE DOWNSTREAM SIDE OF THE FILTERS IN ALL RECIRCULATING AIR SYSTEMS HANDLING OVER 2000 C.F.M. NOTE: SMOKE DETECTORS TO BE WIRED TO BUILDING FIRE ALARM SYSTEM BY FIRE ALARM CONTRACTOR, FIRE ALARM CONTRACTOR IS TO PROVIDE AND INSTALL ALL WIRING, TERMINATIONS, ETC. TO PROVIDE A COMPLETE, PROPERLY FUNCTIONING AND OPERATING SYSTEM.
32. PROVIDE SMOKE DAMPER IN THE MAIN SUPPLY & RETURN DUCT IN ALL AIR HANDLING UNITS HANDLING OVER 15,000 CFM. SMOKE DAMPERS TO BE INTERCONNECTED TO SMOKE DETECTORS.
33. PROVIDE ACCESS PANELS FOR EQUIPMENT,VALVES, DAMPER, ETC. LOCATED ABOVE A NON ACCESSIBLE CEILING. ACCESS PANELS SHALL BE LARGE ENOUGH FOR ALL REQUIRED MAINTENANCE, ADJUSTMENT, ECT. PROVIDE MULTIPLE ACCESS PANELS AS REQUIRED. COORDINATE COLOR
AND LOCATIONS WITH ARCHITECT. PROVIDE FIRE AND/ OR SMOKE RATED ACCESS PANELS WHERE REQUIRED IN RATED CEILINGS. REFERENCE ARCHITECTURAL DRAWINGS FOR RATED CEILING LOCATIONS. WHERE ACCESS PANELS ARE SHOWN ON ARCHITECTURAL REFLECTED CEILING PLAN, COORDINATE EXACT LOCATION OF EQUIPMENT, DEVICES, ETC. WITH ACCESS PANEL LOCATIONS.
34. PROVIDE TEMPORARY CAPS/PLUGS/COVERING ON ALL OPEN ENDED PIPING & DUCT DURING CONSTRUCTION TO PREVENT DIRT/DEBRIS FROM ENTERING PIPE/DUCT SYSTEMS.
35. PROVIDE PROTECTIVE LOCKABLE THERMOSTAT COVERS FOR THERMOSTATS. COORDINATE WITH OWNER.
36. MECHANICAL CONTRACTOR SHALL COORDINATE WITH PLUMBING CONTRACTOR ON LOCATION OF ALL FLOOR DRAINS & HUB DRAINS AS NOT TO INTERFERE WITH EQUIPMENT & EQUIPMENT PADS. COORDINATE NEW FLOOR DRAIN & HUB LOCATION WHERE EQUIPMENT DOES NOT ALLOW
FOR THE INSTALLATION SHOWN FOR DRAIN. COORDINATE HEIGHT OF HUB DRAINS FOR FAN COIL UNITS & CEILING CASSETTES.
37. PROVIDE TRANSITIONS FROM REAR OF ALL GRILLES TO BRANCH DUCTS AND TO ALL EQUIPMENT AS REQUIRED. REFER TO CONSTRUCTION DOCUMENTS FOR SIZES OF GRILLES AND DUCTS.
38. PRESSURE TEST ALL REUSED/REROUTED PIPING SYSTEMS. TESTING SHALL BE PERFORMED AT NORMAL SYSTEM OPERATING PRESSURE UNLESS INDICATED/SPECIFIED OTHERWISE. REPAIR AND RETEST AS REQUIRED UNTIL SYSTEMS ARE PROVEN TIGHT WITHOUT LEAKS.
39. ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT OR PIPING INSULATION IS APPLIED.
40. LOCATE ALL TEMPERATURE PRESSURE AND FLOW MEASURING DEVICES IN ACCESSIBLE LOCATIONS WITH STRAIGHT SECTION OF PIPE OR DUCT UP AND DOWN STREAM AS RECOMMENDED BY THE MANUFACTURER.
41. REINFORCEMENT, DETAILING, AND PLACEMENT OF CONCRETE SHALL CONFORM TO ASTM 315 AND ACI 318. CONCRETE SHALL CONFORM TO ASTM C94. CONCRETE WORK SHALL CONFORM TO ACI318, PART ENTITLED “CONSTRUCTION REQUIREMENTS.” COMPRESSIVE STRENGTH IN 28 DAYS
SHALL BE 3,000 PSI. TOTAL AIR CONTENT OF EXTERIOR CONCRETE SHALL BE BETWEEN 5 AND 7 PERCENT BY VOLUME. SLUMP SHALL BE BETWEEN 3 AND 4 INCHES. CONCRETE SHALL BE CURED FOR 7 DAYS AFTER PLACEMENT.
42. COORDINATE ALL EQUIPMENT CONNECTION WITH MANUFACTURERS’ CERTIFIED DRAWINGS. COORDINATE AND PROVIDE ALL DUCT AND PIPING TRANSITIONS REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND COORDINATE ALL DUCT AND
PIPING DIMENSIONS BEFORE FABRICATION.
43. MINIMUM CONCRETE PAD THICKNESS SHALL BE 4 INCHES. PAD SHALL EXTEND BEYOND THE EQUIPMENT A MINIMUM OF 6 INCHES ON EACH SIDE UNLESS OTHERWISE DIRECTED IN THESE DOCUMENTS 15 LOCATIONS AND SIZES OF ALL FLOOR, WALL, AND ROOF OPENINGS SHALL BE
COORDINATED WITH ALL OTHER TRADES INVOLVED. REFER TO TYPICAL DETAILS FOR DUCTWORK, PIPING, AND EQUIPMENT INSTALLATION.
44. INSTALL TRANSITION DUCT FROM INLET AND OUTLET OF EQUIPMENT TO DUCT SIZE SHOWN ON PLANS; CONSULT EQUIPMENT MANUFACTURER FOR INLET AND OUTLET SIZE.
45. ALL DUCT ELBOWS, BENDS, AND TEES SHALL BE PROVIDED WITH DOUBLE THICKNESS TURNING VANES OR RADIUS ELBOWS UNLESS SHOWN OR NOTED OTHERWISE. ELBOWS IN DISHWASHER, KITCHEN, AND LAUNDRY EXHAUST SHALL BE UNVANED SMOOTH RADIUS CONSTRUCTION WITH A
RADIUS OF 1.5 TIMES THE WIDTH OF THE DUCT.
46. PROVIDE ESCUTCHEONS AT ALL EXPOSED LOCATIONS WHERE PIPE PENETRATES WALL.
47. THE CONDENSATE DRAIN LINE SHALL NOT DECREASE IN SIZE FROM THE DRAIN PAN CONNECTION TO THE FLOOR DRAIN; ELEVATE UNIT TO ACCOMMODATE P-TRAP.
48. ALL EQUIPMENT AND DEVICES TO BE FURNISHED AND INSTALLED PER THE REQUIREMENTS OF CONTRACT DRAWINGS, SPECIFICATIONS, MANUFACTURERS RECOMMENDATIONS, AND ACCORDING TO CODE.
49. PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS (SUPPLY, RETURN, AND EXHAUST) CONNECTED TO AIR HANDLING UNITS, FANS, AND OTHER EQUIPMENT WHICH REQUIRE VIBRATION ISOLATION. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AT THE POINT OF CONNECTION TO
THE EQUIPMENT UNLESS OTHERWISE DIRECTED IN THESE DOCUMENTS.
50. UNLESS OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD, TIGHT TO UNDERSIDE OF THE STRUCTURE, WITH SPACE FOR INSULATION.
51. ALL ROOF CURBS SHALL BE INSTALLED TO THE ROOFING STRUCTURE AND FINISH A MINIMUM 12" ABOVE THE FINISHED ROOF FOR COUNTER FLASH ENDORSED BY ROOF MANUFACTURER. ROOF CURBS SHALL BE PITCHED WHERE REQUIRED TO ENSURE EQUIPMENT IS INSTALLED LEVEL.
52. ALL MISCELLANEOUS ROOFTOP EQUIPMENT SUPPORTS SHALL BE ENDORSED BY BOTH THE RESPECTIVE EQUIPMENT MANUFACTURER AND ROOF SYSTEM MANUFACTURER.
53. ALL WALL APPLIED ITEMS SHALL BE INSTALLED PLUMB, LEVEL AND IN LOCATIONS DESIGNATED IN CONTRACT DOCUMENTS. ALL DEVICE COVERS AND TRIM SHALL FIT TIGHT TO WALL SURFACE ON ALL SIDES. WHERE SPECIFIC LOCATIONS FOR ITEMS NOT SHOWN OR CLEAR, CONTRACTOR
SHALL OBTAIN CLARIFICATION AND DIRECTION FROM ARCHITECT AND MECHANICAL ENGINEER PRIOR TO INSTALLATION.
54. ALL FLEX DUCT SERVING DIFFUSERS SHALL BE LIMITED TO RUNS OF 6'. FLEX DUCT SHALL BE FLEXMASTER 1M-R6 OR APPROVED EQUAL AND USE STAINLESS STEEL (OR NYLON IF APPROVED BY MECHANICAL ENGINEER) TO CONNECT FLEX TO DUCT AND GRILLES.
55. FLEXIBLE DUCT NOT ACCEPTABLE FOR EXHAUST, RETURN AND FRESH AIR SYSTEMS UNLESS SPECIFIED OR NOTED OTHERWISE. FLEX DUCT SHALL NOT PENETRATE ANY WALLS UNLESS SUBMITTED AND APPROVED ON TO BOTH THE ARCHITECT AND MECHANICAL ENGINEER.
56. PROVIDE ADDITIONAL SUSPENDED SUPPORTS AS REQUIRED TO PREVENT FLEXIBLE DUCT FROM CONTACTING THE CEILING MATERIAL AND/OR CEILING FRAME/GRID ASSEMBLY.
57. ALL ROUND TAPS OFF RECTANGULAR DUCTWORK TO DIFFUSERS SHALL BE MADE WITH HIGH EFFICIENCY SIDE TAKEOFFS WITH 2" INSULATION STANDOFF BRACKETS AND LOCKING QUADRANT, FLEXMASTER MODEL STOD-BO3 OR APPROVED EQUAL.
58. ALL GRILLES LOCATED IN LAY-IN CEILINGS SHALL HAVE 24x24 FRAMES, STYLES TO FIT THE GRID TYPE, EITHER 15/16" OR 9/16" GRID, VERIFY GRID WITH ARCHITECTURAL DRAWINGS. PROVIDE PLASTER FRAMES FOR SURFACE MOUNT APPLICATIONS, PRICE MODEL AMF OR APPROVED EQUAL.
59. PROVIDE MANUAL VOLUME DAMPERS IN ALL BRANCH DUCT CONNECTIONS TO LOW PRESSURE MAIN DUCTS.
60. ALL EQUIPMENTS SUPPLIED TO THE PROJECT SHALL BE PER SPECIFICATIONS. OBTAINING APPROVED SUBMITTALS DOES NOT RELIEVE THE CONTRACTOR/SUPPLIER OF PROVIDING ALL FEATURES, OPTIONS AND ACCESSORIES INCLUDED WITHIN THE CONSTRUCTION DOCUMENTS.
AC AIR CONDITIONING
ACCU AIR COOLED CONDENSING UNIT
AFF ABOVE FINISHED FLOOR
AFS AIR FLOW STATION
AHU AIR HANDLING UNIT
AMB AMBIENT
AS AIR SEPARATOR
AV AIR VENT
BAS BUILDING AUTOMATION SYSTEM
BDD BACKDRAFT DAMPER
BFP BACKFLOW PREVENTER
BOD BOTTOM OF DUCT
BTUH BRITISH THERMAL UNIT PER HOUR
CC COOLING COIL
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CH CHILLER
CHWCF CHILLED WATER CHEMICAL FEED
CHP CHILLED WATER PUMP
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
COMP COMPRESSOR
CP CIRCULATING PUMP
CU CONDENSING UNIT
CT COOLING TOWER
CV CONTROL VALVE
CW COLD WATER
CWCF CONDENSER WATER CHEMICAL FEED
CWR CONDENSER WATER RETURN
CWP CONDENSER WATER PUMP
CWS CONDENSER WATER SUPPLY
DB DRY BULB TEMP (DEG F)
DDC DIRECT DIGITAL CONTROL
DN DOWN
DP DIFFERENTIAL PRESSURE
DPS DIFFERENTIAL PRESSURE SWITCH
DWG DRAWING
DX DIRECT EXPANSION
EA EXHAUST AIR
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EL ELEVATION
ELEC ELECTRICAL
ENT ENTERING
ECU ELECTRIC CONDENSING UNIT
ERU ELECTRIC REFRIGERANT UNIT
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EUH ELECTRIC UNIT HEATER
EVAP EVAPORATOR
EX EXHAUST
EXT EXTERNAL
FA FRESH AIR
FC/FCUFAN COIL UNIT
FD FIRE DAMPER
FT FEET
FLA FULL LOAD AMPS
FPM FEET PER MINUTE
FV FACE VELOCITY
GALV GALVANIZED
GPM GALLONS PER MINUTE
GPH GALLONS PER HOUR
GUH GAS UNIT HEATER
HC HEATING COIL
HP HORSEPOWER
HR HOUR
HWS HEATING WATER SUPPLY
HWR HEATING WATER RETURN
ID INSIDE DIAMETER
IN INCHES
KW KILOWATTS
LVG LEAVING
MA MIXED AIR
MAX MAXIMUM
MD MOTORIZED DAMPER
MECH MECHANICAL
NG NATURAL GAS
MIN MINIMUM
MVD MANUAL VOLUME DAMPER
NC NORMALLY CLOSED
NFPA NATIONAL FIRE PROTECTION ASSOC.
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NOM NOMINAL
NTS NOT TO SCALE
OA OUTSIDE AIR
OAF OUTSIDE AIR FAN
OAU OUTSIDE AIR UNITS
OS&Y OUTSIDE STEM AND YOKE
OZ OUNCES (PRESSURE)
PD PRESSURE DROP
PTAC PACKAGED TERMINAL AIR CONDITIONER
PSI POUNDS PER SQUARE INCH
RA RETURN AIR
REF REFERENCE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RND ROUND
RPM REVOLUTIONS PER MINUTE
RTU ROOF TOP UNIT
SA SUPPLY AIR
SD SMOKE DAMPER
SEER SEASONAL ENERGY EFFICIENCY RATIO
SF SUPPLY AIR FAN
SP STATIC PRESSURE
SPEC SPECIFICATIONS
TEMP TEMPERATURE
TOD TOP OF DUCT
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
UG UNDERGROUND
UL UNDERWRITERS LISTED
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
W / WITH
W / O WITHOUT
WB WET BULB (DEG F)
ABBREVIATION LEGEND
DETAIL SYMBOL
GRID LINE
SECTION SYMBOL
DEMO NOTE
REVISION TAG
TIE INTOMATCHLINE
1 / M101
MATCHLINE
THERMOSTAT SYMBOLT99
NEW EQUIPMENT OR FIXTURE
EXISTING TO REMAIN
EXISTING TO BE DEMOLISHED
A-500 DIFFUSER TAG
MARK
NEW WORK
CFM
M101
M101
SECTION
DETAIL
SHEET NUMBER
SHEET NUMBER
1 GENERAL NOTE
RE: 1 / M101 SHEET REFERENCE TAG
SHEET NUMBER
VIEW NUMBER
MECHANICAL SYMBOL LEGEND
GENERAL
(REFER TO DRAWINGS AND SPECIFICATIONS FOR FURTHER REQUIREMENTS)
MITERED 90º ELBOW WITH DOUBLE DEFLECTION
TURNING VANES
RECTANGULAR TRANSITION; SYMMETRIC
RECTANGULAR TRANSITION; ASYMMETRIC
MITERED 45º ELBOW WITH DOUBLE DEFLECTION
TURNING VANES
DUCT WITH FLEXIBLE CONNECTION
45º RECTANGULAR TAP
ROUND EXHAUST DUCT UP
ROUND EXHAUST DUCT DOWN
CHANGE IN RECTANGULAR DUCT ELEVATION; RISE
CHANGE IN ROUND DUCT ELEVATION; DROP
4-WAY S/A DIFFUSER; SEE SCHEDULE FOR SIZE
3-WAY S/A DIFFUSER; SEE SCHEDULE FOR SIZE
2-WAY S/A DIFFUSER; SEE SCHEDULE FOR SIZE
1-WAY S/A DIFFUSER; SEE SCHEDULE FOR SIZE
R/A GRILLE; SEE SCHEDULE FOR SIZE
DUCT WITH MANUAL VOLUME DAMPER
DUCT WITH FIRE DAMPER
DUCT WITH SMOKE DAMPER
DUCT WITH COMBINATION FIRE/SMOKE DAMPER
DUCT WITH ACCESS DOOR
DUCT WITH MOTORIZED DAMPER
45º LEAD-IN WITH MANUAL VOLUME DAMPER
RADIUS ELBOW
E/A GRILLE; SEE SCHEDULE FOR SIZE
INTERNALLY INSULATED DUCT
SUPPLY DUCT
RETURN DUCT
EXHAUST DUCT
RECTANGULAR SUPPLY DUCT UP
RECTANGULAR EXHAUST DUCT DN
ROUND SUPPLY DUCT UP
ROUND SUPPLY DUCT DN
ROUND RETURN DUCT UP
ROUND RETURN DUCT DN
RECTANGULAR SUPPLY DUCT DN
RECTANGULAR RETURN DUCT UP
RECTANGULAR RETURN DUCT DN
RECTANGULAR EXHAUST DUCT UP
DUCT WITH HUMIDIFIER
R
D
DUCT WITH BACK DRAFT DAMPER
DUCTWORK
SHEET NUMBER
SHEET NAME
DATE:
REVISIONS
DRAWN BY:
CHECKED BY:
PROJECT #:
SHEET INFORMATION
SEAL
PROJECT INFORMATION
All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.
7600 Innovation Park Drive
Baton Rouge, LA 70820
225.332.0222 parisheng.com
M0.0
MECHANICAL COVER SHEET
CTD
LJB
06/13/2025
19-671-22-01
C H
IL
L
E R
R E
P L
A C
E M
E N
T C
E N
T R
A L
P L
A N
T S
U N
O N
E W
O R
L E
A N
S
L A
INDEX - MECHANICAL SHEETS
M0.0 MECHANICAL COVER SHEET
M1.0 MECHANICAL DEMOLITION PLAN
M1.1 MECHANICAL RENOVATION PLAN
M2.0 MECHANICAL PLAN 3D
SCHEDULE - CHILLERS - WATER COOLED
MARK
COOLING
CAPACITY
COMPRESSOR(S) EVAPORATOR CONDENSER ELECTRICAL SERVICE
WEIGHT MANUFACTURER / MODELQTY TYPE
WATER FLOW
EWT LWT WATER PD
WATER FLOW
EWT LWT WATER PDF VOLTS PH FREQDESIGN MINIMUM MAXIMUM DESIGN MINIMUM MAXIMUM
CH-3(E) 780.0 ton 1 CENTRIFUGAL 1872 GPM 1196 GPM 4091 GPM 55 °F 45 °F 10.30 psi 2340 GPM 2106 GPM 4494 GPM 85 °F 94 °F 14.70 psi 480 V 3 60 Hz 30000 lb YORK MODEL YKK9K2H9_EVH
SCHEDULE - EXISTING COOLING TOWER
MARK
WATER
GPM EWT
WATER
TEMP DROP
AMBIENT
WB TEMP
STARTER FAN MOTOR NO. OF
CELLS TYPE COMMENTSTYPE LOCATION HP VOLTS PH
CT-3(E) 2340 95°F 85°F 80°F VFD MECH ROOM 60 480 V 3 1 CROSSFLOW EXISTING COOLING TOWER TO REMAIN
SCHEDULE - EXISTING PUMPS
MARK GPM
DISC. HEAD
FT. WATER RPM TYPE
ELECTRICAL DATA
TYPE LOCATION COMMENTSHP VOLTS PH
CHP-3(E) 1872 125 1150 DOUBLE SUCTION 100 480 V 3 VFD NEAR PUMP EXISTING PUMP TO REMAIN
CP-3(E) 2340 50 1150 DOUBLE SUCTION 40 480 V 3 COMB NEAR PUMP EXISTING PUMP TO REMAIN
4-Room
2923 ft²
5-Room
1844 ft²
6-Room
4947 ft²
7-Room
272 ft²
8-Room
55 ft²
10-Room
527 ft²
11-Room
1313 ft²
9-Room
49 ft²
CH-1(E) CH-2(E) CH-3(E)
CHP-1 CHP-2 CHP-3
CP-1(E)
CP-2(E)
CP-3(E)
CT-1(E)
CT-2(E)
CT-3(E)
12" CWS (E)
12" CWR (E)
12" CWS (E)
12" CWR (E)
12" CWS (E)
12" CWR (E)
10" CHR (E)
10" CHS (E)
12" CHR (E)
12" CHS (E)
16" CHR (E)
16" CHS (E)
16" CHR (E)
16" CHS (E)
EXISTING
CH-3
STORAGE
LOCATION
SHEET NUMBER
SHEET NAME
DATE:
REVISIONS
DRAWN BY:
CHECKED BY:
PROJECT #:
SHEET INFORMATION
SEAL
PROJECT INFORMATION
All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.
7600 Innovation Park Drive
Baton Rouge, LA 70820
225.332.0222 parisheng.com
M1.0
MECHANICAL DEMOLITION
PLAN
CTD
LJB
06/13/2025
19-671-22-01
C H
IL
L
E R
R E
P L
A C
E M
E N
T C
E N
T R
A L
P L
A N
T S
U N
O N
E W
O R
L E
A N
S
L A
1/8" = 1'-0"1 MECHANICAL DEMOLITION PLAN
DEMOLITION KEY NOTES:
REMOVE EXISITNG CHILLER 3 AND PLACE IN STORAGE WHERE SHOWN.1
12" CWS (E)
12" CWR (E)
12" CWS (E)
12" CWR (E)
12" CWS (E)
12" CWR (E)
10" CHR (E)
10" CHS (E)
12" CHR (E)
12" CHS (E)
16" CHR (E)
16" CHS (E)
CH-1(E) CH-2(E)
CP-1(E)
CP-2(E)
CP-3(E)
CT-1(E)
CT-2(E)
CT-3(E)
CH-3(E)
CHP-1(E) CHP-2(E) CHP-3(E)
CH-3
SHEET NUMBER
SHEET NAME
DATE:
REVISIONS
DRAWN BY:
CHECKED BY:
PROJECT #:
SHEET INFORMATION
SEAL
PROJECT INFORMATION
All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.
7600 Innovation Park Drive
Baton Rouge, LA 70820
225.332.0222 parisheng.com
M1.1
MECHANICAL RENOVATION
PLAN
CTD
LJB
06/13/2025
19-671-22-01
C H
IL
L
E R
R E
P L
A C
E M
E N
T C
E N
T R
A L
P L
A N
T S
U N
O N
E W
O R
L E
A N
S
L A
1/8" = 1'-0"1 MECHANICAL RENOVATION PLAN
RENOVATION KEY NOTES:
PROVIDE NEW CHILLER, CH-3. CONNECT TO EXISTING CHILLED AND CONDENSING WATER PIPING. CONNECT TO EXISTING REFRIGERANT VENT PIPING.
PROVIDE NEW COUPLING FOR EXISTING CONDENSER WATER PUMP, CP-3(E).
PROVIDE TEST AND BALANCE FOR NEW CHILLER, CH-3, EXISTING CONDENSER WATER PUMP, CP-3(E) AND EXISTING COOLING TOWER, CT-3(E).
CH-3
CH-2(E)
CH-1(E)
CHP-1
CHP-2
CHP-3
CT-3(E)
CT-2(E)
CT-1(E)
CP-3(E)
CP-2(E)
CP-1(E)
12"C
WS
12"CWR
12"C
WS
12"CWR
12"C
WS
12"CWR
10"C
HR 10"CHS
10"CHR
12"CHS
12"CHR
16"CHS
16"CHR
16"CHS
16"CHR
1 MECHANICAL 3D RENDERING
SHEET NUMBER
SHEET NAME
DATE:
REVISIONS
DRAWN BY:
CHECKED BY:
PROJECT #:
SHEET INFORMATION
SEAL
PROJECT INFORMATION
All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.
7600 Innovation Park Drive
Baton Rouge, LA 70820
225.332.0222 parisheng.com
M2.0
MECHANICAL PLAN 3D
CTD
LJB
06/13/2025
19-671-22-01
C H
IL
L
E R
R E
P L
A C
E M
E N
T C
E N
T R
A L
P L
A N
T S
U N
O N
E W
O R
L E
A N
S
L A
JUNCTION BOX
FUSED SAFETY DISCONNECT SWITCH; LOCATE WITHIN
SIGHT OF THE EQUIPMENT SERVED WITH 36" MINIMUM
CLEAR WORKING SPACE IN FRONT OF THE SWITCH; DO
NOT MOUNT DIRECTLY TO EQUIPMENT
JUNCTION BOX FOR MOTORIZED DAMPER
ELECTRICAL SYMBOL LEGEND
M
J
ABOVE-SLAB CONDUIT & WIRE/CABLING
BELOW-SLAB CONDUIT & WIRE/CABLING;
3/4" MINIMUM CONDUIT SIZE UON
GENERATOR REMOTE ANNUNCIATOR PANEL; PROVIDE
CONDUIT/CABLING TO GENERATOR AS REQUIRED PER
THE MANUFACTURER'S SPECIFICATIONS.
GEN-ANNC
PANELBOARD, SWITCHBOARD, OR OTHER DISTRIBUTION
EQUIPMENT AS NOTED; INSTALL WITH SUFFICIENT
WORKING SPACE AND CLEARANCES TO MEET ALL
REQUIREMENTS OF NEC SECTION 110.26.
GENERAL
KEYNOTE1
HOMERUN TO PANEL;
TICK MARKS INDICATED NUMBER OF WIRES
EQUIPMENT CONNECTIONS
MOTOR RATED SWITCH WITH THERMAL OVERLOAD; LOCATE
WITHIN SIGHT OF THE EQUIPMENT SERVED; DO NOT MOUNT
DIRECTLY TO EQUIPMENT; WHEN LOCATED ABOVE CEILING,
MOUNT TO STRUCTURAL MEMBER NEARBY.
M S
ELECTRICAL MOTOR, HORSEPOWER AS NOTED
WIRE, CONDUIT, AND RACEWAY
DISTRIBUTION
(REFER TO DRAWINGS AND SPECIFICATIONS FOR FURTHER REQUIREMENTS)
CIRCUIT TAG; PANEL AND CIRCUIT DESIGNATION
AS INDICATED; E.G. PANEL "A", CIRCUIT #1,3
A-1,3
(PROVIDE CONDUIT AND WIRE PER THE PANEL SCHEDULE)
ABBREVIATIONS
AMPERE(S)A
ABOVE COUNTER (6" ABOVE BACKSPLASH)AC
AMPERE(S) FUSEDAF
ARC FAULT CIRCUIT INTERRUPTERAFCI
ABOVE FINISHED FLOORAFF
ABOVE FINISHED GRADEAFG
AMPERE(S) TRIPAT
AMERICAN WIRE GAUGEAWG
BELOW GRADEBG
BUILDINGBLDG
BREAKERBKR
CONDUITC
CATEGORYCAT
CABLE TELEVISIONCATV
CIRCUIT BREAKERCB
CIRCUITCKT
CLGCLG
CORRIDORCORR
CURRENT TRANSFORMERCT
CONTROLLERCTRL
DISCONNECTDISC.
DISTRIBUTIONDIST.
DRAWINGDWG
EMPTY CONDUITEC
ENCLOSED CIRCUIT BREAKERECB
EXHAUST FANEF
EQUIPMENT GROUNDING CONDUCTOREGC
EMERGENCYEMER.
ELECTRICAL METALLIC TUBINGEMT
EQUALEQ
EQUIPMENTEQUIP.
ELECTRIC WATER COOLEREWC
ELECTRIC WATER HEATEREWH
EXISTINGEXIST.
FIRE ALARM CONTROL PANELFACP
FIRE ALARM CONTROL PANEL REMOTE ANNUNCIATORFACPRA
FOOTCANDLEFC
FAN COIL UNITFCU
FULL LOAD AMPERE(S)FLA
FIBER OPTIC CABLEFOC
GROUNDG, GND
GROUNDING ELECTRODE CONDUCTORGEC
GROUND FAULT CIRCUIT INTERRUPTERGFCI
GALVANIZED RIGID STEELGRS
HANDHOLEHH
HORSEPOWERHP
1,000 AMP SYMMETRICAL INTERRUPTING CAPACITY RMSKAIC
1,000 WATT HOURSKWH
1,000 VOLT AMPERESKVA
LOCAL AREA NETWORKLAN
LIGHTINGLTG
MINIMUM CIRCUIT AMPACITYMCA
MAIN CIRCUIT BREAKERMCB
1,000 CIRCULAR MILSMCM/KCMIL
MECHANICALMECH.
MANHOLEMH
MAIN LUGS ONLYMLO
MAXIMUM OVERCURRENT PROTECTIONMOCP
MOUNTEDMTD
MOUNTINGMTG
NATIONAL ELECTRICAL CODENEC
NEUTRALNEU
NOT IN CONTRACTNIC
NON-FUSEDNF
NORMALLY OPENNO
OVERHEADOH
OVERHEAD ELECTRICALOHE
OUTSIDE PLANTOSP
UTILITY POWER POLEUPP
PULL BOXPB
PHASEPH
PANELPNL
PHOTOVOLTAICPV
POLYVINYL CHLORIDEPVC
QUANTITYQTY
RECEPTACLERCPT
REQUIREDREQ'D
SUPPLY FANSF
SOLID NEUTRALS/N
SURGE PROTECTIVE DEVICESPD
STANDARDSTD
TELEPHONETEL
TELECOMMUNICATIONSTELECOM
TELECOMMUNICATIONS GROUND BUSTGB
TELECOMMUNICATIONS MAIN GROUND BUSTMGB
TELECOM TERMINAL BOARDTTB
TELEVISIONTV
TRANSIENT VOLTAGE SURGE SUPPRESSIONTVSS
TYPICALTYP.
UNIT HEATERUH
UNDERWRITER'S LABORATORY, INC.UL
UNDERGROUNDUG
UNDERGROUND PRIMARYUGP
UNDERGROUND SECONDARYUGS
UNLESS OTHERWISE NOTEDUON
VOLTSV
VOLTS ALTERNATING CURRENTVAC
VOLTS DIRECT CURRENTVDC
VARIABLE FREQUENCY DRIVEVFD
WATER HEATERWH
WEATHERPROOFWP
TRANSFORMERXFMR
EXISTING TO REMAINE
TO BE DEMOLISHEDD
LIGHTING CONTACTORLC
AMP SYMMETRICAL INTERRUPTING CAPACITY RMSAIC
NIGHT LIGHTNL
NORMALLY CLOSEDNC
WEATHERPROOF IN-USE COVERNU
ELECTRICAL GENERAL NOTES
1. ALL ELECTRICAL WORK SHALL BE DONE IN STRICT ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL
CODE AS ADOPTED BY THE AHJ.
2. THE WORDS "PROVIDE" AND "PROVIDED" AS USED HEREIN SHALL BE UNDERSTOOD TO MEAN, "PROVIDE COMPLETE IN PLACE," THAT IS "FURNISH AND INSTALL". EQUIPMENT AND MATERIAL INDICATED TO BE PROVIDED SHALL BE NEW UNLESS OTHERWISE NOTED AND SHALL BE OF THE MOST SUITABLE GRADE FOR THE PURPOSE INTENDED.
3. ROUTE NEW CONDUIT AND WIRING CONCEALED IN WALLS AND CEILING WHERE POSSIBLE. COORDINATE INSTALLATION OF
EXPOSED CONDUIT AND WIRING WITH THE ARCHITECT.
4. CONTRACTOR SHALL PROVIDE ELECTRICAL SERVICE TO NEW HVAC UNITS AS FURNISHED BY THE MECHANICAL CONTRACTOR. VERIFY THE EXACT ELECTRICAL REQUIREMENTS WITH THE REVIEWED HVAC SUBMITTALS PRIOR TO
ORDERING ELECTRICAL EQUIPMENT.
5. BEFORE INSTALLATION, CONTRACTOR SHALL SUBMIT DETAILED DRAWINGS TO THE ENGINEER FOR REVIEW COVERING PROPOSED LOCATIONS, MOUNTING, AND ROUTING FOR ALL CONDUITS, SERVICES, FITTINGS, GROUND RODS, SUPPORTS, ETC.
6. CONTRACTOR IS RESPONSIBLE FOR OVER-CURRENT PROTECTIVE DEVICE SHORT CIRCUIT, COORDINATION, AND ARC-
FLASH STUDIES.
7. MATERIALS AND MANUFACTURERS NOTED ON DRAWINGS ARE TO BE USED AS BASIS OF DESIGN TO ESTABLISH QUALITY AND PERFORMANCE STANDARDS AND SHALL BE PROVIDED AS SPECIFIED. SUBSTITUTIONS WILL BE CONSIDERED WHERE SUFFICIENT PRODUCT INFORMATION IS PROVIDED TO MAKE A PROPER EVALUATION. REVIEW OF A SUBSTITUTION IS AT
THE SOLE DISCRETION OF THE PROFESSIONAL.
8. THE CONTRACTOR SHALL SUBMIT COPIES OF THE PRODUCT DATA, SHOP DRAWINGS, ETC. OF ALL MATERIALS NOTED ON THE DRAWINGS. ALL SUBMITTED PRODUCT DATA, SHOP DRAWINGS, ETC. SHALL BE MARKED WITH THE NAME OF THE PROJECT AND SHALL BEAR THE STAMP OF APPROVAL OF THE CONTRACTOR AS EVIDENCE THAT THE MATERIAL HAS BEEN
CHECKED BY THE CONTRACTOR.
9. DRAWINGS SPECIFIC TO THIS TRADE DO NOT LIMIT THE RESPONSIBILITY OR WORK REQUIRED BY THE CONTRACT DOCUMENTS. REFER TO DRAWINGS AND SPECIFICATIONS OF OTHER TRADES FOR COMPLETE INFORMATION PRIOR TO BID.
10. WHERE CONFLICTS EXIST AMONG DRAWINGS, SPECIFICATIONS, AND EQUIPMENT SCHEDULES, THE MOST STRINGENT REQUIREMENT OR QUANTITY SHALL APPLY. NOTIFY THE ARCHITECT/ENGINEER OF ALL CONFLICTS FOR RESOLUTION OR
INTERPRETATION.
11. NO EQUIPMENT SHALL BE ORDERED OR INSTALLED UNTIL THE PROJECT ENGINEER HAS RECEIVED A COPY STAMPED "NO EXCEPTIONS TAKEN." "NO EXCEPTIONS TAKEN" DOES NOT RELIEVE THE CONTRACTOR FROM CONFORMANCE WITH THE CONTRACT, EXTEND TO QUANTITIES OR DIMENSIONS, IMPLY THAT THE EQUIPMENT CAN BE INSTALLED OR OPERATE SATISFACTORILY, THAT THE EQUIPMENT CONTAINS ALL NECESSARY COMPONENTS, OR THAT IT WILL COORDINATE WITH
OTHER REVIEWED ITEMS.
12. OMISSION FROM THIS SHEET OF ANY ITEM SHOWN ELSEWHERE IN THE PLANS DOES NOT RELIEVE THE CONTRACTOR
FROM THE RESPONSIBILITY FOR ANY ASSOCIATED WORK.
13. COORDINATE INSTALLATION OF NEW ITEMS AND EQUIPMENT WITH THE OWNER'S REPRESENTATIVE AND THE WORK OF OTHER TRADES. THE CONTRACTOR SHALL INCUR ALL COSTS ASSOCIATED WITH THE RELOCATION OF EQUIPMENT
CONFLICTING WITH NEW WORK BY OTHER TRADES THAT HAS NOT BEEN COORDINATED.
14. COORDINATE ALL ASPECTS OF NEW SERVICE WITH UTILITY COMPANY AND INCLUDE ALL COSTS IN BID.
15. WARNING TAPE SHALL BE INSTALLED 12 TO 18 INCHES BELOW GRADE OVER ALL CONDUITS.
16. PROVIDE 1/4" MINIMUM DIAMETER PULL ROPE. PULL ROPE SHALL NOT BE NYLON STRING.
17. FOR SERVICE ENTRANCE CONDUITS, UTILIZE LONG RADIUS (36") CONDUIT BENDS.
18. ALL CONDUIT RISERS FROM UNDERGROUND SHALL HAVE RIGID METAL ELLS AND RISERS.
19. PRIOR TO CONSTRUCTION, VERIFY THE LOCATION OF ALL EXISTING UNDERGROUND UTILITIES. AVOID DISTURBANCE OF
EXISTING UTILITIES NOT INCLUDED IN THIS PROJECT.
20. SET SCREW CONDUIT FITTINGS SHALL NOT BE PERMITTED.
SPECIAL SYSTEMS GENERAL NOTES
1. VERIFY EXACT LOCATION, VOLTAGE, PHASE, AMPERAGE, ETC. OF ALL MECHANICAL EQUIPMENT WITH MECHANICAL
CONTRACTOR PRIOR TO ORDERING ELECTRICAL GEAR.
DEMOLITION GENERAL NOTES
1. THE LOCATIONS OF EXISTING CIRCUITS AND EQUIPMENT ARE SHOWN IN AN APPROXIMATE WAY ONLY AND HAVE NOT BEEN INDEPENDENTLY VERIFIED BY THE OWNER OR ITS REPRESENTATIVE. THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXISTING ELECTRICAL DEVICES, EQUIPMENT, AND WIRING BEFORE COMMENCING WORK AND AGREES TO BE FULLY RESPONSIBLE FOR ANY AND ALL DAMAGES WHICH MIGHT BE CAUSE BY THE CONTRACTOR'S FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL EXISTING PORTIONS OF THE ELECTRICAL SYSTEMS.
2. THE CONTRACTOR SHALL REMOVE SUCH EXISTING WORK AS CALLED FOR ON THE DRAWINGS OR AS REQUIRED TO CLEAR
THE AREAS OF NEW CONSTRUCTION.
3. ALL EQUIPMENT REMOVED THAT IS NOT BEING REUSED SHALL REMAIN THE PROPERTY OF THE OWNER OR SHALL BE
DISPOSED OF AS REQUIRED.
4. EXCEPT AS OTHERWISE NOTED, ALL EXISTING ELECTRICAL WORK WHICH WILL NOT BE RENDERED OBSOLETE AND WHICH MAY BE DISTURBED DUE TO ANY CHANGES REQUIRED UNDER THIS CONTRACT, SHALL BE RESTORED TO ITS ORIGINAL OPERATING CONDITION. OTHER ELECTRICAL WORK OR MATERIAL RENDERED OBSOLETE SHALL BE ABANDONED WHERE CONCEALED AND REMOVED WHERE EXPOSED. OLD, UNUSED WIRING AND DEVICES SHALL BE REMOVED FROM THE ABANDONED (CONCEALED) CONDUITS. OUTLETS SHALL BE PROVIDED WITH BLANK COVERS. ANY CONDUITS STUBBED OUT
OF MASONRY SURFACE SHALL BE CUT INTO SURFACE AND PATCHED.
5. WHERE EXISTING ELECTRICAL WORK INTERFERES WITH NEW WORK AND WHERE SUCH INSTALLATIONS ARE TO REMAIN IN USE, THE INSTALLATIONS SHALL BE DISCONTINUED AND RELOCATED AND/OR RECONNECTED TO COORDINATE WITH THE
WORK INDICATED ON THE CONTRACT DRAWINGS AS SPECIFIED.
6. WHERE EXISTING RACEWAYS THAT ARE NOT TO BE REUSED INTERFERE WITH NEW WORK, THESE RACEWAYS SHALL BE
REMOVED BACK TO THE NEAREST JUNCTION BOX OR PULL BOX AND THE OPENINGS BLANKED.
7. CONTRACTOR SHALL MAINTAIN CONTINUITY OF BRANCH CIRCUITS SERVING MULTIPLE ITEMS OF WHICH ONE OR MORE ARE BEING DEMOLISHED. CONDUCTORS AND CONDUITS FOR THOSE ITEMS BEING DEMOLISHED SHALL BE REMOVED AS
FAR AS PRACTICABLE.
8. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO REMOVE ALL EXISTING ELECTRICAL EQUIPMENT AND DATA WIRING
NOT REUSED OR NOT NECESSARY FOR THE COMPLETION OF THIS PROJECT.
9. IF ANY BRANCH CIRCUIT WIRING FEEDING EQUIPMENT TO REMAIN IN PLACE FOR REUSE IS DAMAGED DURING CONSTRUCTION, THE CONTRACTOR SHALL REPLACE THE NEW BRANCH CIRCUIT WIRING OF THE SAME SIZE AND TYPE AS
THAT OF THE EXISTING AT NO COST TO THE OWNER.
10. EXISTING DEVICES ARE SHOWN IN GRAY. CONDUIT AND WIRING ARE NOT GENERALLY SHOWN AND SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. ADDITIONAL DEMOLITION WORK AND CLARIFICATION OF INDICATED WORK WILL BE
GIVEN BY RFI.
11. COORDINATE THE REMOVAL AND REINSTALLATION (OR PROTECTION IN PLACE) OF EXISTING ELECTRICAL EQUIPMENT AND DEVICES WITH THE WORK OF OTHER TRADES TO REPLACE OR REFINISH EXISTING WALLS AND CEILINGS.
12. WHERE EXISTING CIRCUITS ARE BEING REMOVED IN EXISTING PANELS, PROVIDE A NEW, NEATLY TYPED DIRECTORY WHICH INDICATES WHERE "SPARE" BREAKERS ARE LOCATED. ANY EXISTING BREAKERS THAT ARE NOT FEEDING DEVICES
SHALL REMAIN AND BE LABELED AS A "SPARE."
SHEET NUMBER
SHEET NAME
DATE:
REVISIONS
DRAWN BY:
CHECKED BY:
PROJECT #:
SHEET INFORMATION
SEAL
PROJECT INFORMATION
All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.
7600 Innovation Park Drive
Baton Rouge, LA 70820
225.332.0222 parisheng.com
E0.0
ELECTRICAL COVER SHEET
SPG
SPG
06/13/2025
19-671-22-01
C H
IL
L
E R
R E
P L
A C
E M
E N
T C
E N
T R
A L
P L
A N
T S
U N
O N
E W
O R
L E
A N
S
L A
ALL SYMBOLS, ABBREVIATIONS, AND NOTES ABOVE ARE TYPICAL AND ARE NOT NECESSARILY USED IN THESE CONSTRUCTION DOCUMENTS
INDEX - ELECTRICAL SHEETS
COVER COVER SHEET
E0.0 ELECTRICAL COVER SHEET
E1.0 ELECTRICAL DEMOLITION PLAN
E1.1 ELECTRICAL RENOVATION PLAN
4-Room
2923 ft²
5-Room
1844 ft²
6-Room
4947 ft²
7-Room
272 ft²
8-Room
55 ft²
10-Room
527 ft²
11-Room
1313 ft²
9-Room
49 ft²
CH-1(E) CH-2(E) CH-3(E)
CHP-1 CHP-2 CHP-3
CP-1(E)
CP-2(E)
CP-3(E)
CT-1(E)
CT-2(E)
CT-3(E)
EXISTING
CH-3
STORAGE
LOCATION
SHEET NUMBER
SHEET NAME
DATE:
REVISIONS
DRAWN BY:
CHECKED BY:
PROJECT #:
SHEET INFORMATION
SEAL
PROJECT INFORMATION
All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.
7600 Innovation Park Drive
Baton Rouge, LA 70820
225.332.0222 parisheng.com
E1.0
ELECTRICAL DEMOLITION
PLAN
SPG
SPG
06/13/2025
19-671-22-01
C H
IL
L
E R
R E
P L
A C
E M
E N
T C
E N
T R
A L
P L
A N
T S
U N
O N
E W
O R
L E
A N
S
L A
1/8" = 1'-0"1 ELECTRICAL DEMOLITION PLAN
ELECTRICAL DEMOLITION KEYNOTES
DISCONNECT EXISTING CHILLER. PROTECT EXISTING CONDUIT AND
WIRE DURING DEMOLITION.
CH-1(E) CH-2(E)
CP-1(E)
CP-2(E)
CP-3(E)
CT-1(E)
CT-2(E)
CT-3(E)
CH-3(E)
CHP-1(E) CHP-2(E) CHP-3(E)
CH-3
5-Room
1844 ft²
4-Room
2923 ft²
6-Room
4947 ft²
7-Room
272 ft²
8-Room
55 ft²
9-Room
49 ft²
10-Room
527 ft²
11-Room
1313 ft²
SHEET NUMBER
SHEET NAME
DATE:
REVISIONS
DRAWN BY:
CHECKED BY:
PROJECT #:
SHEET INFORMATION
SEAL
PROJECT INFORMATION
All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated, used, or disclosed without written consent of the engineer. Do not scale drawings. Contractor is responsible for verifying any and all quantities included in these documents when bidding and during construction.
7600 Innovation Park Drive
Baton Rouge, LA 70820
225.332.0222 parisheng.com
E1.1
ELECTRICAL RENOVATION
PLAN
SPG
SPG
06/13/2025
19-671-22-01
C H
IL
L
E R
R E
P L
A C
E M
E N
T C
E N
T R
A L
P L
A N
T S
U N
O N
E W
O R
L E
A N
S
L A
1/8" = 1'-0"1 ELECTRICAL RENOVATION PLAN
ELECTRICAL RENOVATION KEYNOTES
RECONNECT EXISTING CONDUIT AND WIRE TO NEW CHILLER "CH-3".
VERIFY THE ELECTRICAL REQUIREMENTS WITH THE CHILLER PROVIDER
PRIOR TO RECONNECTION.
| Sheets |
| COVER - COVER SHEET |
| M0.0 - MECHANICAL COVER SHEET |
| M1.0 - MECHANICAL DEMOLITION PLAN |
| M1.1 - MECHANICAL RENOVATION PLAN |
| M2.0 - MECHANICAL PLAN 3D |
File details come from the government source that posted it. Updated .