36C26119B0030-003.pdf
PDF 2 MB Posted
- Attached to
- 654-19-3-6059-0061 Replace CLC Transformer Federal contract opportunity
- Solicitation number
- 36C26119B0030
About this file
36C26119B0030 Project Combined Drawing.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C26119C0102-000.docx | DOCX document | |
| 36C26119B0030-0004000.docx | DOCX document | |
| 36C26119B0030-0003000.docx | DOCX document | |
| 36C26119B0030-0002000.docx | DOCX document | |
| 36C26119B0030-0001000.docx | DOCX document | |
| 36C26119B0030-0001001.pdf | ||
| 36C26119B0030-004.pdf | ||
| 36C26119B0030-006.docx | DOCX document | |
| 36C26119B0030-015.pdf | ||
| 36C26119B0030-007.docx | DOCX document | |
| 36C26119B0030-016.pdf | ||
| 36C26119B0030-013.pdf | ||
| 36C26119B0030-008.doc | DOC document | |
| 36C26119B0030-002.txt | TXT text file | |
| 36C26119B0030-009.pdf | ||
| 36C26119B0030-005.docx | DOCX document | |
| 36C26119B0030-014.pdf | ||
| 36C26119B0030-010.pdf | ||
| 36C26119B0030-001.docx | DOCX document | |
| 36C26119B0030-011.pdf | ||
| 36C26119B0030-012.pdf | ||
| 36C26119B0030-000.docx | DOCX document |
Show all 22
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
G-001
GENERAL INFORMATION
VA SIERRA NEVADA HEALTH CARE SYSTEM, RENO
REPLACE TRANSFORMER CLC
ARCHITECTURE ENGINEERING CONSTRUCTION
PROJECT NUMBER: 654-18-813
GENERAL NOTES
VA PROJECT TEAM
CONTRACTING OFFICER:
MEGAN BARR - CONTRACTING OFFICER
SIERRA PACIFIC NETWORK
NETWORK CONTRACTING OFFICE 21
3801 MIRANDA AVE. BLDG. T-50
PALO ALTO, CA 94304
DEPARTMENT OF VETERANS AFFAIRS
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVENUE
RENO, NV 89502
ABBREVIATIONS
EX EXISTING
(N) NEW
N.I.C. NOT IN CONTRACT
E.T.S. EXPOSED TO STRUCTURE
N.T.S. NOT TO SCALE
NTS NOT TO SCALE
SIM. SIMILAR
BLDG.A. BUILDING
PH. PHONE
INC. INCORPORATED
S. SOUTH
DL DEAD LEG
GPM GALLONS PER MINUTE
O.C. ON CENTER
FDC FIRE DEPARTMENT CONNECTION
DR. DRIVE
ST. STREET
CMU CONCRETE MASONRY UNIT
EQ. EQUAL
STL. STAINLESS
NR. NOT RATED
A.F.F. ABOVE FINISHED FLOOR
EJ EXPANSION JOINT
CJ CONTROL JOINT
Q.R.S QUICK RELEASE SPRINKLER
°F DEGREES FAHRENHEIT
ICRA INFECTION CONTROL RISK ASSESSMENT
PHASING
SEE PHASING PLAN ON SHEET C-102 FOR PHASING INFORMATION.
SITE PLAN
SIGNATURE BLOCK
MEDICAL CENTER DIRECTOR DATE
ASSOCIATE MEDICAL CENTER DIRECTOR DATE
CHIEF OF STAFF DATE
CHIEF, ENGINEERING SERVICES DATE
SAFETY OFFICER DATE
INDUSTRIAL HYGIENIST DATE
INFECTION CONTROL OFFICER DATE
PRESIDENT AFGE 2250 DATE
ASSOCIATE DIRECTOR PATIENT CARE SERVICES DATE
E-601 ELECTRICAL SINGLE-LINE DIAGRAM
1. CONTRACTOR SHALL VISIT ALL AREAS OF WORK, INCLUDING WALKING THE SITE, MEASURING EXISTING
DIMENSIONS AND OBSERVING EXISTING CONDITIONS BEFORE, ORDERING MATERIALS, OR STARTING ANY
CONSTRUCTION. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS OF EXISTING SITE CONDITION PRIOR TO
START OF WORK AND ORDERING OF MATERIALS.
2. CONTRACTOR SHALL RECYCLE REMOVED MATERIALS WHENEVER POSSIBLE.
SEE SPECIFICATION SECTION 01 74 19.
3. CONTRACTOR TO PROTECT AREA ADJACENT TO THE DEMOLITION AND NEW CONSTRUCTION WORK TO
PREVENT DAMAGES. (IF DAMAGED, REPAIR, RE-PATCH, SAND SMOOTH AND REFINISH TO MATCH EXISTING.)
ENERGY ENGINEER DATE
ELECTRICAL
E-001
ELECTRICAL LEGEND, NOTES, AND ABBREVIATIONS
INDEX OF DRAWINGS
DRAWING TITLEDWG NO.
GENERAL INFORMATION OF
SHEET OF #
G-001
GENERAL
1 1
CIVIL
C-101 EXISTING CONDITIONS AND SITE DEMOLITION PLAN
EP101 PROPOSED TRANSFORMER REPLACEMENT SITE PLAN
OF1 3
C-102 SITE PLANS OF2 3
C-103 SITE DETAILS OF3 3
OF1 3
OF2 3
OF3 3
AREA OF WORK
EAST TAYLOR STREET
L O
C U
S T
T R
E E
T
BURNS STREET
K I R
M A
N
A
V E
N U
E
BELLI DRIVE
NORTH
1 1
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
B C
D E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date# 04/05/2019
REPLACE TRANSFORMER
CLC
654-18-813
VA SIERRA NEVADA
HEALTH CARE SYSTEM
975 KIRMAN AVE., RENO, NV 89502
PROJECT DIRECTOR
18-284
BID DOCUMENTS
SES MJJ
DocuSign Envelope ID: 9573FDC9-2BF2-4E3F-8795-416EB88FAF9F
4/4/2019
C-101
EXISTING CONDITIONS AND SITE
DEMOLITION PLAN
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date# 04/05/2019
REPLACE TRANSFORMER
CLC
654-18-813
VA SIERRA NEVADA
HEALTH CARE SYSTEM
975 KIRMAN AVE., RENO, NV 89502
PROJECT DIRECTOR
18-284
BID DOCUMENTS
MJJ SES
DEMOLITION LEGEND
REMOVE CONCRETE
REMOVE FENCE
LIMITS OF DISTURBANCE
REMOVE TREE
DEMOLITION NOTES:
1. REFER TO SHEET G-001 FOR GENERAL NOTES.
2. REMOVE CONCRETE (WHERE REQUIRED) TO THE FIRST
COLD JOINT OR SAW CUT TO OBTAIN A CLEAN EDGE.
3. CLEANOUTS AND WATER VALVES LOCATED IN AREAS OF
DEMOLITION OR SUBSEQUENT CONSTRUCTION SHALL BE
PROTECTED FROM DAMAGE AND RAISED TO BE FLUSH
WITH NEW GRADE.
4. ANY UTILITY SERVICES SHOWN TO BE REMOVED OR
RELOCATED SHALL BE COORDINATED WITH THE
APPROPRIATE UTILITY PROVIDER. CONTRACTOR IS
RESPONSIBLE FOR APPROPRIATE SEQUENCING OF UTILITY
DEMOLITION WITH THE RESPECTIVE UTILITY AGENCIES.
5. VERIFY ALL UTILITIES PRIOR TO BEGINNING DEMOLITION
OPERATIONS.
6. CLEAN SOILS SHALL BE UTILIZED FOR BACKFILL.
COMPACTION OF THESE SOILS SHALL BE PERFORMED IN
ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS.
7. ALL ITEMS DESIGNATED TO BE REMOVED SHALL BE
REMOVED COMPLETELY, INCLUDING ALL SUBGRADE
MATERIALS DIRECTLY ASSOCIATED WITH ITEMS TO BE
REMOVED.
8. ALL ITEMS DESIGNATED TO BE REMOVED SHALL BE
DISPOSED OF LEGALLY OFF-SITE UNLESS OTHERWISE
NOTED ON THIS PLAN.
9. ALL DEMOLITION SHALL BE IN ACCORDANCE WITH ALL
APPLICABLE STATE AND LOCAL JURISDICTIONAL CODES OR
REQUIREMENTS.
10. ITEMS DESIGNATED TO BE SALVAGED AND/OR RE-USED
SHALL BE REMOVED BY THE CONTRACTOR AND PROVIDED
TO THE OWNER. COORDINATE STORAGE LOCATION WITH
OWNER'S REPRESENTATIVE.
11. REPAIR ALL DAMAGES TO THE EXISTING DRIVEWAY,
PARKING LOT, SIDEWALK AND CURB AND GUTTER AS A
RESULT OF CONSTRUCTION ACTIVITY AND TRAFFIC.
CONTRACTOR SHALL MAINTAIN A PRE-CONSTRUCTION
VIDEO OR PHOTO DOCUMENTATION TO SHOW NO DAMAGES
OCCURRED.
12. ALL MATERIALS, FURNISHINGS, UTILITIES, AND PAVEMENT
THAT ARE NOT SCHEDULED TO BE DEMOLISHED AND ARE
DAMAGED BY THE CONTRACTOR AS A RESULT OF THE
DEMOLITION OR CONSTRUCTION OPERATIONS SHALL BE
REPAIRED BY THE CONTRACTOR AT NO ADDITIONAL COST
TO THE OWNER.
13. WHERE UTILITIES ARE SHOWN TO BE "REMOVED",
CONTRACTOR SHALL INCLUDE NECESSARY PLUG OR
VALVES TO ENSURE UTILITY LINES TO REMAIN WILL
CONTINUE TO BE IN SERVICE. COORDINATE NECESSARY
SHUT DOWN AND REMOVAL WITH THE LOCAL JURISDICTION
OR UTILITY OWNER.
14. PROVIDE PEDESTRIAN INGRESS / EGRESS TO ALL EXISTING
BUILDINGS, PARKING LOTS, AND PATHS OF PEDESTRIAN
TRAVEL THROUGHOUT THE CONSTRUCTION PERIOD
STORM DRAIN MANHOLE
SANITARY SEWER MANHOLE
ELECTRIC MANHOLE
UNDERGROUND TELEPHONE LINE
UNDERGROUND GAS LINE
UNDERGROUND ELECTRIC LINE
UNDERGROUND WATER LINE
SANITARY SEWER LINE
STORM DRAIN LINE
UNIDENTIFIED LINE
DIP
PVC
HDPE
RCP
CMP
MH
T
G
E
W
SS
U
DUCTILE IRON PIPE
POLYVINYL CHLORIDE PIPE
HIGH-DENSITY POLYETHYLENE PIPE
REINFORCED CONCRETE PIPE
CORRUGATED METAL PIPE
MANHOLE
UNKNOWN DESTINATION
EXISTING
CHAIN LINK FENCE
CONCRETE SURFACE
SURVEY LEGEND:
EXISTING BUILDING
COLUMN (TYP.)
EXISTING TREE
STUMP
SD
TELECOMMUNICATION MANHOLE
UNFINISHED DIRT
SURFACE
EXISTING SANITARY CLEAN
OUT TO REMAIN.
VERIFY LOCATION IN THE FIELD.
EXISTING DRAINAGE
VALVE
REMOVE EXISTING
ACCESS RESTRICTION
FENCE AND GATE.
EXISTING FENCE AND FENCE POST
TO REMAIN
REMOVE AND RETAIN EXISTING
GATE FOR REINSTALLATION
SAW CUT EXISTING CONCRETE
AT NEAREST SCORE JOINT
SAW CUT EXISTING CONCRETE TO ALIGN
WITH EXISTING EDGE OF CONCRETE
EXISTING TRANSFORMER
AND PAD TO REMAIN
(E) GENERATOR #5
(E) GENERATOR
(E)
SS MH
0.00'
(E)
E MH
(E)
T MH
E
E
M
H
(E)
SD MH
(E) TRANSFORMER
T7
(E) BLDG. 1
(E) 5000 GAL. DIESEL
FUEL STORAGE TANK
(E) COURTYARD
(E) BUILDING 10
ELECTRIC ROOM
(E) BUILDING 10
(E)
TRANSFORMER
T14
(E) TREE
UNFINISHED DIRT
SURFACE
ADJUST RIM ELEVATION TO MATCH
PROPOSED CONCRETE PAVING
REMOVE AND RETAIN EXISTING DRAINAGE
VALVE FOR INSTALLATION
IN NEW SPILL CONTAINMENT CURB
(SEE 1 / C-102 FOR LOCATION)
(E) GENERATOR #5
(E) GENERATOR #9
(E) GENERATOR
PAD
(E)
SS MH
0.00'
(E)
E MH
(E)
T MH
E
E
M
H
(E)
SD MH
(E) TRANSFORMER
T7
(E) BLDG. 1
NORTH
(E) CONCRETE PAVING
MAIN COURTYARD
(E) 5000 GAL. DIESEL
FUEL STORAGE TANK
E
E
M E
R G
E N
C Y
G
E N
E R
A T
O R
R
O O
M
(E) COURTYARD
(E) BUILDING 10
ELECTRIC ROOM
(E) BUILDING 10
(E)
TRANSFORMER
T14
(E) TREE
REMOVE EXISTING TREE STUMP
AND ROOT BALL TO A DEPTH OF
2 FEET
AFTER NEW TRANSFORMER IS
OPERATIONAL, DE-ENERGIZE
TRANSFORMER AND REMOVE
TRANSFORMER, CONCRETE PAD, AND
PRIMARY CONDUCTOR AND CONDUIT
(E) GENERATOR #5
(E) GENERATOR
(E)
SS MH
0.00'
(E)
E MH
(E)
T MH
E
E
M
H
(E)
SD MH
(E) TRANSFORMER
T7
(E) BLDG. 1
(E) 5000 GAL. DIESEL
FUEL STORAGE TANK
(E) COURTYARD
(E) BUILDING 10
ELECTRIC ROOM
(E) BUILDING 10
(E)
TRANSFORMER
T14
(E) TREE
PHASE 1 PROPOSED SITE IMPROVEMENTS
(SEE SHEET 1/C-102)
DocuSign Envelope ID: 2CDC020E-F149-41CA-8EB5-658FC3A58A1F
4/5/2019
C-102
SITE PLANS
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date# 04/05/2019
REPLACE TRANSFORMER
CLC
654-18-813
VA SIERRA NEVADA
HEALTH CARE SYSTEM
975 KIRMAN AVE., RENO, NV 89502
PROJECT DIRECTOR
18-284
BID DOCUMENTS
MJJ SES
NORTH
NORTH
SITE LEGEND
PROPOSED CONCRETE PAVING
PROPOSED FENCE
LIMITS OF DISTURBANCE
SITE NOTES:
1. INSTALL AND MAINTAIN THE CONSTRUCTION LAYDOWN AREA,
PERIMETER FENCE, AND ASSOCIATED GATES. REMOVE THE
CONSTRUCTION LAYDOWN AREA PERIMETER FENCE AND
ASSOCIATED GATES AT THE COMPLETION OF THE PROJECT.
2. REFERENCE THE DESIGN PLANS FOR DIMENSIONS, JOINT
LOCATIONS, AND INLAY SPECIFICATIONS NEAR BUILDINGS AND
IN COURTYARDS. PROVIDE JOINTS IN WALKWAYS AND
HARDSCAPE PER DETAILS OR AS INDICATED ON
LANDSCAPE/HARDSCAPE PLAN SHEETS.
3. ALL DIMENSIONS ARE IN DECIMAL FEET TO OUTSIDE FACE OF
BUILDINGS, TO CENTERLINES, AND/OR FACE OF CURB UNLESS
OTHERWISE NOTED.
4. VERIFY ALL DIMENSIONS AND COORDINATES AND REPORT ANY
DISCREPANCIES TO THE OWNER'S REPRESENTATIVE PRIOR TO
ANY CONSTRUCTION.
5. ALL WRITTEN DIMENSIONS SHALL PREVAIL. DO NOT SCALE
FROM DRAWINGS.
6. ALL UTILITIES WITH SURFACE ACCESS SHALL BE LOCATED
WITHIN THE PAVING PATTERN AND SHALL BE COORDINATED
WITH LANDSCAPE ARCHITECT PRIOR TO CONSTRUCTION.
REFER TO LAYOUT DRAWINGS.
7. ALL ANGLES ARE 90 DEGREES UNLESS OTHERWISE NOTED.
8. ALIGN ALL JOINTS, CORNERS, AND EDGES AS SHOWN
9. REFER AND COORDINATE WITH MEP DRAWINGS AT ALL TIMES
PRIOR TO AND DURING CONSTRUCTION.
10. WHERE NEW CONCRETE PAVING ADJOINS EXISTING
CONCRETE PAVING, PROVIDE EXPANSION JOINT BY DRILLING
INTO THE FACE OF THE EXISTING WALK FOR PLACEMENT OF
DOWELS.
11. MAXIMUM RUNNING SLOPE FOR WALKING SURFACES CANNOT
BE GREATER THAN 1:20 AND CROSS SLOPES CANNOT BE
GREATER THAN 1:48.
(E) TRANSFORMER
T7
(E) TREE
7.50'
0.50'
NEW TRANSFORMER AND
PRECAST TRANSFORMER PAD,
SEE ELECTRICAL SHEETS
FOR DETAILS
4" HEIGHT CONCRETE CURB
7.25'
CONTRACTOR TO VERIFY THAT THE
LOCATION OF THE PROPOSED CURB
DOES NOT OVERLAP THE EXISTING
TELECOM VAULT.
EXISTING TRANSFORMER SHALL
REMAIN ENERGIZED UNTIL NEW
TRANSFORMER HAS BEEN INSTALLED.
EXISTING TELECOMMUNICATION LINE.
VERIFY LOCATION IN FIELD PRIOR TO CONSTRUCTION.
2% SLOPE
M
I N
ALIGN OUTSIDE EDGE OF CURB WITH
THE CENTER OF THE ELECTRICAL MANHOLE
PROTECT EXISTING SANITARY SEWER
CLEAN OUT IN PLACE.
3.50'
3.50'
E Q
E Q
L O
P E
EMBED SALVAGED DRAINAGE VALVE IN
CONCRETE CURB AT LOW POINT
OF CONCRETE SLAB (SEE DETAIL 6 / C-103)
X
X
X
X
X
X
X
X
X
DOWELLED
EXPANSION JOINT
(SEE DETAIL 4/C-103)
4" HEIGHT
CONCRETE
CUR0B
(SEE DETAIL
5 / C-103)
MATCH EXISTING GRADE
MATCH EXISTING GRADE
MATCH EXISTING GRADE
MATCH EXISTING GRADE
FENCE AND GATE SHALL ALIGN
WITH EXISTING FENCE POST AND FENCE
EXISTING FENCE GATE,
TO BE REINSTALLED
EXISTING FENCE AND POST
2% SLOPE
2% SLOPE
12.54'
24.68'
CONCRETE PAD TO MATCH
EXISTING CONCRETE PAVING
EXISTING CONCRETE
PAVING TO REMAIN
1.00'
4.01'
4.01'
3.01'
3.50'
4.00'
4.65'
ALIGN JOINT WITH
CENTER OF MANHOLE
ALIGN JOINT WITH EXISTING
CONCRETE SIDEWALK CORNER
ALIGN JOINT WITH
CENTER OF GATE POST
ALIGN JOINTS WITH
CORNER OF CURB
ALIGN JOINTS WITH
CORNER OF CURB
ALIGN JOINTS WITH
CENTER OF MANHOLE
ADJUST TELECOMMUNICATION MANHOLE
RIM ELEVATION TO BE FLUSH WITH PROPOSED CONCRETE
C-103
SITE DETAILS
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date# 04/05/2019
REPLACE TRANSFORMER
CLC
654-18-813
VA SIERRA NEVADA
HEALTH CARE SYSTEM
975 KIRMAN AVE., RENO, NV 89502
PROJECT DIRECTOR
18-284
BID DOCUMENTS
MJJ SES
SECTION
= 1'-0"
CONCRETE PAVING
SECTION
= 1'-0"3"
CONCRETE PAVING JOINTS
SECTION
= 1'-0"
DOWELLED EXPANSION JOINT
SECTION
= 1'-0"3"
PHASE 1 TO PHASE 2 CONCRETE JOINT
SECTION
= 1'-0"3"
CONCRETE CURB
SECTION
= 1'-0"3"
DRAINAGE VALVE
DOWELED EXPANSION
JOINT (SEE DETAIL 1 / C904)
THICKENED CONCRETE
EDGE
9.00'9.00'
CABC
COMPACTED SUBGRADE
CONCRETE PAVING
(SEE DETAIL #/C-103)
CABC (TYP.)
COMPACTED SUBGRADE
1/2" EXPANSION JOINT (TYP.)
#4 X 12" SS GREASED DOWEL @ 18" O.C.
PLASTIC SLEEVE AT ONE END. (TYP.),
CENTER VERTICALLY.
CONCRETE PAVING
CABC BASE
COMPACTED SUBGRADE
4,000 PSI AIR-ENTRAINED CONCRETE SLAB
LIGHT BROOM FINISH
PAVING JOINTS (TYP.)
(SEE DETAIL 4 / C103)
PREMOLDED ASPHALT IMPREGNATED
FIBER, FULL DEPTH. (RECESSED
1/2" W @ 4" AND 8" CONCRETE
END REBAR 1" FROM EDGE
1"
EXPANSION JOINT
CABC BASE
" WIDE SAW CUT CONTROL JOINT
JOINT DEPTH EQUAL TO
OF THE
DEPTH OF CONCRETE
NOTE:
1) PROVIDE AN EXPANSION JOINT EVERY 60' (MIN.).
2) REFER TO PLAN FOR LAYOUT AND SPACING OF JOINTS.
3) EXPANSION JOINTS SHALL OCCUR AT ALL AREAS WHERE PAVEMENT MEETS WALLS / VERTICAL SURFACE
AND AT ALL COLD JOINTS.
CONCRETE PAVING (TYPE AND FINISH
VARIES, SEE SITE PLANS)
COMPACTED
SUBGRADE
DEPTH
VARIES
(SEE
MATERIALS
PLANS)
CONCRETE CURB
CONCRETE PAVING
(SEE DETAIL 1 / C-103
6"
R
T
Y
P
EXPANSION JOINT
(SEE DETAIL 2 / C-103
SPILL CONTAINMENT
AREA
CONCRETE CURB
CONCRETE PAVING
(SEE DETAIL 1 / C-103
SPILL CONTAINMENT
AREA
SALVAGED DRAINAGE VALVE
FROM EXISTING SPILL CONTAINMENT
CURB
1 4
1 4
E-001
ELECTRICAL LEGEND, NOTES,
& ABBREVIATIONS
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date# 04/05/2019
REPLACE TRANSFORMER
CLC
654-18-813
VA SIERRA NEVADA
HEALTH CARE SYSTEM
975 KIRMAN AVE., RENO, NV 89502
PROJECT DIRECTOR
18-284
BID DOCUMENTS
CAS MJJ
Δ DELTA
1PH SINGLE-PHASE
1P SINGLE POLE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE-PHASE
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC FREQUENCY
CONTROL, OR AVAILABLE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB AMBIENT
AMP OR A AMPERE
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BATT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISH FLOOR
BFG BELOW FINISH GRADE
BLDG BUILDING
BPIP BOILER PLANT INSTRUMENTATION PANEL
BRKR BREAKER
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATE
CAP CAPACITY
CATV COMMUNITY ANTENNA TELEVISION
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAX CABLE
COMM COMMUNICATION
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
CUR CURRENT
D DEEP / DEPTH
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EX, EXIST EXISTING
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FLA FULL LOAD AMPS
FMC FLEXIBLE METALLIC CONDUIT
FP FIRE PROTECTION
FT FEET OR FOOT
FS FUSED SWITCH
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G OR GND GROUND
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GRS GALVANIZED RIGID STEEL
GTB GROUND TERMINAL BOX
H HIGH / HEIGHT
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
J-BOX JUNCTION BOX
kV KILOVOLT kVA KILOVOLT AMPERE kVAH KILOVOLT AMPERE PER HOUR kW KILOWATT kWH KILOWATT HOUR kWHM KILOWATT HOUR METER
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LRA LOCKED ROTOR AMPS
LTCP LOCAL TEMPERATURE CONTROL PANEL
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT OR MICROWAVE
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NEUT OR N NEUTRAL
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, PULL BOX, OR PUSHBUTTON
PCB POLYCHLORINATED BIPHENYL
PC PHOTOELECTRIC CELL
PF POWER FACTOR
PH PHASE
PNL PANEL
POD POWER OPERATED DAMPER
POS POSITION
PRI, PRIM PRIMARY
PVC POLYVINYL CHLORIDE (PLASTIC)
REC RECESSED
RECPT RECEPTACLE
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
REQD REQUIRED
SCC SHORT CIRCUIT CAPACITY
SEC SECONDARY
SES SERVICE ENTRANCE SECTION
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
W WATT OR WIDTH IN DIMENSION STRING
WH WATER HEATER
WP WEATHERPROOF
WQMP WATER QUALITY MONITORING PANEL
XFER TRANSFER
XFMR TRANSFORMER
1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL
BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS,
THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE
LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT, THE
LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, AND THE VA
STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT
AND FEEDERS WHERE THE BUILDING CONSTRUCTION IS NOT SUITABLE
FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR
SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS,
FLOORS, CEILINGS AND ROOFS IN ACCORDANCE WITH THE
REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTINGS
REQUIREMENT AND THE APPLICABLE BUILDING CODES.
4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES,
TRIMS AND ALL REQUIRED MOUNTING HARDWARE TO SUIT THE
PARTICULAR INSTALLATION.
5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES
DURING CONSTRUCTION.
6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO
INSTALLATION SO AS TO AVOID CONFLICT DURING CONSTRUCTION.
8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES.
9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR
DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE
NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER.
PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE
ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".
10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL,
BREAKER OR PARTICULAR EQUIPMENT MANUFACTURER'S
SPECIFICATIONS.
11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES
SHALL BE TERMINATED ON THE DEVICE'S SCREW TERMINALS.
12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET,
FIXTURE, OR EQUIPMENT UNLESS NOTED OTHERWISE.
13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS
OTHERWISE NOTED.
15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC
CONDUIT MAY BE USED ON VIBRATING EQUIPMENT.
16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT
SHALL BE LABEL LISTED BY AN APPROVED THIRD PARTY TESTING
AGENCY.
17. DIMENSIONS, QUANTITIES AND LOCATIONS OF EXISTING CONDUIT AND
EQUIPMENT AS SHOWN ON THESE DRAWINGS ARE BASED ON RECORD
DRAWINGS AND CASUAL OBSERVATION AND ARE NOT NECESSARILY
COMPLETELY ACCURATE. CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING ANY AND ALL EXISTING EQUIPMENT AND CONDITIONS THAT
MIGHT AFFECT THE WORK.
18. EQUIPMENT AND SUPPORTS/ANCHORING SUBMITTED SHALL BE
CERTIFIED TO MEET OR EXCEED SEISMIC FORCES (SPECTRAL RESPONSE
ACCELERATION) FOUND AT THE PROJECT LOCATION AS DEFINED BY THE
VA SEISMIC DESIGN REQUIREMENTS H 18-8. FOR THE RENO FACILITY:
Ss = 1.833g
S1 = 0.618g
J
J
S
VFD
ELECTRICAL LEGEND
E
JUNCTION BOX, PURPOSE AS NOTED
JUNCTION BOX IN WALL, PURPOSE AS NOTED:
18" AFF STANDARD UNO
DISCONNECT SWITCH NON-FUSED
DISCONNECT SWITCH FUSED
SWITCH: 44" AFF STANDARD UNO
SWITCH MODIFIERS:
M - MOTOR RATED
3 - THREE-WAY
LV - LOW -VOLTAGE (0-10V) DIMMER
PANELBOARD
VARIABLE FREQUENCY DRIVE, PROVIDED BY MECHANICAL
CONTRACTOR
EQUIPMENT ELECTRICAL CONNECTION
HOMERUN - 120V OR 277V
HOMERUN - 208V OR 480V
120V DUPLEX RECEPTACLE: 18" AFF STANDARD, UNO
RECEPTACLE MODIFIERS:
GFCI - GROUND FAULT CIRCUIT INTERRUPTER
WP - WEATHERPROOF
DED - DEDICATED
TELEPHONE OUTLET
K
KIRK-KEY MANUAL INTERLOCK
CABLE TRAY
CONNECTION POINT FOR NEW TO EXISTING
CONDUIT, CABLE TRAY, JUNCTION BOXES ETC.
POINT OF DEMOLITION FOR EXISTING
CONDUIT, CABLE TRAY, JUNCTION BOXES ETC.
UNDERGROUND ELECTRICALUGE
PM
POWER METER/MONITOR
CONTACTOR OR MOTOR STARTER
FIRE SYSTEM SMOKE DETECTOR AS INDICATED
LOAD BREAK JUNCTION
GENERAL NOTES ELECTRICAL ABBREVIATIONS
__A/__F/_P
___V N__
DISCONNECT SWITCH RATINGS
(AMP RATING / FUSE RATING / NUMBER OF POLES
VOLTAGE CLASS / NEMA RATING)
VS
VACANCY SENSOR, DUAL TECHNOLOGY - CEILING MOUNTED
SHORT CIRCUIT CURRENT CALCULATIONS WILL BE PERFORMED ON THE
ELECTRICAL SYSTEM USING A BOLTED THREE-PHASE FAULT CONDITION FOR
CALCULATIONS TO ACHIEVE MAXIMUM THERMAL AND MECHANICAL STRESS
TO THE SYSTEM FOR CALCULATION PURPOSES. EXISTING SHORT CIRCUIT
VALUES WILL BE USED OUTSIDE THE WORK AREA FOR THE STARTING POINT
OF THE CALCULATIONS.
METHOD OF SHORT CIRCUIT
CURRENT CALCULATIONS
USING OHM'S LAW AND THE KNOWN RESISTIVITY CONSTANT OF CONDUCTOR
METAL (CIRCUILAR MIL-OHM PER FOOT) FOR COPPER CONDUCTORS, OUR
INTENT IS TO CALCULATE THE REQUIRED WIRE SIZE NECESSARY SO AS NOT
TO EXCEED THE RECOMMENDED VOLTAGE-DROP OF 3% FOR BRANCH
CIRCUIT CONDUCTORS.
METHOD OF VOLTAGE-DROP
CALCULATIONS
UNDERGROUND ELECTRICAL
EP101
PROPOSED TRANSFORMER
REPLACEMENT SITE PLAN
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
SHEET KEY NOTES:
04/05/2019
REPLACE TRANSFORMER
CLC
654-18-813
VA SIERRA NEVADA
HEALTH CARE SYSTEM
975 KIRMAN AVE., RENO, NV 89502
PROJECT DIRECTOR
18-284
BID DOCUMENTS
CAS MJJ
NORTH
NORTH NORTH
38"
(36" MIN.)
X
XX
X
X
X
X
X
X
X X
X X
X X
X X
X
X
X
XX
X X
X X
X X
X X
X
E-601
ELECTRICAL
SINGLE-LINE DIAGRAM
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
SHEET KEY NOTES:
04/05/2019
REPLACE TRANSFORMER
CLC
654-18-813
VA SIERRA NEVADA
HEALTH CARE SYSTEM
975 KIRMAN AVE., RENO, NV 89502
PROJECT DIRECTOR
18-284
BID DOCUMENTS
CAS MJJ 3
| G-001 |
| Sheets and Views |
| G-001 |
| C-101 |
| C-102 |
| C-103 |
| E-001 |
| Sheets and Views |
| E-001 |
| EP101 |
| Sheets and Views |
| EP101 |
| E-601 |
| Sheets and Views |
| E-601 |