Fire Damper Inspection.pdf

PDF 813 KB Posted

Attached to
J063--Fire/Smoke Damper Repair/Inspection Federal contract opportunity
Solicitation number
36C25924Q0022
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19

About this file

This document is a fire and smoke damper inspection report for the Jack C Montgomery VA Medical Center conducted in 2023. The report details inspections of 104 dampers across various buildings and floors at the facility, with results including 19% failing inspection, 17% unable to be tested, and 64% passing. Notable issues found include inaccessible dampers, dampers not attached properly, and dampers that did not fully close when power was removed. The related federal contract opportunity is solicitation number 36C25924Q0022 for fire/smoke damper repair and inspection services at the Jack C Montgomery VA Medical Center, issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19. The solicitation seeks these repair and inspection services to address the deficiencies identified in the damper inspection report.

View the file

Other files for this federal contract opportunity

Other files attached to J063--Fire/Smoke Damper Repair/Inspection, newest first.
File Type Posted
RFQ 36C25924Q0022 Amendment 0001 Fire-Smoke Damper Repairs MUS.pdf PDF
36C25924Q0022.docx DOCX document
FireDampReq6YrTesting.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FIRE/SMOKE DAMPER

INSPECTION REPORT

Jack C Montgomery VA Medical Center

1011 Honor Heights Dr Muskogee, OK. 74401

Veterans Fire & Life Safety 7 Sherri Ln.

St. Peters, MO. 63376

Jack C Montgomery VA Medical Center 1011 Honor Heights Dr Muskogee, OK. 74401 ATTN: Gary Ridenour

On Aug.23,2023, Veterans Fire & Life Safety conducted a thorough fire/smoke damper inspection at Jack C Montgomery VA Medical Center.

This inspection was completed by Anthony Monzon, a certified life safety inspector, using the 2012 edition of NFPA 101, as well as the latest edition of the VA Health facility code. This inspection is required every 4 years with the exception of hospitals which is every 6 years. The Life Safety plans were not provided for this inspection.

Veterans Fire & Life Safety nor Anthony Monzon are representatives of any damper manufacturer or supplier of dampers or hardware. The following report describes the condition of the dampers at the facility on the date of the inspection. Veterans Fire & Life Safety nor Anthony Monzon can warrant the future operation or condition of the dampers.

Please do not hesitate to contact us with any questions you may have regarding this report or the codes referenced. Thank you for the opportunity to complete this inspection for you.

Sincerely, Anthony Monzon

7 Sherri Ln.

St. Peters, MO. 63376

Red- Fail 19%

Yellow - N/A 17%

Green - Passed 64%

Inspection Results

Red- Fail Yellow - N/A Green - Passed

Total Dampers Inspected Total Dampers without

Deficiencies Total Dampers with

Deficiencies N/A – Dampers Unable to be tested 104 66 20 18

BUILDING FLOOR INSPECTION DATE

FACILITY

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

53/1 6 Aug.22,2023 FSD001 Building 53, 6A-101 Mechanical Fire

Pass

53/1 6 Aug.22,2023 FSD002 Building 53, 6A-101 Mechanical Fire

Fail Unable to access damper.

Door has been sealed with fire caulk.

53/1 5 Aug.22,2023 FSD003 Building 53 Interstitial Mechanical Fire

Pass

53/1 5 Aug.22,2023 FSD004 Building 53 Interstitial Mechanical Fire

Pass

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Jack C Montgomery VA Medical Center

53/1 5 Aug.22,2023 FSD005 Building 53 Interstitial Mechanical Fire

NA See Additional Notes. No damper installed

53/1 5 Aug.22,2023 FSD006 Building 53 Interstitial Mechanical Fire

Pass

53/1 5 Aug.22,2023 FSD007 Building 53 Interstitial Mechanical Fire

Pass

53/1 5 Aug.22,2023 FSD-008 Building 53 Interstitial Mechanical Fire

Pass

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Jack C Montgomery VA Medical Center

53/1 5 Aug.22,2023 FSD009 Building 53 Interstitial Pneumatic Damper

Pass

53/1 5 Aug.22,2023 FSD010 Building 53 Interstitial Pneumatic Damper

Pass

53/1 5 Aug.22,2023 FSD011 Building 53 Interstitial Mechanical Fire

Pass

53/1 5 Aug.22,2023 FSD012 Building 53 Interstitial Mechanical Fire

Fail Unable to access damper.|See Additional Notes.

Unable to access damper due to obstructions in path. Cardinal NE

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Jack C Montgomery VA Medical Center

53/1 5 Aug.22,2023 FSD013 Building 53 Interstitial Pneumatic Damper

Pass

53/1 5 Aug.22,2023 FSD014 Building 53 Interstitial Mechanical Fire

Pass

53/1 5 Aug.22,2023 FSD015 Building 53 Interstitial Mechanical Fire

Fail Unable to access damper.|See Additional Notes.

Access door has been removed.

53/1 5 Aug.22,2023 FSD016 Building 53 Interstitial Pneumatic Damper

Fail

Damper did not close when power was removed from the actuator.|See Additional

Notes.

Damper did not close when power was removed from the actuator.

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Jack C Montgomery VA Medical Center

53/1 4 Aug.22,2023 FSD017 Building 53 Interstitial Pneumatic Damper

Pass

53/1 4 Aug.22,2023 FSD018 Building 53 Interstitial Pneumatic Damper

Fail

Damper did not close when power was removed from the actuator.|See Additional

Notes.

Damper did not close when power was removed from the actuator.

53/1 4 Aug.22,2023 FSD019 Building 53 Interstitial Mechanical Fire

Pass

53/1 4 Aug.22,2023 FSD020 Building 53 Interstitial Mechanical

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Jack C Montgomery VA Medical Center

53/1 4 Aug.22,2023 FSD021 Building 53 Interstitial Pneumatic Damper

Pass

53/1 4 Aug.22,2023 FSD022 Building 53 Interstitial Pneumatic Damper

Pass

53/1 4 Aug.22,2023 FSD023 Building 53 Interstitial Mechanical Fire

Pass

53/1 4 Aug.22,2023 FSD024 Building 53 Interstitial Mechanical

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Jack C Montgomery VA Medical Center

53/1 3 Aug.22,2023 FSD025 Above O.R. 4 Mechanical Fire

Fail See Additional Notes.

Damper not attached to actuator or fusible link.

53/1 3 Aug.22,2023 FSD026 Above O.R. 2 Mechanical Fire

Fail See Additional Notes.

Damper not attached to actuator or fusible link.

53/1 3 Aug.22,2023 FSD027 Above O.R. 3 Mechanical Fire

Fail

Damper not attached to actuator or fusible link.

53/1 3 Aug.22,2023 FSD028 Above O.R.s Mechanical

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Jack C Montgomery VA Medical Center

53/1 3 Aug.22,2023 FSD029 Above O.R. 1 Mechanical Fire

Fail

Damper not attached to actuator or fusible link.

53/1 3 Aug.22,2023 FSD030 Above O.R.s Mechanical Fire

Pass

53/1 3 Aug.22,2023 FSD031 Above O.R.s Mechanical Fire

Pass

53/1 4 Aug.22,2023 FSD032 Building 53 Interstitial Mechanical

Fail No Access Door Installed.

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Jack C Montgomery VA Medical Center

53/1 4 Aug.22,2023 FSD033 Building 53 Interstitial Mechanical Fire

Pass

53/1 4 Aug.22,2023 FSD034 Building 53 Interstitial Mechanical Fire

Pass

53/1 4 Aug.22,2023 FSD035 Building 53 Interstitial Mechanical Fire

Fail Unable to access damper.|See Additional Notes.

Unable to access damper due to door being blocked.

53/1 4 Aug.22,2023 FSD036 Building 53 Interstitial Mechanical Fire

Fail See Additional Notes.

Unable to close damper due to fasteners on the track

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Jack C Montgomery VA Medical Center

53/1 4 Aug.22,2023 FSD037 Building 53 Interstitial Mechanical Fire

Pass

53/1 5 Aug.22,2023 FSD038 Building 53 Interstitial Mechanical Fire

Fail No Access Door Installed.

53/1 3 Aug.23,2023 FSD039 Building 53 Interstitial Mechanical Fire

Pass

53/1 3 Aug.23,2023 FSD040 Building 53 Interstitial Mechanical

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Jack C Montgomery VA Medical Center

53/1 3 Aug.23,2023 FSD041 Building 53 Interstitial Mechanical Fire

Pass

53/1 3 Aug.23,2023 FSD042 Building 53 Interstitial Mechanical Fire

Pass

53/1 3 Aug.23,2023 FSD043 Building 53 Interstitial Mechanical Fire

Pass

53/1 3 Aug.23,2023 FSD044 Building 53 Interstitial Pneumatic Damper

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Jack C Montgomery VA Medical Center

53/1 3 Aug.23,2023 FSD045 Building 53 Interstitial Pneumatic Damper

Pass

53/1 3 Aug.23,2023 FSD046 Building 53 Interstitial Pneumatic Damper

Pass Visual Inspection due to ICU Air Handler

53/1 3 Aug.23,2023 FSD047 Building 53 Interstitial Pneumatic Damper

Pass Visual Inspection due to ICU air handler

53/1 3 Aug.23,2023 FSD048 Building 53 Interstitial Mechanical

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Jack C Montgomery VA Medical Center

53/1 3 Aug.23,2023 FSD049 Building 53 Interstitial Mechanical Fire

Pass

53/1 3 Aug.23,2023 FSD050 Building 53 Interstitial Mechanical Fire

Pass

53/1 2 Aug.23,2023 FSD051 Building 53 Interstitial Pneumatic Damper

Pass

53/1 2 Aug.23,2023 FSD052 Building 53 Interstitial Pneumatic

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Jack C Montgomery VA Medical Center

53/1 2 Aug.23,2023 FSD053 Building 53 Interstitial Mechanical Fire

Pass

53/1 2 Aug.23,2023 FSD054 Building 53 Interstitial Mechanical Fire

Pass

53/1 2 Aug.23,2023 FSD055 Building 53 Interstitial Pneumatic Damper

Pass

53/1 2 Aug.23,2023 FSD056 Building 53 Interstitial Pneumatic

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Jack C Montgomery VA Medical Center

53/1 3 Aug.23,2023 FSD057 1C102A Pneumatic Damper

Pass

53/1 2 Aug.23,2023 FSD058 Building 53 Interstitial Mechanical Fire

Fail Unable to access damper.|See Additional Notes.

Damper out of arms reach with obstructions in path.

53/1 2 Aug.23,2023 FSD059 IN2A-107 Mechanical Fire

Pass

53/1 2 Aug.23,2023 FSD060 IN2A-107 Mechanical

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Jack C Montgomery VA Medical Center

53/1 2 Aug.23,2023 FSD061 Building 53 Interstitial Mechanical Fire

Pass

53/1 2 Aug.23,2023 FSD062 Building 53 Interstitial Pneumatic Damper

Pass

53/1 2 Aug.23,2023 FSD063 Building 53 Interstitial Pneumatic Damper

Fail See Additional Notes.

Damper does not fully close when power is removed from actuator.

53/1 2 Aug.23,2023 FSD064 Building 53 Interstitial Mechanical

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Jack C Montgomery VA Medical Center

53/1 2 Aug.23,2023 FSD065 Womens bathroom across service elevators

Mechanical Fire

Pass

53/1 5 Aug.23,2023 FSD066 5C-100 Mechanical Fire

NA See Additional Notes.

Not on drawings, was instructed to make a report on damper.

53/1 5 Aug.23,2023 FSD067 5C-100 Mechanical Fire

NA See Additional Notes.

Not on drawings, was instructed to make a report on damper.

53/1 5 Aug.23,2023 FSD068 Next to 5C-106 Mechanical Fire

NA See Additional Notes.

Not on drawings, was instructed to make a report on damper.

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Jack C Montgomery VA Medical Center

53/1 5 Aug.23,2023 FSD069 Next to 5C-106 Mechanical Fire

NA See Additional Notes.

Not on drawings, was instructed to make a report on damper.

53/1 4 Aug.23,2023 FSD070 4C-100 Mechanical Fire

NA See Additional Notes.

Not on drawings, was instructed to make a report on damper.

53/1 4 Aug.23,2023 FSD071 4C-100 Mechanical Fire

NA See Additional Notes.

Not on drawings, was instructed to make a report on damper.

53/1 4 Aug.23,2023 FSD072 4C-108 Mechanical Fire

NA See Additional Notes.

Not on drawings, was instructed to

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Jack C Montgomery VA Medical Center

53/1 4 Aug.23,2023 FSD073 4C-108 Mechanical Fire

NA See Additional Notes.

Not on drawings, was instructed to make a report on damper.

53/1 3 Aug.23,2023 FSD074 3C-100 Mechanical Fire

NA See Additional Notes.

Not on drawings, was instructed to make a report on damper.

53/1 3 Aug.23,2023 FSD075 3C-100 Mechanical Fire

NA See Additional Notes.

Not on drawings, was instructed to make a report on damper.

53/1 3 Aug.23,2023 FSD076 3C-108 Mechanical Fire

NA See Additional Notes.

Not on drawings, was instructed to

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Jack C Montgomery VA Medical Center

53/1 3 Aug.23,2023 FSD077 3C-108 Mechanical Fire

NA See Additional Notes.

Not on drawings, was instructed to make a report on damper.

53/1 1 Aug.23,2023 FSD078 1C-100 Mechanical Fire

NA See Additional Notes.

Not on drawings, was instructed to make a report on damper.

53/1 1 Aug.23,2023 FSD079 1C-100 Mechanical Fire

NA See Additional Notes.

Not on drawings, was instructed to make a report on damper.

53/1 B Aug.23,2023 FSD080 B-100 Mechanical Fire

NA See Additional Notes.

Unable to find dampers, believed to be removed in area

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Jack C Montgomery VA Medical Center

53/1 B Aug.23,2023 FSD081 Across from BB-120 Mechanical Fire

NA See Additional Notes.

Not on drawings, was instructed to make a report on damper.

53/1 B Aug.23,2023 FSD082 Across from BB-120 Mechanical Fire

NA See Additional Notes.

Not on drawings, was instructed to make a report on damper.

53/1 2 Aug.23,2023 FSD083 Biohazard Room Mechanical Fire

Pass

53/1 2 Aug.23,2023 FDS084 Biohazard Room Mechanical

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Jack C Montgomery VA Medical Center

53/1 2 Aug.23,2023 FSD085 Interstitial Above XRay Mechanical Fire

Pass

53/1 2 Aug.23,2023 FSD086 Interstitial above XRay Electrical Fire/Smoke

Pass

53/1 2 Aug.23,2023 FSD087 Interstitial above XRay Electrical Fire/Smoke

Pass

53/1 2 Aug.23,2023 FSD088 Interstitial Above XRay Electrical Fire/Smoke

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Jack C Montgomery VA Medical Center

53/1 2 Aug.23,2023 FSD089 Interstitial above XRay Electrical Fire/Smoke

Pass See Additional Notes.

Visual Inspection ony. Actuator does not have a test switch. Instructed to not remove power at junction box.

53/1 2 Aug.23,2023 FSD090 Interstitial above XRay Electrical Fire/Smoke

Pass See Additional Notes.

Visual Inspection ony. Actuator does not have a test switch. Instructed to not remove power at junction box.

53/1 2 Aug.23,2023 FSD091 Interstitial above XRay Electrical Fire/Smoke

Fail Unable to access damper.|See Additional Notes.

Pipes blocking access to damper

53/1 2 Aug.23,2023 FSD092 Interstitial above XRay Electrical Fire/Smoke

Fail Unable to access damper.|See Additional Notes.

Unable to access damper due to blockage

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Jack C Montgomery VA Medical Center

53/1 2 Aug.23,2023 FSD093 Interstitial above XRay Electrical Fire/Smoke

Pass See Additional Notes.

Visual Inspection ony. Actuator does not have a test switch. Instructed to not remove power at junction box.

53/1 2 Aug.23,2023 FSD094 Interstitial above XRay Electrical Fire/Smoke

Fail No Access Door

Installed.|See Additional Notes.

Access door removed, unable to access damper

53/1 2 Aug.23,2023 FSD095 Interstitial above XRay Electrical Fire/Smoke

Pass Visual Inspection. Out of arms reach|See Additional Notes.

Visual Inspection ony. Actuator does not have a test switch. Instructed to not remove power at junction box.

53/1 2 Aug.23,2023 FSD096 Interstitial above XRay Electrical Fire/Smoke

Pass See Additional Notes.

Visual Inspection ony. Actuator does not have a test switch. Instructed to not remove power at junction box.

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Jack C Montgomery VA Medical Center

53/1 5 Aug.23,2023 FSD097 5B-50 Mechanical Fire

Pass

53/1 5 Aug.23,2023 FSD098 5B-50 Mechanical Fire

Pass

53/1 5 Aug.23,2023 FSD099 5A-20 Mechanical Fire

Fail Unable to access damper.|See Additional Notes.

2 Dampers with no access

53/1 4 Aug.23,2023 FSD100 4A-20 Mechanical Fire

Fail Unable to access damper. 2 Dampers with no access

DAMPER ID

DAMPER LOCATION DAMPER TYPE

INSPECTION

RESULT

NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE

22 4 Aug.23,2023 FSD101 4B-36 Mechanical Fire

Fail Unable to access damper. 2 Dampers with no access

22 SB Aug.23,2023 FSD102 Building 22 Next to B-5 Mechanical Fire

Pass

22 SB Aug.23,2023 FSD103 Building 22 Next to B-5 Mechanical Fire

Pass

22 SB Aug.23,2023 FSD104 Building 22 Next to B-5 Mechanical Fire

Pass

Veterans Fire & Life Safety

NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023

Cover_sheet_Jack C Montgomery Fire_Smoke Damper Report 2023-08-23[2].pdf
Jack C Montgomery Fire_Smoke Damper Report 2023-08-22.pdf

File details come from the government source that posted it. Updated .