Fire Damper Inspection.pdf
PDF 813 KB Posted
- Attached to
- J063--Fire/Smoke Damper Repair/Inspection Federal contract opportunity
- Solicitation number
- 36C25924Q0022
About this file
This document is a fire and smoke damper inspection report for the Jack C Montgomery VA Medical Center conducted in 2023. The report details inspections of 104 dampers across various buildings and floors at the facility, with results including 19% failing inspection, 17% unable to be tested, and 64% passing. Notable issues found include inaccessible dampers, dampers not attached properly, and dampers that did not fully close when power was removed. The related federal contract opportunity is solicitation number 36C25924Q0022 for fire/smoke damper repair and inspection services at the Jack C Montgomery VA Medical Center, issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19. The solicitation seeks these repair and inspection services to address the deficiencies identified in the damper inspection report.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| RFQ 36C25924Q0022 Amendment 0001 Fire-Smoke Damper Repairs MUS.pdf | ||
| 36C25924Q0022.docx | DOCX document | |
| FireDampReq6YrTesting.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRE/SMOKE DAMPER
INSPECTION REPORT
Jack C Montgomery VA Medical Center
1011 Honor Heights Dr Muskogee, OK. 74401
Veterans Fire & Life Safety 7 Sherri Ln.
St. Peters, MO. 63376
Jack C Montgomery VA Medical Center 1011 Honor Heights Dr Muskogee, OK. 74401 ATTN: Gary Ridenour
On Aug.23,2023, Veterans Fire & Life Safety conducted a thorough fire/smoke damper inspection at Jack C Montgomery VA Medical Center.
This inspection was completed by Anthony Monzon, a certified life safety inspector, using the 2012 edition of NFPA 101, as well as the latest edition of the VA Health facility code. This inspection is required every 4 years with the exception of hospitals which is every 6 years. The Life Safety plans were not provided for this inspection.
Veterans Fire & Life Safety nor Anthony Monzon are representatives of any damper manufacturer or supplier of dampers or hardware. The following report describes the condition of the dampers at the facility on the date of the inspection. Veterans Fire & Life Safety nor Anthony Monzon can warrant the future operation or condition of the dampers.
Please do not hesitate to contact us with any questions you may have regarding this report or the codes referenced. Thank you for the opportunity to complete this inspection for you.
Sincerely, Anthony Monzon
7 Sherri Ln.
St. Peters, MO. 63376
Red- Fail 19%
Yellow - N/A 17%
Green - Passed 64%
Inspection Results
Red- Fail Yellow - N/A Green - Passed
Total Dampers Inspected Total Dampers without
Deficiencies Total Dampers with
Deficiencies N/A – Dampers Unable to be tested 104 66 20 18
BUILDING FLOOR INSPECTION DATE
FACILITY
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
53/1 6 Aug.22,2023 FSD001 Building 53, 6A-101 Mechanical Fire
Pass
53/1 6 Aug.22,2023 FSD002 Building 53, 6A-101 Mechanical Fire
Fail Unable to access damper.
Door has been sealed with fire caulk.
53/1 5 Aug.22,2023 FSD003 Building 53 Interstitial Mechanical Fire
Pass
53/1 5 Aug.22,2023 FSD004 Building 53 Interstitial Mechanical Fire
Pass
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
Jack C Montgomery VA Medical Center
53/1 5 Aug.22,2023 FSD005 Building 53 Interstitial Mechanical Fire
NA See Additional Notes. No damper installed
53/1 5 Aug.22,2023 FSD006 Building 53 Interstitial Mechanical Fire
Pass
53/1 5 Aug.22,2023 FSD007 Building 53 Interstitial Mechanical Fire
Pass
53/1 5 Aug.22,2023 FSD-008 Building 53 Interstitial Mechanical Fire
Pass
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
Jack C Montgomery VA Medical Center
53/1 5 Aug.22,2023 FSD009 Building 53 Interstitial Pneumatic Damper
Pass
53/1 5 Aug.22,2023 FSD010 Building 53 Interstitial Pneumatic Damper
Pass
53/1 5 Aug.22,2023 FSD011 Building 53 Interstitial Mechanical Fire
Pass
53/1 5 Aug.22,2023 FSD012 Building 53 Interstitial Mechanical Fire
Fail Unable to access damper.|See Additional Notes.
Unable to access damper due to obstructions in path. Cardinal NE
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
Jack C Montgomery VA Medical Center
53/1 5 Aug.22,2023 FSD013 Building 53 Interstitial Pneumatic Damper
Pass
53/1 5 Aug.22,2023 FSD014 Building 53 Interstitial Mechanical Fire
Pass
53/1 5 Aug.22,2023 FSD015 Building 53 Interstitial Mechanical Fire
Fail Unable to access damper.|See Additional Notes.
Access door has been removed.
53/1 5 Aug.22,2023 FSD016 Building 53 Interstitial Pneumatic Damper
Fail
Damper did not close when power was removed from the actuator.|See Additional
Notes.
Damper did not close when power was removed from the actuator.
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
Jack C Montgomery VA Medical Center
53/1 4 Aug.22,2023 FSD017 Building 53 Interstitial Pneumatic Damper
Pass
53/1 4 Aug.22,2023 FSD018 Building 53 Interstitial Pneumatic Damper
Fail
Damper did not close when power was removed from the actuator.|See Additional
Notes.
Damper did not close when power was removed from the actuator.
53/1 4 Aug.22,2023 FSD019 Building 53 Interstitial Mechanical Fire
Pass
53/1 4 Aug.22,2023 FSD020 Building 53 Interstitial Mechanical
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
Jack C Montgomery VA Medical Center
53/1 4 Aug.22,2023 FSD021 Building 53 Interstitial Pneumatic Damper
Pass
53/1 4 Aug.22,2023 FSD022 Building 53 Interstitial Pneumatic Damper
Pass
53/1 4 Aug.22,2023 FSD023 Building 53 Interstitial Mechanical Fire
Pass
53/1 4 Aug.22,2023 FSD024 Building 53 Interstitial Mechanical
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
Jack C Montgomery VA Medical Center
53/1 3 Aug.22,2023 FSD025 Above O.R. 4 Mechanical Fire
Fail See Additional Notes.
Damper not attached to actuator or fusible link.
53/1 3 Aug.22,2023 FSD026 Above O.R. 2 Mechanical Fire
Fail See Additional Notes.
Damper not attached to actuator or fusible link.
53/1 3 Aug.22,2023 FSD027 Above O.R. 3 Mechanical Fire
Fail
Damper not attached to actuator or fusible link.
53/1 3 Aug.22,2023 FSD028 Above O.R.s Mechanical
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
Jack C Montgomery VA Medical Center
53/1 3 Aug.22,2023 FSD029 Above O.R. 1 Mechanical Fire
Fail
Damper not attached to actuator or fusible link.
53/1 3 Aug.22,2023 FSD030 Above O.R.s Mechanical Fire
Pass
53/1 3 Aug.22,2023 FSD031 Above O.R.s Mechanical Fire
Pass
53/1 4 Aug.22,2023 FSD032 Building 53 Interstitial Mechanical
Fail No Access Door Installed.
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
Jack C Montgomery VA Medical Center
53/1 4 Aug.22,2023 FSD033 Building 53 Interstitial Mechanical Fire
Pass
53/1 4 Aug.22,2023 FSD034 Building 53 Interstitial Mechanical Fire
Pass
53/1 4 Aug.22,2023 FSD035 Building 53 Interstitial Mechanical Fire
Fail Unable to access damper.|See Additional Notes.
Unable to access damper due to door being blocked.
53/1 4 Aug.22,2023 FSD036 Building 53 Interstitial Mechanical Fire
Fail See Additional Notes.
Unable to close damper due to fasteners on the track
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
Jack C Montgomery VA Medical Center
53/1 4 Aug.22,2023 FSD037 Building 53 Interstitial Mechanical Fire
Pass
53/1 5 Aug.22,2023 FSD038 Building 53 Interstitial Mechanical Fire
Fail No Access Door Installed.
53/1 3 Aug.23,2023 FSD039 Building 53 Interstitial Mechanical Fire
Pass
53/1 3 Aug.23,2023 FSD040 Building 53 Interstitial Mechanical
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
Jack C Montgomery VA Medical Center
53/1 3 Aug.23,2023 FSD041 Building 53 Interstitial Mechanical Fire
Pass
53/1 3 Aug.23,2023 FSD042 Building 53 Interstitial Mechanical Fire
Pass
53/1 3 Aug.23,2023 FSD043 Building 53 Interstitial Mechanical Fire
Pass
53/1 3 Aug.23,2023 FSD044 Building 53 Interstitial Pneumatic Damper
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
Jack C Montgomery VA Medical Center
53/1 3 Aug.23,2023 FSD045 Building 53 Interstitial Pneumatic Damper
Pass
53/1 3 Aug.23,2023 FSD046 Building 53 Interstitial Pneumatic Damper
Pass Visual Inspection due to ICU Air Handler
53/1 3 Aug.23,2023 FSD047 Building 53 Interstitial Pneumatic Damper
Pass Visual Inspection due to ICU air handler
53/1 3 Aug.23,2023 FSD048 Building 53 Interstitial Mechanical
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
Jack C Montgomery VA Medical Center
53/1 3 Aug.23,2023 FSD049 Building 53 Interstitial Mechanical Fire
Pass
53/1 3 Aug.23,2023 FSD050 Building 53 Interstitial Mechanical Fire
Pass
53/1 2 Aug.23,2023 FSD051 Building 53 Interstitial Pneumatic Damper
Pass
53/1 2 Aug.23,2023 FSD052 Building 53 Interstitial Pneumatic
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
Jack C Montgomery VA Medical Center
53/1 2 Aug.23,2023 FSD053 Building 53 Interstitial Mechanical Fire
Pass
53/1 2 Aug.23,2023 FSD054 Building 53 Interstitial Mechanical Fire
Pass
53/1 2 Aug.23,2023 FSD055 Building 53 Interstitial Pneumatic Damper
Pass
53/1 2 Aug.23,2023 FSD056 Building 53 Interstitial Pneumatic
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
Jack C Montgomery VA Medical Center
53/1 3 Aug.23,2023 FSD057 1C102A Pneumatic Damper
Pass
53/1 2 Aug.23,2023 FSD058 Building 53 Interstitial Mechanical Fire
Fail Unable to access damper.|See Additional Notes.
Damper out of arms reach with obstructions in path.
53/1 2 Aug.23,2023 FSD059 IN2A-107 Mechanical Fire
Pass
53/1 2 Aug.23,2023 FSD060 IN2A-107 Mechanical
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
Jack C Montgomery VA Medical Center
53/1 2 Aug.23,2023 FSD061 Building 53 Interstitial Mechanical Fire
Pass
53/1 2 Aug.23,2023 FSD062 Building 53 Interstitial Pneumatic Damper
Pass
53/1 2 Aug.23,2023 FSD063 Building 53 Interstitial Pneumatic Damper
Fail See Additional Notes.
Damper does not fully close when power is removed from actuator.
53/1 2 Aug.23,2023 FSD064 Building 53 Interstitial Mechanical
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
Jack C Montgomery VA Medical Center
53/1 2 Aug.23,2023 FSD065 Womens bathroom across service elevators
Mechanical Fire
Pass
53/1 5 Aug.23,2023 FSD066 5C-100 Mechanical Fire
NA See Additional Notes.
Not on drawings, was instructed to make a report on damper.
53/1 5 Aug.23,2023 FSD067 5C-100 Mechanical Fire
NA See Additional Notes.
Not on drawings, was instructed to make a report on damper.
53/1 5 Aug.23,2023 FSD068 Next to 5C-106 Mechanical Fire
NA See Additional Notes.
Not on drawings, was instructed to make a report on damper.
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
Jack C Montgomery VA Medical Center
53/1 5 Aug.23,2023 FSD069 Next to 5C-106 Mechanical Fire
NA See Additional Notes.
Not on drawings, was instructed to make a report on damper.
53/1 4 Aug.23,2023 FSD070 4C-100 Mechanical Fire
NA See Additional Notes.
Not on drawings, was instructed to make a report on damper.
53/1 4 Aug.23,2023 FSD071 4C-100 Mechanical Fire
NA See Additional Notes.
Not on drawings, was instructed to make a report on damper.
53/1 4 Aug.23,2023 FSD072 4C-108 Mechanical Fire
NA See Additional Notes.
Not on drawings, was instructed to
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
Jack C Montgomery VA Medical Center
53/1 4 Aug.23,2023 FSD073 4C-108 Mechanical Fire
NA See Additional Notes.
Not on drawings, was instructed to make a report on damper.
53/1 3 Aug.23,2023 FSD074 3C-100 Mechanical Fire
NA See Additional Notes.
Not on drawings, was instructed to make a report on damper.
53/1 3 Aug.23,2023 FSD075 3C-100 Mechanical Fire
NA See Additional Notes.
Not on drawings, was instructed to make a report on damper.
53/1 3 Aug.23,2023 FSD076 3C-108 Mechanical Fire
NA See Additional Notes.
Not on drawings, was instructed to
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
Jack C Montgomery VA Medical Center
53/1 3 Aug.23,2023 FSD077 3C-108 Mechanical Fire
NA See Additional Notes.
Not on drawings, was instructed to make a report on damper.
53/1 1 Aug.23,2023 FSD078 1C-100 Mechanical Fire
NA See Additional Notes.
Not on drawings, was instructed to make a report on damper.
53/1 1 Aug.23,2023 FSD079 1C-100 Mechanical Fire
NA See Additional Notes.
Not on drawings, was instructed to make a report on damper.
53/1 B Aug.23,2023 FSD080 B-100 Mechanical Fire
NA See Additional Notes.
Unable to find dampers, believed to be removed in area
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
Jack C Montgomery VA Medical Center
53/1 B Aug.23,2023 FSD081 Across from BB-120 Mechanical Fire
NA See Additional Notes.
Not on drawings, was instructed to make a report on damper.
53/1 B Aug.23,2023 FSD082 Across from BB-120 Mechanical Fire
NA See Additional Notes.
Not on drawings, was instructed to make a report on damper.
53/1 2 Aug.23,2023 FSD083 Biohazard Room Mechanical Fire
Pass
53/1 2 Aug.23,2023 FDS084 Biohazard Room Mechanical
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
Jack C Montgomery VA Medical Center
53/1 2 Aug.23,2023 FSD085 Interstitial Above XRay Mechanical Fire
Pass
53/1 2 Aug.23,2023 FSD086 Interstitial above XRay Electrical Fire/Smoke
Pass
53/1 2 Aug.23,2023 FSD087 Interstitial above XRay Electrical Fire/Smoke
Pass
53/1 2 Aug.23,2023 FSD088 Interstitial Above XRay Electrical Fire/Smoke
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
Jack C Montgomery VA Medical Center
53/1 2 Aug.23,2023 FSD089 Interstitial above XRay Electrical Fire/Smoke
Pass See Additional Notes.
Visual Inspection ony. Actuator does not have a test switch. Instructed to not remove power at junction box.
53/1 2 Aug.23,2023 FSD090 Interstitial above XRay Electrical Fire/Smoke
Pass See Additional Notes.
Visual Inspection ony. Actuator does not have a test switch. Instructed to not remove power at junction box.
53/1 2 Aug.23,2023 FSD091 Interstitial above XRay Electrical Fire/Smoke
Fail Unable to access damper.|See Additional Notes.
Pipes blocking access to damper
53/1 2 Aug.23,2023 FSD092 Interstitial above XRay Electrical Fire/Smoke
Fail Unable to access damper.|See Additional Notes.
Unable to access damper due to blockage
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
Jack C Montgomery VA Medical Center
53/1 2 Aug.23,2023 FSD093 Interstitial above XRay Electrical Fire/Smoke
Pass See Additional Notes.
Visual Inspection ony. Actuator does not have a test switch. Instructed to not remove power at junction box.
53/1 2 Aug.23,2023 FSD094 Interstitial above XRay Electrical Fire/Smoke
Fail No Access Door
Installed.|See Additional Notes.
Access door removed, unable to access damper
53/1 2 Aug.23,2023 FSD095 Interstitial above XRay Electrical Fire/Smoke
Pass Visual Inspection. Out of arms reach|See Additional Notes.
Visual Inspection ony. Actuator does not have a test switch. Instructed to not remove power at junction box.
53/1 2 Aug.23,2023 FSD096 Interstitial above XRay Electrical Fire/Smoke
Pass See Additional Notes.
Visual Inspection ony. Actuator does not have a test switch. Instructed to not remove power at junction box.
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
Veterans Fire & Life Safety
NFPA 80/101 FIRE & SMOKE DAMPER INSPECTION REPORT 2023
Jack C Montgomery VA Medical Center
53/1 5 Aug.23,2023 FSD097 5B-50 Mechanical Fire
Pass
53/1 5 Aug.23,2023 FSD098 5B-50 Mechanical Fire
Pass
53/1 5 Aug.23,2023 FSD099 5A-20 Mechanical Fire
Fail Unable to access damper.|See Additional Notes.
2 Dampers with no access
53/1 4 Aug.23,2023 FSD100 4A-20 Mechanical Fire
Fail Unable to access damper. 2 Dampers with no access
DAMPER ID
DAMPER LOCATION DAMPER TYPE
INSPECTION
RESULT
NOTES ADDITIONAL NOTES OPEN DAMPER PICTURE CLOSED DAMPER PICTURE
22 4 Aug.23,2023 FSD101 4B-36 Mechanical Fire
Fail Unable to access damper. 2 Dampers with no access
22 SB Aug.23,2023 FSD102 Building 22 Next to B-5 Mechanical Fire
Pass
22 SB Aug.23,2023 FSD103 Building 22 Next to B-5 Mechanical Fire
Pass
22 SB Aug.23,2023 FSD104 Building 22 Next to B-5 Mechanical Fire