36C25920Q0072-0002019.pdf
PDF Posted
- Attached to
- Fire Alarm Testing Federal contract opportunity
- Solicitation number
- 36C25920Q0072
About this file
36C25920Q0072 0002 Grand Junction VAMC Fire Alarm and LSS Inspection Certificate.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25920Q0072-0002018.docx | DOCX document | |
| 36C25920Q0072-006.docx | DOCX document | |
| 36C25920Q0072-007.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire Alarm and Life Safety System
Inspection Certificate
For
Grand Junction VAMC Bldg 1
2121 North Ave
Grand Junction, CO 81501
Kinetix has performed this inspection and testing service in compliance with The Joint
Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with The Joint Commission/VHA Memorandum 23 Concurrence on EC &
LS Standards effective September 2017. This Inspection was performed in accordance with applicable
NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Inspection Completion Date
Dec 17, 2018
Building: Grand Junction VAMC Bldg 1 Company: Kinetix
Contact: Jeremy Morkus Contact: Brandon Penrod
Title: M&O Foreman Title: Fired Technician
Kinetix 1 12/23/2018
Executive Summary Generated by: BuildingReports.com
Building Information
Building: Grand Junction VAMC Bldg 1 Contact: Jeremy Morkus
Address: 2121 North Ave Phone: 970-697-8543
Address: Fax:
City/State/Zip: Grand Junction, CO 81501 Mobile:
Country: United States of America Email:
Inspection Performed By
Company: Kinetix Inspector: Brandon Penrod
Address: 12 Creek Parkway Phone: 314-349-0006
Address: Fax:
City/State/Zip: Boothwyn, PA 19061 Mobile:
Country: United States of America Email: bpenrod@kinetixfire.com
Monitoring Company: Phone: Account #:
Central Station Signal Verification Type: Mfg: Model #:
Test Time/Date: Restore Time
Kinetix 2 12/23/2018
Inspection Completion Date: Dec 17, 2018
Building: Grand Junction VAMC Bldg 1
EC 02.03.05 EP 01
Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory
Devices Tested This
Quarter Pass Fail
Tested YTD
(2018)
Untested YTD
(2018) Total Quantity
Power Loss 0 0 0 2 0 2
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches
Devices Tested This
Quarter Pass Fail
Tested YTD
(2018)
Untested YTD
(2018) Total Quantity
Tamper Switch 39 39 0 39 0 39
Waterflow Switch 32 32 0 32 0 32
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Devices Tested This
Quarter Pass Fail
Tested YTD
(2018)
Untested YTD
(2018) Total Quantity
Duct Detector 0 0 0 41 0 41
Heat Detector 0 0 0 15 0 15
Pull Station 0 0 0 68 0 68
Smoke Detector 0 0 0 203 0 203
EC 02.03.05 EP 04
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Devices Tested This
Quarter Pass Fail
Tested YTD
(2018)
Untested YTD
(2018) Total Quantity
Releasing Device 0 0 0 63 0 63
Speaker 0 0 0 1 0 1
Speaker/Strobe 0 0 0 183 0 183
Strobe 0 0 0 64 0 64
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment per NFPA 90A-2018
Devices Tested This
Quarter Pass Fail
Tested YTD
(2018)
Untested YTD
(2018)
Duct Detector 0 0 0 41 0 41
LS 02.01.30 EP 25
All other Life Safety Code fire and smoke protection requirements related to
NFPA 101-2018 18/19.3
Devices Tested This
Quarter Pass Fail
Tested YTD
(2018)
Untested YTD
(2018)
Damper 0 0 0 1 0 1
LS 02.01.34 EP 03
Approved location for remote annunciator panel
Devices Tested This
Quarter Pass Fail
Tested YTD
(2018)
Untested YTD
(2018)
Annunciator 0 0 0 1 0 1
LS 02.01.34 EP 04
All other Life Safety Code fire alarm requirements related to NFPA 101-2018
18/19.3.4
Kinetix 3 12/23/2018
Devices Tested This
Quarter Pass Fail
Tested YTD
(2018)
Untested YTD
(2018) Total Quantity
Battery 6 6 0 6 0 6
Power Supply 0 0 0 3 0 3
Total Device Count: 722
Kinetix 4 12/23/2018
Certification
Company: Kinetix Building: Grand Junction VAMC Bldg 1
Inspector: Brandon Penrod Contact: Jeremy Morkus
Signed: Signed:
Kinetix 5 12/23/2018
Discrepancy Report
Building: Grand Junction VAMC Bldg 1 Control Panel: N/A
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is listed on the Consumer
Product Safety Commission's website and is subject to a recall by the manufacturer is included.
Device Type Manufacturer ModelNumber Date Qty
Items listed for Recall by Manufacturer Pull Station Notifier NBG-12LX 10/03/2011 7
More Information: http://image.exct.net/lib/feef1078766c0d/d/1/SSD%20Pullstation%20Bulletin.pdf
Kinetix 6 12/23/2018
Notes & Recommendations
Building: Grand Junction VAMC Bldg 1 Control Panel: 1
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection.
ScanID Note Device Type Location Comment
LS 02.01.34 EP 04 All other Life Safety Code fire alarm requirements related to NFPA 101-2018 18/19.3.4
49799135 1 Battery 3rd Rm 3608 Passed
Replaced -December 2018
49799136 2 Battery 3rd Rm 3608 Passed
Replaced -December 2018
49799138 3 Battery 3rd Rm 3608 Passed
Replaced -December 2018
49799139 4 Battery 3rd Rm 3608 Passed
Replaced -December 2018
49798127 5 Battery Penthouse Rm 7000 Elevator Equip Passed
Replaced-December 2018
49798128 6 Battery Penthouse Rm 7000 Elevator Equip Passed
Replaced-December 2018
Kinetix 7 12/23/2018
Inspection & Testing
The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 01
Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory
Verify correct receipt of alarm, supervisory and trouble signals. (NFPA 72 Table 14.4.3.2 (2)(a))
Devices Tested Q4/18 Pass Q4/18 Fail Q4/18 Tested YTD (2018) Total Quantity
Power Loss 0 0 0 2 2
Device Type Location ScanID Address Q2/18 Q4/18
Power Loss Basement Stair 7 Elevator Equip Rm 49798547 1-L2M53 05/09-P
Power Loss 3rd By Stair Elevator shaft 49798531 1 05/09-P
Device Total: 2
Kinetix 8 12/23/2018
Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72 Table 14.4.3.2 (17)(j)(1))
Tamper Switch 39 39 0 39 39
Tamper Switch Basement Building 34 Stair 1 49798852 1-L2M28 05/14-P 12/10-P
Tamper Switch Basement Stair 4 49798378 1 05/08-P 12/10-P
Tamper Switch Basement Stair 2 49798786 1-L2M29 05/14-P 12/10-P
Tamper Switch Basement By Loading Dock 49798794 1-L2M45 05/10-P 12/10-P
Tamper Switch 1st Stair 9 49798834 1-L2M15 05/11-P 12/10-P
Tamper Switch 1st Stair 4 49798788 1-L2M40 05/14-P 12/10-P
Tamper Switch 1st Stair 1 49798847 1-L2M90 05/14-P 12/10-P
Tamper Switch 1st Stair 8 49798819 1-L2M17 05/11-P 12/11-P
Tamper Switch 1st Mech Rm 1633 49797680 1-L2M12 05/11-P 12/11-P
Tamper Switch 1st Mech Rm 1633 49797685 1-L2M10 05/14-P 12/11-P
Tamper Switch 1st Mech Rm 1633 49797686 1-L2M13 05/11-P 12/11-P
Tamper Switch 1st Mech Rm 1633 49797687 1-L2M09 05/14-P 12/11-P
Tamper Switch 1st Outside AccessAmbulance Bay Mech
Rm 1635
49798860 1-L2M96 05/14-P 12/11-P
Tamper Switch 1st Rear of Building 49799203 1 05/18-P 12/11-P
Tamper Switch 1st Rear of Building 49799239 1 05/18-P 12/11-P
Tamper Switch 2nd Stair 9 49798835 1-L3M08 12/10-P
Tamper Switch 2nd Stair 9 49798795 1-L4M50 05/14-P 12/10-P
Tamper Switch 2nd Stair 4 49798789 1-L3M31 05/14-P 12/10-P
Tamper Switch 2nd Stair 1 49798848 1-L3M91 05/10-P 12/10-P
Tamper Switch 2nd Stair 3 49798672 1-L2M65 05/14-P 12/10-P
Tamper Switch 2nd Stair 2 49798774 1-L4M43 05/10-P 12/10-P
Tamper Switch 2nd Stair 8 49798817 1-L3M10 05/11-P 12/11-P
Tamper Switch 3rd Stair 1 49798808 1-L4M31 05/10-P 12/10-P
Tamper Switch 3rd Stair 3 49798670 1-L3M45 05/10-P 12/10-P
Tamper Switch 3rd Stair 2 49798771 1-L4M15 05/10-P 12/10-P
Tamper Switch 3rd Stair 2 49798776 1-L2M55 05/14-P 12/10-P
Tamper Switch 3rd Stair 4 49798778 1-L4M03 05/10-P 12/10-P
Tamper Switch 3rd Stair 2 49798779 1-L5M37 05/14-P 12/10-P
Tamper Switch 3rd Stair 8 49798449 1-L4M53 05/11-P 12/11-P
Tamper Switch 3rd Stair 8 49798832 1-L2M11 05/11-P 12/11-P
Tamper Switch 4th Stair 1 49798811 1-L5M21 05/10-P 12/10-P
Tamper Switch 4th Stair 3 49798668 1-L4M11 05/10-P 12/10-P
Tamper Switch 4th Stair 2 49798699 1-L5M13 05/10-P 12/10-P
Tamper Switch 5th Stair 3 49798666 1-L5M10 05/10-P 12/10-P
Tamper Switch 5th Stair 3 49798698 1-L6M13 05/10-P 12/10-P
Tamper Switch 6th Stair 1 49798813 1-L7M05 05/10-P 12/10-P
Tamper Switch 6th Stair 3 49798703 1-L7M04 05/10-P 12/10-P
Tamper Switch 6th Stair 3 49798704 1-L7M14 05/10-P 12/10-P
Tamper Switch 6th Stair 3 49798702 1-L7M16 05/10-P 12/10-P
Device Total: 39
Kinetix 9 12/23/2018
Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25. (NFPA 72 Table 14.4.3.2 (17)(k))
Waterflow Switch 32 32 0 32 32
Waterflow Switch Basement Stair 2 49798785 1-L2M26 05/14-P 12/10-P
Waterflow Switch Basement By Loading Dock 49798793 1-L2M45 05/10-P 12/10-P
Waterflow Switch Basement Building 34 Stair 1 49798845 1-L2M24 05/14-P 12/10-P
Waterflow Switch 1st Stair 9 49798833 1-L2M14 05/11-P 12/10-P
Waterflow Switch 1st Stair 2 49798783 1-L2M54 05/14-P 12/10-P
Waterflow Switch 1st Stair 1 49798846 1-L2M91 05/14-P 12/10-P
Waterflow Switch 1st Stair 8 49798820 1-L2M16 05/11-P 12/11-P
Waterflow Switch 1st Mech Rm 1633 49797684 1-L2M11 05/11-P 12/11-P
Waterflow Switch 2nd Stair 9 49798816 1-L3M07 05/11-P 12/10-P
Waterflow Switch 2nd Stair 4 49798790 1-L3M30 05/14-P 12/10-P
Waterflow Switch 2nd Stair 4 49798791 1-L2M39 05/10-P 12/10-P
Waterflow Switch 2nd Stair 1 49798851 1-L3M95 05/10-P 12/10-P
Waterflow Switch 2nd Stair 3 49798673 1-L2M64 05/14-P 12/10-P
Waterflow Switch 2nd Stair 2 49798773 1-L4M42 05/10-P 12/10-P
Waterflow Switch 2nd Stair 8 49798818 1-L3M09 05/11-P 12/11-P
Waterflow Switch 3rd Stair 9 49798796 1-L4M51 05/10-P 12/10-P
Waterflow Switch 3rd Stair 4 49798777 1-L5M36 05/14-P 12/10-P
Waterflow Switch 3rd Stair 1 49798809 1-L4M30 05/10-P 12/10-P
Waterflow Switch 3rd Stair 2 49798772 1-L4M16 05/10-P 12/10-P
Waterflow Switch 3rd Stair 3 49798671 1-L3M46 05/10-P 12/10-P
Waterflow Switch 3rd Stair 1 49798807 1-L3M90 05/10-P 12/10-P
Waterflow Switch 3rd Stair 8 49798448 1-L4M54 05/11-P 12/11-P
Waterflow Switch 4th Stair 2 49798669 1-L4M12 05/10-P 12/10-P
Waterflow Switch 4th Stair 4 49798787 1-L4M04 05/10-P 12/10-P
Waterflow Switch 5th Stair 1 49798814 1-L7M03 05/10-P 12/10-P
Waterflow Switch 5th Stair 3 49798667 1-L5M11 05/10-P 12/10-P
Waterflow Switch 5th Stair 3 49798700 1-L5M14 05/10-P 12/10-P
Waterflow Switch 5th Stair 1 49798810 1-L5M20 05/10-P 12/10-P
Waterflow Switch 5th Stair 2 49798675 1-L6M23 05/10-P 12/11-P
Waterflow Switch 6th Stair 3 49798664 1-L7M15 05/10-P 12/10-P
Waterflow Switch 6th Stair 3 49798665 1-L7M02 05/10-P 12/10-P
Waterflow Switch 6th Stair 3 49798701 1-L7M13 05/10-P 12/10-P
Device Total: 32
Kinetix 10 12/23/2018
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72 Table 14.4.3.2 (17)(g)(5))
Duct Detector 0 0 0 41 41
Duct Detector 1st in women’s room 1254 49797510 1-L2D38 04/30-P
Duct Detector 1st in women’s room 1254 49797511 1-L2D37 04/30-P
Duct Detector 1st Main Entry Mech Rm 49797559 1-L2D23 05/01-P
Duct Detector 1st Main Entry Mech Rm 49797562 1-L2D22 05/01-P
Duct Detector 1st Mech Rm 1219 49797505 1-L2D80 04/30-P
Duct Detector 1st Mech Rm 1219 49797552 1-L2D81 04/30-P
Duct Detector 1st Mech Rm 1232 49797696 1-L2D83 05/01-P
Duct Detector 1st Mech Rm 1622 49797695 1-L2D24 05/01-P
Duct Detector 1st Mech Rm 1633 49797688 1-L2D26 05/01-P
Duct Detector 1st Mech Rm 1633 49797689 1-L2D25 05/01-P
Duct Detector 1st Mech Rm 1689 49797556 1-L2D41 05/01-P
Duct Detector 1st Mech Rm 1689 49797557 1-L2D40 05/01-P
Duct Detector 2nd Roof Acess PTL Mech rm 2600 49797825 1-L3D91 05/01-P
Duct Detector 2nd Roof Acess PTL Mech rm 2600 49797826 1-L3D92 05/01-P
Duct Detector 2nd Mech Rm 2239 49797914 1-L3D29 05/02-P
Duct Detector 2nd Mech Rm 2239 49797915 1-L3D30 05/02-P
Duct Detector 2nd Mech Rm 2639 49797820 1-L3D84 05/16-P
Duct Detector 2nd Mech Rm 2639 49797821 1-L3D86 05/16-P
Duct Detector 2nd Mech Rm 2639 49797822 1-L3D85 05/16-P
Duct Detector 2nd Mech Rm 2639 49797823 1-L3D85 05/16-P
Duct Detector 2nd Mech Rm 2663 49797751 1-L3D73 05/01-P
Duct Detector 2nd Mech Rm 2663 49797779 1-L3D88 05/16-P
Duct Detector 2nd Mech Rm 2663 49797780 1-L3D87 05/16-P
Duct Detector 2nd Mech Rm 2663 49797781 1-L3D89 05/16-P
Duct Detector 3rd By Rm 3627 49798868 1-L4D84 05/14-P
Duct Detector 3rd By Rm 3627 49798869 1-L4D85 05/14-P
Duct Detector 3rd Mech Rm 3014 49797952 1-L4D40 05/02-P
Duct Detector 3rd Mech Rm 3014 49797979 1-L4D41 05/02-P
Duct Detector 3rd Mech Rm 3014 49797980 1-L4D42 05/02-P
Duct Detector 3rd Rm 3667 49799180 1-L4D75 05/17-P
Duct Detector 3rd Rm 3667 49799186 1-L4D79 05/17-P
Duct Detector 3rd Rm 3667 49799187 1-L4D76 05/17-P
Duct Detector 3rd Rm 3667 49799189 1-L4D80 05/17-P
Duct Detector 4th Rm 4211 49797974 1-L5D10 05/02-P
Duct Detector 4th Rm 4211 49797975 1-L05D11 05/17-P
Duct Detector 6th By Rm 6208 49798093 1-L7D19 05/03-P
Duct Detector 6th Men’s Restroom 49798091 1-L7D17 05/03-P
Duct Detector 6th Rm 6210 49798094 1-L7D18 05/03-P
Duct Detector 6th Rm 6210 49798123 1-L7D20 05/03-P
Duct Detector Penthouse Rm 7000 49798147 1-L8D06 05/03-P
Duct Detector Penthouse Rm 7000 49798148 1-L8D07 05/03-P
Device Total: 41
Kinetix 11 12/23/2018
Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions.
Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically. (NFPA 72 Table 14.4.3.2 (17)(d))
Heat Detector 0 0 0 15 15
Heat Detector Basement Stair 7 Elevator Equip Rm 49798549 1-L2D67 05/09-P
Heat Detector 1st Rm 2013 49799113 1-L3D40 05/16-P
Heat Detector 3rd Above Prep Area 49798068 1-L4D98 05/03-P
Heat Detector 3rd Above Prep Area 49798069 1-L4D99 05/03-P
Heat Detector 3rd Kitchen Dry Storage 49798070 1-L4D100 05/03-P
Heat Detector 3rd Next to Kitchen Hood 49798067 1-L4D97 05/03-P
Heat Detector Penthouse Rm 7000 Elevator Equip 49798152 1-L8D04 05/03-P
Heat Detector Penthouse Rm 7000 Elevator Equip 49798154 1-L8D03 05/03-P
Heat Detector Penthouse Rm 7000 Elevator Equip 49798155 1-L8D02 05/03-P
Heat Detector Penthouse Stair 4 Elevator Equip Rm 49798143 1-L5D31 05/03-P
Heat Detector Penthouse Stair 4 Elevator Equip Rm 49798144 1-L5D90 05/09-P
Heat Detector Penthouse Stair 4 Mech Rm 49798139 1-L5D 05/03-F
Heat Detector Penthouse Stair 4 Mech Rm 49798140 1-L5D13 05/17-F
Heat Detector Penthouse Stair 4 Mech Rm 49798141 1-L5D30 05/03-F
Heat Detector Penthouse Stair 4 Mech Rm 49798142 1-L5D 05/03-F
Device Total: 15
Kinetix 12 12/23/2018
Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72 Table 14.4.3.2 (17e))
Pull Station 0 0 0 68 68
Pull Station Basement Rear Of Building Storage 49799103 1-L2M44 05/16-P
Pull Station Basement Stair 1 49798844 1-L2M27 05/10-P
Pull Station Basement Stair 2 49798782 1-L2M25 05/10-P
Pull Station Basement Stair 3 49799104 1-L2M46 05/16-P
Pull Station Basement Stair 7 Elevator Equip Rm 49798551 1-L2M61 05/16-P
Pull Station Basement Stair 8 49799107 1-L2M48 05/16-P
Pull Station Basement Stair 8 49799108 1-L2M47 05/16-P
Pull Station 1st 20 By Stair 2 49797519 1-L2M08 04/30-P
Pull Station 1st Across From Rm 1608 49797692 1-L2M01 05/16-P
Pull Station 1st By Rm 1010 49797516 1-L2M57 05/09-P
Pull Station 1st By Rm 1018 49797515 1-L2M59 04/30-P
Pull Station 1st By Rm 1018 49797566 1-L2M58 05/09-P
Pull Station 1st By Rm 1237 49797701 1-L2M35 05/08-P
Pull Station 1st By Rm 1237 Stair 4 49797697 1-L2M42 05/08-P
Pull Station 1st By Rm 1636 Stair 9 49797630 1-L2M02 05/01-P
Pull Station 1st By Rm 1688 Stair 8 49797643 1-L2M22 05/08-P
Pull Station 1st By Stair 1 49797592 1-L2M93 05/14-P
Pull Station 1st By Stair 2 49797521 1-L2M56 04/30-P
Pull Station 1st By Stair 3 49797554 1-L2M51 04/30-P
Pull Station 1st By Stair 5 49797591 1-L2M94 05/09-P
Pull Station 1st exit by room 1219 49797603 1-L2M32 04/30-P
Pull Station 1st exit in cafeteria by serving line 49797504 1-L2M33 05/01-P
Pull Station 1st Exit to Morge 49797605 1-L2M60 04/30-P
Pull Station 1st MRI Trailer 49799099 1-L2M49 05/16-P
Pull Station 1st Rm 1235 Generator Rm 49799119 1-L2M43 05/16-P
Pull Station 1st Rm 1242d 49799082 1-L2M36 05/16-P
Pull Station 1st Stair 1 Exit 49798850 1-L2M92 05/14-P
Pull Station 1st Stair 3 Exit 49797595 1-L2M50 04/30-P
Pull Station 1st Stair 4 49798375 1-L2M23 05/08-P
Pull Station 1st Stair 4 49798376 1-L2M41 05/08-P
Pull Station 2nd By Rm 2019 49797806 1-L3M01 05/01-P
Pull Station 2nd By Rm 2410 49798849 1-L3M92 05/10-P
Pull Station 2nd By Rm 2424 49797840 1-L3M93 05/01-P
Pull Station 2nd By Rm 2639 Stair 9 49797789 1-L3M02 05/01-P
Pull Station 2nd By Rm 2663 49797754 1-L3M03 05/01-P
Pull Station 2nd By Rm 2688 49797797 1-L3M17 05/14-P
Pull Station 2nd Stair 2 49798775 1-L3M41 05/10-P
Pull Station 2nd Stair 3 49797927 1-L3M44 05/09-P
Pull Station 2nd Stair 4 49797918 1-L3M33 05/02-P
Pull Station 2nd Stair 6 49797941 1-L3M40 05/01-P
Pull Station 3rd By Rm 3658 49798323 1-L4M76 05/17-P
Pull Station 3rd Kitchen Entrance 49797894 1-L4M125 05/02-F
Pull Station 3rd Nurses Station 2620 49799196 1-L4M77 05/17-P
Pull Station 3rd Nurses Station 3025 49799164 1-L4M14 05/17-P
Pull Station 3rd Nurses Station 3611 49799165 1-L4M78 05/17-P
Pull Station 3rd Stair 1 49797987 1-L4M32 05/02-P
Pull Station 3rd Stair 2 49797865 1-L4M17 05/02-P
Pull Station 3rd Stair 3 49797873 1-L4M13 05/02-P
Pull Station 3rd Stair 4 49797883 1-L4M02 05/02-P
Kinetix 13 12/23/2018
Pull Station 3rd Stair 5 49797985 1-L4M33 05/02-P
Pull Station 3rd Stair 5 49798463 1-L4M62 05/08-P
Pull Station 3rd Stair 6 49797861 1-L4M18 05/14-P
Pull Station 3rd Stair 8 49798445 1-L4M63 05/08-P
Pull Station 4th Stair 1 49798004 1-L5M22 05/02-P
Pull Station 4th Stair 2 49797964 1-L5M15 05/03-F
Pull Station 4th Stair 3 49797972 1-L5M12 05/03-P
Pull Station 4th Stair 5 49798008 1-L5M23 05/02-P
Pull Station 4th Stair 6 49797968 1-L5M16 05/02-P
Pull Station 5th Rm 5031 49799191 1-L6M25 05/17-P
Pull Station 5th Stair 1 49798019 1-L6M31 05/02-P
Pull Station 5th Stair 2 49798052 1-L6M149 05/03-P
Pull Station 5th Stair 2 49798054 1-L6M148 05/03-P
Pull Station 5th Stair 3 49797988 1-L6M12 05/03-P
Pull Station 5th Stair 5 49798021 1-L6M30 05/02-P
Pull Station 6th Stair 1 49798115 1-L6M01 05/17-P
Pull Station 6th Stair 3 49798089 1-L6M06 05/17-P
Pull Station Penthouse Stair 4 49798181 1-L5M06 05/18
Removed
Pull Station Penthouse Rm 7000 49798182 1-L8M09 05/03-P
Pull Station Penthouse Stair 4 49798137 1-L5M06 05/03-P
Device Total: 68
Kinetix 14 12/23/2018
Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72 Table 14.4.3.2 (17)(g)(1))
Smoke Detector 0 0 0 203 203
Smoke Detector Basement Stair 7 Elevator Equip Rm 49798550 1-L2D66 05/09-P
Smoke Detector 1st By ED Check In 49797747 1-L2D17 05/01-P
Smoke Detector 1st by main elevators 49797594 1-L2D54 05/03-P
Smoke Detector 1st By Rm 1205 49799190 1-L2D53 05/17-P
Smoke Detector 1st By Rm 1214 49797507 1-L2D30 04/30-P
Smoke Detector 1st By Rm 1226 49797600 1-L2D32 05/14-P
Smoke Detector 1st By Rm 1236 49797699 1-L2D34 05/14-P
Smoke Detector 1st By Rm 1237 49798377 1-L2D35 05/14-P
Smoke Detector 1st By Rm 1405 49797609 1-L2D70 05/09-P
Smoke Detector 1st By Rm 1411B 49797610 1-L2D71 05/09-P
Smoke Detector 1st By Rm 1607 49797681 1-L2D01 05/01-P
Smoke Detector 1st By Rm 1619 49797555 1-L2D02 05/01-P
Smoke Detector 1st By Rm 1623 49797627 1-L2D03 05/01-P
Smoke Detector 1st By Rm 1639 49797628 1-L2D04 05/08-P
Smoke Detector 1st By Rm 1645 49797633 1-L2D05 05/08-P
Smoke Detector 1st By Rm 1652 49797622 1-L2DD06 05/16-P
Smoke Detector 1st By Rm 1657A 49797621 1-L2D18 05/01-P
Smoke Detector 1st By Rm 1661 49797748 1-L2D16 05/01-P
Smoke Detector 1st By Rm 1667 49797746 1-L2D21 05/01-P
Smoke Detector 1st By Rm 1671 49797635 1-L2D19 05/08-P
Smoke Detector 1st By Rm 1673 49797636 1-L2D20 05/08-P
Smoke Detector 1st By Rm 1676 49797634 1-L2D07 05/16-P
Smoke Detector 1st By Rm 1685 49797644 1-L2D09 05/08-P
Smoke Detector 1st By Rm 1692 49797647 1-L2D10 05/08-P
Smoke Detector 1st By Rm 1698 49797648 1-L2D11 05/08-P
Smoke Detector 1st By Rm 1707 49797558 1-L2D12 05/08-P
Smoke Detector 1st By Rm 2664 49797752 1-L3D19 05/01-P
Smoke Detector 1st By Rm 2673B 49799112 1-L3D34 05/20-F
Smoke Detector 1st by room 1006 and 1004 49797513 1-L2D51 04/30-P
Smoke Detector 1st by room 1007 in pharmacy 49797615 1-L2D55 05/09-P
Smoke Detector 1st by room 1219 49797601 1-L2D31 04/30-P
Smoke Detector 1st by room 1419 49797526 1-L2D72 05/09-P
Smoke Detector 1st by room 1426 49797547 1-L2D73 05/09-P
Smoke Detector 1st by stair 2 49797523 1-L2D59 05/03-P
Smoke Detector 1st By Stair 8 49797777 1-L3D18 05/01-P
Smoke Detector 1st Canteen Entrance 49797560 1-L2D33 05/01-P
Smoke Detector 1st in hallway by main elevators 49797611 1-L2D56 05/03-P
Smoke Detector 1st in pharmacy 49797524 1-L2D57 05/09-P
Smoke Detector 1st in pharmacy 49797549 1-L2D58 05/09-P
Smoke Detector 1st in pharmacy 49797593 1-L2D61 05/09-P
Smoke Detector 1st in pharmacy by exit 49797525 1-L2D62 05/09-P
Smoke Detector 1st in pharmacy by Stair 2 49797548 1-L2D60 05/09-P
Smoke Detector 1st Main Elevator Lobby 49797745 1-L2D13 05/01-P
Smoke Detector 1st MRI Trailer 49799100 1-L2D49 05/16-P
Smoke Detector 1st Pharmacy Waiting Rm 49797744 1-L2D14 05/01-P
Smoke Detector 1st Service Elevator Lobby 49798153 1-L2D52 05/17-P
Smoke Detector 2nd Audiology Elevator Lobby 49797807 1-L3D26 05/09-P
Smoke Detector 2nd Audiology Elevator Shaft Lobby 49798600 1-L3D55 05/09-P
Smoke Detector 2nd By Mental Health 49797776 1-L3D14 05/01-P
Kinetix 15 12/23/2018
Smoke Detector 2nd By Micro bio 49797905 1-L3D45 05/02-P
Smoke Detector 2nd By Rm 2005 49797947 1-L3D62 05/01-P
Smoke Detector 2nd By Rm 2007A 49797946 1-L3D63 05/01-P
Smoke Detector 2nd By Rm 2208 49797924 1-L3D70 05/02-P
Smoke Detector 2nd By Rm 2215 Eye wash 49797908 1-L3D49 05/02-P
Smoke Detector 2nd By Rm 2218 49797907 1-L3D48 05/02-P
Smoke Detector 2nd By Rm 2221 49797904 1-L3D43 05/02-P
Smoke Detector 2nd By Rm 2228 49797919 1-L3D44 05/03-P
Smoke Detector 2nd By Rm 2228 49797920 1-L3D47 05/03-P
Smoke Detector 2nd By Rm 2231 49797906 1-L3D46 05/02-P
Smoke Detector 2nd By Rm 2238 49797917 1-L3D42 05/09-P
Smoke Detector 2nd By Rm 2402 49797834 1-L3D61 05/01-P
Smoke Detector 2nd By Rm 2404 49797929 1-L3D69 05/02-P
Smoke Detector 2nd By Rm 2404 Elevator Lobby 49797928 1-L3D72 05/09-P
Smoke Detector 2nd By Rm 2406 49797835 1-L3D80 05/01-P
Smoke Detector 2nd By Rm 2414 49797836 1-L3D81 05/01-P
Smoke Detector 2nd By Rm 2419 49797837 1-L3D82 05/01-P
Smoke Detector 2nd By Rm 2424 49797838 1-L3D83 05/01-P
Smoke Detector 2nd By Rm 2605 49797949 1-L3D60 05/01-P
Smoke Detector 2nd By Rm 2605 49797950 1-L3D33 05/01-P
Smoke Detector 2nd By Rm 2607 49797808 1-L3D27 05/01-P
Smoke Detector 2nd By Rm 2609 Elevator 49797811 1-L3D04 05/09-P
Smoke Detector 2nd By Rm 2611 49797828 1-L3D03 05/14-P
Smoke Detector 2nd By Rm 2618 49797830 1-L3D01 05/01-P
Smoke Detector 2nd By Rm 2626 49797827 1-L3D05 05/14-P
Smoke Detector 2nd By Rm 2626 49797910 1-L3D50 05/02-P
Smoke Detector 2nd By Rm 2626 49797922 1-L3D51 05/02-P
Smoke Detector 2nd By Rm 2629 49797813 1-L3D06 05/14-P
Smoke Detector 2nd By Rm 2633 49797891 1-L3D16 05/02-P
Smoke Detector 2nd By Rm 2641 49797756 1-L3D09 05/01-P
Smoke Detector 2nd By Rm 2643 49797763 1-L3D11 05/01-P
Smoke Detector 2nd By Rm 2651 49797775 1-L3D15 05/01-P
Smoke Detector 2nd By Rm 2654 49797774 1-L3D08 05/01-P
Smoke Detector 2nd By Rm 2659 49797773 1-L3D17 05/01-P
Smoke Detector 2nd By Rm 2667 49797802 1-L3D22 05/01-P
Smoke Detector 2nd By Rm 2673 49797816 1-L3D13 05/14-P
Smoke Detector 2nd By Rm 2673B 49797817 1-L3D07 05/14-P
Smoke Detector 2nd By Rm 2679 49797805 1-L3D25 05/14-P
Smoke Detector 2nd By Rm 2682 49798879 1-L3D24 05/14-P
Smoke Detector 2nd By Rm 2683 49797796 1-L3D23 05/14-P
Smoke Detector 2nd By Rm 2694 49797799 1-L3D21 05/14-P
Smoke Detector 2nd By Stair 2 49797945 1-L3D64 05/01-P
Smoke Detector 2nd By Stair 6 49797937 1-L3D67 05/01-P
Smoke Detector 2nd By Stair 6 49797938 1-L3D68 05/01-P
Smoke Detector 2nd By Stair 6 49797939 1-L3D65 05/01-P
Smoke Detector 2nd By Stair 6 49797940 1-L3D66 05/01-P
Smoke Detector 2nd Mental Health Check In 49797768 1-L3D35 05/01-P
Smoke Detector 2nd Mental Health Check Waiting Area 49797764 1-L3D12 05/01-P
Smoke Detector 2nd Rm 2404 49797887 1-L3D75 05/02-P
Smoke Detector 3rd 49797863 1-L415 05/20
Smoke Detector 3rd Across Pre-Op Nurses Station 49798421 1-L4D39 05/20
Smoke Detector 3rd Across From Rm 3250 49798095 1-L4D12 05/03-P
Smoke Detector 3rd Across Pre-Op Nurses Station 49798335 1-L4D62 05/08-P
Kinetix 16 12/23/2018
Smoke Detector 3rd By Rm 3009 49798342 1-L4D61 05/08-P
Smoke Detector 3rd By Rm 3020B 49797862 1-L4D17 05/17-P
Smoke Detector 3rd By Rm 3027 49797856 1-L4D14 05/02-P
Smoke Detector 3rd By Rm 3027 Nurses station 49797855 1-L4D10 05/17-P
Smoke Detector 3rd By Rm 3209 49797867 1-L4D16 05/17-P
Smoke Detector 3rd By Rm 3209 49797876 1-L4D13 05/02-P
Smoke Detector 3rd By Rm 3213 49797879 1-L4D01 05/02-P
Smoke Detector 3rd By Rm 3400 49798353 1-L4D30 05/08-P
Smoke Detector 3rd By Rm 3406 49797986 1-L4D32 05/02-P
Smoke Detector 3rd By Rm 3406 49798424 1-L4D57 05/08-P
Smoke Detector 3rd By Rm 3410 49797983 1-L4D33 05/02-P
Smoke Detector 3rd By Rm 3421 49797853 1-L4D31 05/02-P
Smoke Detector 3rd By Rm 3602 49798329 1-L4D59 05/08-P
Smoke Detector 3rd By Rm 3606 49798330 1-L4D60 05/08-P
Smoke Detector 3rd By Rm 3608 49798328 1-L4D56 05/08-P
Smoke Detector 3rd By Rm 3609 49798332 1-L4D64 05/08-P
Smoke Detector 3rd By Rm 3614 49798337 1-L4D63 05/08-P
Smoke Detector 3rd By Rm 3622 49799153 1-L4D87 05/17-P
Smoke Detector 3rd By Rm 3623 49799154 1-L4D37 05/17-P
Smoke Detector 3rd By Rm 3626 49799155 1-L4D43 05/17-P
Smoke Detector 3rd By Rm 3627 49798467 1-L4D45 05/08-P
Smoke Detector 3rd By Rm 3631 49798469 1-L4D49 05/08-P
Smoke Detector 3rd By Rm 3633 49798470 1-L4D50 05/08-P
Smoke Detector 3rd By Rm 3634 49798419 1-L4D51 05/08-P
Smoke Detector 3rd By Rm 3636 49798462 1-L4D52 05/08-P
Smoke Detector 3rd By Rm 3640 49798423 1-L4D54 05/08-P
Smoke Detector 3rd By Rm 3641 49798468 1-L4D46 05/08-P
Smoke Detector 3rd By Rm 3642 49798461 1-L4D68 05/08-P
Smoke Detector 3rd By Rm 3643 49798460 1-L4D67 05/08-P
Smoke Detector 3rd By Rm 3647 49798105 1-L4D44 05/08-P
Smoke Detector 3rd By Rm 3647 49799148 1-L4D39 05/17-P
Smoke Detector 3rd By Rm 3650 49798420 1-L4D55 05/08-P
Smoke Detector 3rd By Rm 3650 49798442 1-L4D71 05/08-P
Smoke Detector 3rd By Rm 3653 49798324 1-L4D66 05/08-P
Smoke Detector 3rd By Rm 3666 49798443 1-L4D72 05/08-P
Smoke Detector 3rd By Rm 3671B 49798439 1-L4D70 05/08-P
Smoke Detector 3rd By Rm 3672 49798433 1-L4D69 05/08-P
Smoke Detector 3rd By Stair 3 Elevator Lobby 49797895 1-L4D06 05/10-P
Smoke Detector 3rd Main Elevators Lobby 49797872 1-L4D11 05/02-P
Smoke Detector 3rd Rm 3017A 49797864 1-L4D90 05/14-P
Smoke Detector 3rd Rm 3608 49799132 1-L4D65 05/17-P
Smoke Detector 3rd Rm 3629 49798464 1-L4D48 05/08-P
Smoke Detector 3rd Rm 3641 49798427 1-L4D58 05/08-P
Smoke Detector 3rd Rm 3642 49798428 1-L4D88 05/08-P
Smoke Detector 3rd Rm 3642 49798429 1-L4D89 05/08-P
Smoke Detector 3rd Rm 3656 49798510 1-L4D82 05/08-P
Smoke Detector 3rd Rm 3656 49798512 1-L4D81 05/08-P
Smoke Detector 3rd Rm 3658 49798456 1-L4D77 05/08-P
Smoke Detector 3rd Rm 3658 49798457 1-L4D78 05/08-P
Smoke Detector 3rd Stair 8 49798444 1-L4D73 05/08-P
Smoke Detector 3rd Stair 8 49798446 1-L4D74 05/08-P
Smoke Detector 3rd Stair 9 49799133 1-L4D47 05/17-P
Smoke Detector 4th By Rm 4001 49798016 1-L5D04 05/02-P
Smoke Detector 4th By Rm 4003 49798015 1-L5D01 05/03-P
Smoke Detector 4th By Rm 4008 49797960 1-L5D05 05/02-P
Kinetix 17 12/23/2018
Smoke Detector 4th By Rm 4016 49797963 1-L5D06 05/02-P
Smoke Detector 4th By Rm 4021 49797966 1-L5D08 05/02-P
Smoke Detector 4th By Rm 4021 49797967 1-L5D07 05/02-P
Smoke Detector 4th By Rm 4201 Elevator Lobby 49797970 1-L5D25 05/03-P
Smoke Detector 4th By Rm 4201 Elevator Lobby 49797971 1-L5D03 05/03-P
Smoke Detector 4th By Rm 4203 49797973 1-L5D02 05/02-P
Smoke Detector 4th By Rm 4402 49798012 1-L5D20 05/03-P
Smoke Detector 4th By Rm 4413 49798011 1-L5D21 05/02-P
Smoke Detector 4th By Rm 4415 49798010 1-L5D22 05/02-P
Smoke Detector 4th By Rm 4419 49798009 1-L5D23 05/02-P
Smoke Detector 4th Rm 4012 49797959 1-L5D91 05/02-P
Smoke Detector 4th Stair 4 49798780 1-L5D35 05/10-P
Smoke Detector 5th By Rm 5016 49798055 1-L6D22 05/03-P
Smoke Detector 5th By Rm 5020 49798053 1-L6D21 05/03-P
Smoke Detector 5th By Rm 5021 49798046 1-L6D35 05/03-P
Smoke Detector 5th By Rm 5030 49798048 1-L6D20 05/03-P
Smoke Detector 5th By Rm 5034 49798049 1-L6D04 05/03-P
Smoke Detector 5th By Rm 5203 49797995 1-L6D08 05/02-P
Smoke Detector 5th By Rm 5203 49798027 1-L6D02 05/02-P
Smoke Detector 5th By Rm 5203 49798028 1-L6D03 05/02-P
Smoke Detector 5th By Rm 5231 49797997 1-L6D06 05/02-P
Smoke Detector 5th By Rm 5400 Elevator Lobby 49797998 1-L6D05 05/03-P
Smoke Detector 5th By Rm 5400 Elevator Lobby 49797999 1-L6D09 05/03-P
Smoke Detector 5th By Rm 5412 49798029 1-L6D01 05/02-P
Smoke Detector 5th Pych Ward Cooridor 49798674 1-L6D34 05/10-P
Smoke Detector 5th Pych Ward Cooridor 49798676 1-L6D25 05/10-P
Smoke Detector 5th Rm 5033 49798060 1-L6D26 05/03-P
Smoke Detector 5th Rm 5205 49798073 1-L6D07 05/03-P
Smoke Detector 5th Stair 1 49798058 1-L6D24 05/03-P
Smoke Detector 5th Stair 6 49798057 1-L6D23 05/03-P
Smoke Detector 6th By Service Elevator 49798541 1-L7D105 05/20
Smoke Detector 6th By Main Elevators 49798120 1-L7D14 05/03-P
Smoke Detector 6th By Rm 6009 49798119 1-L7D15 05/03-P
Smoke Detector 6th By Rm 6401 49798118 1-L7D03 05/03-P
Smoke Detector 6th By Rm 6405 49798117 1-L7D02 05/17-P
Smoke Detector 6th By Rm 6406 49798116 1-L7D08 05/17-P
Smoke Detector 6th By Service Elevator 49798121 1-L7D04 05/09-P
Smoke Detector 6th By Stair 1 49798113 1-L7D05 05/03-P
Smoke Detector 6th By Stair 3 49798122 1-L7D21 05/03-P
Smoke Detector 6th By Stair 3 49798705 1-L7D07 05/10-P
Smoke Detector 6th Elevator Shafts 49798604 1-L7D22 05/09-F
Smoke Detector 6th Stair 1 49798812 1-L7D01 05/17-P
Smoke Detector Penthouse Elevator Equip Rm 49799201 1-L7D06 05/17-P
Smoke Detector Penthouse Rm 7000 Elevator Equip Rm 49798149 1-L8D10 05/03-P
Smoke Detector Penthouse Rm 7000 Elevator Equip Rm 49798150 1-L8D05 05/03-P
Smoke Detector Penthouse Rm 7000 Elevator Equip Rm 49798151 1-L8D55 05/03-P
Smoke Detector Penthouse Stair 4 Elevator Equip Rm 49798145 1-L5D33 05/09-P
Smoke Detector Penthouse Stair 4 Mech Rm 49798138 1-L5D34 05/03-F
Smoke Detector Penthouse Stair 4 Mech Rm 49799194 1-L5D32 05/17-F
Device Total: 203
Kinetix 18 12/23/2018
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72 Table 14.4.3.2 (20))
Releasing Device 0 0 0 63 63
Releasing Device 1st By Rm 1401 49798880 1 05/14-P
Releasing Device 1st By Rm 1401 49798881 1 05/14-P
Releasing Device 1st by Rm 1647 49797623 1 05/01-P
Releasing Device 1st by Rm 1647 49797624 1 05/01-P
Releasing Device 1st by Rm 1658 49799110 1 05/16-P
Releasing Device 1st by Rm 1658 49799111 1 05/16-P
Releasing Device 1st by Rm 1668 49797638 1 05/01-P
Releasing Device 1st by Rm 1668 49797639 1 05/01-P
Releasing Device 1st by room 1004 49797550 1 04/30-P
Releasing Device 1st by room 1226/entrance to canteen 49797500 1 04/30-P
Releasing Device 1st by room 1226/entrance to canteen 49797502 1 04/30-P
Releasing Device 1st by stair 2 49797551 1 04/30-P
Releasing Device 2nd By Rm 2005 49797930 1 05/01-P
Releasing Device 2nd By Rm 2005 49797931 1 05/01-P
Releasing Device 2nd By Rm 2020 49797932 1 05/01-P
Releasing Device 2nd By Rm 2020 49797933 1 05/01-P
Releasing Device 2nd By Rm 2020 49797934 1 05/01-P
Releasing Device 2nd By Rm 2020 49797935 1 05/01-P
Releasing Device 2nd By Rm 2206 49797888 1 05/02-P
Releasing Device 2nd By Rm 2206 49797896 1 05/02-P
Releasing Device 2nd By Rm 2401 49797848 1 05/01-P
Releasing Device 2nd By Rm 2401 49797849 1 05/01-P
Releasing Device 2nd By Rm 2401 49798496 1 05/08-P
Releasing Device 2nd By Rm 2401 49798498 1 05/08-P
Releasing Device 2nd By Rm 2413 49797583 1 05/01-P
Releasing Device 2nd By Rm 2413 49797749 1 05/01-P
Releasing Device 2nd By Rm 2413 49797750 1 05/01-P
Releasing Device 2nd By Rm 2413 49797782 1 05/01-P
Releasing Device 2nd By Rm 260 49797584 1 05/01-P
Releasing Device 2nd By Rm 260 49797585 1 05/01-P
Releasing Device 2nd By Rm 2602 49798865 1 05/14-P
Releasing Device 2nd By Rm 2602 49798870 1 05/14-P
Releasing Device 2nd By Rm 2604 49797843 1 05/01-P
Releasing Device 2nd By Rm 2604 49797847 1 05/01-P
Releasing Device 2nd By Rm 2650 49797892 1 05/02-P
Releasing Device 2nd By Rm 2650 49797893 1 05/02-P
Releasing Device 2nd By Rm 2673A 49797889 1 05/02-P
Releasing Device 2nd By Rm 2673A 49797890 1 05/02-P
Releasing Device 3rd By Rm 3009 49798340 1 05/08-P
Releasing Device 3rd By Rm 3009 49798341 1 05/08-P
Releasing Device 3rd By Rm 3027 49797857 1 05/02-P
Releasing Device 3rd By Rm 3027 49797858 1 05/02-P
Releasing Device 3rd By Rm 3205 49798422 1 05/08-P
Releasing Device 3rd By Rm 3209 49797874 1 05/02-P
Releasing Device 3rd By Rm 3209 49797875 1 05/02-P
Releasing Device 3rd By Rm 3215 49798066 1 05/03-P
Releasing Device 3rd By Rm 3403 49798343 1 05/08-P
Releasing Device 3rd By Rm 3403 49798344 1 05/08-P
Releasing Device 3rd By Rm 3404 49799145 1 05/17-P
Kinetix 19 12/23/2018
Releasing Device 3rd By Rm 3404 49799146 1 05/17-P
Releasing Device 3rd By Rm 3405 49798065 1 05/03-P
Releasing Device 3rd By Rm 3405 49798350 1 05/08-P
Releasing Device 3rd Rm 3672 49798435 1 05/08-P
Releasing Device 3rd Rm 3672 49798436 1 05/08-P
Releasing Device 4th By Rm 4003 49798013 1 05/02-P
Releasing Device 4th By Rm 4003 49798014 1 05/02-P
Releasing Device 4th By Rm 4007 49797961 1 05/02-P
Releasing Device 4th Rm 4007 49797962 1 05/02-P
Releasing Device 5th By Rm 5217 49798478 1 05/08-P
Releasing Device 5th By Rm 5217 49798486 1 05/08-P
Releasing Device 5th By Rm 5430 49798024 1 05/02-P
Releasing Device 5th By Rm 5430 49798025 1 05/02-P
Releasing Device 6th By Rm 6403 49798114 1 05/03-P
Device Total: 63
Kinetix 20 12/23/2018
For periodic testing, verify the operation of the notification appliances. (NFPA 72 Table 14.4.3.2 (22)(b))
Speaker 0 0 0 1 1
Speaker 1st By Stair 2 49797514 1 05/01
Speaker 2nd Mech Rm 3014 49797770 1 05/01-P
Device Total: 1
Kinetix 21 12/23/2018
For periodic testing, verify the operation of the notification appliances. (NFPA 72 Table 14.4.3.2 (22)(b))
Speaker/Strobe 0 0 0 183 183
Speaker/Strobe Basement Stair 2 49798781 1 05/10-P
Speaker/Strobe Basement Stair 4 49798379 1 05/08-P
Speaker/Strobe Basement Stair 7 Elevator Equip Rm 49798552 1 05/09-P
Speaker/Strobe 1st Outside AccessAmbulance Bay Mech
Rm 1635
49798861 1 05/14-P
Speaker/Strobe 1st Across On 1608 49797693 1 05/01-P
Speaker/Strobe 1st By ER Rm 5 49797683 1 05/01-P
Speaker/Strobe 1st By Info Desk 49797652 1 05/01-P
Speaker/Strobe 1st by main elevators 49797602 1 04/30-P
Speaker/Strobe 1st by men’s room 1216 49797598 1 04/30-P
Speaker/Strobe 1st By Rm 1218 49797599 1 04/30-P
Speaker/Strobe 1st By Rm 1234 49797698 1 05/01-P
Speaker/Strobe 1st By Rm 1237 49797702 1 05/01-P
Speaker/Strobe 1st By Rm 1401 49797608 1 04/30-P
Speaker/Strobe 1st By Rm 1601 49797691 1 05/01-P
Speaker/Strobe 1st By Rm 1603 49797694 1 05/01-P
Speaker/Strobe 1st By Rm 16236 49797629 1 05/01-P
Speaker/Strobe 1st By Rm 1627 49797626 1 05/01-P
Speaker/Strobe 1st By Rm 1645 49797625 1 05/01-P
Speaker/Strobe 1st By Rm 1648 49797618 1 05/01-P
Speaker/Strobe 1st By Rm 1652 49797619 1 05/01-P
Speaker/Strobe 1st By Rm 1658 49797620 1 05/01-P
Speaker/Strobe 1st By Rm 1673 49797617 1 05/01-P
Speaker/Strobe 1st By Rm 1678 49797646 1 05/01-P
Speaker/Strobe 1st By Rm 1679 49797645 1 05/01-P
Speaker/Strobe 1st By Rm 1688 Stair 8 49797642 1 05/01-P
Speaker/Strobe 1st By Rm 1696 49797649 1 05/01-P
Speaker/Strobe 1st By Rm 1707 Waiting Area 49797650 1 05/01-P
Speaker/Strobe 1st by room 1004/pharmacy counseling 49797512 1 04/30-P
Speaker/Strobe 1st By Stair 1 49797589 1 04/30-P
Speaker/Strobe 1st By Stair 2 49797520 1 04/30-P
Speaker/Strobe 1st By Stair 3 49797596 1 04/30-P
Speaker/Strobe 1st By Stair 5 49797590 1 04/30-P
Speaker/Strobe 1st By Stair 9 49799109 1 05/16-P
Speaker/Strobe 1st Canteen 49797581 1 05/01-P
Speaker/Strobe 1st exit in canteen/by serving line 49797503 1 04/30-P
Speaker/Strobe 1st in men’s room 1216 49797597 1 04/30-P
Speaker/Strobe 1st in women’s room 1254 49797508 1 04/30-P
Speaker/Strobe 1st in women’s room 1254 49797509 1 04/30-P
Speaker/Strobe 1st Kitchen line 49797561 1 05/01-P
Speaker/Strobe 1st Main Entry Mech Rm 49797563 1 05/01-P
Speaker/Strobe 1st Medical Clinics Area 49797651 1 05/01-P
Speaker/Strobe 1st Pharmacy by 1010 49797517 1 04/30-P
Speaker/Strobe 1st Pharmacy by 1021 49797567 1 04/30-P
Speaker/Strobe 1st Pharmacy by Vault 49797518 1 04/30-P
Speaker/Strobe 1st Restroom By ER Entrance 49799101 1 05/16-P
Speaker/Strobe 1st Rm 1237 49797700 1 05/01-P
Speaker/Strobe 1st Rm 1633 49797690 1 05/01-P
Speaker/Strobe 1st Rm 1689 49797641 1 05/01-P
Kinetix 22 12/23/2018
Speaker/Strobe 2nd Audiology Waiting Rm 49797809 1 05/01-P
Speaker/Strobe 2nd By dental 49797846 1 05/01-P
Speaker/Strobe 2nd By Rm 2005 49797948 1 05/01-P
Speaker/Strobe 2nd By Rm 2025 49797943 1 05/01-P
Speaker/Strobe 2nd By Rm 2208 49797923 1 05/02-P
Speaker/Strobe 2nd By Rm 2218 49797903 1 05/02-P
Speaker/Strobe 2nd By Rm 2220 49797902 1 05/02-P
Speaker/Strobe 2nd By Rm 2221 49797901 1 05/02-P
Speaker/Strobe 2nd By Rm 2228 49797921 1 05/02-P
Speaker/Strobe 2nd By Rm 2238 49797916 1 05/02-P
Speaker/Strobe 2nd By Rm 2402 49797833 1 05/01-P
Speaker/Strobe 2nd By Rm 2414 49797842 1 05/01-P
Speaker/Strobe 2nd By Rm 2605 49797844 1 05/01-P
Speaker/Strobe 2nd By Rm 2607 49797810 1 05/01-P
Speaker/Strobe 2nd By Rm 2611 49797829 1 05/01-P
Speaker/Strobe 2nd By Rm 2618 49797831 1 05/01-P
Speaker/Strobe 2nd By Rm 2626 49797812 1 05/01-P
Speaker/Strobe 2nd By Rm 2630 49797814 1 05/01-P
Speaker/Strobe 2nd By Rm 2635 49797819 1 05/01-P
Speaker/Strobe 2nd By Rm 2642A 49797766 1 05/01-P
Speaker/Strobe 2nd By Rm 2650 49797765 1 05/01-P
Speaker/Strobe 2nd By Rm 2651 49797769 1 05/01-P
Speaker/Strobe 2nd By Rm 2656 49797771 1 05/01-P
Speaker/Strobe 2nd By Rm 2657 49797772 1 05/01-P
Speaker/Strobe 2nd By Rm 2667 49797801 1 05/01-P
Speaker/Strobe 2nd By Rm 2668 49797815 1 05/01-P
Speaker/Strobe 2nd By Rm 2676 49797818 1 05/01-P
Speaker/Strobe 2nd By Rm 2679 49797804 1 05/01-P
Speaker/Strobe 2nd By Rm 2688 49797798 1 05/01-P
Speaker/Strobe 2nd By Rm 2694 49797800 1 05/01-P
Speaker/Strobe 2nd By Stair 2 49797944 1 05/01-P
Speaker/Strobe 2nd By Stair 8 49797753 1 05/01-P
Speaker/Strobe 2nd Mental Health Waiting Rm 49797762 1 05/01-P
Speaker/Strobe 2nd Rm 2213 49797909 1 05/02-P
Speaker/Strobe 2nd Rm 2214 49797911 1 05/02-P
Speaker/Strobe 2nd Rm 2236 49797912 1 05/02-P
Speaker/Strobe 2nd Rm 2239 49797913 1 05/02-P
Speaker/Strobe 2nd Rm 2266 49797778 1 05/01-P
Speaker/Strobe 2nd Rm 2424 49797839 1 05/01-P
Speaker/Strobe 2nd Rm 2639 49797824 1 05/01-P
Speaker/Strobe 2nd Rm 2642E 49797767 1 05/01-P
Speaker/Strobe 2nd Rm 2644 49797758 1 05/01-P
Speaker/Strobe 2nd Rm 2644 49797759 1 05/01-P
Speaker/Strobe 2nd Rm 2644 49797760 1 05/01-P
Speaker/Strobe 2nd Stair 3 49797897 1 05/02-P
Speaker/Strobe 2nd Stair 3 49799105 1 05/16-P
Speaker/Strobe 2nd Stair 6 49797942 1 05/01-P
Speaker/Strobe 2nd Stair 8 Crawlspace 49799106 1 05/16-P
Speaker/Strobe 3rd 3640 49798425 1 05/08-P
Speaker/Strobe 3rd 3640 49798426 1 05/08-P
Speaker/Strobe 3rd By heat In Kitchen 49798072 1 05/03-P
Speaker/Strobe 3rd By Rm 3009 49798339 1 05/08-P
Speaker/Strobe 3rd By Rm 3020B 49797866 1 05/02-P
Speaker/Strobe 3rd By Rm 3024A 49797868 1 05/02-P
Speaker/Strobe 3rd By Rm 3205 49797869 1 05/02-P
Kinetix 23 12/23/2018
Speaker/Strobe 3rd By Rm 3205 49797870 1 05/02-P
Speaker/Strobe 3rd By Rm 3205 49797871 1 05/02-P
Speaker/Strobe 3rd By Rm 3209 49797877 1 05/02-P
Speaker/Strobe 3rd By Rm 3402 49799147 1 05/17-P
Speaker/Strobe 3rd By Rm 3403 49797854 1 05/02-P
Speaker/Strobe 3rd By Rm 3405 49798351 1 05/08-P
Speaker/Strobe 3rd By Rm 3405 49798352 1 05/08-P
Speaker/Strobe 3rd By Rm 3430 49797852 1 05/02-P
Speaker/Strobe 3rd By Rm 3430 49797984 1 05/02-P
Speaker/Strobe 3rd By Rm 3602 49798866 1 05/14-P
Speaker/Strobe 3rd By Rm 3603 49798320 1 05/08-P
Speaker/Strobe 3rd By Rm 3611 49798338 1 05/08-P
Speaker/Strobe 3rd By Rm 3619 49798327 1 05/08-P
Speaker/Strobe 3rd By Rm 3623 49799150 1 05/17-P
Speaker/Strobe 3rd By Rm 3626 49799156 1 05/17-P
Speaker/Strobe 3rd By Rm 3633 49798431 1 05/08-P
Speaker/Strobe 3rd By Rm 3634 49798432 1 05/08-P
Speaker/Strobe 3rd By Rm 3637 49798437 1 05/08-P
Speaker/Strobe 3rd By Rm 3637 49798459 1 05/08-P
Speaker/Strobe 3rd By Rm 3638 49798430 1 05/08-P
Speaker/Strobe 3rd By Rm 3641 49798465 1 05/08-P
Speaker/Strobe 3rd By Rm 3644 49798098 1 05/08-P
Speaker/Strobe 3rd By Rm 3647 49798103 1 05/08-P
Speaker/Strobe 3rd By Rm 3647 49798104 1 05/08-P
Speaker/Strobe 3rd By Rm 3649 49798321 1 05/08-P
Speaker/Strobe 3rd By Rm 3652 49798322 1 05/08-P
Speaker/Strobe 3rd By Rm 3665 49798440 1 05/08-P
Speaker/Strobe 3rd By Rm 3666 49798441 1 05/08-P
Speaker/Strobe 3rd By Rm 3671B 49798438 1 05/08-P
Speaker/Strobe 3rd By Rm 3673 49798434 1 05/08-P
Speaker/Strobe 3rd By Stair 4 49798071 1 05/03-P
Speaker/Strobe 3rd Kitchen By Dry Storage 49797884 1 05/02-P
Speaker/Strobe 3rd Kitchen By Fire Extinguish 49797885 1 05/02-P
Speaker/Strobe 3rd Kitchen Entrance 49797886 1 05/02-P
Speaker/Strobe 3rd Nurses Station 3620 49799149 1 05/17-P
Speaker/Strobe 3rd Rm 3204 49797878 1 05/02-P
Speaker/Strobe 3rd Rm 3219 49797880 1 05/02-P
Speaker/Strobe 3rd Rm 3219 49797881 1 05/02-P
Speaker/Strobe 3rd Rm 3608 49799142 1 05/17-P
Speaker/Strobe 3rd Rm 3647 49798102 1 05/08-P
Speaker/Strobe 3rd Rm 3648 49798097 1 05/08-P
Speaker/Strobe 3rd Rm 3656 49798450 1 05/08-P
Speaker/Strobe 3rd Rm 3656 49798513 1 05/08-P
Speaker/Strobe 3rd Rm 3656 49798514 1 05/08-P
Speaker/Strobe 3rd Rm 3658 49798454 1 05/08-P
Speaker/Strobe 3rd Rm 3658 49798455 1 05/08-P
Speaker/Strobe 3rd Rm 3658 49798458 1 05/08-P
Speaker/Strobe 3rd Rm 3667 49799179 1 05/17-P
Speaker/Strobe 3rd Stair 8 49798447 1 05/08-P
Speaker/Strobe 4th By Rm 4013 49797957 1 05/02-P
Speaker/Strobe 4th By Rm 4028 49797958 1 05/02-P
Speaker/Strobe 4th By Rm 4211 49797977 1 05/02-P
Speaker/Strobe 4th By Rm 440 49797955 1 05/02-P
Speaker/Strobe 4th By Rm 4400 49797969 1 05/02-P
Speaker/Strobe 4th By Rm 4402 49798000 1 05/02-P
Kinetix 24 12/23/2018
Speaker/Strobe 4th By Rm 4403 49797953 1 05/02-P
Speaker/Strobe 4th By Rm 4412 49798003 1 05/02-P
Speaker/Strobe 4th By Rm 4419 49798006 1 05/02-P
Speaker/Strobe 4th Rm 4012 49797956 1 05/02-P
Speaker/Strobe 4th Rm 4211 49797976 1 05/02-P
Speaker/Strobe 4th Rm 4402 49798001 1 05/02-P
Speaker/Strobe 5th By Rm 5002 49798026 1 05/02-P
Speaker/Strobe 5th By Rm 5005 49798017 1 05/02-P
Speaker/Strobe 5th By Rm 5008B 49798059 1 05/03-P
Speaker/Strobe 5th By Rm 5010B 49798050 1 05/03-P
Speaker/Strobe 5th By Rm 5017 49798056 1 05/03-P
Speaker/Strobe 5th By Rm 5217 49797996 1 05/02-P
Speaker/Strobe 5th By Rm 5412 49798018 1 05/02-P
Speaker/Strobe 5th By Rm 5414 49798020 1 05/02-P
Speaker/Strobe 5th Rm 5031 49798062 1 05/03-P
Speaker/Strobe 5th Rm 5033 49798061 1 05/03-P
Speaker/Strobe 6th By Fax & Copy Area 49798087 1 05/03-P
Speaker/Strobe 6th By Main Elevators 49798084 1 05/03-P
Speaker/Strobe 6th By Rm 6000 49798080 1 05/03-P
Speaker/Strobe 6th By Rm 6009 49798082 1 05/03-P
Speaker/Strobe 6th By Rm 6404 49798085 1 05/03-P
Speaker/Strobe 6th By Service Elevator 49798083 1 05/03-P
Speaker/Strobe 6th By Stair 1 49798086 1 05/03-P
Speaker/Strobe 6th Stair 3 49798088 1 05/03-P
Speaker/Strobe Penthouse Rm 7000 Elevator Equip 49798129 1 05/03-P
Device Total: 183
Kinetix 25 12/23/2018
For periodic testing, verify that each appliance flashes. (NFPA 72 Table 14.4.3.2 (22c))
Strobe 0 0 0 64 64
Strobe 1st Across From ER 5 49797682 1 05/01-P
Strobe 1st By Rm 1235 Generator rm 49799118 1 05/16-P
Strobe 1st Moruge Exit 49797606 1 04/30-P
Strobe 1st Restroom 1625 49798494 1 05/08-P
Strobe 1st Restroom Across From 1218 49797506 1 04/30-P
Strobe 1st Restroom Across From 1218 49797522 1 04/30-P
Strobe 1st Rm 1012 49797565 1 04/30-P
Strobe 1st Rm 1636 49797631 1 05/01-P
Strobe 1st Rm 1637 49797632 1 05/01-P
Strobe 1st Rm 1668 49797640 1 05/01-P
Strobe 1st Rm 1669 49797637 1 05/01-P
Strobe 1st Rm 1687 49797564 1 05/01-P
Strobe 1st Waiting Area By Pharmacy 49797607 1 04/30-P
Strobe 2nd By Rm 2020 49797795 1 05/01-P
Strobe 2nd By Rm 2232 49797900 1 05/02-P
Strobe 2nd By Rm 2412 49797851 1 05/01-P
Strobe 2nd Rm 2005 49797582 1 05/01-P
Strobe 2nd Rm 2015 49797936 1 05/01-P
Strobe 2nd Rm 2201 49797925 1 05/02-P
Strobe 2nd Rm 2202 49797926 1 05/02-P
Strobe 2nd Rm 2232 49797899 1 05/02-P
Strobe 2nd Rm 2233 49797898 1 05/02-P
Strobe 2nd Rm 2408 49797850 1 05/01-P
Strobe 2nd Rm 2418 49797841 1 05/01-P
Strobe 2nd Rm 2601 49797951 1 05/01-P
Strobe 2nd Rm 2605 49797845 1 05/01-P
Strobe 2nd Rm 2623 49797832 1 05/01-P
Strobe 2nd Rm 2640 49797790 1 05/01-P
Strobe 2nd Rm 2643 49797757 1 05/01-P
Strobe 2nd Rm 2643 49797761 1 05/01-P
Strobe 2nd Rm 2679 49797803 1 05/01-P
Strobe 3rd By Rm 3641 49798466 1 05/08-P
Strobe 3rd Restroom 3610 49798333 1 05/08-P
Strobe 3rd Restroom 3612 49798331 1 05/08-P
Strobe 3rd Restroom 3613 49798334 1 05/08-P
Strobe 3rd Restroom 3645 49798096 1 05/08-P
Strobe 3rd Restroom 3657 49798452 1 05/08-P
Strobe 3rd Restroom 3659 49798453 1 05/08-P
Strobe 3rd Restroom Across From Stair 3 49798078 1 05/03-P
Strobe 3rd Restroom Across From Stair 3 49798079 1 05/03-P
Strobe 3rd Rm 3013 49797860 1 05/02-P
Strobe 3rd Rm 3022 49797859 1 05/02-P
Strobe 3rd Rm 3219 49797882 1 05/02-P
Strobe 3rd Rm 3404A 49797982 1 05/02-P
Strobe 3rd Rm 3621 49799151 1 05/17-P
Strobe 3rd Rm 3644 49798099 1 05/08-P
Strobe 3rd Rm 3644 49798100 1 05/08-P
Strobe 3rd Rm 3645 49798101 1 05/08-P
Strobe 4th By Rm 4409 49798002 1 05/02-P
Kinetix 26 12/23/2018
Strobe 4th Rm 4018 49797965 1 05/02-P
Strobe 4th Rm 4204 49797978 1 05/02-P
Strobe 4th Rm 4401 49797954 1 05/02-P
Strobe 4th Rm 4408 49798005 1 05/02-P
Strobe 5th By Rm 5214 49797989 1 05/02-P
Strobe 5th Rm 5010A 49798064 1 05/03-P
Strobe 5th Rm 5021 49798063 1 05/03-P
Strobe 5th Rm 5210 49797990 1 05/02-P
Strobe 5th Rm 5212 49797994 1 05/02-P
Strobe 5th Rm 5413 49798023 1 05/02-P
Strobe 5th Rm 5426 49798022 1 05/02-P
Strobe 5th Rm 5683 49798859 1 05/14-P
Strobe 6th Men’s Restroom 49798090 1 05/03-P
Strobe 6th Rm 6000 49798081 1 05/03-P
Strobe 6th Women’s Restroom 49798092 1 05/03-P
Device Total: 64
Kinetix 27 12/23/2018
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment per NFPA
90A-2018
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72 Table 14.4.3.2 (17)(g)(5))
Duct Detector 0 0 0 41 41
Duct Detector 1st in women’s room 1254 49797510 0-L2D38 04/30-P
Duct Detector 1st in women’s room 1254 49797511 0-L2D37 04/30-P
Duct Detector 1st Main Entry Mech Rm 49797559 0-L2D23 05/01-P
Duct Detector 1st Main Entry Mech Rm 49797562 0-L2D22 05/01-P
Duct Detector 1st Mech Rm 1219 49797505 0-L2D80 04/30-P
Duct Detector 1st Mech Rm 1219 49797552 0-L2D81 04/30-P
Duct Detector 1st Mech Rm 1232 49797696 0-L2D83 05/01-P
Duct Detector 1st Mech Rm 1622 49797695 0-L2D24 05/01-P
Duct Detector 1st Mech Rm 1633 49797688 0-L2D26 05/01-P
Duct Detector 1st Mech Rm 1633 49797689 0-L2D25 05/01-P
Duct Detector 1st Mech Rm 1689 49797556 0-L2D41 05/01-P
Duct Detector 1st Mech Rm 1689 49797557 0-L2D40 05/01-P
Duct Detector 2nd Roof Acess PTL Mech rm 2600 49797825 0-L3D91 05/01-P
Duct Detector 2nd Roof Acess PTL Mech rm 2600 49797826 0-L3D92 05/01-P
Duct Detector 2nd Mech Rm 2239 49797914 0-L3D29 05/02-P
Duct Detector 2nd Mech Rm 2239 49797915 0-L3D30 05/02-P
Duct Detector 2nd Mech Rm 2639 49797820 0-L3D84 05/16-P
Duct Detector 2nd Mech Rm 2639 49797821 0-L3D86 05/16-P
Duct Detector 2nd Mech Rm 2639 49797822 0-L3D85 05/16-P
Duct Detector 2nd Mech Rm 2639 49797823 0-L3D85 05/16-P
Duct Detector 2nd Mech Rm 2663 49797751 0-L3D73 05/01-P
Duct Detector 2nd Mech Rm 2663 49797779 0-L3D88 05/16-P
Duct Detector 2nd Mech Rm 2663 49797780 0-L3D87 05/16-P
Duct Detector 2nd Mech Rm 2663 49797781 0-L3D89 05/16-P
Duct Detector 3rd By Rm 3627 49798868 0-L4D84 05/14-P
Duct Detector 3rd By Rm 3627 49798869 0-L4D85 05/14-P
Duct Detector 3rd Mech Rm 3014 49797952 0-L4D40 05/02-P
Duct Detector 3rd Mech Rm 3014 49797979 0-L4D41 05/02-P
Duct Detector 3rd Mech Rm 3014 49797980 0-L4D42 05/02-P
Duct Detector 3rd Rm 3667 49799180 0-L4D75 05/17-P
Duct Detector 3rd Rm 3667 49799186 0-L4D79 05/17-P
Duct Detector 3rd Rm 3667 49799187 0-L4D76 05/17-P
Duct Detector 3rd Rm 3667 49799189 0-L4D80 05/17-P
Duct Detector 4th Rm 4211 49797974 0-L5D10 05/02-P
Duct Detector 4th Rm 4211 49797975 0-L05D11 05/17-P
Duct Detector 6th By Rm 6208 49798093 0-L7D19 05/03-P
Duct Detector 6th Men’s Restroom 49798091 0-L7D17 05/03-P
Duct Detector 6th Rm 6210 49798094 0-L7D18 05/03-P
Duct Detector 6th Rm 6210 49798123 0-L7D20 05/03-P
Duct Detector Penthouse Rm 7000 49798147 0-L8D06 05/03-P
Duct Detector Penthouse Rm 7000 49798148 0-L8D07 05/03-P
Device Total: 41
Kinetix 28 12/23/2018
LS 02.01.30 EP 25
All other Life Safety Code fire and smoke protection…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .